Anda di halaman 1dari 202

GP01018F/00/EN/01.

13 Products Solutions Services


71217608
Valid as of version
01.00.zz

Description of device parameters


Micropilot
FMR50, FMR51, FMR52, FMR53,
FMR54, FMR56, FMR57
Level radar
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Table of contents

Table of contents

1 Important document information . . . . 4 3.7 Expert → Analog outputs → Analog output


N................................ 147
1.1 Document function . . . . . . . . . . . . . . . . . . . . . 4 3.7.1 Overview . . . . . . . . . . . . . . . . . . . . . 147
1.2 Document conventions . . . . . . . . . . . . . . . . . . . 4 3.7.2 The parameters . . . . . . . . . . . . . . . . 150
1.2.1 Symbols for certain types of 3.8 Expert → Discrete outputs → Discrete output
information . . . . . . . . . . . . . . . . . . . . 4 N................................ 159
1.2.2 Symbols in graphics . . . . . . . . . . . . . . . 4 3.8.1 Overview . . . . . . . . . . . . . . . . . . . . . 159
1.2.3 Symbols at the device . . . . . . . . . . . . . 4 3.8.2 The parameters . . . . . . . . . . . . . . . . 162
3.9 Expert → Diagnostics . . . . . . . . . . . . . . . . . . 170
2 Overview of the operating menu . . . . . 5 3.9.1 Expert → Diagnostics → Diagnostics
list . . . . . . . . . . . . . . . . . . . . . . . . . 172
3.9.2 Expert → Diagnostics → Event
3 The "Expert" menu . . . . . . . . . . . . . . . . 17
logbook . . . . . . . . . . . . . . . . . . . . . . 173
3.1 Expert → System . . . . . . . . . . . . . . . . . . . . . . 20 3.9.3 Expert → Diagnostics → Device
3.1.1 Expert → System → Display . . . . . . . . 21 information . . . . . . . . . . . . . . . . . . 175
3.1.2 Expert → System → Configuration 3.9.4 Expert → Diagnostics → Data
backup display . . . . . . . . . . . . . . . . . 29 logging . . . . . . . . . . . . . . . . . . . . . . 177
3.1.3 Expert → System → Administration . . 33 3.9.5 Expert → Diagnostics → Min/max
3.2 Expert → Sensor . . . . . . . . . . . . . . . . . . . . . . . 36 values . . . . . . . . . . . . . . . . . . . . . . . 180
3.2.1 Overview . . . . . . . . . . . . . . . . . . . . . . 36 3.9.6 Expert → Diagnostics → Simulation . 183
3.2.2 Description of parameters . . . . . . . . . 37 3.9.7 Expert → Diagnostics → Device
3.2.3 Expert → Sensor → Medium . . . . . . . . 42 check . . . . . . . . . . . . . . . . . . . . . . . 184
3.2.4 Expert → Sensor → Level . . . . . . . . . . 44 3.9.8 Expert → Diagnostics → Advanced
3.2.5 Expert → Sensor → Linearization . . . . 54 diagnostics 1/2 . . . . . . . . . . . . . . . . 187
3.2.6 Expert → Sensor → Information . . . . . 63
3.2.7 Expert → Sensor → Sensor
properties . . . . . . . . . . . . . . . . . . . . . 68 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
3.2.8 Expert → Sensor → Distance . . . . . . . . 70
3.2.9 Expert → Sensor → Gas phase
compensation . . . . . . . . . . . . . . . . . . 78
3.2.10 Expert → Sensor → Sensor
diagnostics . . . . . . . . . . . . . . . . . . . . 85
3.2.11 Expert → Sensor → Safety settings . . . 86
3.2.12 Expert → Sensor → Envelope curve . . . 90
3.2.13 Expert → Sensor → Mapping . . . . . . . 91
3.2.14 Expert → Sensor → Tank bottom
evaluation . . . . . . . . . . . . . . . . . . . . . 94
3.2.15 Expert → Sensor → Echo tracking . . . . 95
3.2.16 Expert → Sensor → External input . . . 96
3.3 Expert → Output . . . . . . . . . . . . . . . . . . . . . . 98
3.3.1 Expert → Output → Switch output . . . . 98
3.4 Expert → Communication . . . . . . . . . . . . . . . 103
3.4.1 Expert → Communication →
PROFIBUS PA configuration . . . . . . . 103
3.4.2 Expert → Communication →
PROFIBUS PA info . . . . . . . . . . . . . . 106
3.4.3 Expert → Communication →
Physical block . . . . . . . . . . . . . . . . . 109
3.5 Expert → Analog inputs → Analog input N . . 118
3.5.1 Overview . . . . . . . . . . . . . . . . . . . . . 118
3.5.2 The parameters . . . . . . . . . . . . . . . . 121
3.6 Expert → Discrete inputs → Discrete input N . 137
3.6.1 Overview . . . . . . . . . . . . . . . . . . . . . 137
3.6.2 The parameters . . . . . . . . . . . . . . . . 139

Endress+Hauser 3
Important document information Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

1 Important document information

1.1 Document function


The document is part of the Operating Instructions and serves as a reference for
parameters, providing a detailed explanation of each individual parameter of the operating
menu.

1.2 Document conventions

1.2.1 Symbols for certain types of information

Symbol Meaning

Tip
Indicates additional information.
A0011193

Reference to documentation
Refers to the corresponding device documentation.
A0011194

Reference to page
Refers to the corresponding page number.
A0011195

Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196

Operation via local display


Indicates navigation to the parameter via the local display.
A0013140

Operation via operating tool


Indicates navigation to the parameter via the operating tool.
A0013143

Write-protected parameter
Indicates a parameter that can be locked against changes by entering a user-specific code.
A0013144

1.2.2 Symbols in graphics

Symbol Meaning

1, 2, 3 ... Item numbers

A, B, C, ... Views

A-A, B-B, C-C, ... Sections

1.2.3 Symbols at the device

Symbol Meaning

Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.

Temperature resistance of the connection cables


Specifies the minimum value of the temperature resistance of the connection cables.

4 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu

2 Overview of the operating menu


The following table lists all parameters the "Expert" menu may contain. The page
number refers to where a description of the parameter can be found.
Depending on the device version and parametrization some parameters will not be
available in a given situation. For details on the conditions refer to the "Prerequisite"
category in the description of the respective parameter.

Navigation Direct access Description

Expert → Direct access 0106 (→  17)

Locking status 0004 (→  17)

Access status display 0091 (→  17)

Access status tooling 0005 (→  18)

Enter access code 0092 (→  18)

Navigation Direct access Description

Expert → System → Display → Language 0104 (→  22)

Format display 0098 (→  22)

Value 1 display 0107 (→  24)

Decimal places 1 0095 (→  24)

Value 2 display 0108 (→  24)

Decimal places 2 0117 (→  24)

Value 3 display 0110 (→  24)

Decimal places 3 0118 (→  24)

Value 4 display 0109 (→  24)

Decimal places 4 0119 (→  24)

Display interval 0096 (→  25)

Display damping 0094 (→  25)

Header 0097 (→  25)

Header text 0112 (→  26)

Separator 0101 (→  26)

Number format 0099 (→  27)

Decimal places menu 0573 (→  27)

Contrast display 0105 (→  28)

Backlight 0111 (→  28)

Access status display 0091 (→  17)

Navigation Direct access Description

Expert → System → Configuration backup Operating time 0652 (→  30)


display →

Last backup 0102 (→  30)

Configuration management 0100 (→  30)


1)
Backup state 0121 (→  31)

Comparison result 0103 (→  31)

1) not available for operation via display

Endress+Hauser 5
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Direct access Description

Expert → System → Administration → Activate SW option 0029 (→  35)

Device reset 1013 (→  35)

Define access code 0 (→  34)

Confirm access code 0 (→  34)

Navigation Direct access Description

Expert → Sensor → Distance unit 0551 (→  37)

Temperature unit 0557 (→  37)

Tank type 1175 (→  37)

Tube diameter 1117 (→  38)

Bin property 1176 (→  38)

Max. filling speed liquid 1212 (→  39)

Max. draining speed liquid 1202 (→  39)

Max. filling speed solid 1214 (→  39)

Max. draining speed solid 1213 (→  40)

Advanced process conditions 1177 (→  40)

Application parameter 1126 (→  41)

Navigation Direct access Description

Expert → Sensor → Medium → Medium type 1049 (→  42)

Medium group 1208 (→  42)

Medium property 1165 (→  43)

Calculated DC value 1118 (→  43)

Navigation Direct access Description

Expert → Sensor → Level → Distance offset 2309 (→  45)

Distance 2231 (→  45)

Empty calibration 2343 (→  46)

Full calibration 2308 (→  47)

Level unit 0576 (→  48)

Level limit mode 2314 (→  49)

High limit 2312 (→  49)

Low limit 2313 (→  50)

Level correction 2325 (→  50)

Output mode 2317 (→  51)

Level 2319 (→  51)

Level linearized 2318 (→  52)

Tank/silo height 1148 (→  52)

Navigation Direct access Description

Expert → Sensor → Linearization → Linearization type 2339 (→  56)

Unit after linearization 2340 (→  57)

6 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu

Navigation Direct access Description

Free text 2341 (→  58)

Level linearized 2318 (→  52)

Maximum value 2315 (→  59)

Diameter 2342 (→  59)

Intermediate height 2310 (→  59)

Table mode 2303 (→  60)

Table number 2370 (→  61)

Level 2383/2389 (→  61)

Customer value 2384 (→  62)

Activate table 2304 (→  62)

Navigation Direct access Description

Expert → Sensor → Information → Signal quality 1047 (→  64)

Absolute echo amplitude 1127 (→  64)

Relative echo amplitude 1089 (→  65)

Tank bottom echo 1128 (→  66)


amplitude

Found echoes 1068 (→  66)

Used calculation 1115 (→  66)

Tank trace state 1206 (→  66)

Measurement frequency 1180 (→  67)

Electronic temperature 1062 (→  67)

Navigation Direct access Description

Expert → Sensor → Sensor properties → Sensor module 1101 (→  68)

Free field special 1150 (→  68)

Navigation Direct access Description

Expert → Sensor → Distance → Distance 1124 (→  72)

Dead time 1199 (→  73)

Integration time 1092 (→  75)

Blocking distance 1144 (→  77)

Navigation Direct access Description

Expert → Sensor → Gas phase compensation GPC mode 1034 (→  82)


External pressure selector 1073 (→  82)

External pressure 1220 (→  83)

Gas phase compensation 1209 (→  83)


factor

Present reference distance 1076 (→  83)

Reference distance 1033 (→  83)

Endress+Hauser 7
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Direct access Description

Reference echo threshold 1168 (→  84)

Const. GPC factor 1217 (→  84)

Navigation Direct access Description

Expert → Sensor → Sensor diagnostics → Start self check 1133 (→  85)

Result self check 1134 (→  85)

Noise of signal 1105 (→  85)

Navigation Direct access Description

Expert → Sensor → External input → Level external input 1 2305 (→  96)

Function input 1 Level 2311 (→  96)

Fixed value input 1 2332 (→  96)

Level external input 2 2306 (→  96)

Function input 2 Level 2331 (→  96)

Fixed value input 2 2333 (→  96)

Control measurement 1083 (→  97)

Measurement 1082 (→  97)

Navigation Direct access Description

Expert → Sensor → Safety settings → Output echo lost 2307 (→  86)

Valeu echo lost 2316 (→  86)

Ramp at echo lost 2323 (→  86)

Delay echo lost 1193 (→  87)

Safety distance 1093 (→  88)

In safety distance 1018 (→  88)

Acknowledge alarm 1130 (→  88)

Navigation Direct access Description

Expert → Sensor → Envelope curve → Envelope curve 1207 (→  90)

Navigation Direct access Description

Expert → Sensor → Mapping → Confirm distance 1045 (→  91)

Distance 1124 (→  91)

Mapping end point 1022 (→  92)

Present mapping 1182 (→  92)

Record map 1213 (→  92)

Navigation Direct access Description

Expert → Sensor → Tank bottom evaluation → Tank bottom range 1149 (→  94)

8 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu

Navigation Direct access Description

Expert → Sensor → Echo tracking → Evaluation mode 1112 (→  95)

History reset 1145 (→  95)

Navigation Direct access Description

Expert → Output → Switch output → Switch output function 0481 (→  98)

Assign diagnostic level 0482 (→  98)

Assign limit 0483 (→  98)

Switch-on value 0466 (→  99)

Switch-off value 0464 (→  99)

Assign status 0485 (→  100)

Switch-on delay 0467 (→  101)

Switch-off delay 0465 (→  101)

Switch output failure mode 0486 (→  101)

Switch status 0461 (→  102)

Invert output signal 0470 (→  102)

Navigation Direct access Description

Experte → Communication → PROFIBUS PA Address mode 1468 (→  103)


configuration →

Device address 1462 (→  104)

Ident number selector 1461 (→  105)

Navigation Direct access Description

Expert → Communication → PROFIBUS PA info → Status PROFIBUS Master 1465 (→  106)


Config

PROFIBUS ident number 1471 (→  106)

Profile version 1463 (→  107)

CRC count OK 1469 (→  107)

CRC Count Failed 1470 (→  107)

Good telegrams 1467 (→  107)

Base current 1466 (→  108)

Terminal voltage 1 0662 (→  108)

Navigation Direct access Description

Expert → Communication → Physical block → Tag description 1496 (→  110)

Static revision 1495 (→  110)

Strategy 1494 (→  110)

Alert key 1473 (→  110)

Target mode 1497 (→  111)

Mode block actual 1472 (→  111)

Mode block permitted 1493 (→  111)

Moe block normal 1492 (→  112)

Endress+Hauser 9
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Direct access Description

Alarm summary 1474 (→  112)

Software-Revision 1478 (→  112)

Hardware-Revision 1479 (→  112)

Manufacturer ID 1502 (→  113)

Device ID 1480 (→  113)

Serial number 1481 (→  113)

Diagnostics 1482 (→  114)

Diagnostics extension 1483 (→  114)

Diagnostics mask 1484 (→  114)

Device certification 1486 (→  114)

Factory reset 1488 (→  115)

Descriptor 1489 (→  115)

Device message 1490 (→  115)

Device install date 1491 (→  116)

Ident number selector 1461 (→  105)

Hardware lock 1499 (→  116)

Feature enabled 1476 (→  116)

Feature supported 1477 (→  117)

Condensed status diagnose 1500 (→  117)

Navigation Direct access Description

Expert → Analog inputs → Analog input 1...6 → Tag description 1562 (→  121)

Static revision 1560 (→  121)

Strategy 1559 (→  121)

Alert key 1522 (→  121)

Target mode 1563 (→  122)

Mode block actual 1521 (→  122)

Mode block permitted 1523 (→  122)

Mode block normal 1562 (→  123)

Alarm summary 1537 (→  123)

Batch ID 1533 (→  123)

Batch operation 1534 (→  124)

Batch phase 1535 (→  124)

Batch Recipe Unit 1536 (→  124)


Procedure

Out value 1552 (→  124)

Out status 1564 (→  125)

Out status HEX 1549 (→  125)

PV scale lower range 1554 (→  126)

PV scale upper range 1555 (→  126)

Out scale lower range 1548 (→  126)

Lin type 1523 (→  127)

Channel 1561 (→  127)

10 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu

Navigation Direct access Description

Out unit 1550 (→  128)

Out decimal point 1547 (→  128)

PV filter time 1524 (→  128)

Fail safe type 1525 (→  129)

Fail safe value 1526 (→  129)

Alarm hysteresis 1527 (→  130)

Hi Hi lim 1528 (→  130)

Hi lim 1529 (→  130)

Lo lim 1530 (→  131)

Lo Lo lim 1531 (→  131)

Hi Hi alarm value 1541 (→  131)

Hi Hi alarm state 1540 (→  132)

Hi alarm value 1539 (→  132)

Hi alarm state 1538 (→  132)

Lo alarm value 1543 (→  133)

Lo alarm state 1542 (→  133)

Lo Lo alarm value 1545 (→  133)

Lo Lo alarm state 1544 (→  134)

Simulate enabled 1556 (→  134)

Simulate value 1558 (→  135)

Simulate status 1557 (→  135)

Out unit text 1532 (→  135)

Navigation Direct access Description

Expert → Discrete inputs → Discrete input 1...4 → Tag description 2201 (→  139)

Static revision 2200 (→  139)

Strategy 2199 (→  139)

Alert key 2182 (→  139)

Target mode 2202 (→  140)

Mode block actual 2182 (→  139)

Mode block permitted 2195 (→  140)

Mode block normal 2192 (→  141)

Alarm summary 2191 (→  141)

Batch ID 2183 (→  141)

Batch operation 2184 (→  142)

Batch phase 2185 (→  142)

Batch Recipe Unit 2186 (→  142)


Procedure

Out value 2194 (→  142)

