Anda di halaman 1dari 115

Medium Power Compact

C-BUC (20W to 60W)

Installation and Operation Manual


IM02960153 Rev.F
Reliability Choice Innovation
Copyright Notice

All information contained in this Manual are the property of ST Electronics (Satcom & Sensor Systems) Pte.
Ltd. The Manual in whole or in part, may not be duplicated or reproduced without the written permission
of ST Electronics (Satcom & Sensor Systems) Pte. Ltd.

The Manual is intended to be used as a guide only and may be revised, modified or altered at any time by
ST Electronics (Satcom & Sensor Systems) Pte. Ltd. ST Electronics (Satcom & Sensor Systems) Pte. Ltd.
shall not be liable to users of the Manual nor to any other person, firm, company or other body for any
loss, direct, indirect or consequential, in contract or in tort of for any negligent mis-statement or omission
contained herein, by reason of, arising from or in relation to any such user, other person, company or
body relying or acting upon or purporting to rely or act upon any matter contained in this Manual.

If you have any enquiry or require further technical assistance, please contact our Customer Service
Centre at:

ST Electronics (Satcom & Sensor Systems) Pte. Ltd.


No. 29 New Industrial Road,
ST Electronics Paya Lebar Building
Singapore 536213
Hotline: +65 65217959
Fax: +65 65217333
E-mail: techsvc_stacoms@stee.stengg.com
Website: www.agilissatcom.com

© 2011 ST Electronics (Satcom & Sensor Systems) Pte. Ltd. All Rights Reserved.
Table of Content
Chapter 1 Product Overview............................................................................................. 1
1.1 About The BUC ...................................................................................... 1
1.2 BUC Functions ....................................................................................... 2
1.2.1 BUC Functional Block Diagram.......................................................... 3
1.2.2 Frequency Band Options ................................................................. 4
1.3 BUC Interfaces ...................................................................................... 5
1.3.1 BUC Front View............................................................................ 5
1.3.2 BUC Rear View............................................................................. 6
1.3.3 BUC Side View ............................................................................. 7
1.4 Product Models.....................................................................................10

Chapter 2 System Configurations ......................................................................................11


2.1 Types of System Configurations .................................................................11
2.1.1 Stand-Alone System Configurations ...................................................11
2.1.2 1:1 Redundant System Configurations ................................................14
2.2 System Components ...............................................................................20
2.2.1 Agilis Power Supply Unit (APSVAC48-X00-XX)........................................20
2.2.2 Redundancy Control Unit RCU-T.......................................................22
2.2.3 Redundancy Control Unit RCU-R.......................................................26
2.2.4 TX WR137 Waveguide Switch ..........................................................30
2.2.5 WR229 RX Waveguide Switch ..........................................................31
2.2.6 Transient Protection Box ...............................................................32
2.2.7 Low Noise Block (LNB) ..................................................................32

Chapter 3 Installation....................................................................................................33
3.1 Unpacking the Box.................................................................................33
3.2 Pre-Installation Preparations ....................................................................34
3.2.1 Environmental Considerations .........................................................34
3.2.2 Tools Required ...........................................................................34
3.2.3 Site Preparation Checklist ..............................................................34
3.2.4 Power Supply .............................................................................36
3.2.5 Pre-Installation Test.....................................................................37
3.3 Installing the BUC & Other Components .......................................................39

Chapter 4 BUC Setup and Management ...............................................................................45


4.1 Monitor & Control..................................................................................45
4.2 Using the Agilis EMS Software ...................................................................45
4.2.1 Connecting the PC to the BUC .........................................................45
4.2.2 Installing the Agilis EMS Software .....................................................47
4.2.3 Launching the Agilis EMS Software ....................................................48
4.2.4 Main User Interface......................................................................48
4.2.5 Types of Users ............................................................................49
4.2.6 Selecting the Device to Manage .......................................................49
4.2.7 1:1 BUC Address Initialization using external RCU .................................59
4.2.8 Modifying BUC Configuration Parameters ............................................61
4.2.9 LNB Parameter Configuration ..........................................................62
4.3 Monitor & Control via HTTP (Web)..............................................................63
4.3.1 Connecting the PC to BUC ..............................................................63
4.3.2 Connecting to the Web Interface......................................................64
4.3.3 Monitoring BUC Status...................................................................67
4.3.4 Configuring the BUC .....................................................................70

IM02960153 Rev. F i
4.3.5 Setting Up SNMP Parameters...........................................................73
4.4 Monitor & Control via SNMP ......................................................................74
4.4.2 Connecting the PC to BUC ..............................................................75
4.4.3 Connecting to the SNMP Interface ....................................................75
4.4.4 Managing the BUC via an SNMP Manager .............................................77

Chapter 5 Maintenance & Troubleshooting...........................................................................83


5.1 Preventive Maintenance ..........................................................................83
5.1.1 Fans Maintenance ........................................................................83
5.1.2 Gains Testing .............................................................................84
5.1.3 Completing the Maintenance ..........................................................85
5.2 Understanding Faults in the BUC ................................................................86
5.3 Understanding Faults in the Redundancy System.............................................88
5.4 Understanding Faults in Remote Management ................................................89

Appendix A Customer Service ............................................................................................91


A.1 Warranty Information .............................................................................91
A.2 Return Material Authorization (RMA) ...........................................................92
A.3 Additional Technical Support ....................................................................94

Appendix B Unit Specifications & Outline..............................................................................95


B.1 System Specification Tables .....................................................................95
B.2 Unit Outline Drawings.............................................................................97

Appendix C Compliance Standards ......................................................................................99

Appendix D Document Revision Log ................................................................................... 100

ii IM02960153 Rev. F
List of Figures
Figure 1.1 C-BUC with AC Integrated PSU functional block diagram .............................................. 3

Figure 1.2 C-BUC functional block diagram ........................................................................... 4

Figure 1.3 Frequency Conversion for the Standard C-Band ......................................................... 4

Figure 1.4 Front view of the 20W-60W AC Integrated C-BUC....................................................... 5

Figure 1.5 Front view of the 20W-60W C-BUC ........................................................................ 5

Figure 1.6 Rear view of the 20W-60W AC Integrated C-BUC........................................................ 6

Figure 1.7 Rear view of the 20W-60W C-BUC ......................................................................... 6

Figure 1.8 Left side view of the 20W-60W AC Integrated C-BUC................................................... 7

Figure 1.9 Left side view of the 20W-60W C-BUC .................................................................... 7

Figure 1.10 Right side view of the 20W-60W AC Integrated C-BUC ................................................. 8

Figure 1.11 Right side view of the 20W-60W C-BUC ................................................................... 8

Figure 2.1 C-BUC (AC Integrated PSU) Stand-Alone Configuration................................................11

Figure 2.2 20W – 60W BUC Stand-Alone Configuration Setup......................................................12

Figure 2.3 Stand-Alone LNB Configuration Setup ....................................................................14

Figure 2.4 20W BUC 1:1 Configuration Setup.........................................................................14

Figure 2.5 Medium Power C-BUC (AC Integrated) Redundancy System ..........................................16

Figure 2.6 Medium Power C-BUC Redundancy System ..............................................................17

Figure 2.7 1:1 LNB Configuration Setup...............................................................................19

Figure 2.8 Front view of the Indoor PSU ..............................................................................20

Figure 2.9 Front view of the Outdoor PSU ............................................................................20

Figure 2.10 Rear view of the Indoor PSU ...............................................................................21

Figure 2.11 Rear view of the Outdoor PSU .............................................................................21

Figure 2.12 RCU block diagram ..........................................................................................22

Figure 2.13 Front view of the RCU-T....................................................................................23

Figure 2.14 Rear view of the RCU-T.....................................................................................25

Figure 2.15 Front view of the RCU-R....................................................................................26

Figure 2.16 Rear view of the RCU-R.....................................................................................28

IM02960153 Rev. F iii


Figure 2.17 Waveguide switch outline diagrams ......................................................................30

Figure 2.18 WR229 RX Waveguide switch outline diagrams .........................................................31

Figure 2.19 Transient Protection Box ...................................................................................32

Figure 2.20 Low Noise Block (LNB) ......................................................................................32

Figure 3.1 Typical mounting of the standalone C-BUC and LNB on the OMT of the antenna .................39

Figure 3.2 Typical mounting of the 1:1 C-BUC redundancy system configuration..............................39

Figure 3.3 1:1 C-BUC Redundancy System Configuration on a mounting bracket ..............................40

Figure 3.4 1:1 C-BUC Redundancy System Configuration on a mounting plate .................................40

Figure 3.5 Connecting the AC power cables..........................................................................41

Figure 3.6 1:1 C-BUC Redundancy Cable Connections ..............................................................42

Figure 3.7 Waveguide switch connection diagram ..................................................................43

Figure 3.8 Sealing the connectors .....................................................................................44

Figure 4.1 Connecting PC and BUC via RS232 ........................................................................45

Figure 4.2 Indirect connection between PC and device ............................................................46

Figure 4.4 Agilis EMS Main User Interface.............................................................................48

Figure 4.5 Configuration button........................................................................................61

Figure 4.6 LNB Parameters Configuration ............................................................................62

Figure 4.7 Connecting the BUC via RJ45 ..............................................................................63

Figure 4.8 Configuring static IP.........................................................................................64

Figure 4.9 Disabling proxy server ......................................................................................65

Figure 4.10 BUC’s web configuration interface .......................................................................66

Figure 4.11 BUC and network status information .....................................................................67

Figure 4.12 BUC alarm status information .............................................................................69

Figure 4.13 Logging In .....................................................................................................70

Figure 4.14 Device Configuration Screen...............................................................................71

Figure 4.15 SNMP v2c configuration settings ..........................................................................73

Figure 4.16 SNMP MIB categories ........................................................................................74

Figure 4.17 Connecting via the RJ45....................................................................................75

Figure 4.19 MIB tree .......................................................................................................77

Figure 4.20 SNMP WALK ...................................................................................................80

iv IM02960153 Rev. F
List of Tables
Table 1-1 BUC Transmit Frequency Bands for Compact Medium C-BUC.......................................... 4

Table 1-2 Interfaces present on the front of the BUC unit......................................................... 5

Table 1-3 Interfaces present on the front of the BUC unit......................................................... 6

Table 1-4 Interfaces present on the side of the AC Integrated BUC unit ........................................ 7

Table 1-5 Interfaces present on the side of the BUC unit .......................................................... 7

Table 1-6 Interfaces present on the side of the BUC unit .......................................................... 8

Table 1-7 Interfaces present on the side of the BUC unit .......................................................... 8

Table 1-8 M&C Connector pin-out configuration (without Ethernet) ............................................. 9

Table 1-9 M&C Connector pin-out configuration (with Ethernet) ................................................. 9

Table 1-10 AC IN connector pin-out configuration .................................................................... 9

Table 1-11 DC pin-out configuration .................................................................................... 9

Table 1-12 Product series models ......................................................................................10

Table 2-1 Details of Cables used in Stand-Alone Configuration ..................................................12

Table 2-2 List of accessories and components for standalone system ..........................................13

Table 2-3 List of accessories and components for standalone LNB system .....................................14

Table 2-4 List of accessories and components for 1:1 redundant system.......................................15

Table 2-5 List of accessories and components for 1:1 redundant system.......................................16

Table 2-6 List of accessories and components for 1:1 redundant system.......................................18

Table 2-7 List of accessories and components for LNB redundant system......................................19

Table 2-8 Power Supply Selection Table .............................................................................20

Table 2-9 Interfaces present on the front of the Indoor PSU .....................................................20

Table 2-10 Interfaces present on the front of the Indoor PSU .....................................................20

Table 2-11 AC IN (KPT02E12-3P) Pin Descriptions (Outdoor PSU) .................................................21

Table 2-12 Interfaces present on the rear of the Indoor PSU ......................................................21

Table 2-13 Interfaces present on the rear of the Outdoor PSU ....................................................21

Table 2-14 DC OUT (62IN-12E-12-12S-4) Pin Descriptions...........................................................21

Table 2-15 Interfaces present on the front of the RCU unit........................................................23

Table 2-16 M&C Connector (without Ethernet) pin-out configuration ............................................24

IM02960153 Rev. F v
Table 2-17 M&C Connector (with Ethernet) pin-out configuration ................................................24

Table 2-18 Pin-out configuration and normal status output for FORM C .........................................24

Table 2-19 Interfaces present on the rear of the RCU unit.........................................................25

Table 2-20 TX SW pin-out configuration ...............................................................................26

Table 2-21 M&C-A (M&C-B) Connector pin-out configuration ......................................................26

Table 2-22 Interfaces present on the front of the RCU-R Unit.....................................................27

Table 2-23 RS232/RS484 Pin-Out and Descriptions ..................................................................28

Table 2-24 Form C pin outs / status outputs..........................................................................28

Table 2-25 Interfaces present on the rear of the RCU-R Unit ......................................................29

Table 2-26 RX Switch Pin Descriptions .................................................................................29

Table 2-27 WR137 Waveguide switch port interfaces ...............................................................30

Table 2-28 WR229 RX Waveguide switch port interfaces ...........................................................31

Table 2-29 List of AC Power supply cables with TPB ................................................................32

Table 2-30 TPB AC connector pin-out configuration.................................................................32

Table 3-1 Power specifications ........................................................................................36

Table 4-1 RS232 (P/N: 2502040500) pin-out configuration........................................................45

Table 4-2 RS485 cable (P/N: 2502041169) pin-out configuration ................................................46

Table 4-3 Types of Users................................................................................................49

Table 5-1 AC power tolerance .........................................................................................84

Table 5-2 Troubleshooting faults in the BUC ........................................................................86

Table 5-3 Troubleshooting faults in the redundancy system......................................................88

Table 5-4 Troubleshooting errors in the Agilis EMS software .....................................................89

Table A-1 Pre-RMA Request Checklist.................................................................................92

Table B-1 BUC specification tables....................................................................................95

vi IM02960153 Rev. F
Chapter 1 Product Overview

Agilis, a global leader in the design, development and manufacturing of


quality satellite products for various applications, introduces the Medium
Power Compact C-BUC.

The Medium Power Compact C-BUC is easy to install and redundancy


ready. The Agilis C-Band BUC also offers a wide range of distinctive
advantages and enhanced features for satellite communication systems in
remote or challenging geographic regions. Its innovative and robust design
makes it very reliable under harsh environment conditions.

