Anda di halaman 1dari 2

Project Location:PV Solar Plant - 30MW

30 MW
Sr no. Description Specification UOM Total
11 KV Transformer yard
1 RMU - D ( T2+T2) 11 kV, 630 A, RMU with CT Ratio of 250/1-1 A , 25 KA for 3 sec . Nos 8
2 4 MVA Transformer 0.400-0.400-0.400-0.400/11 kV, OFF CKT TAP ± 5% & Z=6%, Copper Nos 8
4 ACDB(distributio n Indoor A.C. Distribution Board comprising of 1 no. 20 A 4P MCCB for incoming, 3no.s Nos 8
5 300 sqmm Cu cable 1C x 300 mm2, 1.1 kV, XLPE Cable for Inverter to 4 MVA Transformer (5 Meters 6,240
6 16 sqmm AL cable 4C x 16 mm2 , 1.1 kV, Aluminium Armoured XLPE Cable for Aux. Tranfo to Meters 8,000
7 300 mm2 AL 11 KV, 3C x 300 mm2 Aluminium Armoured XLPE Grade Cable (to be laid Meters 8,000
8 300 mm2 AL 11 KV, 3C x 300 mm2 Aluminium Armoured XLPE Grade Cable (to be laid Meters 200
9 Al Lugs (300 Aluminium Lugs for Inverter & Transformer connections (for 1Cx300 sqmm XLPE AL Nos 960
10 Alumminium 4C x 16 mm2 , 1.1 kV, Aluminium Armoured XLPE Cable for Auxiliary Nos 64
11 Heat-Shrinkable Indoor / for 11 KV, 3 Core x 300 mm2 Aluminium Armoured XLPE cable Nos 35
12 Heat-Shrinkable Outdoor for 11 KV, 3 Core x 300 mm2 Aluminium Armoured XLPE cable Nos 8
13 Lighting pole Yard Lighting Pole with switch box containing 6 amps MCB at the bottom including Nos 16
14 Fire Extinguisher 6 kg. (Dry Chemical powder type) as per IS standards Nos 8
15 Fire Extinguisher 9 kg. (Foam type mechanical) as per IS standards Nos 8
16 Fire Extinguisher 9 kg. (CO2) as per IS standards Nos 8
17 Danger Board (showing Danger 11 KV wording) - 4 Nos. per yard Nos 16
18 Fire Bucket stand with canopy having 4 buckets (10 kg) capacity Nos 8
19 Fire Bucket stand without canopy having 4 buckets (10 kg) capacity Nos 8
20 Rubber Hand for 11 KV grade as Per IS Standard Set 8
21 First-AID box Medium size first-aid box kit Set 8
22 Fire blanket Should be ISI marked Pair 8
23 Rubber Mat Class C- Thickness-3 mm, Size- (1 mtr X 3 mtr), as per IS standards Nos 16
24 Earthing Material Should include GI strips, earthing Pipe 40mm as per IS standards, MS Rod, Riser Lot 8
25 LT Control Cable For 2.8 MVA & 2.1 MVA Transformer, 11 KV RMU & Yard Lighting Lot 8
26 Consumables & Should Include Glands, Lugs, Ferrules, Ties, Tags, insulation tapes, Perforated Cable Lot 8
Switch yard & Control Room
27 132 KV LIGHTNING Outdoor, 120 kV, 10 kA Station class metal oxide (gapless) Lightning Nos 9
28 132 KV ISOLATOR Outdoor, 132KV, 1250 A, 31.5 kA for 3 Sec., Double Break, Centre Rotating Type Nos 4
28 132 KV ISOLATOR Outdoor, 132KV, 1250 A, 31.5 kA for 3 Sec., Double Break, Centre Rotating Type Nos 1
33 132 KV POTENTIAL Protection cum Metering PTs: Outdoor, 132 KV, oil-cooled, single phase, hermetically Nos 3
33 132 KV POTENTIAL Protection cum Metering PTs: Outdoor, 132 KV, oil-cooled, single phase, hermetically Nos 6
34 132 KV CURRENT Transformer Protection CTs : Nos 3
34 132 KV CURRENT Transformer Protection CTs : Nos 6
35 132 KV CURRENT Line Protection CTs : Nos 3
36 16 MVA POWER Outdoor, oil-filled, 11/132 KV, 16 MVA, ONAN, 3 Phase, 50 Hz Copper wound Power Nos 2
37 132 KV SF6 Outdoor, 132 kV, 2500 Amps., 31.5 kA for 3 Sec. SF6 Circuit Breaker with Nos 3
38 132 KV CONTROL Control and Relay Panel for 132 KV for Transformer Bay having RS 485 Nos 2
132 KV CONTROL Control and Relay Panel for 132 KV for Line Bay having RS 485 Nos 1
39 11 KV Six PANEL VCB 11 KV, 1250 A, 25 kA VCB Switchboard comprising of Outgoing of (1 no.), Incomers Set 1
39 11 KV Five PANEL VCB 11 KV, 1250 A, 25 kA VCB Switchboard comprising of Outgoing of (1 no.), Incomers Set 1
40 100 KVA STATION 11/0.433 KV, 100 kVA, OFF CKT TAP ± 5% & Z=4%, Copper wound Nos 1