Out status 2203 (→  143)

Out status HEX 2193 (→  143)

Channel 2187 (→  144)

Invert 2188 (→  144)

Endress+Hauser 11
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Direct access Description

Fail safe type 2189 (→  144)

Fail safe value 2189 (→  145)

Simulate enabled 2196 (→  145)

Simulate value 2198 (→  146)

Simulate status 2197 (→  146)

Navigation Direct access Description

Expert → Analog outputs → Analog output 1...4 → Tag description 1667 (→  150)

Static revision 1666 (→  150)

Strategy 1665 (→  150)

Alert key 1632 (→  150)

Target mode 1668 (→  151)

Mode block actual 1631 (→  151)

Mode block permitted 1648 (→  151)

Mode block normal 1643 (→  152)

Alarm summary 1642 (→  152)

Batch ID 1633 (→  152)

Batch operation 1639 (→  153)

Batch phase 1640 (→  153)

Batch Recipe Unit 1641 (→  153)


Procedure

Set point value 1661 (→  153)

Set point status 1660 (→  154)

PV scale lower range 1651 (→  154)

PV scale upper range 1652 (→  154)

Readback value 1659 (→  148)

Readback status 1658 (→  148)

RCAS in value 1655 (→  148)

RCAS in status 1654 (→  148)

Input channel 1670 (→  148)

Output channel 1671 (→  148)

Fail safe time 1635 (→  155)

Fail safe type 1636 (→  155)

Fail safe value 1637 (→  156)

RCAS out value 1657 (→  148)

RCAS out status 1656 (→  148)

Position value 1650 (→  148)

Position status 1649 (→  148)

Setpoint deviation 1653 (→  148)

Simulate enabled 1662 (→  148)

Simulate value 1664 (→  148)

Simulate status 1663 (→  148)

Increase close 1638 (→  148)

12 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu

Navigation Direct access Description

Out value 1647 (→  156)

Out status 1669 (→  156)

Out status HEX 1645 (→  157)

Out scale upper range 1646 (→  157)

Out scale lower range 1644 (→  158)

Navigation Direct access Description

Expert → Discrete outputs → Discrete output 1...4 → Tag description 1721 (→  162)

Static revision 1720 (→  162)

Strategy 1719 (→  162)

Alert key 1694 (→  162)

Target mode 1722 (→  163)

Mode block actual 1691 (→  163)

Mode block permitted 1705 (→  163)

Mode block normal 1702 (→  164)

Alarm summary 1701 (→  164)

Batch ID 1695 (→  164)

Batch operation 1698 (→  165)

Batch phase 1699 (→  165)

Batch Recipe Unit 1700 (→  165)


Procedure

Set point value 1715 (→  165)

Set point status 1714 (→  166)

Out value 1704 (→  166)

Out status 1723 (→  166)

Out status HEX 1703 (→  167)

Readback value 1713 (→  160)

Readback status 1712 (→  160)

RCAS in value 1707 (→  160)

RCAS in status 1706 (→  160)

Input channel 1724 (→  160)

Output channel 1725 (→  160)

Invert 1692 (→  167)

Fail safe time 1697 (→  168)

Fail safe type 1696 (→  168)

Fail safe value 1693 (→  168)

RCAS out value 1711 (→  160)

RCAS out status 1708 (→  160)

Simulate enabled 1716 (→  160)

Simulate value 1718 (→  160)

Simulate status 1717 (→  160)

Endress+Hauser 13
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Direct access Description

Expert → Diagnostics → Actual diagnostics 0691 (→  170)

Previous diagnostics 0690 (→  170)

Operating time from restart 0653 (→  170)

Operating time 0652

Navigation Direct access Description

Expert → Diagnostics → Diagnostics listseliste → Diagnostics 1 0692 (→  172)

Diagnostics 2 0693 (→  172)

Diagnostics 3 0694 (→  172)

Diagnostics 4 0695 (→  172)

Diagnostics 5 0696 (→  172)

Navigation Direct access Description

Expert → Diagnostics → Event logbook → Filter options 0705 (→  173)

Event list - (→  173)

Navigation Direct access Description

Expert → Diagnostics → Device information → Device 0011 (→  175)

Serial number 0009 (→  175)

Firmware version 0010 (→  175)

Device name 0013 (→  175)

Order code 0008 (→  176)

Extended order code 1 0023 (→  176)

Extended order code 2 0021 (→  176)

Extended order code 3 0022 (→  176)

ENP version 0012 (→  176)

Navigation Direct access Description

Expert → Diagnostics → Data logging → Assign channel 1 0851

Assign channel 2 0852

Assign channel 3 0853

Assign channel 4 0854

Logging interval 0856

Clear logging data 0855

Display channel 1 -

Display channel 2 -

Display channel 3 -

Display channel 4 -

14 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Overview of the operating menu

Navigation Direct access Description

Expert → Diagnostics → Min/max values → Max. level value 2357 (→  180)

Time max. level 2385 (→  180)

Min. level value 2358 (→  180)

Time min. level 2386 (→  180)

Max. draining speed 2320 (→  180)

Max. filling speed 2360 (→  181)

Reset min./max. 2324 (→  181)

Max. electronics 1031 (→  181)


temperature

Time max. electronics 1204 (→  181)


temperature

Min. electronics 1040 (→  182)


temperature

Time min. electronics 1205 (→  182)


temperature

Rest min./max. 1173 (→  182)


temperature

Navigation Direct access Description

Expert → Diagnostics → Simulation → Assign simulation process 2328 (→  183)


variable

Value process variable 2329 (→  183)

Switch output simulation 0462 (→  183)

Switch status 0463 (→  184)

Simulation current output 1 0354 (Verweisziel


existiert
nicht, aber
@y.link.requi
red='true')

Value current output 1 0355 (Verweisziel


existiert
nicht, aber
@y.link.requi
red='true')

Simulation current output 2 0354 (Verweisziel


existiert
nicht, aber
@y.link.requi
red='true')

Value current output 2 0355 (Verweisziel


existiert
nicht, aber
@y.link.requi
red='true')

Simulation device alarm 0654 (→  184)

Navigation Direct access Description

Expert → Diagnostics → Device check → Start device check 1013 (→  184)

Result device check 1014 (→  185)

Last check time 1203 (→  185)

Endress+Hauser 15
Overview of the operating menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Direct access Description

Level signal 1016 (→  185)

Area of incoupling 1186 (→  186)

Navigation Direct access Description

Expert → Diagnostics → Advanced diagnostics 1/2 Assign diagnostic signal 11179 (→  192)
→ 1/2

Link AD 1/2 to 11180 (→  192)

Linking logic AD 1/2 11181 (→  192)

Sample time 1/2 11187 (→  193)

Calculation type 1/2 11174 (→  193)

Check mode 1/2 11175 (→  193)

Calculation unit 1/2 11188 (→  194)

Upper limit 1/2 11182 (→  194)

Lower limit 1/2 11184 (→  195)

Hysteresis 1/2 11178 (→  195)

Maximum value 1/2 11183 (→  196)

Minimum value 1/2 11185 (→  196)

Reset min./max. 1/2 11186 (→  196)

Assign status signal to AD 11176 (→  196)


event 1/2

Assign event behaviour 1/2 11177 (→  197)

Alarm delay 11171 (→  197)

16 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3 The "Expert" menu

Direct access (0106)

Navigation Expert → Direct access

Write access Maintenance

Prerequisite Only visible for operation via display module, not for operation via software tool (e.g.
FieldCare).

Description Enter the direct access code to access a parameter directly.

Input range 0 to 65 535

Additional information In this document, the direct access code is indicated in brackets following the parameter
name, e.g. Locking status (0004).

Locking status (0004)

Navigation Expert → Locking status

Write access Read-only parameter

Description Indicates the write protection with the highest priority that is currently active.

Display options • Hardware locked


• WHG locked
• Temporarily locked

Additional information On the display module, the -symbol appears in front of parameters that cannot be
modified since they are write-protected.

Access status display (0091)

Navigation Expert → Access status display


Expert → System → Display → Access status display

Write access Read-only parameter

Prerequisite Only visible for devices with operating and display module (SD02 or SD03)

Description Indicates access authorization to parameters via local display.

Endress+Hauser 17
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Display options • Operator


• Maintenance
• Service

Additional information • The access authorization can be changed via the Enter access code parameter
(→  18).
• If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→  17).
• If a -symbol appears in front of a parameter, the parameter cannot be changed via
the local display with the current access authorization.

Access status tooling (0005)

Navigation Expert → Access status tooling

Write access Read-only parameter

Prerequisite Only visible for operation via operating tool (e.g. FieldCare), not for operation via display
module.

Description Indicates access authorization to parameters via operating tool (e.g. FieldCare).

Display options • Operator


• Maintenance
• Service

Additional information If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→  17).

Enter access code (0092)

Navigation Expert → Enter access code

Write access Operator

Description Enter access code to disable write protection of parameters

Input range 0 to 9 999

18 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Additional information For local operation, the customer-specific access code, which has been defined in the
Expert → System → Define access code sequence, has to be entered.
If an incorrect access code is entered, the user retains his current access authorization.
The write protection affects all parameters marked with the -symbol in the document.
On the local display, the -symbol in front of a parameter indicates that the parameter is
write-protected.
If no key is pressed for 10 minutes, or the user goes from the navigation and editing mode
back to the measured value display mode, the device automatically locks the write-
protected parameters after another 60 s.
Please contact your Endress+Hauser Sales Center if you lose your access code.

Endress+Hauser 19
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.1 Expert → System


The System submenu contains all general parameters which affect neither the
measurement nor the measured value communication.

Submenus
Submenu Meaning Description

Display Parametrization of the local display module (allocation of measured (→  21)


values, display format etc.)

Configuration backup • Backup of the device configuration in the display module (→  29)
display • Copying of the device configuration into another device

Administration • Unlocking software options (→  33)


• Reset of a device
• Definition of an access code

20 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.1.1 Expert → System → Display


For operating tools: The Display submenu is only visible if a display module is
connected to the device.

Overview
The Display submenu is used to parametrize the representation of measured values on the
local display module. Up to four measured values can be allocated to the local display
module. Additionally, display characteristics such as the format of numbers, the associated
texts or the display contrast can be configured.

Parameter Meaning Description

Language Selection of the display language (→  22)

Format Display Selection of the display format (number and size of the displayed (→  22)
measuring values)

Value 1 display Allocation of a measured variable to the first display value (→  24)

Decimal places 1 Number of decimal places for the first display value (→  24)

Value 2 display Allocation of a measured variable to the second display value (→  24)

Decimal places 2 Number of decimal places for the second display value (→  24)

Value 3 display Allocation of a measured variable to the third display value (→  24)

Decimal places 3 Number of decimal places for the third display value (→  24)

Value 4 display Allocation of a measured variable to the fourth display value (→  24)

Decimal places 4 Number of decimal places for the fourth display value (→  24)

Display interval Time the individual variables are displayed in the case of an alternating (→  25)
display

Display damping Time constant for the damping of displayed values (→  25)

Header Selection of the header text: (→  25)


• Device tag
• Free text

Header text Definition of the header text in the case of Header = Free text (→  26)

Separator Selection of the decimal separator (point of comma) (→  26)

Number format Selection of the number format for distance values (decimal or ft-in-1/16") (→  27)

Decimal places menu Number of decimals for values in the operating menu (not the measuring (→  27)
values)

Contrast display Contrast of the LCD (20 ... 80%) (→  28)

Backlight Switch-on/switch-off of the display module SD03 (→  28)

Access status display Displays the user role for operation via the display module (→  17)

Endress+Hauser 21
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Description of parameters

Language (0104)

Navigation Expert → System → Display → Language

Write access Operator

Description Set display language

Options • English
• One additional operating language (see product structuture, feature 500, "Additional
Operation Language")

Factory setting English

Format dipslay (0098)

Navigation Expert → System → Display → Format display

Write access Operator

Description Select how measured values are shown on the display.

Options • 1 value, max. size


• 1 bargraph + 1 value
• 2 values
• 1 value large + 2 values
• 4 values

Factory setting 1 value, max. size

22 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Additional information 1 value, max. size

4841.000
1 Â mm
A0019963

1 bargraph + 1 value

1 Â
93.5 %
1 Â 159.0
mm
A0019964

2 values

1 Â 93.5
%
1 Â 159.0
mm
A0019965

1 value large + 2 values

1 Â 159.0 mm
V 1 Â 23.5 V
1 Â 93.5
%
A0019966

4 values

1 Â 93.5 %
1 Â 159.0 mm
V 1 Â 93.5 V
1 Â 26.3 °C

A0019968

• The Value 1 display - Value 4 display parameters are used to specify what
measured values are shown on the display and in what order (→  24).
• If more measured values are specified than the display mode selected permits, the
values alternate on the device display. The display time until the next change is
configured using the Display interval parameter (→  25).

Endress+Hauser 23
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Value 1 display (0107)


Value 2 display (0108)
Value 3 display (0110)
Value 4 display (0109)

Navigation Expert → System → Display → Value 1/2/3/4 display

Write access Maintenance

Description Select the measured value that is shown on the local display.

Options • None 1)
• Level linearized
• Distance
• Terminal voltage
• Electronics temperature
• Absolute echo amplitude
• Relative echo amplitude
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
• Analog output 1
• Analog output 2
• Analog output 3
• Analog output 4

1) Can not be selected for "Value 1 display".

Factory setting • Value 1 display: Level linearized


• Value 2 display: None
• Value 3 display: None
• Value 4 display: None

Additional information The Format display parameter is used to specify how many measured values are displayed
simultaneously and how (→  22).

Decimal places 1 (0095)


Decimal places 2 (0117)
Decimal places 3 (0118)
Decimal places 4 (0119)

Navigation Expert → System → Display → Decimal places 1/2/3/4

Write access Maintenance

Prerequisite A measured value is specified in the Value 1/2/3/4 display parameter (→  24).

Description Select the number of decimal places for the display value.

24 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Options •x
• x.x
• x.xx
• x.xxx
• x.xxxx

Factory setting x.xx

Additional information This setting does not affect the measuring or computational accuracy of the device.

Display interval (0096)

Navigation Expert → System → Display → Display interval

Write access Operator

Description Set time measured values are shown on display if display alternates between values.

Input range 1 to 10 s

Facotry setting 5s

Additional information An alternating display only occurs automatically if the number of measured values defined
exceeds the number of values the selected display format can display simultaneously.
• The Value 1 display - Value 4 display parameters are used to specify what
measured values are shown on the display (→  24).
• The display format of the displayed measured values is specified using the
Format display parameter (→  22).

Display damping (0094)

Navigation Expert → System → Display → Display damping

Write access Maintenance

Description Set display reaction time to fluctuations in the measured value.

Input range 0 to 999 s

Factory setting 0 s

Header (0097)

Navigation Expert → System → Display → Header

Endress+Hauser 25
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Write access Maintenance

Description Select header contents on local display

Options • Device tag


• Free text

Factory setting Device tag

Additional information
1 XXXXXXXXX

A0013375

1 Position of the header text on the display

Device tag
Is defined in the Setup → Device tag parameter.
Free text
Is defined in the Header text parameter (→  26).

Header text (0112)

Navigation Expert → System → Display → Header text

Write access Maintenance

Prerequisite The Free text option is selected in the Header parameter (→  25).

Description Enter display header text

Input range Max. 12 characters, such as letters, numbers or special characters (e.g. @, %, /)

Factory setting ------------

Additional information
1 XXXXXXXXX

A0013375

1 Position of the header text on the display

User entry
The number of characters displayed depends on the characters used.

Separator (0101)

26 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Navigation Expert → System → Display → Separator

Write access Maintenance

Description Select decimal separator for displaying numerical values

Options • . (point)
• , (comma)

Factory setting . (point)

Number format (0099)

Navigation Expert → System → Display → Number format

Write access Maintenance

Description Choose number format for the display

Options • Decimal
• ft-in-1/16" (Only valid for distance units)

Factory setting Decimal

Decimal places menu (0573)

Navigation Expert → System → Display → Decimal places menu

Write access Maintenance

Description Select number of decimal places for the representation of numbers within the operating
menu.

Options •x
• x.x
• x.xx
• x.xxx
• x.xxxx

Factory setting x.xxxx

Additional information This parameter only determines the representation of numbers within the operating menu
(e.g. Empty calibration, Full calibration). It does not affect the measured value
representation.
For measured values, the number of decimal places is defined in the Decimal places 1 to
Decimal places 4 parameters (→  24).
This setting does not affect the measurement and calculation accuracy of the device.

Endress+Hauser 27
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Contrast display (0105)

Navigation Expert → System → Display → Contrast display

Write access Operator

Description Adjust local display contrast setting to ambient conditions (e.g. lighting or reading angle).