This user manual provides detailed information to system integrators and


end users on how to set-up, operate and maintain the Medium Power
Compact C-BUC.

1.1 About The BUC


The Medium Power Compact BLOCK UP CONVERTER (C-BUC) is a high
performance, cost-effective RF transmitter designed for satellite
communication with high speed transmission capability suitable for both
telephony and high speed data communication.

The C-band BUC can be operated with different modulation formats such
as BPSK, QPSK and FM. Due to stringent performance specifications, it is
suitable for the following applications:

 Single Carrier Per Channel (SCPC)

 Multi-Carrier Per Channel (MCPC)

 Demand Assigned Multiple Access (DAMA)

 Time Division Multiple Access (TDMA)

The Medium Power Compact C-BUC is an outdoor unit mounted directly


onto the orthogonal mount transceiver (OMT) of the antenna. For
mounting, it has one M8 x 10 mm screw hole for support mounted frames.
It can also be mounted directly onto the waveguide orthogonal mount
transducer by means of four screws.

The transmit output waveguide is WR137 with groove and O-ring is


provided. A yellow transparent tape is laminated onto the waveguide;
together with the O-ring and proper installation, this prevents water
ingress through the waveguide.

 Note: DO NOT remove the yellow transparent tape, it is meant to be


permanently laminated at the waveguide transmit output.

IM02960153 Rev. F 1
Chapter 1 Product Overview

1.2 BUC Functions


The main function of the C-Band Block Up Converter (C-BUC) is to up
convert L-band transmit signal to the C-Band transmit frequency range and
amplifies it by an integrated SSPA. The C-BUC is a single stage up
conversion from L-band to C-band frequencies using a 10 MHz external
referenced phase locked oscillator. The spectrum is non-inverted with
phase noise surpassing Intelsat, Insat, Measat 3, ST-1/Palapa-C and Full C
standards and low DC power consumption.

The BUC includes the following function modules:

 Cooling sub-system
The cooling system consists of heat sink and fans and uses forced-air
convection cooling. All RF modules are placed on a heat sink for
effective heat dissipation. High power devices are cooled by inbuilt
fans which operate on DC power generated internally by the power
supply unit.

 Note: Please keep the side of the BUC at least 6” away from any
obstruction to allow air circulation through the fans.

An over-temperature switch monitors the internal temperature of


the unit. When the temperature exceeds acceptable operating
limits, the SSPA module is automatically disabled, minimizing
damage to the power devices.

 Solid state power amplifier


Each BUC has an internal SSPA module. The BUC feeds up-converted
signals into an internal SSPA module to be amplified for transmission
to the satellite via the antenna. The SSPA uses high power FETs to
generate the required output power. The SSPA operates on DC
power internally generated by the internal power supply unit.

 Monitor and control


The M&C module is the central processing hub of the C-BUC. It is
developed on an embedded microcontroller to perform the required
monitoring and control functions. The unit can be connected to a
remote PC via serial communication using RS232/485 or through
Ethernet (SNMP and Web). Using the M&C module, you can:

 Control the BUC


 BUC temperature
 LO unlocked alarm
 Monitor RF (RF output power and temperature) and electrical
readings.
 Check alarm status

 LED status indicator

2 IM02960153 Rev. F
Chapter 1 Product Overview

 Power supply

The Medium Power C-BUC is powered either by an integrated AC


Power Supply Unit (PSU) or an external PSU. The C-BUC with AC
integrated PSU is powered via an external 230V AC power source. An
internal AC-DC converter converts the AC power received into the
DC voltages required by the various modules within the BUC. The
internal AC-DC converter receives AC power and converts it to DC
voltages which are then supplied to the various internal modules and
cooling fans. The Medium Power C-BUC with AC integrated PSU
offers convenience in setup and requires less cabling.

The Medium Power C-BUC that requires an external PSU receives a


48V DC power (range 38V to 60V). This DC power is fed into the C-
BUC which is converted to suitable voltages required by the various
other modules and fans. The power supplies in all Agilis equipment
are compact, reliable, and have adequate consideration for safety,
EMC and EMI.

 Note: The 20W Medium Power Compact C-BUC has an option to


derive its voltage supply through the centre conductor of input
connector.

WARNING: The Compact C-BUC is automatically powered on when


power is applied. To avoid damaging the BUC, do not connect the entire
setup to the primary AC power source until all connections have been
made.

1.2.1 BUC Functional Block Diagram


Mixer Driver Amplifier

RF IN RF OUT
AMP AMP
L-Band,
10MHz Attenuator

10MHz Ref. RF Power Detector


VCO

M&C Monitor
&
Control

AC IN Power
Supply

Medium Power C-BUC

Figure 1.1 C-BUC with AC Integrated PSU functional block diagram

IM02960153 Rev. F 3
Chapter 1 Product Overview

Figure 1.2 C-BUC functional block diagram

1.2.2 Frequency Band Options


Table 1-1 BUC Transmit Frequency Bands for Compact Medium C-BUC
Input Transmit Local Oscillator Output Transmit
(MHz) (GHz) (GHz)
INTELSAT C-Band 950  1525 4.900 5.850 – 6.425
INSAT C-Band 1100 - 1400 5.625 6.725 – 7.025
Measat 3 950 - 1750 4.975 5.925 – 6.725
ST-1 / PALAPA-C 1150 - 1450 5.275 6.425 – 6.725
FULL C C-Band 950 - 1825 4.900 5.850 – 6.725

The diagram below illustrates how the Medium Power Compact C-BUC converts input
frequency to output frequency.

Figure 1.3 Frequency Conversion for the Standard C-Band

4 IM02960153 Rev. F
Chapter 1 Product Overview

1.3 BUC Interfaces


1.3.1 BUC Front View

Figure 1.4 Front view of the 20W-60W AC Integrated C-BUC

Figure 1.5 Front view of the 20W-60W C-BUC

Table 1-2 Interfaces present on the front of the BUC unit


Port Reference Connector Type Signal Details
RF IN 50Ω N-type L-band input signal with
connector 10MHz reference

IM02960153 Rev. F 5
Chapter 1 Product Overview

1.3.2 BUC Rear View

Figure 1.6 Rear view of the 20W-60W AC Integrated C-BUC

Figure 1.7 Rear view of the 20W-60W C-BUC

Table 1-3 Interfaces present on the front of the BUC unit


Port Reference Connector Type Signal Details
RF OUT WR-137G RF Signal
waveguide flange

6 IM02960153 Rev. F
Chapter 1 Product Overview

1.3.3 BUC Side View

Figure 1.8 Left side view of the 20W-60W AC Integrated C-BUC

Table 1-4 Interfaces present on the side of the AC Integrated BUC unit
Port Reference Connector Type Signal Details
Fan DC 4-pin square +12V DC input for fans
flange connector
DC IN Dummy Plate Not used

Figure 1.9 Left side view of the 20W-60W C-BUC

Table 1-5 Interfaces present on the side of the BUC unit


Port Reference Connector Type Signal Details
Fan DC 4-pin square +12V DC input for fans
flange connector
DC IN 3-pin connector To feed 48V DC input to the
for 48V DC power BUC
line

IM02960153 Rev. F 7
Chapter 1 Product Overview

Figure 1.10 Right side view of the 20W-60W AC Integrated C-BUC

Table 1-6 Interfaces present on the side of the BUC unit


Port Reference Connector Type Signal Details
AC IN 3-pin connector AC 230V voltage
M&C OUT Dummy plate Not Used
M&C IN 8-pin square M&C port to be connected
flange female to the PC / laptop
connector
FUSE Fuse holder 10Amp fuse

Figure 1.11 Right side view of the 20W-60W C-BUC

Table 1-7 Interfaces present on the side of the BUC unit


Port Reference Connector Type Signal Details
M&C OUT Dummy plate Not Used
M&C IN 8-pin square M&C port to be connected
flange female to the PC / laptop
connector

8 IM02960153 Rev. F
Chapter 1 Product Overview

Table 1-8 M&C Connector pin-out configuration (without Ethernet)


Pin # Function
Pin A Reserved
Pin B Ground
Pin C Reserved
Pin D Status Link
Pin E Rx232/RS485-
Pin F Tx232/RS485+
Pin G Reserved
Pin H Reserved

Table 1-9 M&C Connector pin-out configuration (with Ethernet)


Pin # Function
Serial Pin B Ground
Pin E Rx232/RS485-
Pin F Tx232/RS485+
Ethernet Pin A Tx+
Pin C Tx-
Pin G Rx+
Pin H Rx-
Pin D Status Link

 Note: The M&C pin-out configuration depends on the supported Agilis


equipment M&C option. Refer to the ALBX90 C-BUC Ordering Information
to view your purchased Agilis equipment features.

Table 1-10 AC IN connector pin-out configuration


Pin # Function
Pin A Ground
Pin B Live
Pin C Neutral

Table 1-11 DC pin-out configuration


Pin # Function
Pin A  Red Positive
Pin B  Blue Negative
Pin C Not Connected

IM02960153 Rev. F 9
Chapter 1 Product Overview

1.4 Product Models


This manual is suitable for the following Medium Power Compact C-BUC
models:

Table 1-12 Product series models


Model Type Model # (F-Type) Model # (N-Type)
20W C-Band BUC ALBX90XXX-20B-F ALBX90XXX-20B
25W C-Band BUC ALBX90XXX-25B-F ALBX90XXX-25B
30W C-Band BUC ALBX90XXX-30B-F ALBX90XXX-30B
40W C-Band BUC ALBX90XXX-40B-F ALBX90XXX-40B
50W C-Band BUC ALBX90XXX-50B-F ALBX90XXX-50B
60W C- Band BUC ALBX90XXX-60B-F ALBX90XXX-60B

ALBX90 C-BUC ORDERING INFORMATION

10 IM02960153 Rev. F
Chapter 2 System Configurations

This chapter explains, in detail, the system in which the BUC is deployed
in and its various components.

2.1 Types of System Configurations


Each BUC unit can be deployed in different system configurations
including:

 Stand-alone

 1:1 Redundant System

Each of these configurations is explained in details below.

2.1.1 Stand-Alone System Configurations

Figure 2.1 C-BUC (AC Integrated PSU) Stand-Alone Configuration

IM02960153 Rev. F 11
Chapter 2 System Configurations

 Note: This table lists the typical accessories required for the
connection. Please contact Agilis for purchase of any of these accessories
if needed.

Table 2-1 Details of Cables used in Stand-Alone Configuration


Item Agilis Description Length Quantity
Part No. (m)

1 1001520980 AC power cable with 2 1


transient protection box
2 2502041169 C/A FOR M&C VSAT - 1
(ETH, RS485)
3 6103480008 CONVERTER USB TO - 1
RS485
4 4203490057 WR137 C-BD TX WG 1 1
FLEXIBLE 1M GROOVED
(Optional)
A - RF cable (L-Band) from To be arranged by
indoor to outdoor, N(M) the customer
to N(M)
- ALBX90 C-BUC - 1

Figure 2.2 20W – 60W BUC Stand-Alone Configuration Setup

12 IM02960153 Rev. F
Chapter 2 System Configurations

The table below lists the accessories and components that can be
obtained from Agilis to setup the system. This setup diagram and table can
also be found at the back of this manual for your convenience.

Table 2-2 List of accessories and components for standalone system


Item Agilis Description Length Quantity
No. Part No. (m)
1 2502040500 RS232 Cable 2 1
2502041313 C/A M&C S/PLUG 12-8P - 1
TO ETH RJ45 (Optional)
2 4203490057 WR137 C-BD TX WG 1 1
FLEXIBLE 1M GROOVED
3 6103480008 Converter RS485 to USB - 1
4 2502041169 C/A For VSAT SPT to - 1
RS485
5 2502041185 C/A Power 3Pin (F) to - 1
4PIN (M) 1.5m (For use
with Outdoor APS)
2502041298 C/A S/PLUG 12-3S TO - 1
DC OPEN (For use with
Indoor APS)
5702200003 Power Supply Connector - 1
A - RF Cable (L-Band) To be arranged by
customer
- ALBX90 C-BUC - 1
- APSVAC48 Agilis Power Supply Unit - 1
(Optional)
- 250316XXXX Accessories For BUC - 1
Hand Held Controller
(Optional)
- 2502041166 Ethernet Cable DB9 to - 1
RJ45 For SNMP config
(Optional)
- 2503160038 BUC Feed Mounting - 1
Accessories
- 2503160146 Accessories For C-BD 20 - 1
to 60W Feed Mount

 Note: The table above is a typical accessories list for the BUC.
Depending on your purchase order, your BUC package may not include
certain optional cables. Please contact Agilis if you wish to purchase any
of the above accessories.

IM02960153 Rev. F 13
Chapter 2 System Configurations

Figure 2.3 Stand-Alone LNB Configuration Setup

The table below lists the accessories and components required to setup
the Stand Alone LNB system. This setup diagram and table can also be
found at the back of this manual for your convenience.

Table 2-3 List of accessories and components for standalone LNB system
Item Agilis Description Length Quantity
No. Part No. (m)
1 - Provided by the - -
customer
- ACA11XXXXX C-Band LNB - 1

 Note: The table above is a typical accessories list for the Stand Alone
LNB System. Depending on your purchase order, your BUC package may
not include certain optional cables. Please contact Agilis if you wish to
purchase any of the above accessories.

2.1.2 1:1 Redundant System Configurations

Figure 2.4 20W BUC 1:1 Configuration Setup

 Note: The 20W Medium Power Compact C-BUC has an option to derive
its voltage supply through the centre conductor of input connector.

14 IM02960153 Rev. F
Chapter 2 System Configurations

The table below lists the accessories and components that can be
obtained from Agilis to setup the system. This setup diagram and table can
also be found at the back of this manual for your convenience.

