Important document information Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Symbol Meaning
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
Reference to page
Refers to the corresponding page number.
A0011195
Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196
Write-protected parameter
Indicates a parameter that can be locked against changes by entering a user-specific code.
A0013144
Symbol Meaning
A, B, C, ... Views
Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
4 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu
Endress+Hauser 5
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
6 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu
Endress+Hauser 7
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Expert → Sensor → Tank bottom evaluation → Tank bottom range 1149 (→ 94)
8 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu
Endress+Hauser 9
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Expert → Analog inputs → Analog input 1...6 → Tag description 1562 (→ 121)
10 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu
Expert → Discrete inputs → Discrete input 1...4 → Tag description 2201 (→ 139)
Endress+Hauser 11
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Expert → Analog outputs → Analog output 1...4 → Tag description 1667 (→ 150)
12 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu
Expert → Discrete outputs → Discrete output 1...4 → Tag description 1721 (→ 162)
Endress+Hauser 13
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Display channel 1 -
Display channel 2 -
Display channel 3 -
Display channel 4 -
14 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu
Endress+Hauser 15
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Expert → Diagnostics → Advanced diagnostics 1/2 Assign diagnostic signal 11179 (→ 192)
→ 1/2
16 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Prerequisite Only visible for operation via display module, not for operation via software tool (e.g.
FieldCare).
Additional information In this document, the direct access code is indicated in brackets following the parameter
name, e.g. Locking status (0004).
Description Indicates the write protection with the highest priority that is currently active.
Additional information On the display module, the -symbol appears in front of parameters that cannot be
modified since they are write-protected.
Prerequisite Only visible for devices with operating and display module (SD02 or SD03)
Endress+Hauser 17
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Additional information • The access authorization can be changed via the Enter access code parameter
(→ 18).
• If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→ 17).
• If a -symbol appears in front of a parameter, the parameter cannot be changed via
the local display with the current access authorization.
Prerequisite Only visible for operation via operating tool (e.g. FieldCare), not for operation via display
module.
Description Indicates access authorization to parameters via operating tool (e.g. FieldCare).
Additional information If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→ 17).
18 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Additional information For local operation, the customer-specific access code, which has been defined in the
Expert → System → Define access code sequence, has to be entered.
If an incorrect access code is entered, the user retains his current access authorization.
The write protection affects all parameters marked with the -symbol in the document.
On the local display, the -symbol in front of a parameter indicates that the parameter is
write-protected.
If no key is pressed for 10 minutes, or the user goes from the navigation and editing mode
back to the measured value display mode, the device automatically locks the write-
protected parameters after another 60 s.
Please contact your Endress+Hauser Sales Center if you lose your access code.
Endress+Hauser 19
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Submenus
Submenu Meaning Description
Configuration backup • Backup of the device configuration in the display module (→ 29)
display • Copying of the device configuration into another device
20 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Overview
The Display submenu is used to parametrize the representation of measured values on the
local display module. Up to four measured values can be allocated to the local display
module. Additionally, display characteristics such as the format of numbers, the associated
texts or the display contrast can be configured.
Format Display Selection of the display format (number and size of the displayed (→ 22)
measuring values)
Value 1 display Allocation of a measured variable to the first display value (→ 24)
Decimal places 1 Number of decimal places for the first display value (→ 24)
Value 2 display Allocation of a measured variable to the second display value (→ 24)
Decimal places 2 Number of decimal places for the second display value (→ 24)
Value 3 display Allocation of a measured variable to the third display value (→ 24)
Decimal places 3 Number of decimal places for the third display value (→ 24)
Value 4 display Allocation of a measured variable to the fourth display value (→ 24)
Decimal places 4 Number of decimal places for the fourth display value (→ 24)
Display interval Time the individual variables are displayed in the case of an alternating (→ 25)
display
Display damping Time constant for the damping of displayed values (→ 25)
Header text Definition of the header text in the case of Header = Free text (→ 26)
Number format Selection of the number format for distance values (decimal or ft-in-1/16") (→ 27)
Decimal places menu Number of decimals for values in the operating menu (not the measuring (→ 27)
values)
Access status display Displays the user role for operation via the display module (→ 17)
Endress+Hauser 21
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description of parameters
Language (0104)
Options • English
• One additional operating language (see product structuture, feature 500, "Additional
Operation Language")
22 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
4841.000
1 Â mm
A0019963
1 bargraph + 1 value
1 Â
93.5 %
1 Â 159.0
mm
A0019964
2 values
1 Â 93.5
%
1 Â 159.0
mm
A0019965
1 Â 159.0 mm
V 1 Â 23.5 V
1 Â 93.5
%
A0019966
4 values
1 Â 93.5 %
1 Â 159.0 mm
V 1 Â 93.5 V
1 Â 26.3 °C
A0019968
• The Value 1 display - Value 4 display parameters are used to specify what
measured values are shown on the display and in what order (→ 24).
• If more measured values are specified than the display mode selected permits, the
values alternate on the device display. The display time until the next change is
configured using the Display interval parameter (→ 25).
Endress+Hauser 23
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Select the measured value that is shown on the local display.
Options • None 1)
• Level linearized
• Distance
• Terminal voltage
• Electronics temperature
• Absolute echo amplitude
• Relative echo amplitude
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
• Analog output 1
• Analog output 2
• Analog output 3
• Analog output 4
Additional information The Format display parameter is used to specify how many measured values are displayed
simultaneously and how (→ 22).
Prerequisite A measured value is specified in the Value 1/2/3/4 display parameter (→ 24).
Description Select the number of decimal places for the display value.
24 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options •x
• x.x
• x.xx
• x.xxx
• x.xxxx
Additional information This setting does not affect the measuring or computational accuracy of the device.
Description Set time measured values are shown on display if display alternates between values.
Input range 1 to 10 s
Facotry setting 5s
Additional information An alternating display only occurs automatically if the number of measured values defined
exceeds the number of values the selected display format can display simultaneously.
• The Value 1 display - Value 4 display parameters are used to specify what
measured values are shown on the display (→ 24).
• The display format of the displayed measured values is specified using the
Format display parameter (→ 22).
Factory setting 0 s
Header (0097)
Endress+Hauser 25
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Additional information
1 XXXXXXXXX
A0013375
Device tag
Is defined in the Setup → Device tag parameter.
Free text
Is defined in the Header text parameter (→ 26).
Prerequisite The Free text option is selected in the Header parameter (→ 25).
Input range Max. 12 characters, such as letters, numbers or special characters (e.g. @, %, /)
Additional information
1 XXXXXXXXX
A0013375
User entry
The number of characters displayed depends on the characters used.
Separator (0101)
26 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options • . (point)
• , (comma)
Options • Decimal
• ft-in-1/16" (Only valid for distance units)
Description Select number of decimal places for the representation of numbers within the operating
menu.
Options •x
• x.x
• x.xx
• x.xxx
• x.xxxx
Additional information This parameter only determines the representation of numbers within the operating menu
(e.g. Empty calibration, Full calibration). It does not affect the measured value
representation.
For measured values, the number of decimal places is defined in the Decimal places 1 to
Decimal places 4 parameters (→ 24).
This setting does not affect the measurement and calculation accuracy of the device.
Endress+Hauser 27
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Adjust local display contrast setting to ambient conditions (e.g. lighting or reading angle).
Input range 20 to 80 %
Factory setting 30 %
Backlight (0111)
Prerequisite Only visible if the display module SD03 with optical keys is connected (SD02 with push
buttons does not have a backlight).
Options • Disable
• Enable
28 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Overview
All software configurations are initially stored in a memory module (HistoROM) in the
housing and are thus permanently connected with the device. As an additional option, the
display module contains a backup memory for the device configuration. The transmission
of configuration data between these two memory modules is controlled by the
Configuration backup display submenu. It provides the following options:
• Backup of a configuration from the device into the display module.
• Restore a device configuration.
This option can be used to restore a configuration back into the device which has
previously been saved in the display module.
• Duplicate a device configuration.
If the configuration has been saved into the display module, the module can be
connected to a different device and the configuration can be duplicated to this device.
This allows to efficiently configure a number of devices in the same way.
• Compare the configurations in the device and in the display module.
The comparison result indicates whether the device configuration has been changed
since the last backup.
Operating time Displays the operating time since the first setup. (→ 30)
Last backup Displays at which time the last backup has been performed. (→ 30)
Endress+Hauser 29
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description of parameters
Display format Days (d), hours (h), minutes (m) and seconds (s)
Description Indicates the operating time at which the last data backup was saved to the display
module.
Display format Days (d), hours (h), minutes (m) and seconds (s)
Description Select action for managing the device data in the display module.
30 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options • Cancel
No action is executed and the user exits the parameter.
• Execute backup
A backup copy of the current device configuration in the HistoROM (built-in in the
device) is saved to the display module of the device. The backup copy comprises the
transmitter and sensor data of the device.
• Restore
The last backup copy of the device configuration is copied from the display module to the
HistoROM of the device. The backup copy comprises the transmitter and sensor data of
the device.
• Duplicate
The transmitter configuration is duplicated to another device using the transmitter
display module.
• Compare
The device configuration saved in the display module is compared to the current device
configuration of the HistoROM.
• Clear backup data
The backup copy of the device configuration is deleted from the display module of the
device.
HistoROM
A HistoROM is a non-volatile device memory in the form of an EEPROM.
While the respective action is in progress, the configuration cannot be edited via the
local display and a message on the processing status appears on the display.
Prerequisite Only visible in the operating tool (not on the local display)
Endress+Hauser 31
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Additional information The comparison is started via the Compare option in the Configuration
management parameter (→ 30).