Input range 20 to 80 %

Factory setting 30 %

Additional information Set the contrast via push-buttons:


• Brighter: press the and buttons simultaneously
E

• Darker: press the and buttons simultaneously


E

Backlight (0111)

Navigation Expert → System → Display → Backlight

Write access Operator

Prerequisite Only visible if the display module SD03 with optical keys is connected (SD02 with push
buttons does not have a backlight).

Description Switch the local display backlight on and off.

Options • Disable
• Enable

Factory setting Disable

Access status display (→  17)


(0091)

28 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.1.2 Expert → System → Configuration backup display


The Configuration backup display submenu is only visible if a display module is
connected to the device.

Overview
All software configurations are initially stored in a memory module (HistoROM) in the
housing and are thus permanently connected with the device. As an additional option, the
display module contains a backup memory for the device configuration. The transmission
of configuration data between these two memory modules is controlled by the
Configuration backup display submenu. It provides the following options:
• Backup of a configuration from the device into the display module.
• Restore a device configuration.
This option can be used to restore a configuration back into the device which has
previously been saved in the display module.
• Duplicate a device configuration.
If the configuration has been saved into the display module, the module can be
connected to a different device and the configuration can be duplicated to this device.
This allows to efficiently configure a number of devices in the same way.
• Compare the configurations in the device and in the display module.
The comparison result indicates whether the device configuration has been changed
since the last backup.

Parameters of the "Configuration backup display" submenu

Parameter Meaning Description

Operating time Displays the operating time since the first setup. (→  30)

Last backup Displays at which time the last backup has been performed. (→  30)

Configuration • Cancel (→  30)


management no action
• Execute backup
Saves the current device configuration into the display module.
• Restore
Writes the configuration back from the display module to the device.
• Duplicate
Copies the configuration from the display module to a device
(different from the device the configuration was saved from)
• Compare
Compares the configuration stored in the display module to the
current configuration in the device.
• Clear backup
Deletes the configuration data stored in the display module.

Backup state 1) Displays the current progress of a backup operation (→  31)

Comparison result Displays the comparison result: (→  31)


• Settings identical
• Settings not identical
• No backup
• Backup corrupt
• Check not done

1) is not available when operating via the display module

Endress+Hauser 29
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Description of parameters

Operating time (0652)

Navigation Expert → System → Configuration backup display → Operating time


Expert → Diagnostics → Operating time

Write acces Read-only parameter

Description Indicates how long the device has been in operation.

Display format Days (d), hours (h), minutes (m) and seconds (s)

Additional information Display


The maximum number of days is 9999, which is equivalent to approximately 27 years.

Last backup (0102)

Navigation Expert → System → Configuration backup display → Last backup

Write acces Read-only parameter

Description Indicates the operating time at which the last data backup was saved to the display
module.

Display format Days (d), hours (h), minutes (m) and seconds (s)

Configuration management (0100)

Navigation Expert → System → Configuration backup display → Configuration management

Write access Maintenance

Description Select action for managing the device data in the display module.

30 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Options • Cancel
No action is executed and the user exits the parameter.
• Execute backup
A backup copy of the current device configuration in the HistoROM (built-in in the
device) is saved to the display module of the device. The backup copy comprises the
transmitter and sensor data of the device.
• Restore
The last backup copy of the device configuration is copied from the display module to the
HistoROM of the device. The backup copy comprises the transmitter and sensor data of
the device.
• Duplicate
The transmitter configuration is duplicated to another device using the transmitter
display module.
• Compare
The device configuration saved in the display module is compared to the current device
configuration of the HistoROM.
• Clear backup data
The backup copy of the device configuration is deleted from the display module of the
device.

Factory setting Cancel

Additional information Compare


The comprison result can be viewed in the Comparison result parameter (→  31).

HistoROM
A HistoROM is a non-volatile device memory in the form of an EEPROM.
While the respective action is in progress, the configuration cannot be edited via the
local display and a message on the processing status appears on the display.

Backup state (0121)

Navigation Expert → System → Conf. backup display → Backup state

Write access Read-only parameter

Prerequisite Only visible in the operating tool (not on the local display)

Description Displays the status of the data backup process.

Display options • None


• Store in progress
• Restore in progress
• Import in progress
• Delete in progress
• Compare in progress

Comparison result (0103)

Navigation Expert → System → Configuration backup display → Comparison result

Endress+Hauser 31
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Write access Read-only parameter

Description Comparison between present device data and display backup

Display options • Settings identical


The current device configuration of the HistoROM is identical to the backup copy in the
display module.
• Settings not identical
The current device configuration of the HistoROM is not identical to the backup copy in
the display module.
• No backup available
There is no backup copy of the device configuration of the HistoROM in the display
module.
• Backup settings corrupt
The current device configuration of the HistoROM is corrupt or not compatible with the
backup copy in the display module.
• Check not done
The device configuration of the HistoROM has not yet been compared to the backup copy
in the display module.
• Dataset incompatible
The comparison is impossible due to incompatibility.

Additional information The comparison is started via the Compare option in the Configuration
management parameter (→  30).

32 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.1.3 Expert → System → Administration

Overview
The Administration submenu contains all parameters for the management of the device.
Its structure depends on the user interface:

The "Administration" submenu on the display module


Parameter Meaning Description

Define access code → Define By defining a user-specific acces code the device configuration (→  34)
access code can be protected against unintended changes.

Define access code → Confirm The access code defined in Define access code must be (→  34)
access code confirmed by repeating it in this parameter.

Activate SW option Unlock certain software options (→  35)

Device reset Resets the configuration to a defined state. (→  35)

The "Administration" submenu for operating tools (e.g. FieldCare)


Parameter Meaning Description

Activate SW option Unlock certain software options (→  35)

Device reset Resets the configuration to a defined state. (→  35)

Define access code By defining a user-specific acces code the device configuration can be (→  34)
protected against unintended changes.

Endress+Hauser 33
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

The "Define access code" sequence 1)

Define access code

Navigation Expert → System → Administration → Define access code → Define access code
Expert → System → Administration → Define access code

Write access Maintenance

Description Define user-specific access code in order to protect the device against unintended changes.

Input range 0 to 9 999

Factory setting 0

Additional information If the factory setting is not changed or 0 is defined as the access code, the parameters are
not write-protected and the configuration data of the device can then always be modified.
The user is logged on in the role of Maintenance .
The write protection affects all parameters marked with the symbol in the
document. On the local display, the symbol in front of a parameter indicates that the
parameter is write-protected.
Once the access code has been defined, write-protected parameters can only be
modified if the access code is entered in the Expert → Enter access code parameter.
Please contact your Endress+Hauser Sales Center if you lose your access code.

For display operation: The new access code is only valid after it has been confirmed in
the Confirm access code parameter and after the user has returned to the main
screen (measured value display).

Confirm access code

Navigation Expert → System → Administration → Define access code → Confirm access code

Write access Maintenance

Prerequisite Only visible for operation via display module, not for operation via operating software (e.g.
FieldCare).

Description Confirm the access code by repeating the value entered in the Define access code
parameter.

Input range 0 to 9 999

Factory setting 0

1) This sequence only exists for operation via the display module. For operation via operating software (e.g. FieldCare), the "Define access code"
parameter is located directly in the "Administration" submenu.

34 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Further parameters

Activate SW option (0029)

Navigation Expert → System → Administration → Activate SW option

Write access Maintenance

Description Enter a code to activate specific software options.

Device reset (1013)

Navigation Expert → System → Administration → Device reset

Write access Maintenance

Description Use this function to reset the device configuration - either entirely or in part - to a defined
state.

Options • Cancel
No action is executed and the user exits the parameter.
• To factory defaults
Every parameter is reset to the order-code specific factory setting.
• To delivery settings
Every parameter is reset to the delivery setting. The delivery setting may differ from the
factory default if customer specific settings have been ordered.
• Of customer settings
Every customer parameter is reset to its factory setting. Service parameters, however,
retain their current value.
• To transducer defaults
Every measurment-related parameter is reset to its factory setting. Service parameters
and communication-related parameters, however, retain their current value.
• Restart device
The restart resets every parameter whose data are in the volatile memory (RAM) to the
factory setting (e.g. measured value data). The device configuration is not modified.

Factory setting Cancel

Additional information To delivery settings


This option is only visible if customer-specific settings have been ordered.

Endress+Hauser 35
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2 Expert → Sensor

3.2.1 Overview
The Sensor submenu contains all parameters related to the measurement and the sensor
settings.

Parameters
Parameter Meaning Description

Distance unit Measuring unit for basic distances (e.g empty and full calibration) (→  37)

Temperature unit Measuring unit for temperatures (e.g. sensor temperature, (→  37)
electronics temperature)

Tank type Selection of the tank type (for liquid measurements) (→  37)

Tube diameter Specification of the bypass or stilling well diameter (for liquid (→  38)
measurements)

Bin property Selection of the bin type (for solid measurements) (→  38)

Max. filling speed liquid Specification of the maximum filling speed (for liquid (→  39)
measurements)

Max. draining speed liquid Specification of the maximum draining speed (for liquid (→  39)
measurements)

Max. filling speed solid Specification of the maximum filling speed (for solid (→  39)
measurements)

Max. draining speed solid Specification of the maximum draining speed (for solid (→  40)
measurements)

Advanced process Specification of additional process conditions (if required) (→  40)


conditions

Application parameter Indicates whether settings depending on the application (→  41)


parameters have been changed after the definition of the
application parameters.

Submenus
Submenu Meaning Description

Medium Properties of the medium (→  42)

Level Parametrization of a level measurement (→  44)

Linearization Transformation of the measured level into a volume or weight for (→  54)
arbitrarily shaped vessels

Information Informs about the current state of the measurement (→  63)

Sensor properties Definition of measurement related properties of the probe (→  68)

Distance Filtering of the raw distance (→  70)

Gas phase Compensation of the influences of a gas or steam above the measured (→  78)
compensation medium.

Sensor diagnostics Informs about the state of the probe and the HF cable. (→  85)

Safety settings Defines the behavior of the device in critical situations (e.g. lost echo, (→  86)
level in safety distance).

Envelope curve Preprocessing of the envelope curve (→  90)

Mapping Suppression of interference echos (→  91)

Tank bottom Evaluation of echoes in the proximity of the tank bottom (→  94)
evaluation

Echo tracking Tracking of level, interface, multiple and interference echos in order to (→  95)
identify the correct echo unambiguously.

36 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.2.2 Description of parameters

Distance unit (0551)

Navigation Expert → Sensor → Distance unit

Write access Maintenance

Description Length unit for distance calculation

Options • mm
•m
• ft
• in

Factory setting m

Temperature unit (0557)

Navigation Expert → Sensor →Temperature unit

Write access Maintenance

Description Select temperature unit

Options • °C
• °F
•K
• °R

Factory setting °C

Tank type (1175)

Navigation Expert → Sensor → Tank type

Write access Maintenance

Prerequisite Medium type = Liquid

Description Defines the tank type

Endress+Hauser 37
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Options • Process vessel with agitator


• Process vessel standard
• Storage vessel
• Bypass / pipe
• Open channel
• Wave guide antenna
• Stilling well
• Sphere
• Workbench test
The antenna type of the device determines which of these options are available.

Factory setting Process vessel standard

Additional information Depending on the Tank type parameter the parameters Max. filling speed liquid and
Max. draining speed liquid are preset among others.

Tube diameter (1117)

Navigation Expert → Sensor → Tube diameter

Write access Maintenance

Prerequisite Tank type = Bypass / pipe

Description Defines the diameter of the bypass or stilling well.

Input range 0 ... 9999 mm (0 ... 390 inch)

Factory setting 0 mm (0 in)

Additional information The tube diameter must be entered for bypass and stilling well applications in order to
optimally adapt the measurement to the measuring point.

Bin property (1176)

Navigation Expert → Sensor → Bin property

Write access Maintenance

Prerequisite Medium type = Solid

Description Defines the bin property

Options • Bin / pile


• Buffer silo (fast)
• Crusher / belt
• Silo
• Workbench test

38 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Factory setting Silo

Additional information Depending on the Bin type parameter, the parameters Max. filling speed solid and Max.
draining speed solid are preset, among others.

Max. filling speed liquid (1212)

Navigation Expert → Sensor → Max. filling speed liquid

Write access Maintenance

Prerequisite Medium type = Liquid

Description Select expected maximum filling speed

Options • Slow < 1cm (0.4in)/min


• Medium < 10cm (4in)/min
• Standard < 1m (40in)/min
• Fast < 2m (80in) /min
• Very fast > 2m (80in) /min
• No filter / test

Factory setting Standard < 1m (40in)/min

Max. draining speed liquid (1202)

Navigation Expert → Sensor → Max. draining speed liquid

Write access Maintenance

Prerequisite Medium type = Liquid

Description Select expected maximum draining speed

Options • Slow < 1cm (0.4in)/min


• Medium < 10cm (4in)/min
• Standard < 1m (40in)/min
• Fast < 2m (80in) /min
• Very fast > 2m (80in) /min
• No filter / test

Factory setting Standard < 1m (40in)/min

Max. filling speed solid (1214)

Navigation Expert → Sensor → Max. filling speed solid

Endress+Hauser 39
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Write access Maintenance

Prerequisite Medium type = Solid

Description Select maximum expected filling speed.

Options • Very slow < 0.5m (1.6ft) /h


• Slow < 1 m (3.3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test

Factory setting Standard < 2m (6,5ft) /h

Additional information The Max. filling speed solid parameter must be set according to the actual process
velocity.

Max. draining speed solid (1213)

Navigation Expert → Sensor → Max. draining speed solid

Write access Maintenance

Prerequisite Medium type = Solid

Description Select maximum expected draining speed.

Options • Very slow < 0.5m (1.6ft) /h


• Slow < 1 m (3.3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test

Factory setting Standard < 2m (6,5ft) /h

Additional information The Max. draining speed solid parameter must be set according to the actual process
velocity.

Advanced process conditions (1177)

Navigation Expert → Sensor → Advanced process conditions

Write access Maintenance

Description Defines additional process conditions (if necessary)

40 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Options • None
• Weak signal
• Many obstacles
• Small tanks (< 1m/3ft)
• Changing DC values
• Foam (> 5cm/0.16ft)

Factory setting None

Additional information • Weak signal


Increases the sensitivity of the device in case of weak signals.
• Many obstacles
Can improve the behavior of the device in case of many obstacles in a silo if strongly
damping media (e.g. flour) are measured.
• Small tanks (< 1m/3ft)
Can improve the near-range measurement in small vessels.
• Changing DC values
Adjusts the signal evaluation of the device to strongly changing DC values of the
measured medium.
• Foam (> 5cm/0.16ft)
Adjusts the signal evaluation of the device to conditions with foam > 5 cm (1.6 in).

Application parameter (1126)

Navigation Expert → Sensor → Application parameter

Write access Read-only parameter

Description Indicates whether parameters have been changed after the basic setup.

Display options • Changed


• Not changed

Additional information Indicates whether a setting which depends on the application parameters (e.g. "Process
property", Advanced process conditions", "Tank type" and "Pipe diameter") has been changed
after the basic setup.
• Changed
Parameters have been changed. The device is no longer in the state defined by the
application parameters.
• Not changed
There have been no changes. The device is still in the state defined by the application
parameters.

Endress+Hauser 41
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.3 Expert → Sensor → Medium

Overview
The Medium submenu is used to specify the relevant properties of the measured medium,
especially the dielectric constant (DC).

Parameter Meaning Description

Medium type Options: "Liquid" or "Solid" (→  42)


1)
Medium group Rough selection of the DC ("Water based" or (→  42)
"Others")

Medium property Finer selection of the DC (→  43)

Calcualted DC value Displays the calculated DC. (→  43)

1) Only available for "Medium type" = "Liquid".

Description of parameters

Medium type (1049)

Navigation Expert → Sensor → Medium → Medium type

Write access Service

Description Indicates the medium type

Display options • Liquid


• Solid

Factory setting • FMR50: Liquid


• FMR51: Liquid
• FMR52: Liquid
• FMR53: Liquid
• FMR54: Liquid
• FMR56: Solid
• FMR57: Solid

Medium group (1208)

Navigation Expert → Sensor → Medium → Medium group

Write access Maintenance

Prerequisite Medium type = Liquid

Description Defines the medium group of the measured product.

Options • Water based (DC ≥ 4)


• Others (DC > 1.9)

42 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Factory setting Others (DC > 1.9)

Additional information If required, smaller DC values can be entered into Expert → Sensor → Medium → Medium
property. This, however, may reduce the measuring range.
Refer to the Technical Information (TI) of the respective device.

Medium property (1165)

Navigation Expert → Sensor → Medium → Medium property

Write access Maintenance

Description DC: Dielectric constant

Options • Unknown
• DC 1.4 to 1.6
• DC 1.6 to 1.9
• DC 1.9 to 2.5
• DC 2.5 to 4
• DC 4 to 7
• DC 7 to 15
• DC > 15

Factory setting Unknown

Additonal information Dielectric constants of important media commonly used in the industry are
summarized in the document SD106F, which can be downloaded from the Endress
+Hauser web page (www.endress.com).