Table 2-4 List of accessories and components for 1:1 redundant system
Item Agilis Description Length Quantity
No. Part No. (m)
1 1001520980 AC Power Supply 3 2
220VAC 3M for RCU
2 6103480008 Converter RS485 to USB - 1
3 2502041169 C/A For VSAT SPT to - 1
RS485
4 2502040137 C/A RF RFT TO SSPA / 3 2
LNA 3M
2502040162 C/A 50ohm 1/4" FIA- 3 2
PNMNM-3M-AG1
5 2502040155 C/A TXSW RCU TO 3 1
WR137 SW 3M
6 2503160010 Accessories VSAT RS - 1 set
WR137 SW
7 4203490022 WR137 Waveguide H- - 2
Bend 80mm Indoor
8 2502040561 C/A RCU to BUC 2M - 2
A - RF Cable (L-Band) To be arranged by
customer
- ALBX90 C-BUC - 2
- AAV610XXXX AAV-610 Series - 1
- 2502041166 Ethernet Cable DB9 to - 1
RJ45 For SNMP config
(Optional)
- 2503160038 BUC Feed Mounting - 2
Accessories
- 2503160097 Mounting Kit for RCU - 1
- 2503160152 Accessories For C-BD 20 - 1
to 60W 1+1

 Note: The table above is a typical accessories list for the BUC.
Depending on your purchase order, your BUC package may not include
certain optional cables. Please contact Agilis if you wish to purchase any
of the above accessories.

IM02960153 Rev. F 15
Chapter 2 System Configurations

Figure 2.5 Medium Power C-BUC (AC Integrated) Redundancy System

The table below lists the accessories and components that can be
obtained from Agilis to setup the system. This setup diagram and table can
also be found at the back of this manual for your convenience.

Table 2-5 List of accessories and components for 1:1 redundant system
Item Agilis Description Length Quantity
No. Part No. (m)
1 1001520980 AC Power Supply 3 4
220VAC 3M for RCU
2 6103480008 Converter RS485 to USB - 1
3 2502040561 C/A RCU to BUC 2M - 2

4 2502040137 C/A RF RFT TO SSPA / 3 2


LNA 3M
2502040162 C/A 50ohm 1/4" FIA- 3 2
PNMNM-3M-AG1
5 2502040155 C/A TXSW RCU TO 3 1
WR137 SW 3M
6 4203490042 WR137 C-BD TX SW - 1
150W LOAD
7 4203490022 WR137 Waveguide H- - 2
Bend 80mm Indoor
8 2502041169 C/A For VSAT SPT to - 1
RS485
9 4203490055 WR137 C-BD TX WG - 2
FLEXIBLE (Optional)
A - RF Cable (L-Band) To be arranged by
customer
- ALBX90 C-BUC - 2
- AAV610XXXX AAV-610 Series - 1

16 IM02960153 Rev. F
Chapter 2 System Configurations

Item Agilis Description Length Quantity


No. Part No. (m)
- 5903290003 WR137 Waveguide - 1
Switch 235VAC CPRG
W/4 GASKETS
- 2502041166 Ethernet Cable DB9 to - 1
RJ45 For SNMP config
(Optional)
- 2503160038 BUC Feed Mounting - 2
Accessories
- 2503160097 Mounting Kit for RCU - 1
- 2503160152 Accessories For C-BD 20 - 1
to 60W 1+1

 Note: The table above is a typical accessories list for the BUC.
Depending on your purchase order, your BUC package may not include
certain optional cables. Please contact Agilis if you wish to purchase any
of the above accessories.

20W to 60W C-BUC 1:1 System Configuration

Status
8

L-Band IN
Modem
M&C
Status
IF IN RF 7
A 4 C-BUC A OUT

L-band, 10MHz
DC WR137 TX WG
IF IN M&C_A
BUC_A PSU 9 Switch
AC Source 1 Port 2
T.P.B 1 AC 1
SW1 5
T.P.B 1 AC 2 RCU-T
AC Source 2 6
Port 1
Form C Port 3 RF OUT
L-band, 10MHz
BUC_B PSU 9 Termination To Feed
USB 2 3 M&C
M&C_B Port 4
4 DC
PC Status IF IN C-BUC B RF 7
OUT
M&C

8
Status

Figure 2.6 Medium Power C-BUC Redundancy System

IM02960153 Rev. F 17
Chapter 2 System Configurations

The table below lists the accessories and components that can be
obtained from Agilis to setup the system. This setup diagram and table can
also be found at the back of this manual for your convenience.

Table 2-6 List of accessories and components for 1:1 redundant system
Item Agilis Description Length Quantity
No. Part No. (m)
1 1001520980 AC Power Supply 3 2
220VAC 3M for RCU
2 6103480008 Converter RS485 to USB - 1
3 2502041169 C/A For VSAT SPT to - 1
RS485
4 2502040137 C/A RF RFT TO SSPA / 3 2
LNA 3M
2502040162 C/A 50ohm 1/4" FIA- 3 2
PNMNM-3M-AG1
5 2502040155 C/A TXSW RCU TO 3 1
WR137 SW 3M
6 2503160010 Accessories VSAT RS - 1 set
(2,5,10,20W) WR137 SW
7 4203490022 WR137 Waveguide H- - 2
Bend 80mm Indoor
8 2502040561 C/A RCU to BUC 2M - 2
9 2502041185 C/A Power 3Pin (F) to - 2
4PIN (M) 1.5m (For use
with Outdoor APS)
2502041298 C/A S/PLUG 12-3S TO - 2
DC OPEN (For use with
Indoor APS)
5702200003 Power Supply Connector - 2
A - RF Cable (L-Band) To be arranged by
customer
- ALBX90 C-BUC - 2
- AAV610XXXX AAV-610 Series - 1
- 2502041166 Ethernet Cable DB9 to - 1
RJ45 For SNMP config
(Optional)
- 2503160038 BUC Feed Mounting - 2
Accessories
- 2503160097 Mounting Kit for RCU - 1
- 2503160152 Accessories For C-BD 20 - 1
to 60W 1+1

 Note: The table above is a typical accessories list for the BUC.
Depending on your purchase order, your BUC package may not include
certain optional cables. Please contact Agilis if you wish to purchase any
of the above accessories.

18 IM02960153 Rev. F
Chapter 2 System Configurations

Figure 2.7 1:1 LNB Configuration Setup

The table below lists the accessories and components required to setup
the LNB system. This setup diagram and table can also be found at the
back of this manual for your convenience.

Table 2-7 List of accessories and components for LNB redundant system
Item Agilis Description Length Quantity
No. Part No. (m)
1 1001520980 AC Power Cable with 2 2
Transient Protection
Box
2 6103480008 Converter RS485 to USB - 1
3 2502041169 C/A For VSAT SPT to - 1
RS485
4 2502040137 C/A RF RFT TO LNA 3M 3 2
5 2502040155 C/A RXSW RCU TO 3 1
WR229 SW 3M
6 2503160009 Accessories VSAT RS - 1
WR229 SW
A - RF Cable (L-Band) To be arranged by
customer
- ACA11XXXXX C-BAND LNB - 2
- AAV610XXXX AAV-610 RX Only - 1
- 2503160097 Mounting Kit For RCU - 1

 Note: The table above is a typical accessories list for the C-Band LNB
System. Depending on your purchase order, your BUC package may not
include certain optional cables. Please contact Agilis if you wish to
purchase any of the above accessories.

IM02960153 Rev. F 19
Chapter 2 System Configurations

2.2 System Components


This section explains the various system components, aside from the BUC
unit, that is required to setup the entire system.

2.2.1 Agilis Power Supply Unit (APSVAC48-X00-XX)


The Agilis APS Series Power Supply Unit (PSU) is a compact, highly reliable
and cost effective AC to DC switching power supply for the Agilis Block-Up
Converter (BUC). The Agilis APS Power Supply Unit is available in both
indoor and outdoor package.

Table 2-8 Power Supply Selection Table


Power Indoor Outdoor
20W to 25W APSVAC48-300-DM APSVAC48-300
40W to 60W APSVAC48-400-DM APSVAC48-400

Figure 2.8 Front view of the Indoor PSU

Table 2-9 Interfaces present on the front of the Indoor PSU


Port Reference Connector Type Signal Details
AC IN 3-pin connector AC 230V voltage
48V DC IN Binding Post +48VDC Output

Figure 2.9 Front view of the Outdoor PSU

Table 2-10 Interfaces present on the front of the Indoor PSU


Port Reference Connector Type Signal Details
AC IN 3-pin connector AC 230V voltage
FUSE Fuse holder 10Amp fuse

20 IM02960153 Rev. F
Chapter 2 System Configurations

Table 2-11 AC IN (KPT02E12-3P) Pin Descriptions (Outdoor PSU)


Pin # Function
Pin A Earth
Pin B Live
Pin C Neutral

Figure 2.10 Rear view of the Indoor PSU

Table 2-12 Interfaces present on the rear of the Indoor PSU


Port Reference Connector Type Signal Details
POWER LED Indicator Power supply LED indicator

Figure 2.11 Rear view of the Outdoor PSU

Table 2-13 Interfaces present on the rear of the Outdoor PSU


Port Reference Connector Type Signal Details
DC OUT 4-pin connector +48VDC Output

Table 2-14 DC OUT (62IN-12E-12-12S-4) Pin Descriptions


Pin # Function
Pin A +
Pin B -
Pin C N/C
Pin D N/C

IM02960153 Rev. F 21
Chapter 2 System Configurations

2.2.2 Redundancy Control Unit RCU-T


The BUC 1:1 Redundancy Controller Unit (BUC RCU) is used with two
Agilis’ BUCs in redundancy operation. A fault condition in the Online BUC,
or an operator-generated command, will switch the offline BUC into the
transmission path and the online BUC out of the transmission path.

Fault condition is determined by the alarm status of the BUC. If the status
signal (at Pin D of connectors M&C_A & M&C_B) of the BUC is lower than
1.4V, an alarm will be generated.

The RCU can operate in two redundancy modes, “Manual” and “Auto”.
Under “Manual” mode, users control the switching mechanism. The RCU
does not automatically generate a switch even when a BUC is faulty. This
mode allows users to repair faults or perform routine maintenance of any
BUC without disrupting signal transmission.

Under “Auto” mode, the RCU automatically control the switching


mechanism based on the operating status of each BUC. This is the
recommended mode for daily operations.

 Note: This manual provides basic information on the RCU unit. Please
refer to the RCU manual for detailed explanations.

RCU-T BLOCK DIAGRAM


BUC -A &
BUC -B LED

AC2 IN
M&C-A

250W Power RF Board


Supply
L-BD +
DC Insert 10MHz+DC BUC-A
+24V
Circuit
AC1 IN 250W Power
Supply

AC For
WG SW
L-BD IN 2-ways TX SW
IF IN Splitter M&C Board
WG SW
10MHz Control
OCXO

SW

10MHz L-BD + BUC-B


OCXO +5V DC Insert 10MHz+DC

Regulator Circuit
+5V
+12V Regulator
+12V M&C-B

M&C

FormC

AAV610XXXX-T

Figure 2.12 RCU block diagram

22 IM02960153 Rev. F
Chapter 2 System Configurations

RCU-T FRONT VIEW

Figure 2.13 Front view of the RCU-T

Table 2-15 Interfaces present on the front of the RCU unit


Port Reference Connector Type Signal Details
Fuse 1 / 2 - Fuse for AC1/AC2 power
supply (5A, 250V)
AC1 3-pin square Primary AC power supply,
flange male providing AC power to the
connector waveguide switches and a
KPT02E12-3P built in AC-DC converter.
For connection to 230VAC or
110VAC using the Agilis’ AC
power cord (with transient
protection box).
 Note: AC1 must be
connected to enable switching
of signal paths for
redundancy.
AC2 3-pin square Secondary AC power supply,
flange male providing AC power to another
connector built in AC-DC converter.
KPT02E12-3P For connection to 230VAC or
110VAC using the Agilis’ AC
power cord (with transient
protection box).
IF_1 50 Ω female N- To connect to the RF OUT port
type connector of an indoor modem. L-band
signals from the modem are
fed through this connector.
M&C 8-pin square To connect to an indoor
flange terminal (such as a PC) to
KPT02E12-8S manage the unit’s operation.
Or (Optional)
FORM C KPT02E12-8P Provides potential free Form C
status outputs of the unit.

IM02960153 Rev. F 23
Chapter 2 System Configurations

The following tables provide the pin-out details of the M&C and FORM C
connectors.

Table 2-16 M&C Connector (without Ethernet) pin-out configuration


Pin # Function
Pin A Reserved
Pin B Common
Pin C RS232 Tx
Pin D RS232 Rx
Pin E RS485-
Pin F RS485+
Pin G Reserved
Pin H Reserved

Table 2-17 M&C Connector (with Ethernet) pin-out configuration


Pin # Function
Serial Pin B Ground
Pin E RS485-
Pin F RS485+
Ethernet Pin A Tx+
Pin C Tx-
Pin G Rx+
Pin H Rx-
Pin D Status Link

Table 2-18 Pin-out configuration and normal status output for FORM C
Pin # Function Normal Fault
A, F BUC-A NC Status Close Open
B, F BUC-A NO Status Open Close
D, F BUC-B NC Status Close Open
E, F BUC-B NO Status Open Close
C Ground - -
G Reserved - -
H Reserved - -

24 IM02960153 Rev. F
Chapter 2 System Configurations

RCU-T REAR VIEW

Figure 2.14 Rear view of the RCU-T

Table 2-19 Interfaces present on the rear of the RCU unit


Port Reference Connector Type Description
BUC-A 50 Ω female N- Connects to BUC-A and BUC-B
BUC-B type connectors respectively.

TX SW KPT02E10-6S Connects to the control


(6-pin, socket) interface of the waveguide
switch, allowing the RCU to
control the switching
mechanism.
M&C-A KPT02E12-8S To connect the RCU to the
M&C-B BUCs, providing an RS485
interface (2-way serial
communication) for
monitoring and controlling the
operation of the BUC from the
RCU.