32 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Overview
The Administration submenu contains all parameters for the management of the device.
Its structure depends on the user interface:
Define access code → Define By defining a user-specific acces code the device configuration (→ 34)
access code can be protected against unintended changes.
Define access code → Confirm The access code defined in Define access code must be (→ 34)
access code confirmed by repeating it in this parameter.
Define access code By defining a user-specific acces code the device configuration can be (→ 34)
protected against unintended changes.
Endress+Hauser 33
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Navigation Expert → System → Administration → Define access code → Define access code
Expert → System → Administration → Define access code
Description Define user-specific access code in order to protect the device against unintended changes.
Factory setting 0
Additional information If the factory setting is not changed or 0 is defined as the access code, the parameters are
not write-protected and the configuration data of the device can then always be modified.
The user is logged on in the role of Maintenance .
The write protection affects all parameters marked with the symbol in the
document. On the local display, the symbol in front of a parameter indicates that the
parameter is write-protected.
Once the access code has been defined, write-protected parameters can only be
modified if the access code is entered in the Expert → Enter access code parameter.
Please contact your Endress+Hauser Sales Center if you lose your access code.
For display operation: The new access code is only valid after it has been confirmed in
the Confirm access code parameter and after the user has returned to the main
screen (measured value display).
Navigation Expert → System → Administration → Define access code → Confirm access code
Prerequisite Only visible for operation via display module, not for operation via operating software (e.g.
FieldCare).
Description Confirm the access code by repeating the value entered in the Define access code
parameter.
Factory setting 0
1) This sequence only exists for operation via the display module. For operation via operating software (e.g. FieldCare), the "Define access code"
parameter is located directly in the "Administration" submenu.
34 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Further parameters
Description Use this function to reset the device configuration - either entirely or in part - to a defined
state.
Options • Cancel
No action is executed and the user exits the parameter.
• To factory defaults
Every parameter is reset to the order-code specific factory setting.
• To delivery settings
Every parameter is reset to the delivery setting. The delivery setting may differ from the
factory default if customer specific settings have been ordered.
• Of customer settings
Every customer parameter is reset to its factory setting. Service parameters, however,
retain their current value.
• To transducer defaults
Every measurment-related parameter is reset to its factory setting. Service parameters
and communication-related parameters, however, retain their current value.
• Restart device
The restart resets every parameter whose data are in the volatile memory (RAM) to the
factory setting (e.g. measured value data). The device configuration is not modified.
Endress+Hauser 35
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
3.2.1 Overview
The Sensor submenu contains all parameters related to the measurement and the sensor
settings.
Parameters
Parameter Meaning Description
Distance unit Measuring unit for basic distances (e.g empty and full calibration) (→ 37)
Temperature unit Measuring unit for temperatures (e.g. sensor temperature, (→ 37)
electronics temperature)
Tank type Selection of the tank type (for liquid measurements) (→ 37)
Tube diameter Specification of the bypass or stilling well diameter (for liquid (→ 38)
measurements)
Bin property Selection of the bin type (for solid measurements) (→ 38)
Max. filling speed liquid Specification of the maximum filling speed (for liquid (→ 39)
measurements)
Max. draining speed liquid Specification of the maximum draining speed (for liquid (→ 39)
measurements)
Max. filling speed solid Specification of the maximum filling speed (for solid (→ 39)
measurements)
Max. draining speed solid Specification of the maximum draining speed (for solid (→ 40)
measurements)
Submenus
Submenu Meaning Description
Linearization Transformation of the measured level into a volume or weight for (→ 54)
arbitrarily shaped vessels
Gas phase Compensation of the influences of a gas or steam above the measured (→ 78)
compensation medium.
Sensor diagnostics Informs about the state of the probe and the HF cable. (→ 85)
Safety settings Defines the behavior of the device in critical situations (e.g. lost echo, (→ 86)
level in safety distance).
Tank bottom Evaluation of echoes in the proximity of the tank bottom (→ 94)
evaluation
Echo tracking Tracking of level, interface, multiple and interference echos in order to (→ 95)
identify the correct echo unambiguously.
36 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options • mm
•m
• ft
• in
Factory setting m
Options • °C
• °F
•K
• °R
Factory setting °C
Endress+Hauser 37
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Additional information Depending on the Tank type parameter the parameters Max. filling speed liquid and
Max. draining speed liquid are preset among others.
Additional information The tube diameter must be entered for bypass and stilling well applications in order to
optimally adapt the measurement to the measuring point.
38 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Additional information Depending on the Bin type parameter, the parameters Max. filling speed solid and Max.
draining speed solid are preset, among others.
Endress+Hauser 39
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Additional information The Max. filling speed solid parameter must be set according to the actual process
velocity.
Additional information The Max. draining speed solid parameter must be set according to the actual process
velocity.
40 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options • None
• Weak signal
• Many obstacles
• Small tanks (< 1m/3ft)
• Changing DC values
• Foam (> 5cm/0.16ft)
Description Indicates whether parameters have been changed after the basic setup.
Additional information Indicates whether a setting which depends on the application parameters (e.g. "Process
property", Advanced process conditions", "Tank type" and "Pipe diameter") has been changed
after the basic setup.
• Changed
Parameters have been changed. The device is no longer in the state defined by the
application parameters.
• Not changed
There have been no changes. The device is still in the state defined by the application
parameters.
Endress+Hauser 41
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Overview
The Medium submenu is used to specify the relevant properties of the measured medium,
especially the dielectric constant (DC).
Description of parameters
42 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Additional information If required, smaller DC values can be entered into Expert → Sensor → Medium → Medium
property. This, however, may reduce the measuring range.
Refer to the Technical Information (TI) of the respective device.
Options • Unknown
• DC 1.4 to 1.6
• DC 1.6 to 1.9
• DC 1.9 to 2.5
• DC 2.5 to 4
• DC 4 to 7
• DC 7 to 15
• DC > 15
Additonal information Dielectric constants of important media commonly used in the industry are
summarized in the document SD106F, which can be downloaded from the Endress
+Hauser web page (www.endress.com).
Additional information Indicates a DC value calculated by the device. The calculation is only possible for small DC
values as it requires the tank bottom signal.
Endress+Hauser 43
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Overview
The Level submenu is used to parametrize the calculation of the level from the measured
distance.
1 2 3 4 5
R
L 100%
D
D
100%
D0
100% B
E A DL
D0 D L0 L0 B L
F
DD 0%
t A
0% 0%
A0016141
44 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description of parameters
Additonal Information The value speicified in this parameter is added to the measured distance between the
reference point of the measurement and the level echo.
• Positive values increase the distance and thus decrease the level.
• Negative values decrease the distance and thus increase the level.
R R
D0
D0
D
DD(<0)
DD(>0)
A0016081
A value entered into this parameter is taken into account in the calculation of the
level. However, it does not influence the indicated distance.
Distance (2231)
Endress+Hauser 45
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
A0019483
A0019485
Additional information The value is displayed in the selected "Level unit" (→ 48).
46 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
0%
A0019486
0%
A0019488
Endress+Hauser 47
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
0%
A0019487
100%
0%
A0019489
Options •%
•m
• mm
• ft
• in
Factory setting %
Additional information The level unit may differ from the distance unit defined in the Distance unit parameter
(→ 37):
• The distance unit is used for the basic calibration ("Empty calibration" and "Full
calibration").
• The level unit is used to display the (unlinearized) level.
48 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options • Off
• Low limit
• High limit
• Low and high limit
Additional information The parameter determines to which direction the level is limited. The exact limits are
defined in the High limit and Low limit parameters.
A B C
L L L
100% 100% 100%
1 1
a a
2 2 2 2
b b
0% 0% 0%
t 1 t 1 t
A0016083
3 Effect of the parameters "Level limit mode", "High limit" and "Low limit"
A Level limit mode = High limit
B Level limit mode = Low limit
C Level limit mode = Low and high limit
a High limit
b Low limit
1 Level before limitation
2 Level after limitation
Prerequisite Level limit mode = High limit or Low and high limit
Endress+Hauser 49
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Additional information Levels exceeding the value specified in this parameter will be ignored. Instead, the device
uses the value specified in this parameter (for measured value transformation and output).
Prerequisite Level limit mode = Low limit or Low and high limit
Factory setting 0%
Additional information Levels falling below the value specified in this parameter will be ignored. Instead, the
device uses the value specified in this parameter (for measured value transformation and
output).
50 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Factory setting 0%
Additional information The value specified in this parameter is added to the measured level (before linearization).
Options • Ullage
• Level linearized
100%
B
A
0%
A0016086
Level (2319)
Endress+Hauser 51
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
0%
A0019482
L
0%
A0019484
Additional information The value is displayed in the selected "Level unit" (→ 48).
Additional information The unit of this parameter is defined in the Unit after linearization parameter
(→ 57).
Tank/silo height
52 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Total height of the tank or silo as measured from the process connection.
A0019867
E Empty calibration
1 Tank/Silo height
0%
A0019868
E Empty calibration
1 Tank/Silo height
Endress+Hauser 53
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Overview
2
A
L
100%
L 1 B L‘
0%
M L‘
L
100%
C L2
L1
0% L‘1L‘2 L‘
L
100%
H
D
0% M L‘
L
100%
h
E
0% M L‘
L
100%
F
h
0% M L‘
L
100%
G d
0%
M L‘
L
100%
H d
0%
M L‘
A0019648
5 Linearization: Transformation of the level into a volume or weight; the transformation is dependent on
the shape of the vessel.
