SEPCO - AZZOUR COMPLAINTS


1 1. Bay 2 ,11, 20 , 17 Sparking in cable chamber ( might be insulation failure ) .
2 2. Line Voltage indicator Bay 6 , 20 Now working .
3 3. Bay 7 , was not check , due to earth switch mechanical problem .
4. Bay 16 , Voltage transformer inserting finger for R phase shorter than
4 another two phase ,

5 5. Bay 8,9,10,32,29,18 , voltage indication swapped between L1/L3 .

6 6. Bay No.17 CT- still not yet received .


7. Protection relay showing voltage reading even voltage is Zero – Technical
7 clarification is required -.
8. Multi function meter showing Few ampere reading ( 0.15 A , 0.18 A, 0.17 A)
8 even No current input .
9 6. VCB racking problem, Bay-1,2,3,18,27,32.
7. Voltmeter ratio is not correct. It should be replaced by a new one. It shows
10 6.6kV when injecting 63.51V.
10. Bay 1 Protection relay measurement accuracy is not ok. it shows less 30A
11 when injecting the rated current.

11. CT data label is not matching the FAT report. Please let your person correct
12 it.

13 All CBCT Sec. wiring no protection cover


14 TTB Protection cover not fix yet
IEPC Comments
Rectified - Closed
Rectified - Closed
PDN - REPALCED WITH NEW ONE

CHANGED & RECTIFIED

At Site, we didn’t see this swapped between L1 & L3, found all OK.

CT replaced & found OK, CT report submitted to them

CUSTOMER SIDE EARTHING WAS NOT OK, THEY RECTIFIED

CUSTOMER SIDE EARTHING WAS NOT OK, THEY RECTIFIED, AS WELL AS


SUPPLIER EMAILED REPLY
VCB RACK IN / OUT CHEKED FOUND OK
This is prolong issue, supplier is not giving any corrective action, refer my
email send to you on behalf of this (email attached)

EARTHING IS RECTFIED AT CUSTOMER SIDE BY THE CUSTOMER

Which CT data label ? Which bay ? All updated reports already submitted
to them

Issued & fixed


Still in progress BY PDN Technicains
Remarks / STATUS
CLOSED
CLOSED
CLOSED

CLSOED

CLOSED

CLOSED

CLOSED

EMAIL ATTACHED & CLOSED

CLOSED

OPEN (email attached fyi actions)

AWAITING THE FINAL REPORT FROM


CUSTOMER

Need to be verify the label afixed by the


PDN techncain is not matching with the
actual CT inside panel, hence need to
change the labels accordingly.
CLOSED
OPEN