IM02960153 Rev. F 25
Chapter 2 System Configurations

Table 2-20 TX SW pin-out configuration


Pin # Function
Pin A Position 1 (Command)
Pin B Common (Command)
Pin C Position 2 (Command)
Pin D Position 1 (Indicator)
Pin E Common (Indicator)
Pin F Position 2 (Indicator)

Table 2-21 M&C-A (M&C-B) Connector pin-out configuration


Pin # Function
Pin A Reserved
Pin B Common (GND)
Pin C Reserve
Pin D BUC-A (BUC-B) Status
Pin E RS485 -
Pin F RS485 +
Pin G Reserved
Pin H Reserved

2.2.3 Redundancy Control Unit RCU-R

RCU – R FRONT VIEW

Figure 2.15 Front view of the RCU-R

26 IM02960153 Rev. F
Chapter 2 System Configurations

Table 2-22 Interfaces present on the front of the RCU-R Unit


Port Reference Connector Type Signal Details
AC1 IN 3-pin, plug AC1 IN is the primary AC
KPT02E12-3P power supply input. It
provides an AC supply for
built-in power supply A (250W
AC-DC converter) from this
connector.
Connect to an AC power
source through Agilis’ AC
power cord (with transient
protection box, part no.
1001520980) to 230VAC or
110VAC.
 Note: AC1 IN must be
connected to an AC power
source for redundancy
operation.
AC2 IN 3-pin, plug Backup AC power supply
KPT02E12-3P input. It provides an AC supply
to the waveguide switch and
to built-in power supply B
(250W AC-DC converter) from
this connector.
Connect to an AC power
source through Agilis’ AC
power cord (with transient
protection box, part no.
1001520980) to 230VAC or
110VAC.
FUSE 1 - 5A AC~250V fuse inside for the
AC1 IN power supply.
FUSE 2 - 5A AC~250V fuse inside for the
AC2 IN power supply.
IF OUT 50 Ω female N- Connect the IF OUT port to
type connector the RF input of a modem or an
L-Band converter (Indoor
Unit).
An L-Band signal from the 1:1
LNBs via a 1:1 switch in the
RCU-R is fed from this
connector to the indoor unit.
M&C 8-pin square Provides an RS485/RS232
flange interface for an indoor DTE
KPT02E12-8S (usually a PC) to monitor and
control the LNB RCU
operation.
FORM C KPT02E12-8P Provides potential free Form C
status outputs of the LNB
RCU.

IM02960153 Rev. F 27
Chapter 2 System Configurations

The following tables provide the pin-out details of the M&C and FORM C
connectors.

Table 2-23 RS232/RS484 Pin-Out and Descriptions


Pin # Function
Pin A Reserved
Pin B Common
Pin C RS232 Rx
Pin D RS232 Rx
Pin E RS485-
Pin F RS485+
Pin G Reserved
Pin H Reserved

Table 2-24 Form C pin outs / status outputs


Function PIN Normal Fault
LNB-A Normally Close A, F Close Open
Status
LNB-A Normally Open B, F Open Close
Status
LNB-B Normally Close D, F Close Open
Status
LNB-B Normally Open E, F Open Close
Status
GND C
Reserve G
Reserve H

RCU – R REAR VIEW

Figure 2.16 Rear view of the RCU-R

28 IM02960153 Rev. F
Chapter 2 System Configurations

Table 2-25 Interfaces present on the rear of the RCU-R Unit


Port Reference Connector Type Signal Details
RX SW 6-pin, socket Connects to the control
KPT02E10-6S interface of the waveguide
switch using accessory cable
with part number 2502040108.
LNB A 50 Ω female N- The LNB-A port connects to
type connector the L-Band output from LNB-
A, which is connected to Port
2 of the waveguide switch
LNB B 50 Ω female N- The LNB-B port connects to
type connector the L-Band output from LNB-B
which is connected to Port 4
of the waveguide switch

Table 2-26 RX Switch Pin Descriptions


Pin # Function
Pin A Position 1 (Command)
Pin B Common (Command)
Pin C Position 2 (Command)
Pin D Position 1 (Indicator)
Pin E Common (Indicator)
Pin F Position 2 (Indicator)

STATUS INDICATIONS FOR LNB-A AND LNB-B


Alarm Condition LED Color
LNB A – Alarm Condition LNB A LED - RED
LNB A – No Alarm Condition LNB A LED - GREEN
LNB B – Alarm Condition LNB B LED - RED
LNB B – No Alarm Condition LNB B LED - GREEN

IM02960153 Rev. F 29
Chapter 2 System Configurations

2.2.4 TX WR137 Waveguide Switch


The outdoor RF waveguide transfer switches are electromechanical
switches with manual override feature. They are actuated by 230VAC
50/60Hz from the AC mains during switch over. The switches do not
consume any power while idling.

The RF waveguide transfer switch is a four ports waveguide switch. Two


ports are connected to the two BUCs. A third port connects to the dummy
load while the last connects to the antenna feed.

The switch over can be automatically or manually controlled by the


operator. In “Auto” mode, the built-in redundancy system of the BUC
initiates a switching operation at the waveguide switch when a fault is
detected at either streams of the transmitter, switching the streams to
the offline BUC. This allows the link to be maintained while performing
fault diagnosis on the faulty BUC. You can also manually initiate this
switch for maintenance or diagnosis purposes.

The figure below shows the outline dimensions of the waveguide switch.
The time for each switch operation is 50ms.

0.13
10-32 X .31 Dp MIN (4)
5.12 (STD CKT) OR M5 ON METRIC UNITS
(LATCHING UNITS)
PORT 1 MANUAL OVERRIDE & PORT MARKING 1.750
RF PATH INDICATOR TYP 1.375
0.300 TYP TYP

PORT 4
PORT 2 2.250
PORT 2

(OMIT IF SQ
SPDT)
CONN (STD CKT)
MS3112E-10-6P
AGI LIS
REMOVED
VOID IF

CONNECTOR POS.
FOR LARGER CKTS. CPRF FLANGE SHOWN
PORT 3 (MS3112E-14-12P & (SEE P/N SELECTION)
LARGER SIZE) 10-32 X .25 Dp or M5
CONNECTOR TYPE FOR METRIC UNITS.
DEPENDENT ON CKT
DESIRED.

Figure 2.17 Waveguide switch outline diagrams

The following table details the connectors located on the switch.

Table 2-27 WR137 Waveguide switch port interfaces


Port Reference Connector Type Description
Port 1 CPR137-G Connects to the antenna feed
to send RF signals
Port 2 Connects to a BUC
Port 3 Connects to a dummy load for
output protection
Port 4 Connects to a BUC
Control MS3112E-10-6P Connects to the Switch
Control port of the BUC. This
connection allows the BUC to
initiate a switching operation
and monitor the status of the
waveguide switch position

30 IM02960153 Rev. F
Chapter 2 System Configurations

2.2.5 WR229 RX Waveguide Switch


The figure below shows the outline dimensions of the WR229 RX
waveguide switch.

8.50 3.450
PORT 1 1.725
2.375 TYP

1.375
TYP

PORT 2
2.750
PORT 4 PORT 2 TYP

PORT 3 MS3112E-10-6P

Figure 2.18 WR229 RX Waveguide switch outline diagrams

The following table details the connectors located on the switch.

Table 2-28 WR229 RX Waveguide switch port interfaces


Port Reference Connector Type Description
Port 1 WR229-G Connects to the antenna feed
to send RF signals to the LNB.
Port 2 Connects to a LNB.
Port 3 Connects to a dummy load for
output protection.
Port 4 Connects to a LNB.
Control MS3112E-10-6P Connects to the Switch
Control port of the Indoor
RCU. This connection allows
the Indoor RCU to initiate a
switching operation and
monitor the status of the
waveguide switch position
between the LNBs.

IM02960153 Rev. F 31
Chapter 2 System Configurations

2.2.6 Transient Protection Box


Transient protection prevents spikes in electrical discharges that may
cause damage to the Agilis equipment or other connected components.

Figure 2.19 Transient Protection Box

Table 2-29 List of AC Power supply cables with TPB


Agilis Part No. Description Length (m)
1001520980 AC Power Supply 220VAC 3M 3

For the TPB to work effectively, please keep clean outgoing lines away
from the incoming or earth leads.

 Note: Ground the TPB by connecting the M6 Earth Stud to a grounding


rod. Note that this is vital to the proper operation of the TPB.

Table 2-30 TPB AC connector pin-out configuration


Pin # Function
Pin A Ground
Pin B Live
Pin C Neutral

2.2.7 Low Noise Block (LNB)


LNBs are mounted near the reflector dish. Wide bands of frequency signals
are fed into the LNB which then amplifies and converts these signals to
minimize signal loss. Agilis’ LNB devices are specially designed for satellite
earth station receiver front ends and other applications.

Figure 2.20 Low Noise Block (LNB)

32 IM02960153 Rev. F
Chapter 3 Installation

This chapter explains a step-by-step process to safely mount and install


your Agilis products.

WARNING: Always handle the C-BUC with care. Dropping or knocking it


may cause damage to the unit. Agilis’ warranty does not extend to defects
due to excessive shock or vibration.

Do not operate the C-BUC without a cable or a RF load connected to the


RF OUTPUT waveguide port. The load should be at least double the BUC
wattage.

3.1 Unpacking the Box


Before unpacking the box, check if it had been damaged or opened. If the
shipment may have been tempered with, open the box in front of a
representative from the shipping company.

Upon opening the box, carefully remove the items in the package and
check them against the packing list. If any of the items are damaged or
missing, please contact Agilis or your local Agilis representative before
proceeding.

We recommend that you keep the original packing materials until you
have completed the checks and confirmed that the unit is in working
order.

If you need to repack the product for shipping, please use the original
shipping container and packing materials whenever possible. Alternatively,
you may also use high quality commercial packing materials to repack the
unit. Please seal the container firmly and clearly mark “FRAGILE
Electronic Equipment” on the exterior.

IM02960153 Rev. F 33
Chapter 3 Installation

3.2 Pre-Installation Preparations


3.2.1 Environmental Considerations
The Medium Power Compact C-BUC is an outdoor unit mounted directly
onto the orthogonal mount transducer (OMT) of the antenna. This design
allows the transmitter (power amplifier) to be installed close to the
transmitter antenna. The unit’s aluminium chassis is coated with white,
enamelled epoxy for environmental protection. All interface connectors
are sealed to prevent air and moisture from entering the unit.

According to the instructions supplied by the antenna manufacturer,


locate and install the antenna in an area that is free from RF interference
from motors and electronic equipment. A clear line of sight from the
antenna to the satellite is essential. To ensure safety and protection of
personnel and equipment, lightning arresters should also be used at the
site. Size 3/0 or 4/0 stranded copper wire should be used to bond the C-
BUC, LNB and Booster to the antenna frame and to the lightning
protection ground rod. The grounding resistance of the antenna should not
be more than 10 Ω.

Before proceeding with the mounting process, please ensure that the
environmental conditions in the area where the BUC is to be mounted is
appropriate for its optimal operation. These include:

 Temperature: -40ºC to +60ºC


 Relative Humidity: Up to 100% Weather protection sealed to IP65

3.2.2 Tools Required


We highly recommend having the following tools on hand before starting
the installation:

 1 complete set of socket wrench


 1 Philips head screwdriver
 1 cutter
 1 bag of cable ties (long and medium length)
 1 multi-meter

3.2.3 Site Preparation Checklist


The following table provides a checklist to help you ensure that your site
is adequately equipped to perform the installation.

Checklist Item Y/N


Equipment required for site survey Inclinometer
Compass / DataScope
1-meter rectangular bar
Scientific calculator
100-meter measuring tape
Site location map
GPS receiver
Road distance wheel

34 IM02960153 Rev. F
Chapter 3 Installation

Checklist Item Y/N


Vernier calliper
Location markers / flags
Is site in the satellite footprint? Yes No
Approximate length of cables
between ODU and IDU
IF cable routing method Underground Surface
Is there a clear path for cables from Yes No
ODU to IDU?
Proposed mounting location Antenna structure
Near the antenna
Inside the shelter
Other: ________________
Does the mounting location provide Yes No
the best route for cables from IDU
to ODU to antenna?
Is there an unobstructed view from Yes No
the satellite(s) of interest?
Are there any hazards near the site Yes No
location that may damage or If yes, please specify:
obstruct the ODU? (old buildings,
trees, planned future construction) ____________________________
Are there possible RF interference Yes No
from other nearby
telecommunication towers?
Will your installation cause Yes No
interference to other nearby setup?
Is sufficient power supply available? Yes No
Is grounding available? Yes No
Is the site prone to the following? Heavy wind
Heavy rainfall
Ice/snow accumulation
Extreme temperatures
Sand/Dust storms
Others: ______________

IM02960153 Rev. F 35
Chapter 3 Installation

3.2.4 Power Supply

POWER SUPPLY  AC INTEGRATED C-BUC


The AC Integrated C-BUC requires an operating AC voltage of 230V (range
96 to 264VAC).

The PSU power supply specification is shown in the table below.

Table 3-1 Power specifications


Power Specification Value
Primary Power 230VAC (range 96 to 264VAC)
Power Consumption 280W
(Typical)

POWER SUPPLY  MEDIUM POWER COMPACT C-BUC


The Medium Power Compact C-BUC works with a +48VDC (38V to 60V
range) voltage supply through the DC IN connector. The DC IN is the
standard power supply interface of the Medium Power Compact C-BUC.

 Note: The 20W Medium Power Compact C-BUC has an option to derive
its voltage supply through the centre conductor of input connector.

SELECTING AN APPROPRIATE AC POWER SOURCE


When selecting the AC power source to connect your indoor and outdoor
units, please ensure that the voltages are within the limits specified in the
table below. You are recommended to use an Automatic Voltage Regulator
if your power source falls outside of these limitations.

Tolerance X VAC, where X is the AC requirement of the device


Live  Neutral 230 VAC ± 15%
Live  Earth 230 VAC ± 15%
Neutral  Earth < 5 VAC

 Note: The equipment may be damaged if the Neutral  Earth tolerance


exceeds 5VAC. Please check your grounding setup if this occurs.

 Note: Please note that you may interchange the wiring connection
between the live and neutral pins. Interchanging these two pins will still
power up the RCU but may affect the switching operation of the setup.

POWER SUPPLY  RCU


The RCU requires at least one, or up to two AC power sources for its
operation. AC power supply can be connected to either AC1 or AC2 of the
RCU. The RCU is able to provide power to the waveguide switches and
monitor the BUCs statuses if at least one interface, AC1 or AC2, is
connected to a working power source.

 Note: For the RCU to perform switching via the waveguide switch for
redundancy, the unit must be connected to a working power source via
AC1.

36 IM02960153 Rev. F
Chapter 3 Installation

3.2.5 Pre-Installation Test


Performing a pre-installation test prior to the actual field installation
helps you to:

 Confirm that the unit has not been damaged during shipment.

 Check that the unit is in working order before performing a tiring


and costly mounting procedure on your antenna.

 Following are the test procedures for the ODU system. There are
two tests that are recommended; namely, the uplink and downlink
tests.