1 Selection of linearization type and unit
2 Parametrization of the linearization
A Linearization type = None
B Linearization type = Linear
C Linearization type = Table
D Linearization type = Pyramid bottom
E Linearization type = Conical bottom
F Linearization type = Angled bottom
G Linearization type = Horizontal cylinder
H Linearization type = Sphere
L Level before linearization (measured in level unit)
L' Level after linearization (corresponds to volume or weight)
M Maximum value
d Diameter
h Intermediate height
54 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Diameter (→ 59)
Level (→ 61)
1) Only for operation via operating tool (e.g. FieldCare), not on the local display module
Endress+Hauser 55
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description of parameters
Options • None
The level is transmitted to the output 100%
without linearization.
• Linear (A) A
• Table (B)
• Pyramid bottom (C) 0%
• Conical bottom (D)
• Angled bottom (E) 100%
• Horizontal cylinder (F)
• Sphere (G) B
0%
100%
C/D
0%
100%
0%
100%
F/G
0%
A0013299
56 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Endress+Hauser 57
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Prerequisite Only visible if a linearization has been selected (i.e. Linearization type ≠ None)
Factory setting %
Additional information The selected unit is only used to be indicated on the display. The measured value is not
transformed according to the selected unit.
It is also possible to parametrize a distance-to-distance linearization, i.e. a
transformation from the level unit to a different distance unit. To do so, select the
Table linearization mode. In order to define the new level unit, select the Free text
option in the Unit after linearization parameter and enter the unit into the Free text
parameter.
Prerequisite Only visible for operation via operating tool (e.g. FieldCare), not on the local display
module.
58 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Prerequisites Only visible if one of the following linearization types has been selected:
• Linear
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere
Description Definition of the maximum content of the vessel (100%), as measured in the Unit
linearized.
Diameter (2342)
Prerequisites Only visible if one of the following linearization types has been selected:
• Horizontal cylinder
• Sphere
Additional information The value must be specified in the selected distance unit (→ 37).
Endress+Hauser 59
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Prerequisites Only visible if one of the following linearization types has been selected:
• Pyramid bottom
• Conical bottom
• Angled bottom
H
0%
A0013264
Additional information The value must be specified in the selected distance unit (→ 37).
Prerequisite Only visible if the "Table" linearization type has been selected.
Description Defines the method used to enter linearization points into the table.
Options • Manual
The level and the associated linearized value are entered manually for each linearization
point.
• Semi-automatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
• Clear table
Deletes the existing linearization table.
• Sort table
Rearranges the linerization points into an ascending order.
60 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Number of the table point which will be defined by the next two parameters (Level and
Cusotmer value).
Input range 1 to 32
Factory setting 1
Level (2383/2389)
Description Definition or display of the (unlinearized) level of the respective linearization point.
Input range Depending on the parametrized measuring range. See the parameters Empty calibration
(→ 46) and Full calibration (→ 47).
Factory setting 0
Endress+Hauser 61
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Factory setting 0
Prerequisite Only visible if the "Table" linearization type has been selected.
Options • Disable
A linearization is not calculated. If the Linearization type parameter has been set to
Table, the error message F435 is generated.
• Enable
The measured value is linearized according to the table before being sent to the output.
Additional information When editing the table, this parameter is automatically reset to the Disable option. After
finishing the editing procedure it must be set to the Enable option again.
62 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Overview
The Information submenu comprises all display parameters which give information about
the current state of the measurement:
Parameter ParameterDescription
Endress+Hauser 63
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description of parameters
Additional information The signal quality indicated in this parameter always refers to the currently evaluated
echo: either the level echo or the tank bottom echo. To differentiate between these two,
the quality of the tank bottom echo is always displayed in brackets.
64 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Additional information
A0019961
Description Indicates the relative amplitude of the level echo, i.e. the difference between the level echo
and the echo threshold.
In the envelope curve display of FieldCare, the absolute echo amplitude is indicated
instead of the relative amplitude (see the number on the top right of the echo peak in
the example).
Additional information
A0019962
1 The relative echo amplitude is the difference between the weighting curve (blue) and the peak in the envelope
curve (red).
Endress+Hauser 65
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Additional information The tank bottom echo amplitude is only evaluated for media with a small DC value.
Description Indicates which echoes are used for the calculation fo the measured value.
66 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Displays the current measurement frequency (number of pulses per second).
Additional information The unit is defined in the Expert → Sensor → Temperature unit parameter .
Endress+Hauser 67
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Overview
The Sensor properties submenu comprises all parameters which describe the
measurement-related properties of the probe and the envelope curve.
Description This parameter can be switched on in the case of free-field applications (e.g. below a
bridge).
68 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options • No
• Yes
Factory setting No
Endress+Hauser 69
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Overview
The Distance submenu contains all parameters by which the filtering of the raw distance
D1 is controlled. The resulting distance D0 is used for the subsequent level calculation
(→ 44).
1 2
D1 D0
A0016175
70 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Endress+Hauser 71
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Distance (1124)
A0019483
72 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Input range 0 to 60 s
Slow
8s 6s 4s 2s 0s 0s
< 1cm (0,4in)/min
Medium
6s 6s 4s 2s 0s 0s
< 10cm (4in)/min
Standard
4s 4s 4s 2s 0s 0s
< 1m (40in)/min
Fast
2s 2s 2s 2s 0s 0s
< 2m (80in)/min
Very fast
0s 0s 0s 0s 0s 0s
> 2m (80in)/min
No filter / test 0s 0s 0s 0s 0s 0s
Endress+Hauser 73
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Very slow
< 0,5m 180 s 180 s 120 s 60 s 40 s 0s 0s
(1,6ft)/h
Slow
180 s 180 s 120 s 60 s 40 s 0s 0s
< 1m (3,3ft)/h
Standard
120 s 120 s 60 s 60 s 40 s 0s 0s
< 2m (6,5ft)/h
Medium
60 s 60 s 60 s 40 s 40 s 0s 0s
< 4m (13ft)/h
Fast
40 s 40 s 40 s 40 s 20 s 0s 0s
< 8m (26ft)/h
Very fast
0s 0s 0s 0s 0s 0s 0s
> 8m (26ft)/h
No filter / test 0s 0s 0s 0s 0s 0s 0s
2 3
1 t
A0016164
Disadvantages
• The device slows down.
• Fast level changes are registered with a delay.
74 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
D
1
5xt t
A0016169
Endress+Hauser 75
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Slow
30 s 15 s 5s 1s 0s 0s
< 1cm (0,4in)/min
Medium
15 s 15 s 5s 1s 0s 0s
< 10cm (4in)/min
Standard
5s 5s 5s 1s 0s 0s
< 1m (40in)/min
Fast
1s 1s 1s 1s 0s 0s
< 2m (80in)/min
Very fast
0s 0s 0s 0s 0s 0s
> 2m (80in)/min
No filter / test 0s 0s 0s 0s 0s 0s
Very slow
< 0,5m 250 s 200 s 200 s 100 s 50 s 1s 0s
(1,6ft)/h
Slow
200 s 200 s 200 s 100 s 50 s 1s 0s
< 1m (3,3ft)/h
Standard
200 s 200 s 100 s 100 s 50 s 1s 0s
< 2m (6,5ft)/h
Medium
100 s 100 s 100 s 50 s 50 s 1s 0s
< 4m (13ft)/h
Fast
50 s 50 s 50 s 50 s 20 s 1s 0s
< 8m (26ft)/h
Very fast
1s 1s 1s 1s 1s 1s 0s
> 8m (26ft)/h
No filter / test 0s 0s 0s 0s 0s 0s 0s
Additional information Increasing the integration time results in a calmer measuring signal. However, this also
means that the measuring signal indicates level changes with a certain delay.
76 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Defines the distance below the process connection in which no measurement is performed.
BD
A0019492
Endress+Hauser 77
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Overview
High pressures reduce the propagation velocity of the measuring signals in the gas/vapor
above the fluid. This effect depends on the kind of gas/vapor and of its temperature. This
results in a systematic measuring error that gets bigger as the distance increases between
the reference point of the measurement (flange) and the product surface.
°C °F 1 bar (14.5 psi) 10 bar (145 psi) 50 bar (725 psi) 100 bar (1 450 psi) 160 bar (2 320 psi)
310 590 - - - 22 % -
78 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Endress+Hauser 79
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
A
B
B = FA
A0020199
80 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
2
ENDRESS + HAUSER
A0016304
External pressure selector Select the AO block through which the externally (→ 82)
measured pressure is received.
External pressure Displays the pressure read in from the AO block (→ 83)
Suitable value of the gas phase compensation factor for saturated steam in the
temperature range 100 to 350 °C (212 to 662 °F):
F = 0.00505 / bar
Endress+Hauser 81
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Options • Off
The gas phase compensation is deactivated.
• On
This option can only be selected for probes with reference echo. The gas phase
compensation is calculated from the position of this reference echo. The displayed
envelope curve does already contain the correction.
• Without correction
This option can only be selected for probes with reference echo.The correction factor is
calculated from the reference echo but not applied to the measurement.
This option is only used for diagnostic purposes and should not be used for normal
applications. The envelope curve is displayed without the correction.
• External correction
This option can only be selected for devices with PROFIBUS PA or FOUNDATION
Fieldbus. The device receives the externally measured pressure through an AO block and
uses it together with the gas phase compensation factor F to calculate the gas phase
compensation. The displayed envelope curve does already contain the correction.
• Const. GPC factor
The correction factor is a constant defined by the user. A reference echo or an externally
measured pressure are not needed. The displayed envelope curve does already contain
the correction.
Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction
Description Defines the AO block through which the external pressure used for gas phase
compensation is received.
Options • None
• Analog output 1
• Analog output 2
• Analog output 3
• Analog output 4
82 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction
Description Displays the pressure which is currently read-in from the AO block.