Calculated DC value (1118)

Navigation Expert → Sensor → Medium → Calculated DC value

Write access Read-only parameter

Description DC: Dielectric constant

Additional information Indicates a DC value calculated by the device. The calculation is only possible for small DC
values as it requires the tank bottom signal.

Endress+Hauser 43
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.4 Expert → Sensor → Level

Overview
The Level submenu is used to parametrize the calculation of the level from the measured
distance.

1 2 3 4 5

R
L 100%

D
D

100%
D0

100% B
E A DL
D0 D L0 L0 B L
F

DD 0%
t A
0% 0%

A0016141

1 Calculation of the level from the measured distance


1 Correction of the measured distance
2 Level calculation
3 Level limitation
4 Correction of the level
5 Definition of the output value: Level (A) or Ullage (B)

Parameters of the "Level" submenu

Task Required parameters Parameter Description

Correction of the measured distance Distance offset (2309) (→  45)

Distance (2231) (→  45)

Level calculation Empty calibration (2343) (→  46)

Full calibration (2308) (→  47)

Level unit (0576) (→  48)

Level limitation Level limit mode (2314) (→  49)

High limit (2312) (→  49)

Low limit (2313) (→  50)

Level correction Level correction (2325) (→  50)

Definition of the output value Output mode (2317) (→  51)

Level indication Level (2319) (→  51)

Level linearized (2318) (→  52)

Definition of the tank or silo height Tank/silo height (→  52)

44 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Description of parameters

Distance offset (2309)

Navigation Expert → Sensor → Level → Distance offset

Write access Maintenance

Description Definition of the distance offset

Input range -200.000,0 ... +200.000,0 mm (-60 ... +60 ft)

Factory setting 0.0 mm

Additonal Information The value speicified in this parameter is added to the measured distance between the
reference point of the measurement and the level echo.
• Positive values increase the distance and thus decrease the level.
• Negative values decrease the distance and thus increase the level.

R R
D0

D0
D

DD(<0)
DD(>0)

A0016081

2 Effect of the "Distance offset" parameter


ΔD Distance offset
D0 Measured distance (as indicated in "Expert → Sensor → Distance → Distance")
D Corrected distance (is used to calculate the level)
R Reference point

A value entered into this parameter is taken into account in the calculation of the
level. However, it does not influence the indicated distance.

Distance (2231)

Navigation Expert → Sensor → Level → Distance

Write access Read-only parameter

Endress+Hauser 45
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Description Displays the measured distance D from the


reference point (lower edge of the flange or
threaded connection) to the level.
D

A0019483

A0019485

Additional information The value is displayed in the selected "Level unit" (→  48).

Empty calibration (2343)

Navigation Expert → Sensor → Level → Empty calibration

Write access Maintenance

Description Distance process connection to min. level

Input range 0 to 100 m (0 to 328 ft)

Factory setting • FMR50: 40 m (131 ft)


• FMR51: 40 m (131 ft)
• FMR52: 40 m (131 ft)
• FMR53: 20 m (66 ft)
• FMR54: 20 m (66 ft)
• FMR56: 30 m (98 ft)
• FMR57: 70 m (230 ft)
A different value can be defined when ordering the device.

46 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Additional information The empty calibration E is the distance


between the reference point (lower edge of the
flange or threaded connection) and the
minimum level (0%).

0%

A0019486

0%

A0019488

Full calibration (2308)

Navigation Expert → Sensor → Level → Full calibration

Write access Maintenance

Description Span: max. level - min. level

Input range 0.001 to 100 m (0.003 to 328 ft)

Factory setting Empty calibration - Blocking distance


A different value can be defined when ordering the device.

Endress+Hauser 47
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Additional information The full calibration F is the distance between


the minimum level (0%) and the maximum
level (100%).
100%

0%

A0019487

100%

0%

A0019489

Level unit (0576)

Navigation Expert → Sensor → Level → Level unit

Write access Maintenance

Description Defines the level unit

Options •%
•m
• mm
• ft
• in

Factory setting %

Additional information The level unit may differ from the distance unit defined in the Distance unit parameter
(→  37):
• The distance unit is used for the basic calibration ("Empty calibration" and "Full
calibration").
• The level unit is used to display the (unlinearized) level.

48 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Level limit mode (2314)

Navigation Expert → Sensor → Level → Level limit mode

Write access Maintenance

Description Defines the typ of level limitation

Options • Off
• Low limit
• High limit
• Low and high limit

Factory setting Low limit

Additional information The parameter determines to which direction the level is limited. The exact limits are
defined in the High limit and Low limit parameters.

A B C
L L L
100% 100% 100%
1 1
a a
2 2 2 2
b b

0% 0% 0%
t 1 t 1 t

A0016083

3 Effect of the parameters "Level limit mode", "High limit" and "Low limit"
A Level limit mode = High limit
B Level limit mode = Low limit
C Level limit mode = Low and high limit
a High limit
b Low limit
1 Level before limitation
2 Level after limitation

High limit (2312)

Navigation Expert → Sensor → Level → High limit

Write access Maintenance

Prerequisite Level limit mode = High limit or Low and high limit

Description Defines the upper limit of the level signal.

Endress+Hauser 49
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Input range Depending on the selected distance unit:


• 0.0 to 100.0 %
• 0.0 to +200.0 m
• 0.2 to +656.2 ft
• 0.0 to +7874.0 inch
• 00.0 to +200,000.0 mm

Factory setting 100%

Additional information Levels exceeding the value specified in this parameter will be ignored. Instead, the device
uses the value specified in this parameter (for measured value transformation and output).

Low limit (2313)

Navigation Expert → Sensor → Level → Low limit

Write access Maintenance

Prerequisite Level limit mode = Low limit or Low and high limit

Description Defines the lower limit of the level signal.

Input range Depending on the selected distance unit:


• 0.0 to 100.0 %
• 0.0 to +200.0 m
• 0.0 to +656.2 ft
• 0.0 to +7874.0 inch
• 00.0 to +200,000.0 mm

Factory setting 0%

Additional information Levels falling below the value specified in this parameter will be ignored. Instead, the
device uses the value specified in this parameter (for measured value transformation and
output).

Level correction (2325)

Navigation Expert → Sensor → Level → Level correction

Write access Maintenance

Description Defines a level correction

Input range Depending on the selected level unit:


• -100.0 to 100.0 %
• -200.0 to +200.0 m
• -656.2 to +656.2 ft
• -7874.0 to +7874.0 inch
• -200,000.0 to +200,000.0 mm

50 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Factory setting 0%

Additional information The value specified in this parameter is added to the measured level (before linearization).

Output mode (2317)

Navigation Expert → Sensor → Level → Output mode

Write access Maintenance

Description Defines the output mode

Options • Ullage
• Level linearized

Factory setting Level linearized

Additional information • Ullage


The unfilled space of the tank or silo is indicated.
• Level linearized
The level is indicated (more precisely: the linearized value if a linearization has been
activated).

100%
B
A

0%

A0016086

4 Definition of the "Output mode" parameter


A Level linearized
B Ullage

Level (2319)

Navigation Expert → Sensor → Level → Level

Write access Read-only parameter

Endress+Hauser 51
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Description Displays the measured level L (before


linearization)

0%

A0019482

L
0%

A0019484

Additional information The value is displayed in the selected "Level unit" (→  48).

Level linearized (2318)

Navigation Expert → Sensor → Level → Level linearized


Expert → Sensor → Linearization → Level linearized

Write access Read-only parameter

Description Displays the linearized level.

Additional information The unit of this parameter is defined in the Unit after linearization parameter
(→  57).

Tank/silo height

Navigation Expert → Sensor → Level → Tank/silo height

52 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Write access Maintenance

Description Total height of the tank or silo as measured from the process connection.

Input range –999.999 to +999.999 m (–3 280 to +3 280 ft)

Factory setting 4 m (13.1 ft)

Additional information If the parametrized measuring range (Empty


calibration) differs significantly from the tank
or silo height, it is recommended to enter the
tank or silo height. On default, Tank/Silo
height is always equal to Empty calibration.
E
Example: Continuous level monitoring in the
upper third of a tank or silo. 0%
1

A0019867

E Empty calibration
1 Tank/Silo height

0%

A0019868

E Empty calibration
1 Tank/Silo height

Endress+Hauser 53
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.5 Expert → Sensor → Linearization

Overview

2
A
L
100%
L 1 B L‘
0%
M L‘
L
100%
C L2
L1
0% L‘1L‘2 L‘
L
100%

H
D
0% M L‘
L
100%

h
E
0% M L‘
L
100%
F
h

0% M L‘
L
100%
G d

0%
M L‘
L
100%
H d

0%
M L‘

A0019648

5 Linearization: Transformation of the level into a volume or weight; the transformation is dependent on
the shape of the vessel.
1 Selection of linearization type and unit
2 Parametrization of the linearization
A Linearization type = None
B Linearization type = Linear
C Linearization type = Table
D Linearization type = Pyramid bottom
E Linearization type = Conical bottom
F Linearization type = Angled bottom
G Linearization type = Horizontal cylinder
H Linearization type = Sphere
L Level before linearization (measured in level unit)
L' Level after linearization (corresponds to volume or weight)
M Maximum value
d Diameter
h Intermediate height

54 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Parameters of the "Linearization" submenu

Task Required parameters Parameter description

Selection of linearization type and unit after Linearization type (→  56)


linearization
Unit after linearization (→  57)

Free text (→  58)


1)
Display of the linearized level Level linearized (→  52)

Parametrization of the linearization Linearization type = Linear

Maximum value (→  59)

Linearization type = Horizontal cylinder / Sphere

Maximum value (→  59)

Diameter (→  59)

Linearization type = Pyramid bottom / Conical bottom / Angled


bottom

Maximum value (→  59)

Intermediate height (→  59)

Linearization type = Table

Table mode (→  60)


1)
Table number (→  61)

Level (→  61)

Customer value (→  62)

Activate table (→  62)

1) Only for operation via operating tool (e.g. FieldCare), not on the local display module

Endress+Hauser 55
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Description of parameters

Linearization type (2339)

Navigation Expert → Sensor → Linearization → Linearization type

Write access Maintenance

Description Defines the type of linearization

Options • None
The level is transmitted to the output 100%
without linearization.
• Linear (A) A
• Table (B)
• Pyramid bottom (C) 0%
• Conical bottom (D)
• Angled bottom (E) 100%
• Horizontal cylinder (F)
• Sphere (G) B

0%

100%

C/D

0%

100%

0%

100%
F/G

0%

A0013299

Factory setting None

56 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Additional information • None


The level is transmitted in the level unit without linearization.
• Linear
The output value (volume/weight) is directly proportional to the level L. This is valid, for
example, for vertical cylinders. Additionally, the following parameters have to be
specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
• Table
The relationship between the measured level L and the output value (volume/weight) is
given by a linearization table consisting of up to 32 pairs of values "level - volume" or
"level - weight", respectively.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Table mode (2303)
– For each table point: Level (2383)
– For each table point: Customer value (2384)
– Activate table (2304)
• Pyramid bottom
The output value corresponds to the volume or weight in a silo with pyramid bottom.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Intermediate height (2310): The height of the pyramid
• Conical bottom
The output value corresponds to the volume or weight in a tank with conical bottom.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Intermediate height (2310): The height of the conical part of the tank
• Angled bottom
The output value corresponds to the volume or weight in a silo with an angled bottom.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Intermediate height (2310): Height of the angled bottom
• Horizontal cylinder
The output value corresponds to the volume or weight in a horizontal cylinder tank.
Additionally, the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Diameter (2342)
• Sphere
The output value corresponds to the volume or weight in a spherical tank. Additionally,
the following parameters have to be specified:
– Unit after linearization (2340)
– Maximum value (2315): Maximum volume or weight
– Diameter (2342)

Unit after linearization (2340)

Navigation Expert → Sensor → Linearization → Unit after linearization

Write access Maintenance

Endress+Hauser 57
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Prerequisite Only visible if a linearization has been selected (i.e. Linearization type ≠ None)

Description Defines the unit of the linearized value.

Options • Free text


•t
• lb
• ton
• kg
• impGal
• UsGal
• cf
• cm3
• dm3
• m3
• hl
•l
•%

Factory setting %

Additional information The selected unit is only used to be indicated on the display. The measured value is not
transformed according to the selected unit.
It is also possible to parametrize a distance-to-distance linearization, i.e. a
transformation from the level unit to a different distance unit. To do so, select the
Table linearization mode. In order to define the new level unit, select the Free text
option in the Unit after linearization parameter and enter the unit into the Free text
parameter.

Free text (2341)

Navigation Expert → Sensor → Linearization → Free text

Write access Maintenance

Prerequisite Only visible for Unit linearized = Free text.

Description Definiton of the unit

Input range Up to 32 alphanumerical characters (letters, numbers, special characters)

Factory setting Free text

Level linearized (2318) (→  52)

Prerequisite Only visible for operation via operating tool (e.g. FieldCare), not on the local display
module.

58 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Maximum value (2315)

Navigation Expert → Sensor → Linearization → Maximum value

Write access Maintenance

Prerequisites Only visible if one of the following linearization types has been selected:
• Linear
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere

Description Definition of the maximum content of the vessel (100%), as measured in the Unit
linearized.

Input range -50000 ... +50000

Factory setting 100

Diameter (2342)

Navigation Expert → Sensor → Linearization → Diameter

Write access Maintenance

Prerequisites Only visible if one of the following linearization types has been selected:
• Horizontal cylinder
• Sphere

Description Definition of the tank diameter

Input range 0 ... 9999.999 m (32808 ft)

Factory setting 2 m (6.6 ft)

Additional information The value must be specified in the selected distance unit (→  37).

Intermediate height (2310)

Navigation Expert → Sensor → Linearization → Intermediate height

Write access Maintenance

Endress+Hauser 59
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Prerequisites Only visible if one of the following linearization types has been selected:
• Pyramid bottom
• Conical bottom
• Angled bottom

Description Definition of the intermediate height H

H
0%

A0013264

Input range 0 to 200 m (0 to 656 ft)

Factory setting 0 m (0 ft)

Additional information The value must be specified in the selected distance unit (→  37).

Table mode (2303)

Navigation Expert → Sensor → Linearization → Table mode

Write access Maintenance

Prerequisite Only visible if the "Table" linearization type has been selected.

Description Defines the method used to enter linearization points into the table.

Options • Manual
The level and the associated linearized value are entered manually for each linearization
point.
• Semi-automatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
• Clear table
Deletes the existing linearization table.
• Sort table
Rearranges the linerization points into an ascending order.

Factory setting Manual

60 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Additional information Conditions the linearization table must meet:


• The table may consist of up to 32 pairs of values "Level - Linearized Value".
• The table must be monotonic (monotonically increasing or decreasing).
• The first linearization point must refer to the minimum level.
• The last linearization point must refer to the maximum level.
Entering the table
• Via FieldCare: The table points may be entered via the parameters Table number,
Level and Customer value. As an alternative, the graphical table editor can be
used: Device Operation → Device Functions → Additional Functions →Linearization
(Online/Offline)
• Via the local display module: Access the graphical table editor by the Edit table
option. The table is dispayed on the display module and can be edited row by row.
The factory setting for the level unit is "%". If you want to enter the linearization table
in physical units, a suitable level unit has to be selected beforehand in the Expert →
Sensor → Level → Level unit parameter.

Table number (2370)

Navigation Expert → Sensor → Linearization → Table number

Write access Maintenance

Prerequisite • Only visible for Linearization type = Table


• Only visible via operating tool (e.g. FieldCare), but not on the local display module.

Description Number of the table point which will be defined by the next two parameters (Level and
Cusotmer value).

Input range 1 to 32

Factory setting 1

Level (2383/2389)

Navigation Expert → Sensor → Linearization → Level

Write access • For Table mode = Semiautomatic: Maintenance


• For Table mode = Manual: Read-only parameter

Prerequisite • Only visible for Linearization type = Table


• Only visible via operating tool (e.g. FieldCare), but not on the local display module.

Description Definition or display of the (unlinearized) level of the respective linearization point.

Input range Depending on the parametrized measuring range. See the parameters Empty calibration
(→  46) and Full calibration (→  47).

Factory setting 0

Endress+Hauser 61
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Additional information For Table mode = Manual: Level is a writable parameter.


For Table mode = Semi-automatic: Level is a read-only parameter.

Customer value (2384)

Navigation Expert → Sensor → Linearization → Customer value

Write access Maintenance

Prerequisite • Only visible for Linearization type = Table


• Only visible via operating tool (e.g. FieldCare), but not on the local display module.

Description Specification of the linearized value of the respective linearization point.