 Note: Ensure that no alarm or fault appears on the Medium Power


Compact C-BUC before performing any test.

 Note: To avoid damaging the C-BUC accidentally, connect a 30 dB, >


20W power attenuator to the RF output.

UPLINK TEST PROCEDURE

Step 1 Connect the C-BUC as shown in the figure below and power up the system.

Connection for uplink test procedure

 Note: * represents equipment not provided by Agilis

Step 2 Use the modem to input an L-Band pure carrier (by turning on the transmit
carrier and set the pure carrier feature to ON). Adjust the modem output
power so that the IF level input to C-BUC is -25 dBm.

IM02960153 Rev. F 37
Chapter 3 Installation

Step 3 Measure the RF OUT of the C-BUC using a spectrum analyzer at C-band.
1. Calculate the total transmit gain based on this formula: Output
power – Input power + Amount of attenuation.
2. Compare the result against the specifications (Appendix B Unit
Specifications & Outline). If there is no signal, check that the
channel setting is correct.
Example:
Transmit gain = RF OUT power - IF IN power + Attenuation =
8 - (-25) + 30 = 63 dB

DOWNLINK TEST PROCEDURE

Step 1 Connect a waveguide adapter to the LNB and connect the IF out of the LNB
to the spectrum analyzer via a T-Bias as shown figure below. Connect an
external 10 MHz reference signal to the T-Bias, LNB supply voltage and
power up the T-Bias DC supply.

Step 2 Input a -90 dBm C-Band CW signal to the LNB.

Step 3 Measure the IF OUT of the C-LNB by a spectrum analyzer. Set the Spectrum
Analyzer to 100 kHz span. Calculate the LNB receive gained by
subtracting the input power from the output power.

38 IM02960153 Rev. F
Chapter 3 Installation

3.3 Installing the BUC & Other Components


Step 1 All Agilis components in this system are outdoor mounted equipment
designed to withstand most weather conditions. Mount the standalone BUC
onto the antenna OMT. A set of mounting accessories is provided to mount
the standalone C-BUC to the OMT of the antenna. The LNB is fixed to the
receive port (or via a transmit rejection filter) of the OMT.
A mounting bracket or a mounting plate with a set of mounting accessories
is provided for the 1+1 C-BUC Redundancy System. Mount the 1+1 C-BUC
Redundancy System onto the antenna feed boom. Shown below are the
typical mounting diagrams for a C-BUC Standalone and Redundancy
System.

 Note: Agilis provides different mounting solutions to suit your needs.


The mounting diagrams shown below are typical mounting solutions
provided by Agilis. Please contact Agilis if you wish to purchase any of the
accessories shown on the diagrams.

Figure 3.1 Typical mounting of the standalone C-BUC and LNB on the OMT
of the antenna

Figure 3.2 Typical mounting of the 1:1 C-BUC redundancy system


configuration

IM02960153 Rev. F 39
Chapter 3 Installation
4203490022
4001761744G 4203490055
4203490055
4004430042 4203490022

Figure 3.3 1:1 C-BUC Redundancy System Configuration on a mounting


bracket

WAVEGUIDE SWITCH
(5903290003)
H-BEND H-BEND
(4203490142G) (4203490142G)

Use M4 Screws
to mount the TPBs

TPB
(1001522942)

TPB
(1001522942)

C-BUC A
C-BUC B

RCU-T

MOUNTING PLATE

FRONT REAR

Figure 3.4 1:1 C-BUC Redundancy System Configuration on a mounting


plate

 Note: Please contact Agilis if you wish to purchase any of the


accessories shown on the diagrams.

40 IM02960153 Rev. F
Chapter 3 Installation

Step 2 Connecting the BUC


The following connections need to be performed if you are setting up the
BUC in a standalone system configuration.

1. Connect the RF IN port of the BUC to an indoor modem using a


standard IF coaxial cable.
2. Connect the M&C port of the BUC to an indoor terminal (such as a
PC) for monitoring purposes using the cable provided. Please skip
this step if you are setting up a 1:1 redundancy system
configuration.
3. Using the TPB with AC power cables (P/N: 1001520980), connect
an AC power source to the BUC’s AC IN interface located at the
front of the AC Integrated C-BUC. If you are using an external PSU
for the C-BUC, connect the DC cable provided (P/N: 2502041298 or
P/N: 2502041185) to the PSU.
Please skip to step 8 to continue your installation if you are setting up a
standalone system. Steps 3 to 7 illustrate the installation procedure for a
redundancy system configuration.

Step 3 Connecting the RCU to AC power supply

WARNING: Please ensure that the power source is OFF before


connecting the AC cable from the power source to the RCU.

AC POWER CABLE AC POWER CABLE


WITH TPB WITH TPB

Figure 3.5 Connecting the AC power cables

Using the TPB with AC power cables (P/N: 1001520980 or P/N:


1001522942), connect an AC power source to the RCU’s AC1 or AC2
interfaces located at the front of the RCU.

 Note: A TPB is attached to each AC power cable for transient and surge
protection.

The RCU can operate with one or both AC interfaces connected. Note,
however, that AC1 supplies power to the waveguide switches. Hence, the
unit is only able to perform switching if AC1 is connected to a working
power source.

IM02960153 Rev. F 41
Chapter 3 Installation

Step 4 Connecting the BUCs to the RCU


Shown below are the cable connections that must be made between the
BUC and the RCU.

CABLE LIST:
2502041619

WAVEGUIDE
SWITCH
2502041621

1001522942

70m 0.6m

BUC A BUC B

BUC A BUC B

RCU-T
TPB TPB
TPB TPB

RCU-T

Figure 3.6 1:1 C-BUC Redundancy Cable Connections

2. Connect the RF IN port of the BUC A to the BUC-A port on the rear
panel of the RCU using the RG8 RF cable (P/N: 2502041621 or P/N:
2502040137).
3. Connect the M&C port of the BUC-A to the M&C-A port on the rear
panel of the RCU using the C/A RCU to BUC cable (P/N:
2502041620 or P/N: 2502040561).
4. Repeat the above two connections for BUC B, connecting to the
BUC-B and M&C-B port.
 Note: Please contact Agilis if you wish to purchase any of the
accessories shown on the diagrams.

42 IM02960153 Rev. F
Chapter 3 Installation

Step 5 Connecting the waveguide switch


The waveguide switch connection involves multiple ports. Refer to the
diagram shown in 2.1.2 1:1 Redundancy System Configuration. A full page
version of this diagram is also provided at the last page of this manual for
your convenience.

 Note: Please ensure that waveguide joints are properly equipped with
a gasket to prevent water from leaking into and damaging the equipments.

To RCU TX BUC-A
SW Port
5 2

Port 2
Port 3 3
Port 3
Port 1 RF OUT to
Termination 1 Antenna
Port 4

BUC-B

Figure 3.7 Waveguide switch connection diagram

Step 6 Connecting the RCU to the modem


In a redundancy system configuration, the RCU receives L-band signals
from an indoor modem to be transmitted to the antenna. Therefore an IF
connection between the RCU and the modem must be made.

Connect the IF IN port of the RCU to an indoor modem using a standard IF


coaxial cable.

Step 7 Grounding the installation


This process provides a conductive path for static electrical charges to be
discharged safely from the equipment to the ground. This prevents a build
up of static charges that may cause the equipment to spark.

1. Locate an appropriate grounding spot. Most soil has sufficient


conductivity to allow for an efficient grounding connection. Soils
that are mainly rock may need to be treated with additional
minerals like rock salt, copper sulphate or magnesium sulphate to
increase their conductivity.
2. Drive a 3m lightning rod into the ground about 30cm from the
antenna pole. Bolt an aluminium wire, minimum 9mm in diameter,
to the ground pole. A tight clamp is used to make contact at the
top end. Avoid sharp bends when routing the wire as these may
impede current flow.
3. Using size 3/0 or 4/0 stranded wires, bond the Compact Medium
Power C-BUC and other components to the antenna frame and
lightning protection ground rod.
 Note: Grounding resistance of the antenna should be no more than
10Ω.

WARNING: Please ensure that the wire is tightly connected between


the rod and the equipment to prevent sparks.

IM02960153 Rev. F 43
Chapter 3 Installation

Step 8 Switch on the unit

WARNING: Please ensure that the DC power source is off from the
modem before connecting the IFL cable to BUC.

FOR STAND ALONE SYSTEMS


Connect the DC power source to the BUC using modem or external
multiplexer. Ensure that all connections have been completed before
turning on the power supply.

The BUC will automatically power on when an appropriate DC current is


fed into the unit. The LED indicator should light on, indicating that the
device is turned on. The following table explains the LED colors.

LED Color Description


Green BUC is operating normally
Red BUC has an alarm condition
Amber BUC is offline or power is low
No Light This can mean either:
1) BUC is not receiving power
2) LED failure

FOR REDUNDANCY SYSTEMS


Turn on the AC power sources connected to the RCU. All devices (RCU,
BUC and switch) should power on and the respective LED indicators should
be lighted.

Step 9 Sealing the cables


To complete the physical installation, all connectors and important joints
in the system must be sealed. Note that the sealing must begin from the
chassis of the ODUs up to the heatshrink of the cable.

All unused connections must be sealed to prevent water ingress.


Waveguide joints must be equipped with an appropriate gasket. Please
ensure that all connectors are hand tightened before sealing.

Figure 3.8 Sealing the connectors

44 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.1 Monitor & Control


Agilis’ devices can be monitored and controlled remotely or locally via
various methods including:

 Agilis EMS Software

 Optional web browser (HTTP) and SNMP protocol

This chapter looks at how you can set up and manage your BUC system
using the various tools above.

4.2 Using the Agilis EMS Software


The Agilis EMS Software is a lightweight network management software
that allows the user to monitor and control the Medium Power Compact C-
Band BUC remotely through a PC.

4.2.1 Connecting the PC to the BUC


Two serial connection methods are available to connect your PC to the
BUC unit. These include:

 Via RS232 cable

Figure 4.1 Connecting PC and BUC via RS232

The RS232 cable pin-out configuration is detailed in the table below:

Table 4-1 RS232 (P/N: 2502040500) pin-out configuration


Male Circular Female Circular Signal
Pin E Pin 3 Rx – receive
Pin F Pin 2 Tx – transmission
Pin B Pin 5 Ground

IM02960153 Rev. F 45
Chapter 4 BUC Setup and Management

 Via RS485 cable

Connect your PC to the devices using the provided RS485 M&C cable
and the USB to RS485 connector. The connection diagram is shown in
the figure below.

Figure 4.2 Indirect connection between PC and device

The table below details the pin-out configuration of the RS485


cable.

Table 4-2 RS485 cable (P/N: 2502041169) pin-out configuration


RS485 cable USB-RS485 converter
Male Circular Female DB-9 Signal Male DB-9 Signal
Pin E Pin 2 Data+ Pin 2 Data+
Pin F Pin 1 Data- Pin 1 Data-
Pin B Pin 5 Ground Pin 5 Ground

46 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.2.2 Installing the Agilis EMS Software


The Agilis EMS software must be installed into a PC terminal to be used to
monitor your Agilis devices.

MINIMUM SYSTEM REQUIREMENTS


 Windows XP / Windows 7 operating system
 At least 1GB Hard Disk free space
 2GB RAM (Recommended)
 A M&C serial interface

SOFTWARE INSTALLATION
 Note: For detailed information on the Agilis EMS Software, refer to
IM02960173 Agilis EMS Software Installation and Operation Manual which
can be downloaded from the www.agilissatcom.com.

Step 1 Install the USB-RS485 converter driver into your PC. Please insert the CD
that was included in your package into your disc drive and run the driver
installation.

Step 2 If the Agilis EMS installation CD was included in your package, please
insert the CD into your PC’s disc drive and unzip the setup file.
 Note: You can download the latest version of the Agilis EMS Software
from the www.agilissatcom.com website using this link
http://www.agilissatcom.com/M-C-Software/39/0/page_content.html.

Step 3 Install the Flash player, Java applet, and the mysql ODBC software inside
the 3rd Party Software folder.
 Note: The 3rd party software must be installed before launching the
EMS application; otherwise, the EMS software will not be able to establish
communication with the BUC.

Step 4 Launch the setup file


Locate the setup file and double click the file to start the setup.

Figure 4.3 AgilisEMS.exe icon

 Note: You must have administrator permission on your Windows PC to


install the software.

Step 5 Follow the step-by-step installation instructions to install the EMS


software.

IM02960153 Rev. F 47
Chapter 4 BUC Setup and Management

4.2.3 Launching the Agilis EMS Software


To Launch the Agilis EMS Software, click on Start > All Programs > Agilis
EMS, click on the Launch Agilis EMS to start Agilis EMS.

Once all the required services are started, an Agilis icon would be
displayed in the notification area usually found in the bottom right hand
corner. This would indicate that the startup of services has been initiated.

An IE (Internet Explorer) window will automatically pop-up upon successful


startup.

4.2.4 Main User Interface

Figure 4.4 Agilis EMS Main User Interface

48 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.2.5 Types of Users


Table 4-3 Types of Users
User Password Options Available
Operator (Guest) NA  Analog Charts
 Device Configuration
admin admin  Analog Charts
 Device Configuration
 User Management
 Note: It is recommended to login as an admin when configuring a
device. Configuring a device using an operator account has limitations
such as, the need to exit then re-launch the EMS software for the changes
to take effect.

4.2.6 Selecting the Device to Manage


The Agilis EMS Software can be used to monitor and control a wide range
of Agilis products (BUC, MBUC, iBUC, SSPA, LNB, RCU, AUC, SPT and OHT).
The Medium Power Compact C-Band BUC is under the BUC category.

Before configuring a device, the user must first identify the COM Port
assigned to the Agilis device. To identify the COM Port, follow these steps:

Step 1 Right click ‘Computer’, and select ‘Properties’.

Step 2 Click ‘Device Manager’.

Step 3 Double-click ‘Ports (COM & LPT)’ and take note of the Port number
assigned to the device.

4.2.6.1 Configuring a standalone BUC


1. Login as an ‘admin’.

IM02960153 Rev. F 49
Chapter 4 BUC Setup and Management

2. Click ‘Device Configuration’ under the Administration option in


the Menu Bar.

3. Click on the ‘Add device configuration’ option in the Device


Configuration window.