Navigation Expert → Sensor → Gas phase compensation → Gas phase compensation factor
Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction
Factory setting 0
Additional information Suitable value for saturated steam in the temperature range 100 to 350 °C (212 to 662 °F):
F = 0.00505 / bar
Endress+Hauser 83
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Input parameter for the actual distance of the reference echo.
Additonal information The distance of the aritificially generated reference echo has to be entered into this
parameter. The reference echo must always be in the gas phase; the level must never rise
above the reference echo.
Werkeinstellung –80 dB
Additonal information Only echoes exceeding the defined threshold are accepted as reference echo.
84 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Beschreibung Displays the noise of signal in the envelope curve (in dB).
Endress+Hauser 85
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Prerequisite Only visible if the Value echo lost option has been selected in the Output echo lost
parameter.
Description Defines the constant output value in the case of a lost echo.
Factory setting 0
Additional information The unit is the same as for the output value:
• Without linearization: As defined in the Level unit parameter .
• With linearization: As defined in the Unit after linearization parameter .
86 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Condition Only visible if the Ramp echo lost option has been selected in the Output echo lost
parameter.
A
C
0%
t
min
A0013269
Additional information • The unit for the slope of the ramp is "percentage of the measuring range per minute" (%/
min).
• For a negative slope of the ramp: The measured value is continuously shifted downwards
until it reaches 0%.
• For a positive slope of the ramp: The measured value is continuosly shifted upwards until
it reaches 100%.
Factory setting 60 s
Additional information After an echo loss, the device waits for the time specified in this parameter before reacting
as specified in the Output echo lost parameter. This helps to avoid interruptions of the
mesurement by short-term interferences.
Endress+Hauser 87
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Factory setting 0m
Additional information The safety distance is measured from the reference point of the measurement (lower edge
of the flange or threaded connection). The safety distance can be used to generate a
warning before the level rises into the blocking distance. The In safety distance parameter
defines the rection of the device if the level rises into the safety distance.
Description Defines the behavior if the level rises into the safety distance.
88 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options • No
The alarm is not rest.
• Yes
The alarm is reset. The measurement is resumed.
Factory setting No
Endress+Hauser 89
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Defines which curves are included in the envelope curve display on the display module.
Additional information The display of the selected curve can be accessed in the following way:
A0014279
90 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Confirmation whether the measured distance matches the actual distance. Depending on
the selection the device automatically determines the range over which the mapping will
be recorded.
Additional information For reference purposes the measured distance is displayed together with this parameter.
If the teaching procedure Distance too small or Distance too big is quit before the
distance has been confirmed, a map is not recorded and the teaching procedure is
reset after 60 s.
Distance (1124)
Endress+Hauser 91
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Prerequisite Only visible if the Manual map option has been selected in the Confirm distance
parameter.
Description Definition of the distance up to which the mapping curve will be recorded.
Additional information The distance is measured from the reference point, i.e. from the lower edge of the
mounting flange or the threaded connection.
For reference purposes the Present mapping parameter is displayed together with this
parameter. Present mapping states up to which distance a mapping has already been
recorded.
Prerequisite Only visible if a value has been entered into the Mapping end point parameter.
92 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Selection • No
The map is not recorded. The device quits the sequence ("End of sequence" is displayed).
• Record map
The map is recorded. When the recording is completed, the new measured distance and
the new mapping range appear on the display. These values must be confirmed by
pressing . The device quits the sequence. ("End of sequence" is displayed.)
• Overlay map
• Factory map
• Delete partial map
Factory setting No
Endress+Hauser 93
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Defines the range (starting from Tank/silo height) in which the tank bottom echo is
searched for.
94 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Factory setting The Evaluation mode parameter is preset depending on the Tank type or Bin type
parameter, respectively.
Endress+Hauser 95
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Overview
The behavior of the sensor can be controlled via two external switch inputs: measurement
can be switched on and off. Furthermore, a specific value can be assigned to the level when
the digital switch signal is present, regardless of the actual filling height.
The parameters
Description External input 1 or 2 is assigned a DO block via which the switch signal is read in.
Options • None
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4
Description Defines the response of the level to the presence of a switch signal at external input 1 or 2.
Options • Off
• Minimum (0%)
• Maximum (100%)
• Hold last value
• Fixed value
96 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Defines the level value in the event of a switch signal at external input 1 or 2.
Factory setting 0
Additional information The specific unit after linearization that has been selected applies.
Description Specifies the DO block via which measurement can be switched on and off.
Options • Manual
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4
Measurement (1082)
Options • On
• Off
Factory setting On
Endress+Hauser 97
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Options • Off
The output is always open (not conductive).
• On
The output is always closed (conductive).
• Event level
The output is normally closed and is only opened if a diagnostic event is present. The
Assign diagnostic level parameter determines at which type of event the output is
opened.
• Limit
The output is normally closed and is only opened if a measured varaible exceeds or falls
below a defined limit. The limit values are defined by the parameters Assign limit ,
Switch-on value and Switch-off value .
• Digital output
The switching state of the output tracks the output value of a DI function block or the DI
output of the advanced diagnostics. The function block is selected in the Assign status
parameter.
Options • Alarm
• Alarm + warning
• Warning
98 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Defines the variable to be checked for limit transgression and allocates it to the switch
output.
Options • Off
No measured variable is allocated.
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
Prerequisite Only visible for Switch output function = Limit and Assign limit ¹ Off.
Description Define the switch-on point and switch-off point for the limit evaluation.
Range of values Depending on the selected measuring variable (Parameter Assign limit).
Factory setting Depending on the selected measuring variable (Parameter Assign limit).
Endress+Hauser 99
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Additional information The switching behavior depends on the relative position of the two switch points.
Switch-on point > Switch-off point:
The output is closed if the measured value exceeds the switch-on point.
The output is opened if the measured value falls below the switch-off point.
B
t
D
t
A0015585
A Switch-on point
B Switch-off point
C Output closed
D Output opened
A
t
D
t
A0015586
A Switch-on point
B Switch-off point
C Output closed
D Output opened
100 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Allocates a DI block or the DI output of the advanced diagnostics to the switch output.
Options • Off
No digital block is allocated.
• Digital output AD 1
• Digital output AD 2
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4
Prerequisite Only visible for Switch output function = Limit and Assign limit ¹ Off.
Factory setting 0s
Prerequisite Only visible for Switch output function = Limit and Assign limit ¹ Off.
Description Defines the delay for the switching off of the output.
Factory setting 0s
Description Defines the switching state of the output in the case of an error.
Endress+Hauser 101
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Options • No
The behavior of the switch output is as described above.
• Yes
The states Opend and Closed are inverted as compared to the description above.
102 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Ident number selector Defines how the device ID number is specified. (→ 105)
Description Displays the address mode. The address mode is defined via address switch 8 in the
connection compartment.
Endress+Hauser 103
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
DIP
8
7
6
5
4
3
ON
98
2
1
A0015686
Address switches in the "OFF" position do not form part of the address. Address switches in
the "ON" position form part of the address as defined in the following list:
• Switch 1: value = 1
• Switch 2: value = 2
• Switch 3: value = 4
• Switch 4: value = 8
• Switch 5: value = 16
• Switch 6: value = 32
• Switch 7: value = 64
Example:
ON DIP
98
1 2 3 4 5 6 7 8
2 + 8 = 10
A0015902
Address switches 2 and 4 are in the "ON" position; all other address switches are in the
"OFF" position
Þ Address = 2 + 8 = 10
104 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options • Profile
The ID number of the PROFIBUS profiles is used.
• Manufacturer
The manufacturer-specific ID number is used.
• Old device
The ID number of the old PROFIBUS profiles (2.x) is used.
• Auto
The ID number can be adapted automatically by a Class I PROFIBUS master.
Endress+Hauser 105
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
CRC count failed Number of failed checksum tests of the data telegram
Good telegrams Number of error-free data telegrams between the two last
failed data telegrams
Additional information It is possible to define which ID number is used under Expert → Communication →
PROFIBUS PA configuration → Ident number selector.
106 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Indicates how often the checksum test of the cyclic data telegram was successful.
Description Indicates how often the checksum test of the cyclic data telegram discovered an error.
Endress+Hauser 107
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Indicates how many error-free data telegrams were transmitted between the two last
failed data telegrams.
Description Displays the current consumption at the PROFIBUS input of the device
Description Displays the current terminal voltage at the PROFIBUS input of the device
108 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Overview
The Physical block submenu is only available if the device is operated via an
operating tool (e.g. FieldCare). It is not available if the device is operated via the
display and operating module.
The Physical block submenu contains the parameters of the Physical block as per the
PROFIBUS profiles:
Endress+Hauser 109
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
The parameters
Strategy (1494)
110 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles
Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
Endress+Hauser 111
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.