Input range -3,0 x 1038 ... +3,0 x 1038

Factory setting 0

Activate table (2304)

Navigation Expert → Sensor → Linearization → Activate table

Write access Maintenance

Prerequisite Only visible if the "Table" linearization type has been selected.

Description Enables or disables the linearization table.

Options • Disable
A linearization is not calculated. If the Linearization type parameter has been set to
Table, the error message F435 is generated.
• Enable
The measured value is linearized according to the table before being sent to the output.

Factory setting Disable

Additional information When editing the table, this parameter is automatically reset to the Disable option. After
finishing the editing procedure it must be set to the Enable option again.

62 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.2.6 Expert → Sensor → Information

Overview
The Information submenu comprises all display parameters which give information about
the current state of the measurement:

Parameter ParameterDescription

Signal quality (1047) (→  64)

Absolute echo amplitude (1127) (→  64)

Relative echo amplitude (1089) (→  65)

Tank bottom echo amplitude (1128) (→  66)

Found echoes (1068) (→  66)

Used calculation (1115) (→  66)

Tank trace state (1206) (→  66)

Measurement frequency (1180) (→  67)

Electronic temperature (1062) (→  67)

Endress+Hauser 63
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Description of parameters

Signal quality (1047)

Navigation Expert → Sensor→ Information → Signal quality

Write access Read-only parameter

Description Indicates the signal quality.

Display options • Strong


The evaluated echo exceeds the threshold by at least 10 dB
• Medium
The evaluated echo exceeds the threshold by at least 5 dB.
• Weak
The evaluated echo exceeds the threshold by less than 5 dB.
• No signal
The device does not find a usable echo and generates the following error message
– F941 if the Alarm option has been selected in the Output echo lost parameter
(→  86).
– S941 if another option has been selected in the Output echo lost parameter
(→  86).

Additional information The signal quality indicated in this parameter always refers to the currently evaluated
echo: either the level echo or the tank bottom echo. To differentiate between these two,
the quality of the tank bottom echo is always displayed in brackets.

Absolute echo amplitude (1127)

Navigation Expert → Sensor→ Information → Absolute echo amplitude

Write access Read-only parameter

Description Indicates the absolute amplitude of the level echo.

64 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Additional information

A0019961

1 Absolute echo amplitude in the envelope curve, measured in dB

Relative echo amplitude (1089)

Navigation Expert → Sensor→ Information → Relative echo amplitude

Write access Read-only parameter

Description Indicates the relative amplitude of the level echo, i.e. the difference between the level echo
and the echo threshold.
In the envelope curve display of FieldCare, the absolute echo amplitude is indicated
instead of the relative amplitude (see the number on the top right of the echo peak in
the example).

Additional information

A0019962

1 The relative echo amplitude is the difference between the weighting curve (blue) and the peak in the envelope
curve (red).

Endress+Hauser 65
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Tank bottom echo amplitude (1128)

Navigation Expert → Sensor→ Information → Tank bottom echo amplitude

Write access Read-only parameter

Description Indicates the amplitude of the tank bottom echo

Additional information The tank bottom echo amplitude is only evaluated for media with a small DC value.

Found echoes (1068)

Navigation Expert → Sensor→ Information → Found echos

Write access Read-only parameter

Description Indicates which echoes have been found.

Display options • None


• Level
• Level and TB
• TB (TT)
• Multiple echo (TT)
• Tank bottom

Used calculation (1115)

Navigation Expert → Sensor→ Information → Used calculation

Write access Read-only parameter

Description Indicates which echoes are used for the calculation fo the measured value.

Display options • None


• Level
• Tank bottom
• TB (TT)
• Multiple echo (TT)
• Level and TB

Tank trace state (1206)

Navigation Expert → Sensor→ Information → Tank trace state

66 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Write access Read-only parameter

Description Indicates the current state of the tank trace.

Display options • Not active


A valid tank trace is not available.
• EOP (TT)
A valid EOP tank trace is available.
• Multiple echo (TT)
A valid multiple echo tank trace is available.
• EOP + Multiple echo (TT)
A valid EOP and multiple echo tank trace is available.

Measurement frequency (1180)

Navigation Expert → Sensor→ Information → Measurement frequency

Write access Read-only parameter

Description Displays the current measurement frequency (number of pulses per second).

Electronic temperature (1062)

Navigation Expert → Sensor→ Information → Electronic temperature

Write access Read-only parameter

Description Displays the current temperature of the electronics.

Additional information The unit is defined in the Expert → Sensor → Temperature unit parameter .

Endress+Hauser 67
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.7 Expert → Sensor → Sensor properties

Overview
The Sensor properties submenu comprises all parameters which describe the
measurement-related properties of the probe and the envelope curve.

Overview of the parameters

Eigenschaft Zugehörige Parameter Parameterbeschreibung

Basic properties of the probe (→  68) Sensor module (→  68)

Free field special (→  68)

Basic properties of the probe

Sensor module (1101)

Navigation Expert → Sensor → Sensor properties → Sensor module

Write access Read-only parameter

Description Indicates the type of sensor module.

Display options • SMR6


Radar sensor module 6 GHz; valid for:
– FMR53
– FMR54
• SMR26L
Radar sensor module 26 GHz; valid for:
– FMR50 without "Advanced dynamics" application package
– FMR51 without "Advanced dynamics" application package
– FMR52 without "Advanced dynamics" application package
• SMR26S
Radar sensor module 26 GHz; valid for:
– FMR50 with "Advanced dynamics" application package
– FMR51 with "Advanced dynamics" application package
– FMR52 with "Advanced dynamics" application package
– FMR56
– FMR57

Free field special (1150)

Navigation Expert → Sensor → Sensor properties → Free field special

Write access Maintenance

Description This parameter can be switched on in the case of free-field applications (e.g. below a
bridge).

68 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Options • No
• Yes

Factory setting No

Endress+Hauser 69
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.8 Expert → Sensor → Distance

Overview
The Distance submenu contains all parameters by which the filtering of the raw distance
D1 is controlled. The resulting distance D0 is used for the subsequent level calculation
(→  44).

1 2

D1 D0

A0016175

6 The configurable distance filters


1 Dead time
2 Low pass filter (defined by integration time)

70 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Parameters of the "Distance" submenu

Task Required parameters Description

Display of the distances (→  72) Distance (→  72)

Definition of the dead time (→  73) Dead time (→  73)

Configuration of the low pass filter (→  75) Integration time (→  75)

Definition of the blocking distance (→  77) Blocking distance (→  77)

Endress+Hauser 71
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Display of the distances

Distance (1124)

Navigation Expert → Sensor → Distance → Distance

Write access Read-only parameter

Description Displays the measured distance D from the


reference point (lower edge of the flange or
threaded connection) to the level.
D

A0019483

72 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Definition of the dead time

Dead time (1199)

Navigation Expert → Sensor → Distance → Dead time

Write access Maintenance

Description Defines the dead time (in seconds).

Input range 0 to 60 s

Factory setting Dependent on the following parameters:


• for Medium type = Liquid
– Max. filling speed liquid
– Max. draining spid liquid
• for Medium type = Solid
– Max filling speed solid
– Max. draining speed solid

Dependencies of the "Dead time" parameter for "Medium type" = "Liquid"

Max. filling speed liquid Max. draining speed liquid

Slow Medium Standard Fast Very fast No filter / test


< 1cm (0,4in)/min < 10cm (4in)/min < 1m (40in)/min < 2m (80in)/min > 2m (80in)/min

Slow
8s 6s 4s 2s 0s 0s
< 1cm (0,4in)/min

Medium
6s 6s 4s 2s 0s 0s
< 10cm (4in)/min

Standard
4s 4s 4s 2s 0s 0s
< 1m (40in)/min

Fast
2s 2s 2s 2s 0s 0s
< 2m (80in)/min

Very fast
0s 0s 0s 0s 0s 0s
> 2m (80in)/min

No filter / test 0s 0s 0s 0s 0s 0s

Endress+Hauser 73
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Dependencies of the "Dead time" parameter for "Medium type" = "Solid"

Max. filling Max. draining speed solid


speed solid
Very slow Slow Standard Medium Fast Very fast No filter / test
< 0,5m < 1m (3,3ft)/h < 2m (6,5ft)/h < 4m (13ft)/h < 8m (26ft)/h > 8m (26ft)/h
(1,6ft)/h

Very slow
< 0,5m 180 s 180 s 120 s 60 s 40 s 0s 0s
(1,6ft)/h

Slow
180 s 180 s 120 s 60 s 40 s 0s 0s
< 1m (3,3ft)/h

Standard
120 s 120 s 60 s 60 s 40 s 0s 0s
< 2m (6,5ft)/h

Medium
60 s 60 s 60 s 40 s 40 s 0s 0s
< 4m (13ft)/h

Fast
40 s 40 s 40 s 40 s 20 s 0s 0s
< 8m (26ft)/h

Very fast
0s 0s 0s 0s 0s 0s 0s
> 8m (26ft)/h

No filter / test 0s 0s 0s 0s 0s 0s 0s

Additional information Application


Sudden changes of the measured distance are ignored during the time span defined in this
parameter. In this way it is possible to prevent short-term interferences form disturbing
the output signal.

2 3

1 t

A0016164

7 Effect of the dead time


1 Dead time
2 Signal before the dead time filter
3 Signal after the dead time filter

Disadvantages
• The device slows down.
• Fast level changes are registered with a delay.

74 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Parametrization of the low pass filter


The low pass filter dampens the distance signal with a user defined integration time τ.
After a sudden change of the level, it lasts about 5 x τ until the new measured value is
obtained.

D
1

5xt t
A0016169

8 Low pass filter


1 Signal before the low pass filter
2 Signal after the low pass filter
τ Integration time

Integration time (1092)

Navigation Expert → Sensor → Distance → Integration time

Write access Maintenance

Description Defines the integration time (in seconds).

Input range 0 to 200 000 s

Factory setting Dependent on the following parameters:


• for Medium type = Liquid
– Max. filling speed liquid
– Max. draining spid liquid
• for Medium type = Solid
– Max filling speed solid
– Max. draining speed solid

Endress+Hauser 75
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Dependencies of the "Integration time" parameter for "Medium type" = "Liquid"

Max. filling speed liquid Max. draining speed liquid

Slow Medium Standard Fast Very fast No filter / test


< 1cm (0,4in)/min < 10cm (4in)/min < 1m (40in)/min < 2m (80in)/min > 2m (80in)/min

Slow
30 s 15 s 5s 1s 0s 0s
< 1cm (0,4in)/min

Medium
15 s 15 s 5s 1s 0s 0s
< 10cm (4in)/min

Standard
5s 5s 5s 1s 0s 0s
< 1m (40in)/min

Fast
1s 1s 1s 1s 0s 0s
< 2m (80in)/min

Very fast
0s 0s 0s 0s 0s 0s
> 2m (80in)/min

No filter / test 0s 0s 0s 0s 0s 0s

Dependencies of the "Integration time" parameter for "Medium type" = "Solid"

Max. filling Max. draining speed solid


speed solid
Very slow Slow Standard Medium Fast Very fast No filter / test
< 0,5m < 1m (3,3ft)/h < 2m (6,5ft)/h < 4m (13ft)/h < 8m (26ft)/h > 8m (26ft)/h
(1,6ft)/h

Very slow
< 0,5m 250 s 200 s 200 s 100 s 50 s 1s 0s
(1,6ft)/h

Slow
200 s 200 s 200 s 100 s 50 s 1s 0s
< 1m (3,3ft)/h

Standard
200 s 200 s 100 s 100 s 50 s 1s 0s
< 2m (6,5ft)/h

Medium
100 s 100 s 100 s 50 s 50 s 1s 0s
< 4m (13ft)/h

Fast
50 s 50 s 50 s 50 s 20 s 1s 0s
< 8m (26ft)/h

Very fast
1s 1s 1s 1s 1s 1s 0s
> 8m (26ft)/h

No filter / test 0s 0s 0s 0s 0s 0s 0s

Additional information Increasing the integration time results in a calmer measuring signal. However, this also
means that the measuring signal indicates level changes with a certain delay.

76 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Definition of the blocking distance

Blocking distance (1144)

Navigation Expert → Sensor → Distance → Blocking distance

Write access Maintenance

Description Defines the distance below the process connection in which no measurement is performed.

Input range 0 to 200 m (0 to 656 ft)

Factory setting 0 m (0 ft)

Additional information Echoes from within the blocking distance are


not taken into account in the signal evaluation.

BD

A0019492

Endress+Hauser 77
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.9 Expert → Sensor → Gas phase compensation

Overview
High pressures reduce the propagation velocity of the measuring signals in the gas/vapor
above the fluid. This effect depends on the kind of gas/vapor and of its temperature. This
results in a systematic measuring error that gets bigger as the distance increases between
the reference point of the measurement (flange) and the product surface.

Influence of a gas layer


The following table illustrates this measured error for a few typical gases/vapors (with
regard to distance; a positive value means that too large a distance is being measured):

Gas layer Temperature Pressure

°C °F 1 bar (14.5 psi) 10 bar (145 psi) 50 bar (725 psi) 100 bar (1 450 psi) 160 bar (2 320 psi)

Air/ 20 68 0.00 % 0.22 % 1.2 % 2.4 % 3.89 %


Nitrogen
200 392 –0.01 % 0.13 % 0.74 % 1.5 % 2.42 %

400 752 –0.02 % 0.08 % 0.52 % 1.1 % 1.70 %

Hydrogen 20 68 –0.01 % 0.10 % 0.61 % 1.2 % 2.00 %

200 392 –0.02 % 0.05 % 0.37 % 0.76 % 1.23 %

400 752 –0.02 % 0.03 % 0.25 % 0.53 % 0.86 %

Water 100 212 0.02 % - - - -


(saturated
steam) 180 356 - 2.1 % - - -

263 505.4 - - 8.6 % - -

310 590 - - - 22 % -

364 687 - - - - 41.8 %

Types of gas phase compensation


The influence of the gas phase can be compensated for in the following ways:
• Gas phase compensation with reference signal 2) (→  79)
• Constant gas phase compensation factor (→  80)
• For PROFIBUS PA and FOUNDATION Fieldbus: Compensation with external pressure
measurement (→  81)

2) This type of gas phase compensationis not recommended for Micropilot.

78 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Gas phase compensation with reference signal


This type of gas phase compensation needs an artificaial reference echo at a definite
distance from the process connection. The reference signal must always be above the
maximum level. The position of the reference echo depends on the pressure of the gas
phase. The device uses this echo shift to calculate the correction factor for the distance
measurement.

Endress+Hauser 79
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Constant gas phase compensation factor


If the properties of the gas phase (pressure, temperature, composition) do not change over
the time and are known, a gas phase compensation can also be performed without a
reference signal. Instead, a constant, user-defined correction factor is applied in this case.
This factor is used to adjust the envelope curve and thus the measured echo distance.

A
B

B = FA

A0020199

9 Gas phase compensation with a constant correction factor F


A Position of the level echo in the original envelope curve
B Position of the level echo in the corrected envelope curve.

Parameter Meaning Parameter description

GPC mode Select the Const. GPC factor option. (→  82)

Const. GPC factor Enter correction factor for distances (→  84)

80 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Compensation with external pressure measurement (PROFIBUS PA and FOUNDATION


Fieldbus)
The compensation with external pressure measurement is only available for devices
with PROFIBUS PA or FOUNDATION Fieldbus.
In many cases the dielectric constant is proportional to the pressure of the gas phase. If the
proprotionality factor is known, a gas phase compensation can be performed by measuring
the pressure externally.
The device receives the externally measured pressure p of the gas phase through one of
the Analog Input Blocks and uses the user defined gas phase compensation factor F to
calculate the dielectric constant ε of the gas phase according to the following formula:
ε=1+Fp
ε is then used to calculate the correction of the measured distances.

2
ENDRESS + HAUSER

A0016304

 10 Gas phase compensation with external pressure measurement


1 Levelflex
2 Segment coupler
3 PLC
4 Absolute pressure transmitter

Parameter Meaning Parameter


description

GPC mode Select the External correction option. (→  82)

External pressure selector Select the AO block through which the externally (→  82)
measured pressure is received.

External pressure Displays the pressure read in from the AO block (→  83)

Gas phase compensation factor Enter the factor F. (→  83)

Suitable value of the gas phase compensation factor for saturated steam in the
temperature range 100 to 350 °C (212 to 662 °F):
F = 0.00505 / bar

Endress+Hauser 81
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Description of the parameters

GPC mode (1034)

Navigation Expert → Sensor → Gas phase compensation → GPC mode

Write access Maintenance

Description Selection of the GPC mode

Options • Off
The gas phase compensation is deactivated.
• On
This option can only be selected for probes with reference echo. The gas phase
compensation is calculated from the position of this reference echo. The displayed
envelope curve does already contain the correction.
• Without correction
This option can only be selected for probes with reference echo.The correction factor is
calculated from the reference echo but not applied to the measurement.
This option is only used for diagnostic purposes and should not be used for normal
applications. The envelope curve is displayed without the correction.
• External correction
This option can only be selected for devices with PROFIBUS PA or FOUNDATION
Fieldbus. The device receives the externally measured pressure through an AO block and
uses it together with the gas phase compensation factor F to calculate the gas phase
compensation. The displayed envelope curve does already contain the correction.
• Const. GPC factor
The correction factor is a constant defined by the user. A reference echo or an externally
measured pressure are not needed. The displayed envelope curve does already contain
the correction.