50 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4. Under Communication Settings.


For this example, the Protocol used is ‘Serial’, the COM Port
assigned is 3 and the Baud Rate is 9600.

Under Device Settings.

For this example, the Mode selected is ‘Standalone’ and the

device selected on the Setup list is ‘BUC (Feedmount-

Integrated)’.

The ‘Acronyms’ used in this example is the default ‘BUC-1’.

5. Click ‘Add/Edit’ button.

IM02960153 Rev. F 51
Chapter 4 BUC Setup and Management

6. Click ‘Restart Driver’ for the changes to take effect.

7. Click ‘Refresh’ to refresh the display on the Agilis EMS main


window. The Tree Menu should display the newly configured

device along with the port number.

8. The block diagram of the newly configured device will now be


displayed on the Agilis EMS main window.

52 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.2.6.2 Configuring a 1:1 BUC Redundancy system


1. Login as an ‘admin’.

2. Click ‘Device Configuration’ under the Administration option in


the Menu Bar.

3. Click on the ‘Add device configuration’ option in the Device


Configuration window.

IM02960153 Rev. F 53
Chapter 4 BUC Setup and Management

4. Under Communication Settings.


For this example, the Protocol used is ‘Serial’, the COM Port
assigned is 3 and the Baud Rate is 9600.

For this example, the Mode selected is ‘1:1’ and the

devices selected on the Setup list are ‘(“BUC (Feedmount-

Integrated)” + “RCU (Rev 2)”)

The RCU type is Tx.

The ‘Acronyms’ used in this example are the default ‘RCUR2-1,


BUC-1 and BUC-2’.

 Note: To select multiple devices on the ‘Setup’ list, click and hold the
‘Ctrl’ control button while selecting the devices to be set up.

5. Click ‘Add/Edit’ button.

54 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

6. Click ‘Restart Driver’ for the changes to take effect.

7. Click ‘Refresh’ to refresh the display on the Agilis EMS main


window. The Tree Menu should display the newly configured

device along with the port number.

8. The block diagram of the newly configured device will now be


displayed on the Agilis EMS main window.

IM02960153 Rev. F 55
Chapter 4 BUC Setup and Management

4.2.6.2 Configuring a 1:1 LNB Redundancy system


1. Login as an ‘admin’.

2. Click ‘Device Configuration’ under the Administration option in


the Menu Bar.

3. Click on the ‘Add device configuration’ option in the Device


Configuration window.

56 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4. Under Communication Settings.


For this example, the Protocol used is ‘Serial’, the COM Port
assigned is 3 and the Baud Rate is 9600.

Under Device Settings.

For this example, the Mode selected is ‘1:1’ and the

devices selected on the Setup list are ‘(“LNB” + “RCU (Rev 2)”)

The RCU type is Rx.

The ‘Acronyms’ used in this example are the default ‘RCUR2-1,


LNB-1 and LNB-2’.

 Note: To select multiple devices on the ‘Setup’ list, click and hold the
‘Ctrl’ control button while selecting the devices to be set up.

5. Click ‘Add/Edit’ button.

IM02960153 Rev. F 57
Chapter 4 BUC Setup and Management

6. Click ‘Restart Driver’ for the changes to take effect.

7. Click ‘Refresh’ to refresh the display on the Agilis EMS main


window. The Tree Menu should display the newly configured

device along with the port number.

8. The block diagram of the newly configured device will now be


displayed on the Agilis EMS main window.

58 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.2.7 1:1 BUC Address Initialization using external RCU


For 1:1 BUC Redundancy system, address initialization must be performed.
For the C-BUC, the address of ODU A is 001 and ODU B is 002. The method
of the address-initialization is done by broadcasting a change of ID
command. Every device connected to the RS485 bus will change its
address accordingly.

1. Click on “Init Address” button.

2. A new window will pop up for the user to enter/select the


desired value. Select “A” and click ‘OK’.

3. A dialog box will pop up for the user to confirm the settings.
Select ‘OK’.

4. Another dialog box will popup for the user to confirm before
initializing the address. Connect Unit A to M&C_A of the RCU and
disconnect the other ODU from the RCU. Click ‘OK’.

IM02960153 Rev. F 59
Chapter 4 BUC Setup and Management

5. A message will be displayed to indicate the successful address


initialization of BUC A. Proceed to initialize the address of

Unit B, Select “B” and click ‘OK’.

6. A dialog box would pop up for the user to confirm the settings.
Select ‘OK’.

7. Another dialog box will popup for the user to confirm before
initializing the address. Connect Unit B to M&C_B of the RCU and
disconnect the other ODU from the RCU. Click ‘OK’.

8. A message will be displayed to indicate the successful address


initialization of BUC B. Click ‘Cancel’ or close the window.

60 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.2.8 Modifying BUC Configuration Parameters


Click on the ‘Configuration’ icon from the control panel to SET BUC
device configuration parameters.

To change the values of the device, simply click on the boxes where the
present values are being displayed. A new window pop-up window will
appear for the user to enter/select the desired value. Configuration
parameters are subjective to equipment type. For the BUC, the
configurable parameters are the RF Output and Attenuation.

Figure 4.5 Configuration button

IM02960153 Rev. F 61
Chapter 4 BUC Setup and Management

4.2.9 LNB Parameter Configuration


Click on the ‘Configuration’ icon from the control panel to SET LNB device
configuration parameters.

To view the Current (mA) of the LNB, simply click on the box beside the
parameter to be edited.

A new pop-up window will appear. If the Current (mA) value is within the
desired range, click ‘OK’ to initialize the LNB.

Figure 4.6 LNB Parameters Configuration

62 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.3 Monitor & Control via HTTP (Web)


If you have purchased the optional Ethernet M&C component, you can
monitor and manage the BUC from your PC by simply using a standard web
browser.

The new generation of devices from Agilis provides the capability to


monitor and control the device through a ubiquitous web browser
available on any PC. This simple interface offers a very user-friendly
mechanism to maintain and configure a device for any system
configuration and settings.

At the heart of the device is an embedded http web server. It is a


software component that implements the HTTP protocol and allows any
web browser to access information from the device. This architecture
provides the following benefits:

- It provides a thin-client interface for a traditional application and any


application running the http protocol.

- It provides support for http protocol for the distribution and acquisition
of information to be displayed in the regular interface — possibly a web
service, and possibly using XML as the data format.

- HTTP is a well studied cross-platform protocol and there are mature


implementations freely available. It is seldom blocked by firewalls and
intranet routers.

- HTTP clients (e.g. web browsers) are readily available with all modern
computers.

4.3.1 Connecting the PC to BUC


To monitor and control the BUC using the WEB interface via an Ethernet
connection, connect your PC LAN port to the BUC M&C port using either a
cross LAN cable or an Ethernet hub. A M&C to ETH RJ45 cable (P/N:
2502041313) or a DB9 to RJ45 (P/N: 2502041166) converter may be
provided by Agilis for this connection.

Figure 4.7 Connecting the BUC via RJ45

IM02960153 Rev. F 63
Chapter 4 BUC Setup and Management

4.3.2 Connecting to the Web Interface


Once your BUC is physically connected to the PC, follow the procedure
below to view the monitoring interface.

Step 1 Setup a static IP address for your LAN connection.


1. Navigate to your LAN connection properties. If you are using
Windows 7, this is located in the “Network and Sharing Center”
window. If you are using any other Windows system, please
navigate to the “Network Connections” window. Both windows can
be accessed via your PC’s “Control Panel”.
2. Click the network connection corresponding to the Ethernet port
that the BUC is connected to and open the “Properties” window.
3. Scroll to the “Internet Protocol (TCP/IP)” option and click the
[Properties] button. This will open the “Internet Protocol
(TCP/IP) Properties” dialog window.
4. Here, select Use the following IP address and configure as
follows:
IP Address: 192.168.1.10
Subnet mask: 255.255.255.0

Figure 4.8 Configuring static IP

5. Click [OK] and exit the both properties windows.

Step 2 Activate your Microsoft Internet Explorer web browser.


 Note: The BUC’s HTTP module is designed to work in Internet Explorer.
If you are using any other web browser, alignments may be different and
some functions may not work properly.

64 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

Step 3 Disable proxy server on the web browser.


1. Select “Tools > Internet Options” from your menu bar.
2. Click the “Connections” tab. At the bottom of this window, click
the [LAN Settings] button.
3. In the new dialog window that appears, ensure that the “Proxy
Server” checkbox is unchecked.

Figure 4.9 Disabling proxy server

4. Click [OK] to exit the screen.

IM02960153 Rev. F 65
Chapter 4 BUC Setup and Management

Step 4 In the address bar, enter the BUC’s access IP address. The BUC’s default IP
address is 192.168.1.1. A Welcome page similar to the one below should
display.
 All screenshots in this section are generic for all Agilis ALB190 series
products. Hence these screens are not specific and may differ slightly
from the models covered in this manual.

Figure 4.10 BUC’s web configuration interface

This screen displays the Web Page Version and a pictorial representation
of the BUC operating status. You can use the menu on the top of the
screen to navigate to the various other functions.

This page is automatically refreshed every 500ms and provides a summary


of the operating parameters of the connected BUC.

66 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.3.3 Monitoring BUC Status


To view basic information on the BUC such as device serial number, ID, IP
address and operating status, click “Device Status” on the top menu
(Please refer to the typical screenshot below).

Figure 4.11 BUC and network status information

IM02960153 Rev. F 67
Chapter 4 BUC Setup and Management

Four sets of information are displayed in this screen. This includes:

 Device Information

This displays the BUC hardware information including the part


number, serial number and firmware version.

 Network Information

This displays the internal network settings of the BUC including


device ID, web IP address and gateway, subnet mask and the serial
communication mode.

 BUC Status

This displays the detailed operating information and parameters of


the BUC such as the current unit temperature, attenuation value,
redundancy modes and state, input and output power level etc.

 RCU Status

This displays the RCU status and mode.

This screen automatically refreshes every 500ms to provide an updated


summary of the BUC’s operating parameters. You can also click “Refresh
Status” at the bottom of the screen to manually refresh the page.

68 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

To display all the alarm status of the BUC, click “Device Alarm” on the
top menu.

Figure 4.12 BUC alarm status information

Two sets of alarm information are displayed in this screen. This includes:

 BUC Alarms

A list of alarms and their corresponding status related to the BUC


operation are displayed here.

 Redundancy Alarms

This area lists alarms related to the redundancy status of the


system.

Each alarm can display one of four colour states.

 Green: Indicates that there is no alarm for the corresponding status.

 Red: Indicates a major alarm. Corrective action should be taken


immediately.

IM02960153 Rev. F 69
Chapter 4 BUC Setup and Management

 Amber: Indicates a minor alarm. Correction action should be taken if


necessary.

 Grey: Indicates that this status is not applicable for the BUC being
monitored.

This screen automatically refreshes every 500ms to provide an updated


summary of the BUC’s operating parameters. You can also click “Refresh
Status” at the bottom of the screen to manually refresh the page.

4.3.4 Configuring the BUC


You must login to edit any configuration of the BUC via this HTTP
interface. Click “Device Configuration” and the login window will appear.
Enter the login name and password and click [OK] to enter the
configuration screen.

The factory default login name and password is “admin” and “admin”
respectively.

LOGGING IN

Figure 4.13 Logging In

 Note: Both the “Device Configuration” and “SNMP Configuration”


screens can only be accessed after logging in. Access to both screens is
maintained after logging in until the browser is closed.

70 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

Figure 4.14 Device Configuration Screen

The configuration screen includes four sets of configurations - “Network


Configuration”, “BUC Operation”, “Redundancy Operation” and “Password
Setting”.

MODIFYING BUC NETWORK SETTINGS


“Network Configuration” allows you to configure the BUC network
information including the Device ID, IP and Gateway addresses and
Subnet Mask. You can also specify the IP address of the SNMP Manager
that communicates with this BUC and select the Serial Communication
Mode used to connect to the PC.

To modify any parameters, enter the desired value into the textboxes and
click the corresponding [Set] button.

IM02960153 Rev. F 71
Chapter 4 BUC Setup and Management

WARNING: Setting a wrong IP in Network Configuration may cause the


Device to be not accessible.

 Note: To retrieve the Device IP Address information from an


inaccessible device, use a terminal emulator; such as HyperTerminal, to
view the current IP Address assigned to your Agilis device. Use the COM
port assigned to your Agilis device when establishing serial communication
between your PC and BUC through HyperTerminal.

Once the IP Address information is acquired through a terminal emulator,


use the HTTP WebUI to reset the desired IP Address of the BUC.

 Note: Ensure that the “Serial Communication Mode” is set to the


supported M&C option supported by your Agilis device.

MODIFYING THE BUC OPERATION PARAMETERS


“BUC Operation” allows you to configure the BUC operating parameters
such as Attenuation and RF Operation.

To modify any parameters, enter the desired value into the textboxes or
select from the drop down menu and click the corresponding [Set] button.

MODIFYING THE REDUNDANCY OPERATION PARAMETERS


“Redundancy Operation” allows you to configure redundancy parameters
such as RCU Mode and RCU Switch.

To modify any parameters, enter the desired value into the textboxes or
select from the drop down menu and click the corresponding [Set] button.

CHANGING THE PASSWORD


“Password Setting” allows you to change your current password.

To change password, click on the Change Password link and fill out the
required information.

72 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.3.5 Setting Up SNMP Parameters


“SNMP Configuration” lets you specify how the BUC communicates with
the SNMP Manager. If you have yet to login to the HTTP interface, you will
be prompted to do so when clicking the “SNMP Configuration” menu
option. The factory default username and password is “admin”, “admin”
respectively.

 Note: Both the “Device Configuration” and “SNMP Configuration”


screens can only be accessed after logging in. Access to both screens is
maintained after logging in until the browser is closed.

Figure 4.15 SNMP v2c configuration settings

IM02960153 Rev. F 73
Chapter 4 BUC Setup and Management

4.4 Monitor & Control via SNMP


Simple Network Management Protocol (SNMP) provides a framework for
the definition of management information and the exchange of that
information. A SNMP manager is a software module that manages part or
all of the system configurations while an agent is a software module in the
unit that is being managed. Transfer of information can be initiated by
both the manager (via polling) and the agent (via SNMP Trap).