Description SOFTWARE_REVISION standard parameter of the Physical block as per the PROFIBUS
profiles
112 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description HARDWARE_REVISION standard parameter of the Physical block as per the PROFIBUS
profiles
Manufacturer ID (1502)
Description DEVICE_MAN_ID standard parameter of the Physical block as per the PROFIBUS profiles
Device ID (1480)
Description DEVICE_ID standard parameter of the Physical block as per the PROFIBUS profiles
Description DEVICE_SER_NUM standard parameter of the Physical block as per the PROFIBUS
profiles
Endress+Hauser 113
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Diagnostics (1482)
Description DIAGNOSIS standard parameter of the Physical block as per the PROFIBUS profiles
Description DIAGNOSIS_EXTENSION standard parameter of the Physical block as per the PROFIBUS
profiles
Description DIAGNOSIS_MASK standard parameter of the Physical block as per the PROFIBUS profiles
114 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description DEVICE_CERTIFICATION standard parameter of the Physical block as per the PROFIBUS
profiles
Description FACTORY_RESET standard parameter of the Physical block as per the PROFIBUS profiles
Options • To defaults
• Warmstart device
• Reset bus address
• Cancel
Descriptor (1489)
Description DESCRIPTOR standard parameter of the Physical block as per the PROFIBUS profiles
Endress+Hauser 115
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description DEVICE_MESSAGE standard parameter of the Physical block as per the PROFIBUS profiles
Description DEVICE_INSTAL_DATE standard parameter of the Physical block as per the PROFIBUS
profiles
Description HW_WRITE_PROTECTION standard parameter of the Physical block as per the PROFIBUS
profiles
116 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Enabled element of the HW_WRITE_PROTECTION parameter in the Physical block as per
the PROFIBUS profiles.
Description COND_STATUS_DIAG parameter in the Physical block as per the PROFIBUS profiles
Options • Off
The classic error message format is used
• On
The abbreviated error message format is used
Endress+Hauser 117
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
3.5.1 Overview
There is an Analog input submenu for each Analog Input block in the device. This
submenu contains the block parameters of the individual block. The parameters of the
Analog Input block are described in the PROFIBUS profile. The most important
characteristics of the parameters are summarized below. An Analog Input block can be
used to scale a measured variable of the device and transmit it via the bus to a PLC, for
example.
Out Value
PROFIBUS
Channel
1 2 3
A0017058
A0016781
The diagram describes the function of the Analog Input block in the normal
operational state (Mode block actual = Auto). The block's behavior in other
operational states is described in the Profibus profiles of the Profibus User
Organization (PNO).
118 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
PV scale upper range PV_SCALE 100% mark for the input value
Out scale lower range OUT_SCALE 0% mark for the output value
Out scale upper range OUT_SCALE 100% mark for the output value
Error handling
Endress+Hauser 119
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Simulation
120 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Strategy (1559)
Endress+Hauser 121
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles
Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
122 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.
Batch ID (1533)
Description Batch_ID element of the BATCH standard block parameter as per the PROFIBUS profiles.
Endress+Hauser 123
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Operation element of the BATCH standard block parameter as per the PROFIBUS profiles.
Description Phase element of the BATCH standard block parameter as per the PROFIBUS profiles.
Navigation Expert → Communication → Analog input 1...6 → Batch recipe unit procedure
Description Rup (Recipe unit procedure) element of the BATCH standard block parameter as per the
PROFIBUS profiles.
124 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Value element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles.
Displays the output value of the Analog Input block.
Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. Only the two quality bits are evaluated in this parameter.
Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. The complete status byte is displayed as a two-digit hexadecimal
number in this parameter.
Endress+Hauser 125
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description EU_at_0% element of the PV_SCALE standard parameter in the Analog Input block as
per the PROFIBUS profiles.
Defines the 0% mark for the measured value.
Description EU_at_100% element of the PV_SCALE standard parameter in the Analog Input block as
per the PROFIBUS profiles.
Defines the 100% mark for the measured value.
Navigation Expert → Communication → Analog input 1...6 → Out scale lower range
Description EU_at_0% element of the OUT_SCALE standard parameter in the Analog Input block as
per the PROFIBUS profiles.
Defines the 0% mark for the output value.
126 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Navigation Expert → Communication → Analog input 1...6 → Out scale upper range
Description EU_at_100% element of the OUT_SCALE standard parameter in the Analog Input block
as per the PROFIBUS profiles.
Defines the 100% mark for the output value.
Description LIN_TYPE standard parameter of the Analog Input block as per the PROFIBUS profiles
Channel (1561)
Description CHANNEL standard parameter of the Analog Input block as per the PROFIBUS profiles.
Assigns a measured variable to the Analog Input block.
Endress+Hauser 127
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Units_Index element of the OUT_SCALE standard parameter of the Analog Input block as
per the PROFIBUS profiles. Specifies the unit of the output value. Here, the units are coded
by a numerical index as per the PROFIBUS profiles.
Description Decimal_Point element of the OUT_SCALE standard parameter of the Analog Input block
as per the PROFIBUS profiles. Defines how many decimal places of the output value should
be considered as valid.
128 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description PV_FTIME standard parameter of the Analog Input block as per the PROFIBUS profiles.
Damping time of the Analog Input block, indicated in seconds.
Factory setting 0s
Description FSAFE_TYPE standard parameter of the Analog Input block as per the PROFIBUS profiles.
Specifies the output value of the Analog Input block in the event of an error.
Description FSAFE_VALUE standard parameter of the Analog Input block as per the PROFIBUS
profiles. Specifies the output value of the Analog Input block in the event of an error.
Endress+Hauser 129
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description ALARM_HYS standard parameter of the Analog Input block as per the PROFIBUS profiles.
Specifies the hysteresis if the output value of the Analog Input block exceeds the limit. The
hysteresis is indicated in the unit of the output value (out unit parameter).
Factory setting 0
Hi Hi lim (1528)
Description HI_HI_LIM standard parameter of the Analog Input block as per the PROFIBUS profiles.
An alarm is generated if the output value of the Analog Input block exceeds this value.
Hi lim (1529)
130 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description HI_LIM standard parameter of the Analog Input block as per the PROFIBUS profiles. A
warning is generated if the output value of the Analog Input block exceeds this value.
Lo lim (1530)
Description LO_LIM standard parameter of the Analog Input block as per the PROFIBUS profiles. A
warning is generated if the output value of the Analog Input block falls below this value.
Lo Lo lim (1531)
Description LO_LO_LIM standard parameter of the Analog Input block as per the PROFIBUS profiles.
An alarm is generated if the output value of the Analog Input block falls below this value.
Endress+Hauser 131
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Value element of the HI_HI_ALM standard parameter of the Analog Input block as per
the PROFIBUS profiles. Displays the output value which caused the alarm to be generated.
Description Alarm_State element of the HI_HI_ALM standard parameter of the Analog Input block
as per the PROFIBUS profiles. Indicates whether an alarm has occurred as a result of the
value exceeding the Hi Hi lim.
Description Value element of the HI_ALM standard parameter of the Analog Input block as per the
PROFIBUS profiles. Displays the output value which caused the warning to be generated.
132 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Alarm_State element of the HI_ALM standard parameter of the Analog Input block as
per the PROFIBUS profiles. Indicates whether a warning has occurred as a result of the
value exceeding the Hi lim.
Description Value element of the LO_ALM standard parameter of the Analog Input block as per the
PROFIBUS profiles. Displays the output value which caused the warning to be generated.
Description Alarm_State element of the LO_ALM standard parameter of the Analog Input block as
per the PROFIBUS profiles. Indicates whether a warning has occurred as a result of the
value falling below the Lo lim.
Endress+Hauser 133
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Value element of the LO_LO_ALM standard parameter of the Analog Input block as per
the PROFIBUS profiles. Displays the output value which caused the warning to be
generated.
Description Alarm_State element of the LO_LO_ALM standard parameter of the Analog Input block
as per the PROFIBUS profiles. Indicates whether an alarm has occurred as a result of the
value falling below the Lo Lo lim.
Description Simulate_Enabled element of the SIMULATE standard parameter in the Analog Input
block as per the PROFIBUS profiles. Enables or disables the simulation of the Analog Input
block. If simulation is enabled, the Analog Input block uses a constant simulation value
instead of the measured value selected in Channel. This value is specified in Simulate
value. The associated status is specified in Simulate status.
Options • Disable
• Enable
134 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Simulate_Value element of the SIMULATE standard parameter in the Analog Input block
as per the PROFIBUS profiles. Specifies the simulation value.
Factory setting 0
Description Simulate_Status element of the SIMULATE standard parameter in the Analog Input
block as per the PROFIBUS profiles. Specifies the status of the simulation value.
Description OUT_UNIT_TEXT standard parameter of the Analog Input block as per the PROFIBUS
profiles. This text is used as a unit if the 1995: Textual unit definition option was selected
in Out unit. In this way it is also possible to transmit units that are not provided in the
PROFIBUS profiles.
Endress+Hauser 135
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
136 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
3.6.1 Overview
There is an Discrete input submenu for each Discrete Input block in the device. This
submenu contains the block parameters of the individual block. The parameters of the
Discrete Input block are described in the PROFIBUS profile. The most important
characteristics of the parameters are summarized below. A Discrete Input block can be
used to transmit a discrete measured variable via the bus to a PLC, for example.
Out Value
PROFIBUS
Channel
1 2 3
A0017058
A0016782
The diagram describes the function of the Discrete Input block in the normal
operational state (Mode block actual = Auto). The block's behavior in other
operational states is described in the Profibus profiles of the Profibus User
Organization (PNO).
Endress+Hauser 137
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Error handling
Simulation
138 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Strategy (2199)
Endress+Hauser 139
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Navigation Expert → Discrete inputs → Discrete input 1...4 → Mode block actual
Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles
Navigation Expert → Discrete inputs → Discrete input 1...4 → Mode block permitted
Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
140 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Navigation Expert → Discrete inputs → Discrete input 1...4 → Mode block normal
Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.
Batch ID (2183)
Description Batch_ID element of the BATCH standard block parameter as per the PROFIBUS profiles.
Endress+Hauser 141
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Operation element of the BATCH standard block parameter as per the PROFIBUS profiles.
Description Phase element of the BATCH standard block parameter as per the PROFIBUS profiles.
Navigation Expert → Discrete inputs → Discrete input 1...4 → Batch recipe unit procedure
Description Rup (Recipe unit procedure) element of the BATCH standard block parameter as per the
PROFIBUS profiles.