Factory setting Off

External pressure selector (1073)

Navigation Expert → Sensor → Gas phase compensation → External pressure selector

Write access Maintanance

Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction

Description Defines the AO block through which the external pressure used for gas phase
compensation is received.

Options • None
• Analog output 1
• Analog output 2
• Analog output 3
• Analog output 4

82 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Factory setting None

External pressure (1220)

Navigation Expert → Sensor → Gas phase sompensation → External pressure

Write access Read-only parameter

Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction

Description Displays the pressure which is currently read-in from the AO block.

Gas phase compensation factor (1209)

Navigation Expert → Sensor → Gas phase compensation → Gas phase compensation factor

Write access Maintenance

Prerequisite Only available for PROFIBUS PA or FOUNDATION Fieldbus and if GPC mode = External
correction

Description Defines the gas phase compensation factor F.

Input range -1038 ... + 1038

Factory setting 0

Additional information Suitable value for saturated steam in the temperature range 100 to 350 °C (212 to 662 °F):
F = 0.00505 / bar

Present reference distance (1076)

Navigation Expert → Sensor → Gas phase compensation → Present reference distance

Write access Read-only prarameter

Prerequisite GPC mode = On or Without correction

Description Displays the currently measured distance of the reference echo.

Reference distance (1033)

Endress+Hauser 83
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Expert → Sensor → Gas phase compensation → Reference distance

Write access Maintenance

Prerequisite GPC mode = On oder Without correction

Description Input parameter for the actual distance of the reference echo.

Input range 0 to 200 m

Factory setting 0.3 m

Additonal information The distance of the aritificially generated reference echo has to be entered into this
parameter. The reference echo must always be in the gas phase; the level must never rise
above the reference echo.

Reference echo threshold (1168)

Navigation Expert → Sensor → Gas phase compensation → Reference echo threshold

Write access Maintenance

Prerequisite GPC mode = On or Without correction

Description Definition of the threshold for the reference echo

Input range –999 to +999 dB

Werkeinstellung –80 dB

Additonal information Only echoes exceeding the defined threshold are accepted as reference echo.

Const. GPC factor (1217)

Navigation Expert → Sensor → Gas phase compensation → Const. GPC factor

Write access Maintenance

Prerequisite GPC mode = Const. GPC factor

Description Definition of a constant correction factor for the measured distance.

Input range 0.5 to 1.5

Factory setting 1 (i.e.: without correction)

84 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.2.10 Expert → Sensor → Sensor diagnostics

Start self check (1133)

Navigation Expert → Sensor → Sensor diagnostics → Start self check

Write access Maintenance

Description Starts a self check of the device.

Result self check (1134)

Navigation Expert → Sensor → Sensor diagnostics → Result self check

Write access Maintenance

Description Displays the result of the self check of the device.

Noise of signal (1105)

Navigation Expert → Sensor → Sensor diagnostics → Noise of signal

Write access Read-only parameter

Beschreibung Displays the noise of signal in the envelope curve (in dB).

Endress+Hauser 85
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.11 Expert → Sensor → Safety settings

Output echo lost (2307)

Navigation Expert → Sensor → Safety settings → Output echo lost

Write access Maintenance

Description Defines the output signal in the case of a lost echo.

Options • Last valid value


The last valid value is kept in the case of a lost echo.
• Ramp echo lost
In the case of a lost echo the output value is continously shifted towards 0% or 100%.
The slope of the ramp is defined in the Ramp echo lost parameter.
• Value echo lost
In the case of a lost echo the output assumes the value defined in the Value echo lost
parameter.
• Alarm
In the case of a lost echo the device generates an alarm and the output assumes the
value defined in the Failure mode parameter .

Factory settings Last valid value

Value echo lost (2316)

Navigation Expert → Sensor → Safety settings → Value echo lost

Write access Maintenance

Prerequisite Only visible if the Value echo lost option has been selected in the Output echo lost
parameter.

Description Defines the constant output value in the case of a lost echo.

Input range 0 ... 200000

Factory setting 0

Additional information The unit is the same as for the output value:
• Without linearization: As defined in the Level unit parameter .
• With linearization: As defined in the Unit after linearization parameter .

Ramp at echo lost (2323)

Navigation Expert → Sensor → Safety settings → Ramp at echo lost

86 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Write access Maintenance

Condition Only visible if the Ramp echo lost option has been selected in the Output echo lost
parameter.

Description Defines the slope of the ramp in the case of a


lost echo. 100%
B

A
C

0%
t

min

A0013269

A Delay echo lost


B Ramp echo lost (positive value)
C Ramp echo lost (negative value)

Input range -9999999.0 ... + 9999999.0 %/min

Factory setting 0 %/min

Additional information • The unit for the slope of the ramp is "percentage of the measuring range per minute" (%/
min).
• For a negative slope of the ramp: The measured value is continuously shifted downwards
until it reaches 0%.
• For a positive slope of the ramp: The measured value is continuosly shifted upwards until
it reaches 100%.

Delay echo lost (1193)

Navigation Expert → Sensor → Safety settings → Delay echo lost

Write access Maintenance

Description Defines the delay in the case of a lost echo.

Input range 0 ... 99999.9 s

Factory setting 60 s

Additional information After an echo loss, the device waits for the time specified in this parameter before reacting
as specified in the Output echo lost parameter. This helps to avoid interruptions of the
mesurement by short-term interferences.

Endress+Hauser 87
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Safety distance (1093)

Navigation Expert → Sensor → Safety settings → Safety distance

Write access Maintenance

Description Definition of the safety distance

Input range –200 to +200 m

Factory setting 0m

Additional information The safety distance is measured from the reference point of the measurement (lower edge
of the flange or threaded connection). The safety distance can be used to generate a
warning before the level rises into the blocking distance. The In safety distance parameter
defines the rection of the device if the level rises into the safety distance.

In safety distance (1018)

Navigation Expert → Sensor → Safety settings → In safety distance

Write access Maintenance

Description Defines the behavior if the level rises into the safety distance.

Options • Off (i.e. no reaction)


• Alarm
The device assumes the alarm state and generates the diagnostic event S942 "In safety
distance".
• Warning
The device assumes the warning state and generates the diagnostic event S942 "In safety
distance".
• Self holding
The device assumes the defined alarm state. Additionally, the diagnostic event S942 "In
safety distance" is generated.
If the level drops out of the safety distance, the alarm remains active. The measurement
is continued only after a reset of the self holding via the Acknowledge Alarm
parameter.

Factory setting Warning

Acknowledge alarm (1130)

Navigation Expert → Sensor → Safety settings → Acknowledge alarm

Write access Maintenance

88 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Prerequisite In safety distance = Self holding

Description Resets the self holding alarm of the device.

Options • No
The alarm is not rest.
• Yes
The alarm is reset. The measurement is resumed.

Factory setting No

Endress+Hauser 89
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.12 Expert → Sensor → Envelope curve

Envelope curve (1207)

Write access Maintenance

Navigation Expert → Sensor → Envelope curve → Envelope curve

Description Defines which curves are included in the envelope curve display on the display module.

Options • Envelope curve


• Envelope + Map
• Envelope + Ref.
• Raw envelope curve
• Envelope + EWC

Factory setting Envelope curve

Additional information The display of the selected curve can be accessed in the following way:

A0014279

90 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.2.13 Expert → Sensor → Mapping

Confirm distance (1045)

Navigation Expert → Sensor → Mapping → Confirm distance

Write access Maintenance

Description Confirmation whether the measured distance matches the actual distance. Depending on
the selection the device automatically determines the range over which the mapping will
be recorded.

Options • Manual map


To be selected if the range of mapping is to be defined manually in the Mapping end
point parameter. In this case it is not necessary to confirm the distance.
• Distance ok
To be selected if the measured distance matches the actual distance. The device
performs a mapping and quits the sequence ("End of sequence" appears on the display).
• Distance unknown
To be selected if the actual distance is unknown. A mapping can not be performed and
the device quits the sequence ("End of sequence" appears on the display).
• Distance too small
To be selected if the measured distance is smaller than the actual distance. The device
searches the next echo and returns to the Confirm distance parameter. The new
distance is displayed. The comparison must be repeated until the displayed distance
matches the actual distance. If this is the case, the recording of the map can be started
by selecting Distance ok.
• Distance too big
To be selected if the measured distance is bigger than the actual distance. The device
adjusts the signal evaluation and returns to the Confirm distance parameter. The
distance is recalculated and displayed. The comparison must be repeated until the
displayed distance matches the actual distance.
• Tank empty
To be selected if the tank is completely empty. The device records a mapping covering
the complete length of the probe and quits the sequence ("End of sequence" appears on
the display).
• Factory map
To be selected if the present mapping curve (if one exists) is to be deleted and the
factory map is to be used instead. The device returns to the Confirm distance parameter
and a new mapping can be recorded.

Factory setting Distance unknown

Additional information For reference purposes the measured distance is displayed together with this parameter.
If the teaching procedure Distance too small or Distance too big is quit before the
distance has been confirmed, a map is not recorded and the teaching procedure is
reset after 60 s.

Distance (1124)

Navigation Expert → Sensor → Mapping → Distance

Endress+Hauser 91
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Write access Read-only parameter

Description Displays the currently measured distance.

Mapping end point (1022)

Navigation Expert → Sensor → Mapping → Mapping end point

Write access Maintenance

Prerequisite Only visible if the Manual map option has been selected in the Confirm distance
parameter.

Description Definition of the distance up to which the mapping curve will be recorded.

Input range 0.1 m to Tank/silo height

Factory setting 0.1 m (0.33 ft)

Additional information The distance is measured from the reference point, i.e. from the lower edge of the
mounting flange or the threaded connection.
For reference purposes the Present mapping parameter is displayed together with this
parameter. Present mapping states up to which distance a mapping has already been
recorded.

Present mapping (1182)

Navigation Expert → Sensor → Mapping → Present mapping

Write access Read-only parameter

Description Indicates up to which distance a mapping has already been recorded.

Record map (1213)

Navigation Expert → Sensor → Mapping → Record map

Write access Maintenance

Prerequisite Only visible if a value has been entered into the Mapping end point parameter.

Description Starts the recording of the map.

92 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Selection • No
The map is not recorded. The device quits the sequence ("End of sequence" is displayed).
• Record map
The map is recorded. When the recording is completed, the new measured distance and
the new mapping range appear on the display. These values must be confirmed by
pressing . The device quits the sequence. ("End of sequence" is displayed.)
• Overlay map
• Factory map
• Delete partial map

Factory setting No

Endress+Hauser 93
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.14 Expert → Sensor → Tank bottom evaluation

Tank bottom range (1149)

Navigation Experte → Sensor → Tank bottom evaluation → Tank bottom range

Write access Maintenance

Description Defines the range (starting from Tank/silo height) in which the tank bottom echo is
searched for.

Input range 0 to 99.999 m (0 to 328 ft)

Factory setting 1 m (3.28 ft)

94 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.2.15 Expert → Sensor → Echo tracking

Evaluation mode (1112)

Write access Maintenance

Navigation Expert → Sensor → Echo tracking → Evaluation mode

Description Selection of the evaluation mode for echo tracking.

Options • History off


The envelope curve is evaluated only statically.
• Short time history
In addition to the static algorithms a dynamic echo trace is continuously created.
• Long time history
In addition to the static algorithms and the dynamic echo trace a tank trace is
continuously created. Using the tank trace the device can determine the level even if the
level echo ist lost temporarily.

Factory setting The Evaluation mode parameter is preset depending on the Tank type or Bin type
parameter, respectively.

History reset (1145)

Write access Maintenance

Navigation Expert → Sensor → Echo tracking → History reset

Description Resets the history of the echo and tank tracking.

Options • Reset done


Does not initiate an action but is only a display option. It is displayed as soon as the reset
operation has been accomplished.
• Reset echo tracking
The echo tracking is reset. The tank trace, however, is maintained.
• Delete history
The echo tracking and tank trace are reset.

Factory setting Reset done

Endress+Hauser 95
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.2.16 Expert → Sensor → External input


The External input submenu is only available on devices with PROFIBUS PA or
FOUNDATION Fieldbus.

Overview
The behavior of the sensor can be controlled via two external switch inputs: measurement
can be switched on and off. Furthermore, a specific value can be assigned to the level when
the digital switch signal is present, regardless of the actual filling height.

The parameters

Level external input 1/2 (2305/2306)

Navigation Expert → Sensor → External input → Level external input 1/2

Write permission Maintenance

Description External input 1 or 2 is assigned a DO block via which the switch signal is read in.

Options • None
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4

Factory setting None

Function input 1/2 level (2311/2331)

Navigation Expert → Sensor → External input → Function input 1/2 level

Write permission Maintenance

Description Defines the response of the level to the presence of a switch signal at external input 1 or 2.

Options • Off
• Minimum (0%)
• Maximum (100%)
• Hold last value
• Fixed value

Factory setting Off

Fixed value input 1/2 (2332/2333)

Navigation Expert → Sensor → External input → Fixed value input 1/2

96 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Write permission Maintenance

Prerequisite Only visible if Function input 1/2 level = Fixed value

Description Defines the level value in the event of a switch signal at external input 1 or 2.

User entry 0 to 200 000

Factory setting 0

Additional information The specific unit after linearization that has been selected applies.

Control measurement (1083)

Navigation Expert → Sensor → External input → Control measurement

Write permission Maintenance

Description Specifies the DO block via which measurement can be switched on and off.

Options • Manual
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4

Factory setting Manual

Measurement (1082)

Navigation Expert → Sensor → External input → Measurement

Write permission Maintenance

Description Is used to switch measurement on and off manually.

Options • On
• Off

Factory setting On

Endress+Hauser 97
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.3 Expert → Output

3.3.1 Expert → Output → Switch output

Switch output function (0481)

Navigation Expert → Output → Switch output → Switch output function

Description Defines the function of the switch output (open collector).

Options • Off
The output is always open (not conductive).
• On
The output is always closed (conductive).
• Event level
The output is normally closed and is only opened if a diagnostic event is present. The
Assign diagnostic level parameter determines at which type of event the output is
opened.
• Limit
The output is normally closed and is only opened if a measured varaible exceeds or falls
below a defined limit. The limit values are defined by the parameters Assign limit ,
Switch-on value and Switch-off value .
• Digital output
The switching state of the output tracks the output value of a DI function block or the DI
output of the advanced diagnostics. The function block is selected in the Assign status
parameter.

Factory setting Off

Assign diagnostic level (0482)

Navigation Expert → Output → Switch output → Assign diagnostic level

Prerequisite Only visible for Switch output function = Event level.

Description Defines to which class of diagnostic events the output reacts.

Options • Alarm
• Alarm + warning
• Warning

Factory setting Alarm

Assign limit (0483)

Navigation Expert → Output → Switch output → Assign limit

98 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Prerequisite Only visible for Switch output function = Limit.

Description Defines the variable to be checked for limit transgression and allocates it to the switch
output.

Options • Off
No measured variable is allocated.
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude

Factory setting Off

Switch-on value (0466)


Switch-off value (0464)

Navigation Expert → Output → Switch output → Switch-on value / Switch-off value

Prerequisite Only visible for Switch output function = Limit and Assign limit ¹ Off.

Description Define the switch-on point and switch-off point for the limit evaluation.

Range of values Depending on the selected measuring variable (Parameter Assign limit).

Factory setting Depending on the selected measuring variable (Parameter Assign limit).

Endress+Hauser 99
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Additional information The switching behavior depends on the relative position of the two switch points.
Switch-on point > Switch-off point:
The output is closed if the measured value exceeds the switch-on point.
The output is opened if the measured value falls below the switch-off point.

B
t

D
t

A0015585

A Switch-on point
B Switch-off point
C Output closed
D Output opened

Switch-on point < Switch-off point:


The output is closed if the measured value falls below the switch-on point.
The output is opened if the measured value exceeds the switch-off point.

A
t

D
t

A0015586

A Switch-on point
B Switch-off point
C Output closed
D Output opened

Assign status (0485)

Navigation Expert → Output → Switch output → Assign status

100 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Prerequisite Only visible for Switch output function = Digital output.

Description Allocates a DI block or the DI output of the advanced diagnostics to the switch output.

Options • Off
No digital block is allocated.
• Digital output AD 1
• Digital output AD 2
• Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4

Factory setting Off

Switch-on delay (0467)

Navigation Expert → Output → Switch output → Switch-on delay

Prerequisite Only visible for Switch output function = Limit and Assign limit ¹ Off.