By default, the manager initiates requests and receives responses via port
161. The agent sends SNMP Trap messages via port 162.

A database describing the unit’s application parameters is stored in the


SNMP agent. This SNMP Management Information Base (MIB) database is
used to interpret the signals requested and received between the manager
and agent. The database includes both a standard set of values common to
hardware nodes on a network and a private set of values that is unique to
the specific unit.

Object Identifiers (OID) are a series of numbers that uniquely identify


variable to an SNMP agent. OIDs are arranged in a hierarchical tree
structure.

The figure below shows the categorization of BUC parameters that are
used in defining the MIBs for SNMP enabled Agilis products. These
categories help define various device parameters very distinctly and help
for easy access and navigation when using any manager.

 Note: This figure shows the full set of categories and does not apply to
all Agilis products. These categories are closely used in defining the
product MIBS for all the SNMP enabled devices. The set of parameters that
are available in each Agilis product will differ.

Figure 4.16 SNMP MIB categories

74 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.4.2 Connecting the PC to BUC


If you have purchased the optional Ethernet M&C component, you can
monitor and control the BUC using an SNMP manager via an Ethernet
connection. Connect your PC LAN port to the BUC M&C port using either a
cross LAN cable or an Ethernet hub. A M&C to ETH RJ45 cable (P/N:
2502041313) or a DB9 to RJ45 (P/N: 2502041166) converter may be
provided by Agilis for this connection. An optional Y Cable is also available
for the 40W – 60W product units.

Figure 4.17 Connecting via the RJ45

 Note: The Y Cable is only suitable for 40W – 60W product units. For
20W units, Y cable is not applicable.

4.4.3 Connecting to the SNMP Interface


Once your BUC is physically connected to the PC, follow the procedure
below to connect the SNMP agent module to a SNMP manager in your PC.

Step 1 Activate your SNMP manager. Agilis products will work with most standard
SNMP managers available in the market.
 Note: For the purpose of this manual, all screenshots in this section
are made using the SNMP Manager from iReasoning. You can download or
purchase any standard third party SNMP Manager software and install it
into your PC.

Step 2 In the SNMP manager, enter the BUC’s access IP address. The following
show the default configuration:
Agent IP: 192.168.1.1
Subnet Mask: 255.255.255.0
SNMP Manager: 192.168.1.10

IM02960153 Rev. F 75
Chapter 4 BUC Setup and Management

Step 3 Insert the CD included in your package into your PC’s disc drive and load
the MIB definition file (“AGILIS-PROD-XXX-MIB.mib”) into your SNMP
manager.
You can also download the MIB definition file from our website at
www.agilissatcom.com.

Once the file has been loaded, a tree structure should be displayed in your
manager as shown below.

Figure 4.18 Example MIB tree

76 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

4.4.4 Managing the BUC via an SNMP Manager

NAVIGATING THE MIB TREE

Figure 4.19 MIB tree

Each item in the tree is called a node. A parent or root node can be
expanded into branches. You can view each branch by clicking the +/-
icons in the tree. Each branch eventually terminates at leaf nodes.

To search for a specific node within a branch, right-click on the parent


node of that branch and select “Search” and type the name of the node to
search for.

You can expand or collapse the entire tree or branch by right-clicking on


the parent node and selecting the “Expand subtree” or “Collapse subtree”
option.

IM02960153 Rev. F 77
Chapter 4 BUC Setup and Management

UNDERSTANDING SNMP OPERATIONS


The full set of SNMP commands that can be initiated from the SNMP
manager is explained in the table below.

To execute a command on any node in the tree, simply select the node
and right-click. From the menu that appears, select the command to
execute. Note that not all commands are available for every object in the
tree.

SNMP Command Explanation


GET Used to obtain a single piece of information from the
BUC such as the BUC ID etc.
GET NEXT Used to obtain two pieces of information from the
selected object and the next object.
GET BULK Used to obtain multiple pieces of information from
the BUC at once.
GET SUBTREE Used to poll for information corresponding to all
objects within the subtree.
SET Used to configure a specific parameter in the BUC.
Note that this command will only be available for
configurable parameters.
WALK Used to poll for all data from the objects within the
tree.
TABLE VIEW Used to poll for and view data table of an object.
Note that this is only available if the selected object
stores tabulated data.

USING THE MIB BROWSER


1. Open the MIB Browser. In this example, we use iReasoning MIB Browser
to configure SNMP. Click File and select Load MIBs.

78 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

2. Once done, locate the MIB file in your system.

3. Once the MIB file is loaded, the SNMP MIB details will appear. Click on
the folders to view more information.

IM02960153 Rev. F 79
Chapter 4 BUC Setup and Management

4. Execute a command on any node in the tree. Right click on the node
and select a command you want to execute. In this example, “Walk” is
selected.

5. SNMP values will be retrieved once a command is selected. Below is an


example once “Walk” is selected. Once “Walk” is selected, all nodes’
information in the tree will be retrieved.

The figure below shows an example of the parameters retrieved by the


“WALK” command.

Figure 4.20 SNMP WALK

80 IM02960153 Rev. F
Chapter 4 BUC Setup and Management

6. To configure and update the SNMP values, right click on the nodes in
deviceOperation folder and select “Set”.

IM02960153 Rev. F 81
Chapter 4 BUC Setup and Management

---This page is intentionally left blank---

82 IM02960153 Rev. F
Chapter 5 Maintenance & Troubleshooting

This chapter details various system maintenance operations to help ensure


that your system works under optimal conditions.

WARNING: Disconnect all power sources before performing any


system maintenance and repair.

5.1 Preventive Maintenance


This section explains the various maintenance checks that should be
routinely carried out to ensure that the system is working correctly and in
optimal condition.

Ideally, you should perform a complete maintenance on the system at


least twice a year and record all updates and changes made to each ODU
“SETUP RECORD”. Notify all users that may be affected of a system down
time of roughly two hours prior to maintenance.

WARNING: Disconnect and re-connect cables during maintenance


properly to avoid causing any damage to the cables that may result in
intermittent problems in the future.

Connect the output interface of the equipment to a proper load.

5.1.1 Fans Maintenance


The C-BUC is equipped with fans at the bottom of the unit. It is essential
to ensure that airflow through these fans is not blocked to allow the BUC
to operate at the optimal temperature. Hence, we recommend cleaning
the fans at least once a year (or more depending on environmental
conditions). The cleaning procedure is detailed below:

Step 1 Turn off power supply to the BUC.

Step 2 Using compressed air, blow through the fan assembly to remove any dirt
accumulation

Step 3 Turn on the power supply to the BUC.

IM02960153 Rev. F 83
Chapter 5 Maintenance & Troubleshooting

5.1.2 Gains Testing


The test procedure is as follows:

Step 1 Look at the demodulator status (DEMODULATOR LOCK indicator on the


modem) and check that is “LOCKED” to the receive signal.

Step 2 Check that the transmit and receive configurations on both the modem
and the C-BUC complies with the SETUP RECORD. If there are any
discrepancies, contact the personnel responsible for the previous record
for clarifications before proceeding.

Step 3 Turn on the pure carrier of the modem and measure the power level using
a spectrum analyzer.

Step 4 If your modem is connected to an AC power supply, measure the indoor AC


power supply to the modem to check that the voltages are within the
tolerance limits. You are recommended to use an Automatic Voltage
Regulator if your power source falls outside of these limitations.
 Note: The limit range will differ according to your modem’s AC voltage
requirements. Please use the table as a guideline only.

Table 5-1 AC power tolerance


Tolerance X VAC 50 Hz, where X is the AC requirement of the
device
Live  Neutral X VAC ± 15%
Live  Earth X VAC ± 15%
Neutral  Earth < 5 VAC

Step 5 Check that all IFL and RF cables are labelled.

Step 6 Ensure that all cables are in good working condition by performing the
following procedure:
1. Remove cables at both ends of the connection before taking
measurements.
2. Using a mega ohm meter, measure both ends of the cables.

Step 7 Again using a mega ohm meter, measure the ground resistance of the
antenna. This value should not be greater than 10Ω

84 IM02960153 Rev. F
Chapter 5 Maintenance & Troubleshooting

Step 8 Reconnect the transmit cable to the modem and measure the power level
of the pure carrier transmitted into the C-BUC’s input port. Calculate the
IFL loss and check that it is similar to the value recorded in the SETUP
RECORD.

WARNING: Turn off the C-BUC and connect a power attenuator (30dB,
>30W) to the RF OUT port of the BUC before step 8 below.

Step 9 Turn on the BUC and connect the IF IN cable. Record the RF OUT power
level and calculate the uplink gain. Check that the resultant gain complies
with both the SETUP RECORD and the gain setting on the BUC.

Step 10 Measure the power level and C/N0 of the receive carrier under
consideration at the BUC’s RF OUT port. Check the readings against the
SETUP RECORD. If there is a significant variation in the two, contact the
transmit site for confirmation.

Step 11 Measure the level at the modem’s IF input to determine the Rx IFL loss.
Match this value against the SETUP RECORD.

5.1.3 Completing the Maintenance


Completing each maintenance service requires the following actions:

 Check the sealing on existing connections and re-seal if necessary.


 Tighten and re-seal all connections and important joints that were
disconnected for maintenance.
 Check and ensure that all waveguide joints are properly equipped
with a gasket and sealed.
 Cover all unused connectors with a cap and seal.
 Update the SETUP RECORD.

IM02960153 Rev. F 85
Chapter 5 Maintenance & Troubleshooting

5.2 Understanding Faults in the BUC


The table below lists the faults that may arise in the BUC. The following
information can be found in this table:

 Fault Indication: How do you tell that a fault has occurred?


 Possible Causes: What may have caused the fault and how do you
check?
 Solution: How do you resolve the fault?

Table 5-2 Troubleshooting faults in the BUC


Fault Indication Possible Causes Solution
LED is off BUC is not on Turn on the AC power
source connected to the
power supply unit.
Cables are loose Hand-tighten all cable
connections between the
AC power source and the
BUC.
Power cables are Test the voltage at each
faulty end of the cables. Replace
any faulty cables.
Fans are not Fan cable connector is Check that the fan cable
working loosely or not connector is properly
connected. connected.
Fans failure Replace the fans. Please
contact Agilis for further
support.
LO unlock Circuit failure Please contact Agilis for
further support.
10MHz reference Check 10MHz signal level
power level might be from modem. It should be
low from the modem ± 5 dBm at L-Band input of
the BUC.
LED is RED LO unlock Check 10MHz might be low
from the modem
SSPA is off Check the M&C Software
option to power ON the
SSPA.
Temperature alarm Needs to cool down the
unit. Also, check whether
the fan is working or not.

86 IM02960153 Rev. F
Chapter 5 Maintenance & Troubleshooting

Fault Indication Possible Causes Solution


No RF output BUC is overheated RF output is automatically
power disabled if the BUC is
overheated. Allow the unit
to cool to a safe operating
temperature before
enabling RF.
RF ON/OFF Enabled Check the BUC settings
using the M&C software
and enable RF (“On”).
Internal modules One or more of the
failure internal modules, such as
the power module, driver
and internal RF circuit,
have may have failed.
Please contact Agilis for
further support.
LO unlock Check 10MHz might be low
from the modem
RF output power Attenuation setting is Check the attenuation
is low too high setting using the M&C
Software and adjust
accordingly.
L-Band power level Please contact Agilis for
might be very low to further support. Check the
get rated power from L-Band signal level
BUC (~-30dBm) from the
modem.

IM02960153 Rev. F 87
Chapter 5 Maintenance & Troubleshooting

5.3 Understanding Faults in the Redundancy System


If you are using the BUC in a 1:1 redundancy system architecture, you may
encounter the following faults during the system’s operation. Please note
that this table only includes the faults that are specifically related to the
BUC. If you determined that the fault lies in the RCU components, please
refer to the corresponding RCU operator for the resolution method.

Table 5-3 Troubleshooting faults in the redundancy system


Fault Indication Possible Causes Solution
LED on RCU is off Unit is not receiving Check that the AC power
AC power supply source connected to the
RCU is on and tighten the
AC power cables.
Unable to RCU is operating in Change the mode to
perform a user- “Auto” mode “Manual”.
initiated switch
Switch is faulty Replace the switch and
operation
return the faulty switch to
Agilis for repair
Switch control cable Replace the cables.
connecting RCU to
switch may be faulty

88 IM02960153 Rev. F
Chapter 5 Maintenance & Troubleshooting

5.4 Understanding Faults in Remote Management


The following table lists the errors that you may face when managing the
BUC remotely via the Agilis EMS software.

Table 5-4 Troubleshooting errors in the Agilis EMS software


Fault Indication Possible Causes Solution
Agilis EMS is not Installation was not Reinstall the application again as
starting done properly stated in this document

Windows Firewall Shut down the Windows Firewall


service

Port 80 is being Shut down the application that is


utilized by another using port 80
application
Agilis EMS started Flash plug-in may Reinstall Flash Player preferably
but the flash be outdated from
images are not http://get.adobe.com/flashplayer/
shown
Agilis EMS is not MYSQL ODBC Install the application from EMS CD
logging alarm connecter is not (/3rd Party Software/mysql-
details /analog installed/corrupted connector-odbc-3.51.14-win32.exe)
parameters
PC is not showing M&C cable driver is Install the drivers that came
the COM number not installed together with the purchased M&C
cable (RS232 to USB or RS485 to
USB)
M&C cable is M&C cable could be Replace cable and try again
connected and faulty
COM number is
seen but still Wrong M&C cable is Refer to the product manual and
there’s no used ensure that the pin configuration is
communication correct i.e. RS232 or RS485
For standalone Start the application; click the Init
mode, the address Address button to set the device
must be set to ‘A’. address to ‘A’.
‘Another instance Agilis EMS Open IE and type
of Agilis EMS is application is http://localhost/agilis-ems in the
running’ message already started URL
is displayed when
I try to start the
application
How do I find out NA Start the application, click on Help,
the current click on About Us
version number?
Equipment is not Equipment Start the application, click the Init
displaying its Initializing is not Address button.
status properly done
(e.g. Status
toggling online Equipment Refer to the system manual to make
and offline in EV) Configuration could sure the correct configuration is set.
be wrong
RCU is not going The protocol might Refer to section 1.4 for the various
online be a different versions for RCU and how to replace
version the protocol files if necessary

IM02960153 Rev. F 89
Chapter 5 Maintenance & Troubleshooting

Fault Indication Possible Causes Solution


System Slowing Analog and Alarm Purge the historical Analog and
down data is not cleared Alarm data in the database.
in the database

90 IM02960153 Rev. F
Appendix A Customer Service

Agilis provides a variety of after-sales services. This chapter explains some


of the services offered including warranty information, the Return
Material Authorization process, parts replacement etc.

