Next Planned Update: 31 July 2015 Three-Phase Dry-Type Power Transformers
terminals for outgoing cable connections. Access to the core and coil
assembly for inspection and testing shall also be provided.
8.1.4.3 Danger and warning labels shall be written in both Arabic and
English, utilizing white characters on a red background. If
noted in the Purchase Order the Arabic warning labels will be
provided by others.
8.1.5 In addition to the transformer data the nameplate(s) shall also include the
following which may be on a separate plate:
1) Manufacturer's plant location
2) Buyer's Purchase Order number
3) Manufacturer's Order reference number
4) Equipment year of manufacture
5) Equipment Serial Number
6) Equipment Model Number
8.2 Cores
8.2.1 Cores shall be fabricated using high grade, grain-oriented silicon steel
laminations with high magnetic permeability. Maximum magnetic flux
densities shall be kept well below the saturation point. The core
laminations shall be tightly clamped and compressed. All cuts to be
burr-free and to exact length. Core clamps and all structural parts shall
be grounded to prevent induced voltage build up.
8.2.2 Cores shall have flush bottoms. Design and fabrication shall be done in
such a manner that will minimize losses and audible sound level.