Description Defines the delay for the switching on of the output.

Range of values 0 to 100 s

Factory setting 0s

Switch-off delay (0465)

Navigation Expert → Output → Switch output → Switch-off delay

Prerequisite Only visible for Switch output function = Limit and Assign limit ¹ Off.

Description Defines the delay for the switching off of the output.

Range of values 0 to 100 s

Factory setting 0s

Switch output failure mode (0486)

Navigation Expert → Output → Switch output → Switch output failure mode

Description Defines the switching state of the output in the case of an error.

Endress+Hauser 101
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Options • Actual status


The switch output remains in the state it was in when the error occurred
• Open
• Closed

Factory setting Open

Switch status (0461)

Navigation Expert → Output → Switch output → Switch status


Diagnostics → Measured value → Switch status

Description Indicates the current state of the switch output.

Display options • Open


• Closed

Invert output signal (0470)

Navigation Expert → Output → Switch output → Invert output signal

Description Allows to invert the behavior of the switch output.

Options • No
The behavior of the switch output is as described above.
• Yes
The states Opend and Closed are inverted as compared to the description above.

102 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.4 Expert → Communication

3.4.1 Expert → Communication → PROFIBUS PA configuration


The PROFIBUS PA configuration submenu contains the parameters that are required to
define the bus address and device ID number.

Parameter Meaning Description

Address mode Displays the address mode (→  103)

Device address • If Address mode = Hardware: (→  104)


The bus address of the device is displayed
• If Address mode = Software:
Definition of the bus address of the device

Ident number selector Defines how the device ID number is specified. (→  105)

Address mode (1468)

Navigation Expert → Communication → PROFIBUS PA configuration → Address mode

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Displays the address mode. The address mode is defined via address switch 8 in the
connection compartment.

Display options • Hardware


Address switch 8 is in the "OFF" position. Hardware addressing is therefore active: the
bus address of the device is configured via address switches 1 to 7. Detailed information
on hardware addressing is provided in the Brief Operating Instructions and the
Operating Instructions for the individual device.
• Software
Address switch 8 is in the "ON" position. Software addressing is therefore active: the bus
address of the device is defined under Setup → Device address or Expert →
Communication → PROFIBUS PA configuration → Device address.

Endress+Hauser 103
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Additional information Information on hardware addressing

DIP

8
7
6
5
4
3
ON
98

2
1
A0015686

 11 Address switch in the connection compartment

Address switches in the "OFF" position do not form part of the address. Address switches in
the "ON" position form part of the address as defined in the following list:
• Switch 1: value = 1
• Switch 2: value = 2
• Switch 3: value = 4
• Switch 4: value = 8
• Switch 5: value = 16
• Switch 6: value = 32
• Switch 7: value = 64
Example:

ON DIP
98

1 2 3 4 5 6 7 8

2 + 8 = 10

A0015902

Address switches 2 and 4 are in the "ON" position; all other address switches are in the
"OFF" position
Þ Address = 2 + 8 = 10

Device address (1462)

Navigation Expert → Communication → PROFIBUS PA configuration → Device address

Read permission Operator

Write permission • For hardware addressing:


Read-only (display parameter)
• For software addressing:
Maintenance

Operation via FieldCare Online/offline

Description For displaying or entering the bus address of the device

User entry 0 to 126

104 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Factory setting 126

Ident number selector (1461)

Navigation Expert → Communication → PROFIBUS PA configuration → Ident number selector

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Defines how the device ID number is specified.

Options • Profile
The ID number of the PROFIBUS profiles is used.
• Manufacturer
The manufacturer-specific ID number is used.
• Old device
The ID number of the old PROFIBUS profiles (2.x) is used.
• Auto
The ID number can be adapted automatically by a Class I PROFIBUS master.

Factory setting Auto

Endress+Hauser 105
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.4.2 Expert → Communication → PROFIBUS PA info


The PROFIBUS PA info submenu contains all the parameters that provide information
about the condition of the PROFIBUS PA interface.

Parameter Meaning Description

Status PROFIBUS Master Under development


Config

PROFIBUS ident number ID number of the device

Profile version PROFIBUS profile version

CRC count OK Number of successful checksum tests of the data telegram

CRC count failed Number of failed checksum tests of the data telegram

Good telegrams Number of error-free data telegrams between the two last
failed data telegrams

Base current Current consumption

Terminal voltage 1 Terminal voltage currently present at the PROFIBUS input

Status PROFIBUS Master Config (1465)

Navigation Expert → Communication → PROFIBUS PA info → Status PROFIBUS Master Config

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Under development

Display options • Active


• Not active

PROFIBUS ident number (1471)

Navigation Expert → Communication → PROFIBUS PA information → PROFIBUS ident number

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Displays the ID number of the device

Additional information It is possible to define which ID number is used under Expert → Communication →
PROFIBUS PA configuration → Ident number selector.

106 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Profile version (1463)

Navigation Expert → Communication → PROFIBUS PA info → Profile version

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Displays the PROFIBUS profile version of the device

CRC count OK (1469)

Navigation Expert → Communication → PROFIBUS PA info → CRC count OK

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Indicates how often the checksum test of the cyclic data telegram was successful.

CRC count failed (1470)

Navigation Expert → Communication → PROFIBUS PA info → CRC count failed

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Indicates how often the checksum test of the cyclic data telegram discovered an error.

Good telegrams (1467)

Navigation Expert → Communication → PROFIBUS PA info → Good telegrams

Read permission Operator

Write permission Read-only (display parameter)

Endress+Hauser 107
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Operation via FieldCare Online

Description Indicates how many error-free data telegrams were transmitted between the two last
failed data telegrams.

Base current (1466)

Navigation Expert → Communication → PROFIBUS PA info → Base current

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Displays the current consumption at the PROFIBUS input of the device

Terminal voltage 1 (0662)

Navigation Expert → Communication → PROFIBUS PA info → Terminal voltage 1

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Displays the current terminal voltage at the PROFIBUS input of the device

108 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.4.3 Expert → Communication → Physical block

Overview
The Physical block submenu is only available if the device is operated via an
operating tool (e.g. FieldCare). It is not available if the device is operated via the
display and operating module.
The Physical block submenu contains the parameters of the Physical block as per the
PROFIBUS profiles:

Parameter Parameter name according to the PROFIBUS profiles Description

Tag description TAG_DESC (→  110)

Static revision ST_REV (→  110)

Strategy STRATEGY (→  110)

Alert key ALERT_KEY (→  110)

Target mode TARGET_MODE (→  111)

Mode block actual MODE_BLK (→  111)


Actual element

Mode block permitted MODE_BLK (→  111)


Permitted element

Mode block normal MODE_BLK (→  112)


Normal element

Alarm summary ALARM_SUM (→  112)

Software revision SOFTWARE_REVISION (→  112)

Hardware revision HARDWARE_REVISION (→  112)

Manufacturer ID DEVICE_MAN_ID (→  113)

Device ID DEVICE_ID (→  113)

Serial number DEVICE_SER_NUM (→  113)

Diagnostics DIAGNOSIS (→  114)

Diagnostics extension DIAGNOSIS_EXTENSION (→  114)

Diagnostics mask DIAGNOSIS_MASK (→  114)

Device certification DEVICE_CERTIFICATION (→  114) x

Factory reset FACTORY_RESET (→  115)

Descriptor DESCRIPTOR (→  115)

Device message DEVICE_MESSAGE (→  115)

Device install date DEVICE_INSTAL_DATE (→  116)

Ident number selector IDENT_NUMBER_SELECTOR (→  105)

Hardware lock HW_WRITE_PROTECTION (→  116)

Feature enabled HW_WRITE_PROTECTION (→  116)


Enabled element

Feature supported HW_WRITE_PROTECTION (→  117)


Supported element

Condensed status diagnose COND_STATUS_DIAG (→  117)

Endress+Hauser 109
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

The parameters

Tag description (1496)

Navigation Expert → Communication → Physical block → Tag description

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TAG_DESC standard block parameter as per the PROFIBUS profiles.

User entry Up to 32 alphanumeric characters

Static revision (1495)

Navigation Expert → Communication → Physical block → Static revision

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ST_REV standard block parameter as per the PROFIBUS profiles

Strategy (1494)

Navigation Expert → Communication → Physical block → Strategy

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description STRATEGY standard block parameter as per the PROFIBUS profiles

Alert key (1473)

Navigation Expert → Communication → Physical block → Alert key

110 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description ALERT_KEY standard block parameter as per the PROFIBUS profiles

Target mode (1497)

Navigation Expert → Communication → Physical block → Target mode

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TARGET_MODE standard block parameter as per the PROFIBUS profiles

Mode block actual (1472)

Navigation Expert → Communication → Physical block → Mode block actual

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles

Mode block permitted (1493)

Navigation Expert → Communication → Physical block → Mode block permitted

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

Endress+Hauser 111
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Mode block normal (1492)

Navigation Expert → Communication → Physical block → Mode block normal

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

Alarm summary (1474)

Navigation Expert → Communication → Physical block → Alarm summary

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.

Software revision (1478)

Navigation Expert → Communication → Physical block → Software revision

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description SOFTWARE_REVISION standard parameter of the Physical block as per the PROFIBUS
profiles

Hardware revision (1479)

Navigation Expert → Communication → Physical block → Hardware revision

112 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description HARDWARE_REVISION standard parameter of the Physical block as per the PROFIBUS
profiles

Manufacturer ID (1502)

Navigation Expert → Communication → Physical block → Manufacturer ID

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description DEVICE_MAN_ID standard parameter of the Physical block as per the PROFIBUS profiles

Device ID (1480)

Navigation Expert → Communication → Physical block → Device ID

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online/offline

Description DEVICE_ID standard parameter of the Physical block as per the PROFIBUS profiles

Serial number (1481)

Navigation Expert → Communication → Physical block → Serial number

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description DEVICE_SER_NUM standard parameter of the Physical block as per the PROFIBUS
profiles

Endress+Hauser 113
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Diagnostics (1482)

Navigation Expert → Communication → Physical block → Diagnostics

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description DIAGNOSIS standard parameter of the Physical block as per the PROFIBUS profiles

Diagnostics extension (1483)

Navigation Expert → Communication → Physical block → Diagnostics extension

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description DIAGNOSIS_EXTENSION standard parameter of the Physical block as per the PROFIBUS
profiles

Diagnostics mask (1484)

Navigation Expert → Communication → Physical block → Diagnostics mask

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description DIAGNOSIS_MASK standard parameter of the Physical block as per the PROFIBUS profiles

Device certification (1486)

Navigation Expert → Communication → Physical block → Device certification

Read permission Operator

114 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description DEVICE_CERTIFICATION standard parameter of the Physical block as per the PROFIBUS
profiles

Factory reset (1488)

Navigation Expert → Communication → Physical block → Factory reset

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description FACTORY_RESET standard parameter of the Physical block as per the PROFIBUS profiles

Options • To defaults
• Warmstart device
• Reset bus address
• Cancel

Factory setting Cancel

Descriptor (1489)

Navigation Expert → Communication → Physical block → Descriptor

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description DESCRIPTOR standard parameter of the Physical block as per the PROFIBUS profiles

Device message (1490)

Navigation Expert → Communication → Physical block → Device message

Read permission Operator

Write permission Maintenance

Endress+Hauser 115
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Operation via FieldCare Online/offline

Description DEVICE_MESSAGE standard parameter of the Physical block as per the PROFIBUS profiles

Device install date (1491)

Navigation Expert → Communication → Physical block → Device install date

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description DEVICE_INSTAL_DATE standard parameter of the Physical block as per the PROFIBUS
profiles

Ident number selector (→  105)

Hardware lock (1499)

Navigation Expert → Communication → Physical block → Hardware lock

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description HW_WRITE_PROTECTION standard parameter of the Physical block as per the PROFIBUS
profiles

User interface • Unprotected


• Protected

Feature enabled (1476)

Navigation Expert → Communication → Physical block → Feature enabled

Read permission Operator

Write permission Read-only (display parameter)

116 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Operation via FieldCare Online

Description Enabled element of the HW_WRITE_PROTECTION parameter in the Physical block as per
the PROFIBUS profiles.

Feature supported (1477)

Navigation Expert → Communication → Physical block → Feature supported

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Supported element of the HW_WRITE_PROTECTION parameter in the Physical block as


per the PROFIBUS profiles.

Condensed status diagnose (1500)

Navigation Expert → Communication → Physical block → Condensed status diagnose

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description COND_STATUS_DIAG parameter in the Physical block as per the PROFIBUS profiles

Options • Off
The classic error message format is used
• On
The abbreviated error message format is used

Endress+Hauser 117
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.5 Expert → Analog inputs → Analog input N

3.5.1 Overview
There is an Analog input submenu for each Analog Input block in the device. This
submenu contains the block parameters of the individual block. The parameters of the
Analog Input block are described in the PROFIBUS profile. The most important
characteristics of the parameters are summarized below. An Analog Input block can be
used to scale a measured variable of the device and transmit it via the bus to a PLC, for
example.

Out Value
PROFIBUS

Channel

1 2 3
A0017058

 12 Transmission of an analog value to a PLC via the Analog Input block


1 Transmitter
2 Analog Input block (part of transmitter software)
3 PLC

Data processing in the Analog Input block

Simulate value Enable HiHi alarm value


Simulate status PV scale HiHi alarm state
upper range HiHi lim
Hi alarm value
Hi alarm state
Hi lim Out value
Simulate Lo alarm value Out state
enable Lo alarm state Out unit text
Lo lim
LoLo alarm value
t LoLo alarm state
PV scale LoLo lim
Value lower range
Channel
Status Disable
Out scale Out scale PV filter time
lower range upper range

Out unit; Out decimal point

A0016781

The diagram describes the function of the Analog Input block in the normal
operational state (Mode block actual = Auto). The block's behavior in other
operational states is described in the Profibus profiles of the Profibus User
Organization (PNO).

The parameters of the "Analog input N" submenu

Parameter Parameter name Comments Parameter description


according to PROFIBUS
profile

Standard block parameters

Tag description TAG_DESC Standard block parameter

Static revision ST_REV Standard block parameter

118 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Parameter Parameter name Comments Parameter description


according to PROFIBUS
profile

Strategy STRATEGY Standard block parameter

Alert key ALERT_KEY Standard block parameter

Target mode TARGET_MODE Standard block parameter

Mode block actual MODE_BLK Standard block parameter

Mode block permitted MODE_BLK Standard block parameter

Mode block normal MODE_BLK Standard block parameter

Alarm summary ALARM_SUM Standard block parameter

Batch ID BATCH Standard block parameter

Batch operation BATCH Standard block parameter

Batch phase BATCH Standard block parameter

Batch recipe unit BATCH Standard block parameter


procedure

Parameters of the output value

Out value OUT Number of the output value

Out status OUT Status of the output value


(quality bits as per PROFIBUS
profile)

Out status HEX OUT Status of the output value (full


representation by two-digit
hexadecimal number as per
PROFIBUS profile)

Scaling and further processing of the measured value

PV scale lower range PV_SCALE 0% mark for the input value

PV scale upper range PV_SCALE 100% mark for the input value

Out scale lower range OUT_SCALE 0% mark for the output value

Out scale upper range OUT_SCALE 100% mark for the output value

Lin type LIN_TYPE Standard block parameter; is not


used for Levelflex

Out unit OUT_SCALE Unit of the output value; coded


as per PROFIBUS profile

Out decimal point OUT_SCALE Number of relevant decimal


places

Out unit text OUT_UNIT_TEXT Unit of the output value; entered


as text

PV filter time PV_FTIME Time constant for damping the


output value

Measured variable assignment

Channel CHANNEL Measured variable assignment

Error handling

Fail safe type FSAFE_TYPE Specifies the response if an error


is detected.

Fail safe value FSAFE_VALUE Specifies the output value if an


error is detected.

Check for limit violation

Alarm hysteresis ALARM_HYS Hysteresis for limit detection

Hi Hi lim HI_HI_LIM Upper limit; if exceeded, an


alarm is generated.

Endress+Hauser 119
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Parameter Parameter name Comments Parameter description


according to PROFIBUS
profile

Hi lim HI_LIM Upper limit; if exceeded, a


warning is generated.

Lo lim LO_LIM Lower limit; if undershot, a


warning is generated.

Lo Lo lim LO_LO_LIM Lower limit; if undershot, an


alarm is generated.