A.1 Warranty Information


If the unit fails due to defects in materials or workmanship, Agilis will, at
its sole discretion, repair or replace the defective parts, free of charge,
within two years from the date of its shipment from the Agilis production
factory.

Note that shipping cost to Agilis will not be covered under this warranty
guarantee.

This warranty will be voided, freeing Agilis from any liability or obligation
to the Purchaser with respect to the product in the following situations:

 The product has been damaged during shipment

 Failure caused by products not supplied by Agilis or its authorized


contractors and agents.

 Failure caused by operation of the product outside of its published


electrical and environmental specifications or any causes other than
ordinary use.

 Water ingress due to improper installation.

IM02960153 Rev. F 91
Appendix A Customer Service

A.2 Return Material Authorization (RMA)

PRE-RMA CHECKLIST
Shipping the unit to and from your supplier or the factory for repair is a
costly and time consuming procedure that may cause disruption in your
system for a prolonged period of time. Hence, please inspect your system
thoroughly using the checklist below to help us determine if return
shipping is necessary.

Table A-1 Pre-RMA Request Checklist


Please check
Product model / serial no:
When did the unit fail: Initial startup
Unit worked normally before failure
Initial Fault Symptom:
Consistent or intermittent Consistent
fault Intermittent
Duration of operation before
the failure
Are fans working normally? Yes
No
Is the airflow path blocked? Yes
No
10 MHz Ref. level at failure
IF input level at failure
Output power at failure
LED status
Is the device and setup Yes
properly grounded? No
Weather conditions just Air Temperature: _________
before failure Heavy rain/snowfall/storms: _________
AC Potential Live  Neutral
Live  Ground
Neutral  Ground
AC-DC converter working
status
Is the primary power source Yes
working and free of power No
spikes?
Was there any recent power Yes
outages that affected the No
device?

92 IM02960153 Rev. F
Appendix A: Customer Service

Please check
Are connectors properly Yes
sealed and free from No
debris/water?
Replace the device with a Works with the new device
working one (if available) and Does not work with the new device
check if the system works.
Detail the diagnosis
performed that localized the
fault to the unit as the point
of failure

If you need to return the devices or any components to Agilis for repair,
please contact Agilis to obtain a Return Material Authorization (RMA)
number by filling in our RMA Request form. You can obtain this form via
our website at www.agilissatcom.com. Once you receive a RMA number,
carefully repack the unit and attach this number to the unit to be shipped
to Agilis.

Agilis provides repair services for products under or out of warranty.

IM02960153 Rev. F 93
Appendix A Customer Service

A.3 Additional Technical Support


If you require further technical support, please contact Agilis using the
contact information below:

Address: ST Electronics (Satcom & Sensor Systems) Pte Ltd.


No. 29 New Industrial Road,
ST Electronics Paya Lebar Building
Singapore 536213
Service Hotline: (+65) 6521 7959
Fax: (+65) 6521 7333
Email: techsvc_satcoms@stee.stengg.com

You can also visit www.agilissatcom.com for the addresses and contact
information of our regional service centres.

94 IM02960153 Rev. F
Appendix B Unit Specifications & Outline

B.1 System Specification Tables


Table B-1 BUC specification tables
Frequency Range (MHz)
Input Output Low LO
Intelsat 950 to 1525 5850 to 6425 4900
Insat 1100 to 1400 6725 to 7025 5625
ST-1 / Palapa C 1150 to 1450 6425 to 6725 5275
Full C 950 to 1825 5850 to 6725 4900
Transmit
Rated Output 20W 43dBm
Power
25W 44dBm
30W 44.3dBm
40W 46dBm
50W 47dBm
60W 47.8dBm
Small Signal 20W 70dB (Typ)
Gain
25W 70dB (Typ)
30W 70dB (Typ)
40W 73dB (Typ)
50W 73dB (Typ)
60W 73dB (Typ)
Power 20W 144W @ 48VDC input
Consumption
25W 153.6W @ 48VDC input
(typ)
30W 153.6W @ 48VDC input
40W 300W @ 48VDC input
50W 300W @ 48VDC input
60W 300W @ 48VDC input
Gain Flatness ± 2.0 dB over the O/P frequency band
Gain Variation ± 2.0 dB over the operating temperature range
O/P Spurious According to EN301443

IM02960153 Rev. F 95
Appendix B Unit Specifications & Outline

Phase Noise @1kHz offset -73 dBc/Hz


@10kHz offset -83 dBc/Hz
@100kHz offset -93 dBc/Hz
Input VSWR 2:0:1 max
Input Interface 50Ω N-type Female / 75Ω F-type Female (Optional)
Output Interface WR 137G / 50Ω N-type Female (Optional)
Environmental
Operating -40°C to +60°C
Temperature
Relative Up to 100%
Humidity Weather Protection sealed to IP65
External Reference
Frequency 10MHz
Power -5 to +5 dBm
External -150dBc/Hz
Reference Phase
-155dBc/Hz
Noise
Requirement @ -160dBc/Hz
Frequency
Offset
Monitor and Control
Monitor BUC Temperature
LO unlocked alarm
Status alarm
RF Output Power
LED Status Indicator
Control Adjustable gain with 0.5dB step size
RF output mute
Interface RS232/485 (Standard)
SNMP/HTTP (Optional)
Power Supply
Operating 230VAC (range 90 to 264VAC)
Voltage (AC
Integrated)
Operating 48VDC (range 38 to 60VDC)
Voltage (DC)
Power Supply 3 pins DC Connector (optional common input via IFL)
Interface (DC)
Mechanical
Dimensions 235L x 175W x150H mm (AC Integrated model)
(LxWxH) 235L x 175W x90H mm
Weight 5.7kg / 12.6lbs (AC Integrated model)
3.9kg / 8.6lbs
Colour White Powder Coat

96 IM02960153 Rev. F
Appendix B: Unit Specifications & Outline

B.2 Unit Outline Drawings

Figure B-1 20W – 60W AC Integrated C-BUC outline drawing

IM02960153 Rev. F 97
Appendix B Unit Specifications & Outline

87.20
37.90
120

171

249.59
232.70

120
37.90

Figure B-2 20W – 60W C-BUC outline drawing

98 IM02960153 Rev. F
Appendix C Compliance Standards

IEC 609501  2nd Edition International Safety Standard for


Information Technology Equipment
ETSI EN 301 489-12 Electromagnetic Compatibility and Radio
Spectrum Matters (ERM); ElectroMagnetic
Compatibility (EMC) Standard for radio
equipment and services; Part 12:
Specific conditions for Very Small Aperture
Terminal, Satellite Interactive Earth
Stations operated in the frequency ranges
between 4 GHz and 30 GHz in the fixed
Satellite Service (FSS)
ETSI EN 301 489-1 Electromagnetic Compatibility and Radio
Spectrum Matters (ERM); ElectroMagnetic
Compatibility Standard for Radio Equipment
and Services
FCC Part 15 Class B Two levels of radiation and conducted
emissions limits for unintentional radiators
(FCC Mark)

IM02960153 Rev. F 99
Appendix D Document Revision Log

Revision Date Description


C February 2012 New format with additional
information on redundancy setup,
SNMP, etc.
D May 2013 Removed AMC300 content.
Added Agilis EMS Software
content.
Updated Block Diagrams and
System Connectivity Diagrams.
E June 2013 Added information about the C-
BUC with AC Integrated PSU.
Added information about the 20W,
25W, and 30W Medium Power C-
BUC.
Updated the Connectivity
Diagrams.
F October 2013 Added the ALBX90 ordering
information.
Updated the M&C pin-out
configuration details.
Added information about the HTTP
WebUI device configuration.

IM02960153 Rev. F 100


C-BUC Stand Alone System Configuration (AC Integrated)

L-band, 10MHz C-BUC


Modem A RF IN

AC Power Source TPB 1 4 RF OUT


AC IN RF OUT
To Feed

PC 3 2 M&C
USB RS485

LIST OF ACCESSORIES LIST OF SYSTEM COMPONENTS


Item No. Agilis Part No. Description Length (m) Quantity Agilis Part No. Description Quantity
1 1001520980 AC Power Cable with T.P.B 2 1 ALBX90 C-BUC 1
2 2502041169 C/A FOR M&C VSAT (ETH, RS485) - 1
3 6103480008 CONVERTER USB TO RS485 - 1
4 4203490057 WR137 C-BD TX WG FLEXIBLE 1M 1 1
GROOVED (Optional)
RF Cable (L-Band) from Indoor to To be arranged by
A -
Outdoor, N(M) to N(M) the customer
Note: These tables list the typical accessories for this setup. Depending on your purchase order, your BUC package may not include certain optional items.
Please contact Agilis if you wish to purchase any of the accessories.

IM02960153 Rev. F 101


102 IM02960153 Rev. F
C-Band Stand Alone LNB System

LNB
L-band From
Modem 1 N(F) WR229 Antenna
10MHz, DC RF IN Feed

LIST OF ACCESSORIES
Item No. Agilis Part No. Description Length (m) Quantity
1 - To be arranged by the customer - -
- ACA11XXXXX C-Band LNB - 1
Note: These tables list the typical accessories for this setup. Depending on your purchase
order, your BUC package may not include certain optional items.
Please contact Agilis if you wish to purchase any of the accessories.

IM02960153 Rev. F 103


C-BUC 1:1 System Configuration (AC Integrated)

T.P.B 1

L-Band
Modem
AC IN
RS485+ Status
3 M&C RF OUT 7
A
WR137 TX WG
IF IN M&C_A L-band, 10MHz
BUC_A 4 IF IN C-BUC A 9 Switch
AC Source 1 Port 2
T.P.B 1 AC 1
SW1 5
T.P.B 1 AC 2 RCU-T
AC Source 2 6 RF OUT
Form C Port 3 Port 1 To Feed
L-band, 10MHz Termination
BUC_B
PC 2 8 M&C
USB RS485 M&C_B Port 4
4 IF IN C-BUC B
9

RS485+ Status
3 M&C RF OUT 7
AC IN

T.P.B 1

LIST OF ACCESSORIES LIST OF SYSTEM COMPONENTS


Item No. Agilis Part No. Description Length (m) Quantity Agilis Part No. Description Quantity
1 1001520980 AC Power Cable with T.P.B 2 4 ALBX90 C-BUC 2
2 6103480008 USB to RS485 Converter - 1 5903290003 WR137 Waveguide Switch 235VAC 1
3 2 2 CPRG W/4 GASKETS
2502040561 C/A RCU to BUC 2M
AAV610XXXX-T Redundancy Control Unit-T 1
4 2502040137 CABLE ASSY RF RFT TO SSPA/LNA 3 2
5 2502040155 TX Cable WG SW M&C 3 1 Note: These tables list the typical accessories for this setup. Depending on your purchase
6 4203490042 WR137 C-BD TX SW 150W LOAD - 1 order, your BUC package may not include certain optional items.
7 4203490022 WR137 Waveguide H-Bend 80mm Indoor - 2 Please contact Agilis if you wish to purchase any of the accessories.
8 2502041169 C/A FOR M&C VSAT (ETH, RS485) - 1
9 4203490055 WR137 C-BD TX WG FLEXIBLE (optional) - 2
A RF Cable (L-Band) from Indoor to To be arranged by
Outdoor, N(M) to N(M) the customer
- 2503160152 Accessories for C-BD 20 to 60W 1+1 - 1
- 2503160038 BUC Feed Mounting Accessories - 2
- 2503160097 Mounting Kit for RCU - 1

104 IM02960153 Rev. F


IM02960153 Rev. F 105
20W to 60W C-BUC 1:1 System Configuration

Status
8

L-Band IN
Modem
M&C
Status
IF IN RF 7
A 4 C-BUC A OUT
DC WR137 TX WG
M&C_A L-band, 10MHz
IF IN Switch
BUC_A PSU 9
AC Source 1 Port 2
T.P.B 1 AC 1
SW1 5
T.P.B 1 AC 2 RCU-T
AC Source 2 6
Port 1
Form C Port 3 RF OUT
L-band, 10MHz
BUC_B PSU 9 Termination To Feed
USB 2 3 M&C
M&C_B Port 4
4 DC
PC Status IF IN C-BUC B RF 7
OUT
M&C

8
Status

LIST OF ACCESSORIES LIST OF SYSTEM COMPONENTS


Item No. Agilis Part No. Description Length (m) Quantity Agilis Part No. Description Quantity
1 1001520980 AC Power Supply 220VAC 3M for RCU 3 1 ALBX90 C-BUC 1
2 6103480008 Converter RS485 to USB - 1 AAV610XXXX-T Redundancy Control Unit 1
3 2502041169 C/A For VSAT SPT to RS485 - 1
4 2502040137 C/A RF RFT TO SSPA / LNA 3M 3 2
5 2502040155 C/A TXSW RCU TO WR137 SW 3M 3 1 Note: These tables list the typical accessories for this setup.
6 2503160010 Accessories VSAT RS (2,5,10,20W) - 1 set Depending on your purchase order, your BUC package may not include
WR137 SW certain optional items. Please contact Agilis if you wish to purchase any
7 4203490022 WR137 Waveguide H-Bend 80mm Indoor - 2 of the accessories.

8 2502040561 C/A RCU to BUC 2M - 2


9 2502041185 C/A Power 3Pin (F) to 4PIN (M) 1.5m - 2
(For use with APS)
2502041298 C/A S/PLUG 12-3S TO DC OPEN - 2
5702200003 Power Supply Connector - 2
A - RF Cable (L-Band) To be arranged by
the customer
- 2503160152 Accessories for C-BD 20 to 60W 1+1 - 1
- 2502041166 Ethernet Cable DB9 to RJ45 For SNMP - 1
- config (Optional)
- 2503160038 BUC Feed Mounting Accessories - 2
- 2503160097 Mounting Kit for RCU - 1

106 IM02960153 Rev. F


IM02960153 Rev. F 107

Anda mungkin juga menyukai