142 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Value element of the OUT_D standard parameter in the Discrete Input block as per the
PROFIBUS profiles.
Displays the output value of the Analog Input block.
Description Status element of the OUT_D standard parameter in the Analog Input block as per the
PROFIBUS profiles. Only the two quality bits are evaluated in this parameter.
Navigation Expert → Discrete inputs → Discrete input 1...4 → Out status HEX
Endress+Hauser 143
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. The complete status byte is displayed as a two-digit hexadecimal
number in this parameter.
Channel (2187)
Description CHANNEL standard parameter of the Analog Input block as per the PROFIBUS profiles.
Assigns a switching variable to the Discrete Input block.
Options • None
• Switch output
• Digital output Advanced Diagnostics 1
• Digital output Advanced Diagnostics 2
Invert (2188)
Description INVERT standard parameter of the Discrete Input block as per the PROFIBUS profile.
Enables the inversion of the discrete output signal (the logical states FALSE and TRUE are
swapped).
Options • Off
No inversion
• On
The switching signal is inverted before being transmitted to the bus.
144 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Navigation Expert → Discrete inputs → Discrete input 1...4 → Fail safe type
Description FSAFE_TYPE standard parameter of the Discrete Input block as per the PROFIBUS profiles.
Specifies the output value of the block in the event of an error.
Navigation Expert → Discrete inputs → Discrete input 1...4 → Fail safe value
Description FSAFE_VAL_D standard parameter of the Discrete Input block as per the PROFIBUS
profiles. Specifies the output value of the Discrete Input block in the event of an error.
Endress+Hauser 145
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Simulate_Enabled element of the SIMULATE_D standard parameter in the Discrete Input
block as per the PROFIBUS profiles. Enables or disables the simulation of the Analog Input
block. If simulation is enabled, the Analog Input block uses a constant switching variable
instead of the switching variable selected in Channel. This value is specified in Simulate
value. The associated status is specified in Simulate status.
Options • Disable
• Enable
Description Simulate_Value element of the SIMULATE_D standard parameter in the Discrete Input
block as per the PROFIBUS profiles. Specifies the simulation value.
Factory setting 00
Description Simulate_Status element of the SIMULATE_D standard parameter in the Discrete Input
block as per the PROFIBUS profiles. Specifies the status of the simulation value.
146 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
3.7.1 Overview
There is an Analog output submenu for each Analog Output block in the device. This
submenu contains the parameters of the individual block. The parameters of the Analog
Output block are described in the PROFIBUS profile. The most important characteristics of
the parameters are summarized below.
The device uses the Analog Output block to read in a value, which has been measured
externally, via the bus. This value can be used
• for display on the display module (Expert → System → Display)
• for automatic gas phase compensation in the case of a pressure value (Expert →
Sensor → Gas phase compensation → External pressure selector)
2
ENDRESS + HAUSER
A0016304
14 The level transmitter reads the externally measured pressure via the Analog output block.
1 Level tranmsitter
2 Segment coupler
3 PLC
4 Absolute pressure transmitter
Endress+Hauser 147
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
PV scale
upper range
PV scale
lower range
A0016954
The diagram describes the function of the Analog Output block in the normal
operational state (Mode block actual = Auto). The block's behavior in other
operational states is described in the Profibus profiles of the Profibus User
Organization (PNO).
Input scaling
148 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
PV scale upper range PV_SCALE 100% mark for the input value
Block-specific parameters
Error handling
Block-specific parameters
Output value
Output scaling
Out scale upper range OUT_SCALE 100% mark for the output value
Out scale lower range OUT_SCALE 0% mark for the output value
Endress+Hauser 149
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Strategy (1665)
150 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Navigation Expert → Analog outputs → Analog output 1...4 → Mode block actual
Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles
Navigation Expert → Analog outputs → Analog output 1...4 → Mode block permitted
Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
Endress+Hauser 151
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Navigation Expert → Analog outputs → Analog output 1...4 → Mode block normal
Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.
Batch ID (1633)
Description Batch_ID element of the BATCH standard block parameter as per the PROFIBUS profiles.
152 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Operation element of the BATCH standard block parameter as per the PROFIBUS profiles.
Description Phase element of the BATCH standard block parameter as per the PROFIBUS profiles.
Navigation Expert → Analog outputs → Analog output 1...4 → Batch recipe unit procedure
Description Rup (Recipe unit procedure) element of the BATCH standard block parameter as per the
PROFIBUS profiles.
Endress+Hauser 153
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Navigation Expert → Analog outputs → Analog output 1...4 → Set point value
Navigation Expert → Analog outputs → Analog output 1...4 → Set point status
Navigation Expert → Analog outputs → Analog output 1...4 → PV scale lower range
Description EU_at_0% element of the PV_SCALE standard parameter in the Analog Output block as
per the PROFIBUS profiles.
Defines the 0% mark for the input value.
Navigation Expert → Analog outputs → Analog output 1...4 → PV scale upper range
154 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description EU_at_100% element of the PV_SCALE standard parameter in the Analog Output block
as per the PROFIBUS profiles.
Defines the 100% mark for the input value.
Navigation Expert → Analog outputs → Analog output 1...4 → Fail safe time
Description FSAFE_TIME standard parameter of the Analog Output block as per the PROFIBUS
profiles.
Defines the time (in seconds) between the occurrence of a set point error (set point status
= BAD) and the corresponding response of the AO block.
Factory setting 0
Navigation Expert → Analog outputs → Analog output 1...4 → Fail safe type
Description FSAFE_TYPE standard parameter of the Analog Input block as per the PROFIBUS profiles.
Specifies the output value of the Analog Input block in the event of an error.
Endress+Hauser 155
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Navigation Expert → Analog outputs → Analog output 1...4 → Fail safe value
Description FSAFE_VALUE standard parameter of the Analog Input block as per the PROFIBUS
profiles. Specifies the output value of the Analog Output block in the event of an error.
Factory setting 0
Description Value element of the OUT standard parameter in the Analog Output block as per the
PROFIBUS profiles.
Displays the output value of the Analog Input block.
156 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. Only the two quality bits are evaluated in this parameter.
Navigation Expert → Analog outputs → Analog output 1...4 → Out status HEX
Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. The complete status byte is displayed as a two-digit hexadecimal
number in this parameter.
Navigation Expert → Analog outputs → Analog output 1...4 → Out scale upper range
Description EU_at_100% element of the OUT_SCALE standard parameter in the Analog Output block
as per the PROFIBUS profiles.
Defines the 100% mark for the output value.
Endress+Hauser 157
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Navigation Expert → Analog outputs → Analog output 1...4 → Out scale lower range
Description EU_at_0% element of the OUT_SCALE standard parameter in the Analog Input block as
per the PROFIBUS profiles.
Defines the 0% mark for the output value.
158 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
3.8.1 Overview
There is an Discrete output submenu for each Discrete Output block in the device. This
submenu contains the parameters of the individual block. The parameters of the Discrete
Output block are described in the PROFIBUS profile. The most important characteristics of
the parameters are summarized below.
The device uses the Discrete Output block to read in a discrete value (0-False / 1-
TRUE). This discrete value can be used:
• for transmission via the switch output (terminals 3 and 4 in the connection
compartment). See the operating menu: Expert → Output → Switch output →
Assign status
• for switching the measurement on and off (Expert → Sensor → External input →
Control measurement)
• for transmitting a permanently defined level or interface value, regardless of the
measurement (Expert → Sensor → External input → Level external input /
interface external input)
+
–
3 4 +
–
1 2
Out Value
PROFIBUS
1 2 3
4-
A0017059
15 Transmission of an external discrete value via the switch output of the device
1 PLC
2 Discrete Output block (part of transmitter software)
3 Transmitter
A0017057
Endress+Hauser 159
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Block-specific parameters
Signal inversion
160 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Error handling
Block-specific parameters
Endress+Hauser 161
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Strategy (1719)
162 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Navigation Expert → Discrete outputs → Discrete output 1...4 → Mode block actual
Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles
Navigation Expert → Discrete outputs → Discrete output 1...4 → Mode block permitted
Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
Endress+Hauser 163
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Navigation Expert → Discrete outputs → Discrete output 1...4 → Mode block normal
Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles
Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.
Batch ID (1695)
Description Batch_ID element of the BATCH standard block parameter as per the PROFIBUS profiles.
164 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Operation element of the BATCH standard block parameter as per the PROFIBUS profiles.
Description Phase element of the BATCH standard block parameter as per the PROFIBUS profiles.
Navigation Expert → Discrete outputs → Discrete output 1...4 → Batch recipe unit procedure
Description Rup (Recipe unit procedure) element of the BATCH standard block parameter as per the
PROFIBUS profiles.
Endress+Hauser 165
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Navigation Expert → Discrete outputs → Discrete output 1...4 → Set point value
Navigation Expert → Discrete outputs → Discrete output 1...4 → Set point status
Description Value element of the OUT standard parameter in the Discrete Output block as per the
PROFIBUS profiles.
Displays the output value of the Discrete Input block (0=FALSE or 1=TRUE).
166 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. Only the two quality bits are evaluated in this parameter.
Navigation Expert → Discrete outputs → Discrete output 1...4 → Out status HEX
Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. The complete status byte is displayed as a two-digit hexadecimal
number in this parameter.
Invert (1692)
Description INVERT standard parameter of the Discrete Output block as per the PROFIBUS profile.
Enables the inversion of the discrete output signal (the logical states FALSE and TRUE are
swapped).
Options • Off
No inversion
• On
The switching signal is inverted before being used in the device.