41 Battery, battery charger Battery & Charger with accessories: 110 V, 100 AH MF-Valve Nos 1
42 Main A.C. Distribution (Indoor type) comprising of 1 no. of 100A TPN MCCB for incoming,2 nos. of 100 A Nos 1
43 A.C. Distribution (Outdoor type) shall comply entire 132 KV switch yard power requirements with spare Nos 1
44 Hot-Dip Lot 1
44 Structures for Lightning Galvanised steel structures as per IS standards Nos 9
45 Structures for Current Galvanised steel structures as per IS standards Nos 12
46 Structures for Galvanised steel structures as per IS standards Nos 9
47 Structures for Galvanised steel structures as per IS standards Nos 5
48 Structures for Gantry Galvanised steel structures as per IS standards Set 5
49 CT Junction Boxes for Protection CTs Nos 3
49 PT Junction Boxes for Protection PTs Nos 2
50 ACSR Zebra ACSR Zebra Conductor for connecting all Electrical equipments inside Meters 450
51 Foundation bolts Foundation bolts with nuts & washers for CTs, PTs, LAs, Isolators, CBs & Towers Lot 1
52 MS Templates For CTs (2Nos) , PTs (2 nos), LAs (2 nos), Isolator (1 no), CBs (1 no), Lot 1
Towers (1 No)
53 Clamps & Connectors For ACSR Zebra conductor (CTs, PTs, Isolator, Circuit Breakers, Lightning Lot 1
54 Silicon Composite Disc 132 KV Silicon Composite String Insulator Lot 1
55 Earthing Material 40 mm GI Pipes as per IS standards, GI Strip,Shield wire, MS Rods, Copper Plates, Lot 1
56 630 mm2 AL 11 KV,3R X 1C x 630 mm2 Aluminium Armoured XLPE Grade Cable (to be laid Meters 1,350
57 120 Sqmm AL Cable 1100 V, XLPE insulated, armoured, Aluminium cable - 3.5 core x 120 mm2 - For 100 Meters 80
58 50 Sqmm Al Cable 11 KV, 3C x 50 mm2 Aluminium Armoured XLPE Grade Cable from Meters 80
59 35 Sqmm Al Cable 1100 V, XLPE insulated, armoured, Aluminium cable - 3.5 core x 35 mm2 from Main Meters 80
60 Tubular Poles for fixing lights Set 9
61 Flood light fixtures complete with junction box containing 6 Amps MCCB and wiring etc. Set 12
62 Termination Kits Heat-Shrinkable Indoor Termination kits for 1.1 kV, 3.5 Core x 120 mm2 Nos 2
63 Heat-Shrinkable Indoor / for 11 KV, 1C x 630 mm2 Aluminium Armoured XLPE Earth Grade cable Nos 36
64 35 mm2 Al Lug 1100 V, XLPE insulated, armoured, Aluminium cable - 3.5 core x 35 mm2 from Main Meters 6
65 16 mm2 Al Lug 1100 V, XLPE insulated, armoured, Aluminium cable - 3.5 core x 35 mm2 from Main Meters 2
66 LT Control Cables (1.5, 2.5 Sqmm, 4 Sqmm and 6 sqmm /or as Required with 2 Core, 3 Lot 1
67 Fire Extingusher: 6 kg (CO2 type) as per IS standards Nos 3
68 Fire Extingusher: 6 kg (Dry Chemical Powder type) as per IS standards Nos 3
69 Fire Extingusher: 6 kg (Foam type) as per IS standards Nos 3
70 Danger boards (132KV) 10 nos. of Reflective Type Nos 20
71 Fire Bucket stand with canopy having 4 buckets (10 kg) capacity Set 4
72 Fire Bucket stand without canopy having 4 buckets (10 kg) capacity Set 4
73 First aid Box [Medium Size-22 item] as Per IS Standard Nos 2
74 Fire blanket ISI marked Nos 2
75 First-aid chart Shock Treatment chart (Framed but without glass frame) Nos 2
76 Rubber Hand gloves as Per IS Standard (132 KV) Pair 4
77 Rubber Mat Class C- Thickness-3 mm, Size- (1 mtr X 2 mtr), as per IS standards Nos 15
78 Discharge Rod Highly Insulated FRP telescopic earthing Rodwith 10 Feet length,Locking system should Nos 2
79 Phase Plates (Red, Yellow, Blue) with 1.5 mm Thickness and 80 mm Dia. For each Nos 60
84 Consumables & Should include Glands, Lugs, Ferrules, Ties, Tags, insulation tapes, Galvanized cable Lot 1
85 ETC Job Erection Testing & Commissioning of complete 11 KV Yard & 132 KV Job 1
85 Liasoning Job Liasoning with various department t get commissioning / Job 1
TOTAL SUPPLY 11 KV - 132 KV TY Bay PRICE

Anda mungkin juga menyukai