Endress+Hauser 167
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Navigation Expert → Discrete outputs → Discrete output 1...4 → Fail safe time
Description FSAFE_TIME standard parameter of the Discrete Output block as per the PROFIBUS
profiles.
Defines the time (in seconds) between the occurrence of a set point error (set point status
= BAD) and the corresponding response of the DO block.
Factory setting 0
Navigation Expert → Discrete outputs → Discrete output 1...4 → Fail safe type
Description FSAFE_TYPE standard parameter of the Analog Input block as per the PROFIBUS profiles.
Specifies the output value of the Discrete Input block in the event of an error.
Navigation Expert → Discrete outputs → Discrete output 1...4 → Fail safe value
168 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description FSAFE_VALUE standard parameter of the Discrete Input block as per the PROFIBUS
profiles. Specifies the output value of the Discrete Output block in the event of an error.
Factory setting 0
Endress+Hauser 169
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Use this function to display the current diagnostics message. If two or more messages
occur simultaneously, the message with the highest priority is shown on the display.
Information on what is causing the message, and remedy measures, can be viewed via
the symbol on the display.
User interface Symbol for event behavior, diagnostics event, time the event occurred and event text
Description Use this function to display the diagnostics message last displayed before the current
message. This condition can still apply.
Information on what is causing the message, and remedy measures, can be viewed via
the symbol on the display.
User interface Symbol for event behavior, diagnostics event, time the event occurred and event text
170 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Use this function to display the time the device has been in operation since the last device
restart.
User interface Days (d), hours (h), minutes (m) and seconds (s)
Endress+Hauser 171
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Use this function to display the current diagnostics messages with the highest priority to
the fifth-highest priority.
Unser interface Symbol for event behavior, diagnostics event and event text
172 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Use this function to select the category whose event messages are displayed in the events
list.
The status signals are categorized according to NAMUR NE 107: F = failure, M =
maintenance request, C = function check, S = out of specification
Options • All
• Failure (F)
• Mainenance required (M)
• Function check (C)
• Out of specification (S)
• Information (I)
Event list
Description Use this function to display the history of event messages of the category selected in the
Filter options parameter (→ 173). A maximum of 20 event messges are displayed in
chronological order. If the advanced HistoROM function is enabled in the device, the event
list can contain up to 100 entries.
The following symbols indicate whether an event has occurred or has ended:
• : Event has occurred
• : Event has ended
Information on what is causing the message, and remedy measures, can be viewed via
the -button.
User interface • For event messages in category I: information event, event text, "recording event" symbol
and time event occurred
• For event messages in category F, M, C, S (status signal): diagnostic event, event text,
"recording event" symbol and time event occurred
Endress+Hauser 173
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
HistoROM
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.
174 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Device (0011)
Description Use this function to view the serial number of the device. It can also be found on the
nameplate.
Uses of the serial number
• To identify the device quickly, e.g. when contacting Endress+Hauser.
• To obtain specific information on the device using the Device Viewer:
www.endress.com/deviceviewer
User interface Max. 11-digit character string comprising letters and numbers
Description Use this function to view the device firmware version installed.
Description Use this function to view the name of the device. It can also be found on the nameplate.
Endress+Hauser 175
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Use this function to view the order code of the device. It can also be found on the
nameplate. The order code is generated fronm the extended roder code, which defines all
the device features of the product structure. In contrast, only some of the device features
can be read directly from the order code.
Uses of the order code
• To order an identical spare device.
• To identify the device quickly and easily, e.g. when contacting Endress+Hauser.
Description Use these paameters to display the fist, second or third part of the extended order code. On
account of length restrictions, the extended order code is split into a maximum of 3
parameters.
The extended order code indicates the version of all the features of the preoduct structure
for the device and thus uniaquely identifies the device. It canalso be found on the
nameplate.
Uses of the extended order code
• To order an identical spare device
• To check the ordered device features against the shipping note.
Description Use this function to view the version of the electroni nameplate (ENP).
176 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Use this functionto assign a process variable to the data logging channel.
A total of 500 measured values can be logged. This means:
• 500 data points if 1 logging channel is used
• 250 data points if 2 logging channels are used
• 166 data points if 3 logging channels are used
• 125 data points if 4 logging channels are used
Once the maximum number of data points is reached, the oldest data points in the data log
are cyclically overwritten in such a way that the last 500, 250, 166 or 125 measured
values are always in the log (ring memory principle).
The log contents are cleared if the option selected is changed.
Auswahl • Off
• Level
• Distance
• Current output 1
• Measured current
• Terminal voltage
• Electronics temperature
• Absolute echo amplitude
• Relative echo amplitude
• Signal noise
Endress+Hauser 177
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Definition of the logging interval tlog for data logging. This defines the interval between
the individual data points in the data log, and thus the maximum loggable process time
Tlog.
• If 1 logging channel is used: T log = 500 ⋅ t log
• If 2 logging channels are used: T log = 250 ⋅ t log
• If 3 logging channels are used: T log = 166 ⋅ t log
• If 4 logging channels are used: T log = 125 ⋅ t log
Once this time elapses, the oldest data points in the data log are cyclically overwritten such
that a time of Tlog always remains in the meory (ring memory principle).
Nach Ablauf dieser Zeit werden die ältesten im Speicher vorhandenen Datenpunkte
zyklisch überschrieben, so dass immer eine Zeit von Tlog im Speicher bleibt (Ringspeicher-
Prinzip).
The log contents are cleared if the length of the logging interval is changed.
Factory setting 10 s
Options • Cancel
The data are not cleared. All the data are retained.
• Clear data
The logging data are cleared. The logging process starts from scratch.
178 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Use this function to view the measured value trend for the logging channel in the form of a
chart.
A0013859
• x-axis: depending on the number of channels selected displays 250 to 1000 measured
values of a process variable.
• y-axis: displays the approximate measured value span and constantly adapts this to the
ongoing measurement.
The process variable whose measured valu curve is displayed is specified in the Assign
channel 1 - Assign channel 4 parameters .
Endress+Hauser 179
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Use this parameter to view the maximum level measured until now (drag indicator).
Description Use this parameter to view the operating time at which the maximum level has been
measured.
Description Use this parameter to view the minimum level measured until now (drag indicator).
Description Use this parameter to view the operating time at which the minimum level has been
measured.
180 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Use this parameter to view the maximum draining speed measured until now (drag
indicator).
Description Use this parameter to view the maximum filling speed measured until now (drag
indicator).
Description Use this parameter to view the maximum electronics temperature measured until now
(drag indicator).
Description Use this parameter to view the operating time at which the maximum electronics
temperature has been measured.
Endress+Hauser 181
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Description Use this parameter to view the minimum electronics temperature measured until now
(drag indicator).
Description Use this parameter to view the operating time at which the minimum electronics
temperature has been measured.
182 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Description Use this function to select a process variable for the simulation process that is activated.
The display alternates between the measured value and a diagnostics message of the
"function check" category (C) while simulation is in progress.
The simulation value of the selected process variable is defined in the Value process
variable parameter.
Options • Off
• Level
• Level linearized
Prerequisite One of the following options is selected in the Assign simulation process variable
parameter:
• Level
• Level linearized
Beschreibung Use this function to enter a simulation value for the selected process variable. Subsequent
measured value processing and the signal output use this simulation value. In this way,
users can verify whether the measuring device has been configured correctly.
Factory setting The current value of the selected process variable at the moment the simulation is
activated.
Description Use this parameter to activate or deactivate the simulation of the switch output.
Endress+Hauser 183
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Auswahl • Off
• On
Description Use this parameter to define the switch status for the simulation.
Auswahl • Open
• Closed
Werkseinstellung Open
Description Use this function to switch the device alarm on and off. In this way, users can verify the
correct adjustment of the current output and the correct function of downstream switching
units.
The display alternates between the measured value and a diagnostics message of the
"function check" category (C) while simulation is in progress:
Options • On
• Off
184 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Selection • No
No device check is performed.
• Yes
A device check is performed.
If the error S941 "Echo lost" is present, a device check is not possible. First you have to
eliminte the cause of this error.
Factory setting No
Display • Installation ok
• Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the
signal amplitudes.
• Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check
the mounting position of the device and the dielectric constant of the medium.
• Check not done
Description Displays the operating time at which the last device check has been performed.
Description Displays the result of the device check for the level signal.
Endress+Hauser 185
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
186 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Basic principles
The Advanced Diagnostics offers additional options to monitor the process. The device
contains two Advanced Diagnostics Blocks which can be used separately or in combination.
A measuring variable can be assigned to the input of each Advanced Diagnostics Block.
Based on a freely configurable time interval, the variable can be submitted to a statistical
function (e.g. maximum, minimum, mean, slope). Finally, a limit detection can be
parametrized and its result can be transmitted to a digital output.
The result can be displayed and evaluated by a DCS or PLC. If required, it can also be linked
to the second Advanced Diagnostics block and thus it is possible to combine the two results
by the logical operators AND or OR.
Endress+Hauser 187
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
A A
85%
75%
A0019640
188 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Endress+Hauser 189
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
A L
1
1.2 1.5 2.7 2.8
1.3 2.6
L 1.1
1.4
2
2.2 2.4
A 2.1 2.5
2.3
A0019641
190 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Parameter Description
Hysteresis1/2 (→ 195)
Endress+Hauser 191
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
The parameters
Descriptions Assigns a measuring variable, which is needed for diagnostic purposes, to the Advanced
Diagnostics Block.
Options • None
• Level linearized
• Unfiltered distance
• Relative echo amplitude
• Electronic temperature
• Measured current
• Terminal voltage
• Area of incoupling
Descriptions Links the Advanced Diagnostics Block 1 or 2 to the other Advanced Diagnostics Block in
order to include the linking logic into the configuration (→ 187).
Options • None
• Digital output AD 1
• Digital output AD 2
Prerequisite Only visible if the Advanced Diagnostics Block has been linked to the digital oputput of the
other Advanced Diagnostics Block via the Link AD 1/2 to parameter.
Descriptions Defines the linking logic between the two Advanced Diagnostics Blocks AD1 and AD2.
192 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Options • AND
• OR
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Factory setting 10 s
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Defines, which quantity is derived from the assigned measured variable.
Options • Off
• Maximum
• Minimum
• Mean
• Standard deviation
• Difference Max. - Min.
• Slope
Additional information The calculation is performed based on the defined Sample time. (I.e. the maximum,
minimum, mean, standard deviation, difference max.-min. or average slope within the
sample time are calculated.)
Endress+Hauser 193
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Options • Off
• Upper limit
• Lower limit
• In range
• Out of range
Additional information If a calculation has been selected in the Calculation type parameter, the check does not
refer to the assigned measuring variable but to the quantity calculated from it.
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Upper limit
• In range
• Out of range
194 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Descriptions Defines the upper limit for the selected check mode.
Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Lower limit
• In range
• Out of range
Descriptions Defines the lower limit for the selected check mode.
Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Upper limit
• Lower limit
• In range
• Out of range
Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.
Endress+Hauser 195
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Indicates the maximum value the assigned measuring variable has attained (dragging
indicator).
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Descriptions Indicates the minimum value the assigned measuring variable has attained (dragging
indicator).
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Description Resets the Maximum value and Minimum value dragging indicators.
Options • Off
• Reset max.
• Reset min.
• Reset min./max.
196 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Description Assigns an event category according to NAMUR NE107 to the event of the Advanced
Diagnostics Block.
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Description Assigns an event behavior to the event of the Advanced Diagnostics Block.
Options • Off
• Alarm
• Warning
• Logbook entry only
Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.
Description Assigns an event behavior to the event of the Advanced Diagnostics Block.
Endress+Hauser 197
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
Factory setting 10 s
198 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Index
Index
A Configuration management (Parameter) . . . . . . . . . . 30
Absolute echo amplitude (Parameter) . . . . . . . . . . . . 64 Confirm access code (Parameter) . . . . . . . . . . . . . . . . 34
Access status display (Parameter) . . . . . . . . . . . . . . . 17 Confirm distance (Parameter) . . . . . . . . . . . . . . . . . . 91
Access status tooling (Parameter) . . . . . . . . . . . . . . . 18 Const. GPC factor (Parameter) . . . . . . . . . . . . . . . . . . 84
Acknowledge alarm (Parameter) . . . . . . . . . . . . . . . . 88 Contrast display (Parameter) . . . . . . . . . . . . . . . . . . . 28
Activate SW option (Parameter) . . . . . . . . . . . . . . . . 35 Control measurement (parameter) . . . . . . . . . . . . . . . 97
Activate table (Parameter) . . . . . . . . . . . . . . . . . . . . . 62 CRC count failed (parameter) . . . . . . . . . . . . . . . . . . 107
Actual diagnostics (Parameter) . . . . . . . . . . . . . . . . 170 CRC count OK (parameter) . . . . . . . . . . . . . . . . . . . . 107
Address mode (parameter) . . . . . . . . . . . . . . . . . . . 103 Customer value (Parameter) . . . . . . . . . . . . . . . . . . . 62
Advanced process conditions (Parameter) . . . . . . . . . 40
Alarm delay 1 (Parameter) . . . . . . . . . . . . . . . . . . . 197 D
Alarm delay 2 (Parameter) . . . . . . . . . . . . . . . . . . . 197 Dead time (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 73
Alarm hysteresis (parameter) . . . . . . . . . . . . . . . . . 130 Decimal places 1 (Parameter) . . . . . . . . . . . . . . . . . . 24
Alarm summary (parameter) . . 112, 123, 141, 152, 164 Decimal places 2 (Parameter) . . . . . . . . . . . . . . . . . . 24
Alert key (parameter) . . . . . . . 110, 121, 139, 150, 162 Decimal places 3 (Parameter) . . . . . . . . . . . . . . . . . . 24
Application parameter (Parameter) . . . . . . . . . . . . . . 41 Decimal places 4 (Parameter) . . . . . . . . . . . . . . . . . . 24
Area of incoupling (Parameter) . . . . . . . . . . . . . . . . 186 Decimal places menu (Parameter) . . . . . . . . . . . . . . . 27
Assign channel 1 (Parameter) . . . . . . . . . . . . . . . . . 177 Define access code (Parameter) . . . . . . . . . . . . . . . . . 34
Assign channel 2 (Parameter) . . . . . . . . . . . . . . . . . 177 Delay echo lost (Parameter) (Parameter) . . . . . . . . . . 87
Assign channel 3 (Parameter) . . . . . . . . . . . . . . . . . 177 Descriptor (parameter) . . . . . . . . . . . . . . . . . . . . . . 115
Assign channel 4 (Parameter) . . . . . . . . . . . . . . . . . 177 Device (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . . 175
Assign diagnostic level (Parameter) . . . . . . . . . . . . . . 98 Device address (parameter) . . . . . . . . . . . . . . . . . . . 104
Assign diagnostic signal 1 (Parameter) . . . . . . . . . . 192 Device certification (parameter) . . . . . . . . . . . . . . . . 114
Assign diagnostic signal 2 (Parameter) . . . . . . . . . . 192 Device ID (parameter) . . . . . . . . . . . . . . . . . . . . . . . 113
Assign event behaviour 1 (Parameter) . . . . . . . . . . . 197 Device install date (parameter) . . . . . . . . . . . . . . . . 116
Assign event behaviour 2 (Parameter) . . . . . . . . . . . 197 Device message (parameter) . . . . . . . . . . . . . . . . . . 115
Assign limit (Parameter) . . . . . . . . . . . . . . . . . . . . . . 98 Device name (Parameter) . . . . . . . . . . . . . . . . . . . . 175
Assign simulation process variable (Parameter) . . . . 183 Device reset (Parameter) . . . . . . . . . . . . . . . . . . . . . . 35
Assign status (Parameter) . . . . . . . . . . . . . . . . . . . . 100 Diagnostics (parameter) . . . . . . . . . . . . . . . . . . . . . 114
Assign status signal to AD event 1 (Parameter) . . . . 196 Diagnostics 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
Assign status signal to AD event 2 (Parameter) . . . . 196 Diagnostics 2 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
Diagnostics 3 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
B Diagnostics 4 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
Backlight (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 28 Diagnostics 5 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
Backup state (Parameter) . . . . . . . . . . . . . . . . . . . . . 31 Diagnostics extension (parameter) . . . . . . . . . . . . . . 114
Base current (parameter) . . . . . . . . . . . . . . . . . . . . . 108 Diagnostics mask (parameter) . . . . . . . . . . . . . . . . . 114
Batch ID (parameter) . . . . . . . . . . . . 123, 141, 152, 164 Diameter (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 59
Batch operation (parameter) . . . . . . 124, 142, 153, 165 Direct access (Parameter) . . . . . . . . . . . . . . . . . . . . . 17
Batch phase (parameter) . . . . . . . . . 124, 142, 153, 165 Display channel 1 (Parameter) . . . . . . . . . . . . . . . . . 178
Batch recipe unit procedure (parameter) 124, 142, Display channel 2 (Parameter) . . . . . . . . . . . . . . . . . 178
153, 165 Display channel 3 (Parameter) . . . . . . . . . . . . . . . . . 178
Bin property (Parameter) . . . . . . . . . . . . . . . . . . . . . . 38 Display channel 4 (Parameter) . . . . . . . . . . . . . . . . . 178
Blocking distance (Parameter) . . . . . . . . . . . . . . . . . . 77 Display damping (Parameter) . . . . . . . . . . . . . . . . . . 25
Display interval (Parameter) . . . . . . . . . . . . . . . . . . . 25
C Distance (Parameter) . . . . . . . . . . . . . . . . . . . 45, 72, 91
Calculated DC value (Parameter) . . . . . . . . . . . . . . . . 43 Distance offset (Parameter) . . . . . . . . . . . . . . . . . . . . 45
Calculation type 1 (Parameter) . . . . . . . . . . . . . . . . 193 Distance unit (Parameter) . . . . . . . . . . . . . . . . . . . . . 37
Calculation type 2 (Parameter) . . . . . . . . . . . . . . . . 193 Document
Calculation unit 1 (Parameter) . . . . . . . . . . . . . . . . . 194 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Calculation unit 2 (Parameter) . . . . . . . . . . . . . . . . . 194 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Channel (parameter) . . . . . . . . . . . . . . . . . . . . 127, 144
Check mode 1 (Parameter) . . . . . . . . . . . . . . . . . . . 193 E
Check mode 2 (Parameter) . . . . . . . . . . . . . . . . . . . 193 Electronic temperature (Parameter) . . . . . . . . . . . . . . 67
Clear logging data (Parameter) . . . . . . . . . . . . . . . . 178 Empty calibration (Parameter) . . . . . . . . . . . . . . . . . . 46
Comparison result (Parameter) . . . . . . . . . . . . . . . . . 31 ENP version (Parameter) . . . . . . . . . . . . . . . . . . . . . 176
Condensed status diagnose (parameter) . . . . . . . . . . 117 Enter access code (Parameter) . . . . . . . . . . . . . . . . . . 18
Endress+Hauser 199
Index Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57
200 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Index
Endress+Hauser 201
*71217608*
71217608