Hi Hi alarm value HI_HI_ALM Value which caused the HI-HI


alarm to be generated

Hi Hi alarm state HI_HI_ALM Indicates whether a HI-HI alarm


has occurred

Hi alarm value HI_ALM Value which caused the HI


warning to be generated

Hi alarm state HI_ALM Indicates whether a HI warning


has occurred

Lo alarm value LO_ALM Value which caused the LO


warning to be generated

Lo alarm state LO_ALM Indicates whether a LO warning


has occurred

Lo Lo alarm value LO_LO_ALM Value which caused the LO_LO


alarm to be generated

Lo Lo alarm state LO_LO_ALM Indicates whether a LO_LO


alarm has occurred

Simulation

Simulate enabled SIMULATE Enable/disable a simulation

Simulate value SIMULATE Measured variable simulation


value

Simulate status SIMULATE Status simulation value

120 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.5.2 The parameters

Tag description (1562)

Navigation Expert → Communication → Analog input 1...6 → Tag description

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TAG_DESC standard block parameter as per the PROFIBUS profiles.

User entry Up to 32 alphanumeric characters

Static revision (1560)

Navigation Expert → Communication → Analog input 1...6 → Static revision

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ST_REV standard block parameter as per the PROFIBUS profiles

Strategy (1559)

Navigation Expert → Communication → Analog input 1...6 → Strategy

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description STRATEGY standard block parameter as per the PROFIBUS profiles

Alert key (1522)

Navigation Expert → Communication → Analog input 1...6 → Alert key

Endress+Hauser 121
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description ALERT_KEY standard block parameter as per the PROFIBUS profiles

Target mode (1563)

Navigation Expert → Communication → Analog input 1...6 → Target mode

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TARGET_MODE standard block parameter as per the PROFIBUS profiles

Mode block actual (1521)

Navigation Expert → Communication → Analog input 1...6 → Mode block actual

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles

Mode block permitted (1523)

Navigation Expert → Communication → Analog input 1...6 → Mode block permitted

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

122 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Mode block normal (1562)

Navigation Expert → Communication → Analog input 1...6 → Mode block normal

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

Alarm summary (1537)

Navigation Expert → Communication → Analog input 1...6 → Alarm summary

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.

User interface • Discrete alarm


• Alarm state HiHi limit
• Alarm state Hi limit
• Alarm state LoLo limit
• Alarm state Lo limit
• Update Event

Batch ID (1533)

Navigation Expert → Communication → Analog input 1...6 → Batch ID

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Batch_ID element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 232 - 1

Endress+Hauser 123
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Batch operation (1534)

Navigation Expert → Communication → Analog input 1...6 → Batch operation

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Operation element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 216 - 1

Batch phase (1535)

Navigation Expert → Communication → Analog input 1...6 → Batch phase

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Phase element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 216 - 1

Batch recipe unit procedure (1536)

Navigation Expert → Communication → Analog input 1...6 → Batch recipe unit procedure

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Rup (Recipe unit procedure) element of the BATCH standard block parameter as per the
PROFIBUS profiles.

User entry 0 to 216 - 1

Out value (1552)

124 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Navigation Expert → Communication → Analog input 1...6 → Out value

Read permission Operator

Write permission • For Mode block actual = Man:


Operator
• In all other cases:
Read-only (display parameter)

Operation via FieldCare Online

Description Value element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles.
Displays the output value of the Analog Input block.

Out status (1564)

Navigation Expert → Communication → Analog input 1...6 → Out status

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online/offline

Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. Only the two quality bits are evaluated in this parameter.

User interface • Good


• Uncertain
• Bad

Out status HEX (1549)

Navigation Expert → Communication → Analog input 1...6 → Out status HEX

Read permission Operator

Write permission • For Mode block actual = Man:


Operator
• In all other cases:
Read-only (display parameter)

Operation via FieldCare Online

Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. The complete status byte is displayed as a two-digit hexadecimal
number in this parameter.

Endress+Hauser 125
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

PV scale lower range (1554)

Navigation Expert → Communication → Analog input 1...6 → PV scale lower range

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description EU_at_0% element of the PV_SCALE standard parameter in the Analog Input block as
per the PROFIBUS profiles.
Defines the 0% mark for the measured value.

User entry IEEE floating point number

PV scale upper range (1555)

Navigation Expert → Communication → Analog input 1...6 → PV scale upper range

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description EU_at_100% element of the PV_SCALE standard parameter in the Analog Input block as
per the PROFIBUS profiles.
Defines the 100% mark for the measured value.

User entry IEEE floating point number

Out scale lower range (1548)

Navigation Expert → Communication → Analog input 1...6 → Out scale lower range

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description EU_at_0% element of the OUT_SCALE standard parameter in the Analog Input block as
per the PROFIBUS profiles.
Defines the 0% mark for the output value.

User entry IEEE floating point number

126 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Out scale upper range (1551)

Navigation Expert → Communication → Analog input 1...6 → Out scale upper range

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description EU_at_100% element of the OUT_SCALE standard parameter in the Analog Input block
as per the PROFIBUS profiles.
Defines the 100% mark for the output value.

User entry IEEE floating point number

Lin type (1523)

Navigation Expert → Communication → Analog input 1...6 → Lin type

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description LIN_TYPE standard parameter of the Analog Input block as per the PROFIBUS profiles

Channel (1561)

Navigation Expert → Communication → Analog input 1...6 → Channel

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description CHANNEL standard parameter of the Analog Input block as per the PROFIBUS profiles.
Assigns a measured variable to the Analog Input block.

Endress+Hauser 127
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Options • Level linearized


• Distance
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Noise of signal
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2

Factory setting Level linearized

Out unit (1550)

Navigation Expert → Communication → Analog input → Out unit

Read permission Operator

Write permission Operator

Operation via FieldCare Online/offline

Description Units_Index element of the OUT_SCALE standard parameter of the Analog Input block as
per the PROFIBUS profiles. Specifies the unit of the output value. Here, the units are coded
by a numerical index as per the PROFIBUS profiles.

Out decimal point (1547)

Navigation Expert → Communication → Analog input → Out decimal point

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Decimal_Point element of the OUT_SCALE standard parameter of the Analog Input block
as per the PROFIBUS profiles. Defines how many decimal places of the output value should
be considered as valid.

PV filter time (1524)

Navigation Expert → Communication → Analog input 1...6 → PV filter time

Read permission Operator

128 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Write permission Maintenance

Operation via FieldCare Online

Description PV_FTIME standard parameter of the Analog Input block as per the PROFIBUS profiles.
Damping time of the Analog Input block, indicated in seconds.

User entry IEEE floating point number

Factory setting 0s

Fail safe type (1525)

Navigation Expert → Communication → Analog input 1...6 → Fail safe type

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description FSAFE_TYPE standard parameter of the Analog Input block as per the PROFIBUS profiles.
Specifies the output value of the Analog Input block in the event of an error.

Options • Fail safe value


The value output in the event of an error is defined in the Fail safe value parameter.
• Fallback value
The last output value that was valid before the error occurred is retained.
• Off
The output value follows the current measured value. The status is set to BAD.

Factory setting Off

Fail safe value (1526)

Navigation Expert → Communication → Analog input 1...6 → Fail safe value

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Prerequisite Only visible if Fail safe type = Fail safe value

Description FSAFE_VALUE standard parameter of the Analog Input block as per the PROFIBUS
profiles. Specifies the output value of the Analog Input block in the event of an error.

Value range Depends on the measured variable assigned

Endress+Hauser 129
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Factory setting Depends on the measured variable assigned

Alarm hysteresis (1527)

Navigation Expert → Communication → Analog input 1...6 → Alarm hysteresis

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description ALARM_HYS standard parameter of the Analog Input block as per the PROFIBUS profiles.
Specifies the hysteresis if the output value of the Analog Input block exceeds the limit. The
hysteresis is indicated in the unit of the output value (out unit parameter).

User entry IEEE floating point number

Factory setting 0

Hi Hi lim (1528)

Navigation Expert → Communication → Analog input 1...6 → Hi Hi lim

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description HI_HI_LIM standard parameter of the Analog Input block as per the PROFIBUS profiles.
An alarm is generated if the output value of the Analog Input block exceeds this value.

User entry IEEE floating point number

Factory setting 3.4 ⋅1038 (highest possible value)

Hi lim (1529)

Navigation Expert → Communication → Analog input 1...6 → Hi lim

Read permission Operator

Write permission Maintenance

130 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Operation via FieldCare Online

Description HI_LIM standard parameter of the Analog Input block as per the PROFIBUS profiles. A
warning is generated if the output value of the Analog Input block exceeds this value.

User entry IEEE floating point number

Factory setting 3.4 ⋅1038 (highest possible value)

Lo lim (1530)

Navigation Expert → Communication → Analog input 1...6 → Lo lim

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description LO_LIM standard parameter of the Analog Input block as per the PROFIBUS profiles. A
warning is generated if the output value of the Analog Input block falls below this value.

User entry IEEE floating point number

Factory setting -3.4 ⋅1038 (lowest possible value)

Lo Lo lim (1531)

Navigation Expert → Communication → Analog input 1...6 → Lo Lo lim

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description LO_LO_LIM standard parameter of the Analog Input block as per the PROFIBUS profiles.
An alarm is generated if the output value of the Analog Input block falls below this value.

User entry IEEE floating point number

Factory setting -3.4 ⋅1038 (lowest possible value)

Hi Hi alarm value (1541)

Endress+Hauser 131
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Expert → Communication → Analog input 1...6 → Hi Hi alarm value

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Value element of the HI_HI_ALM standard parameter of the Analog Input block as per
the PROFIBUS profiles. Displays the output value which caused the alarm to be generated.

Hi Hi alarm state (1540)

Navigation Expert → Communication → Analog input 1...6 → Hi Hi alarm state

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Alarm_State element of the HI_HI_ALM standard parameter of the Analog Input block
as per the PROFIBUS profiles. Indicates whether an alarm has occurred as a result of the
value exceeding the Hi Hi lim.

User interface • No alarm


• Alarm state HiHi limit

Hi alarm value (1539)

Navigation Expert → Communication → Analog input 1...6 → Hi alarm value

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Value element of the HI_ALM standard parameter of the Analog Input block as per the
PROFIBUS profiles. Displays the output value which caused the warning to be generated.

Hi alarm state (1538)

Navigation Expert → Communication → Analog input 1...6 → Hi alarm state

132 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Alarm_State element of the HI_ALM standard parameter of the Analog Input block as
per the PROFIBUS profiles. Indicates whether a warning has occurred as a result of the
value exceeding the Hi lim.

User interface • No warning


• Alarm state Hi limit

Lo alarm value (1543)

Navigation Expert → Communication → Analog input 1...6 → Lo alarm value

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Value element of the LO_ALM standard parameter of the Analog Input block as per the
PROFIBUS profiles. Displays the output value which caused the warning to be generated.

Lo alarm state (1542)

Navigation Expert → Communication → Analog input 1...6 → Lo alarm state

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Alarm_State element of the LO_ALM standard parameter of the Analog Input block as
per the PROFIBUS profiles. Indicates whether a warning has occurred as a result of the
value falling below the Lo lim.

User interface • No warning


• Alarm state Lo limit

Lo Lo alarm value (1545)

Navigation Expert → Communication → Analog input 1...6 → Lo Lo alarm value

Endress+Hauser 133
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Value element of the LO_LO_ALM standard parameter of the Analog Input block as per
the PROFIBUS profiles. Displays the output value which caused the warning to be
generated.

Lo Lo alarm state (1544)

Navigation Expert → Communication → Analog input 1...6 → Lo Lo alarm state

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Alarm_State element of the LO_LO_ALM standard parameter of the Analog Input block
as per the PROFIBUS profiles. Indicates whether an alarm has occurred as a result of the
value falling below the Lo Lo lim.

User interface • No alarm


• Alarm state LoLo limit

Simulate enabled (1556)

Navigation Expert → Communication → Analog input 1...6 → Simulate enabled

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Simulate_Enabled element of the SIMULATE standard parameter in the Analog Input
block as per the PROFIBUS profiles. Enables or disables the simulation of the Analog Input
block. If simulation is enabled, the Analog Input block uses a constant simulation value
instead of the measured value selected in Channel. This value is specified in Simulate
value. The associated status is specified in Simulate status.

Options • Disable
• Enable

Factory setting Disable

134 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Simulate value (1558)

Navigation Expert → Communication → Analog input 1...6 → Simulate value

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description Simulate_Value element of the SIMULATE standard parameter in the Analog Input block
as per the PROFIBUS profiles. Specifies the simulation value.

User entry IEEE floating point number

Factory setting 0

Simulate status (1557)

Navigation Expert → Communication → Analog input 1...6 → Simulate status

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description Simulate_Status element of the SIMULATE standard parameter in the Analog Input
block as per the PROFIBUS profiles. Specifies the status of the simulation value.

User entry 0 to 255

Out unit text (1532)

Navigation Expert → Communication → Analog input 1...6 → Out unit text

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description OUT_UNIT_TEXT standard parameter of the Analog Input block as per the PROFIBUS
profiles. This text is used as a unit if the 1995: Textual unit definition option was selected
in Out unit. In this way it is also possible to transmit units that are not provided in the
PROFIBUS profiles.

Endress+Hauser 135
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

User entry Up to 16 alphanumeric characters

136 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.6 Expert → Discrete inputs → Discrete input N

3.6.1 Overview
There is an Discrete input submenu for each Discrete Input block in the device. This
submenu contains the block parameters of the individual block. The parameters of the
Discrete Input block are described in the PROFIBUS profile. The most important
characteristics of the parameters are summarized below. A Discrete Input block can be
used to transmit a discrete measured variable via the bus to a PLC, for example.

Out Value
PROFIBUS

Channel

1 2 3
A0017058

 13 Transmission of a discrete value to a PLC via the Discrete Input block


1 Transmitter
2 Discrete Input block (part of transmitter software)
3 PLC

Data processing in the Discrete Input block

Simulate value Enable


Simulate status
off TRUE TRUE
FALSE FALSE
Simulate Invert Out value
enable Out state
TRUE FALSE
on FALSE TRUE
Value
Channel
Status Disable

A0016782

The diagram describes the function of the Discrete Input block in the normal
operational state (Mode block actual = Auto). The block's behavior in other
operational states is described in the Profibus profiles of the Profibus User
Organization (PNO).

The parameters of the "Discrete input N" submenu

Parameter Parameter name Comments Parameter description


according to PROFIBUS
profile

Standard block parameters

Tag description TAG_DESC Standard block parameter

Static revision ST_REV Standard block parameter

Strategy STRATEGY Standard block parameter

Alert key ALERT_KEY Standard block parameter

Target mode TARGET_MODE Standard block parameter

Endress+Hauser 137
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Parameter Parameter name Comments Parameter description


according to PROFIBUS
profile

Mode block actual MODE_BLK Standard block parameter

Mode block permitted MODE_BLK Standard block parameter

Mode block normal MODE_BLK Standard block parameter

Alarm summary ALARM_SUM Standard block parameter

Batch ID BATCH Standard block parameter

Batch operation BATCH Standard block parameter

Batch phase BATCH Standard block parameter

Batch recipe unit BATCH Standard block parameter


procedure

Parameters of the output value

Out value OUT Discrete output value

Out status OUT Status of the output value


(quality bits as per PROFIBUS
profile)

Out status HEX OUT Status of the output value (full


representation by two-digit
hexadecimal number as per
PROFIBUS profile)

Assignment and further processing of a switching variable

Channel CHANNEL Switching variable assignment

Invert INVERT Inversion of the switching


variable

Error handling

Fail safe type FSAFE_TYPE Specifies the response if an error


is detected.

Fail safe value FSAFE_VALUE Specifies the output value if an


error is detected.

Simulation

Simulate enabled SIMULATE Enable/disable a simulation

Simulate value SIMULATE Discrete simulation value

Simulate status SIMULATE Status simulation value

138 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.6.2 The parameters

Tag description (2201)

Navigation Expert → Discrete inputs → Discrete input 1...4→ Tag description

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TAG_DESC standard block parameter as per the PROFIBUS profiles.

User entry Up to 32 alphanumeric characters

Static revision (2200)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Static revision

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ST_REV standard block parameter as per the PROFIBUS profiles

Strategy (2199)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Strategy

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description STRATEGY standard block parameter as per the PROFIBUS profiles

Alert key (2182)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Alert key

Endress+Hauser 139
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description ALERT_KEY standard block parameter as per the PROFIBUS profiles

Target mode (2202)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Target mode

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TARGET_MODE standard block parameter as per the PROFIBUS profiles

Mode block actual (2181)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Mode block actual

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles

Mode block permitted (2195)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Mode block permitted

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

140 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Mode block normal (2192)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Mode block normal

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

Alarm summary (2191)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Alarm summary

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.

User interface • Discrete alarm


• Alarm state HiHi limit
• Alarm state Hi limit
• Alarm state LoLo limit
• Alarm state Lo limit
• Update Event

Batch ID (2183)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Batch ID

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Batch_ID element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 232 - 1

Endress+Hauser 141
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Batch operation (2184)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Batch operation

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Operation element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 216 - 1

Batch phase (2185)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Batch phase

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Phase element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 216 - 1

Batch recipe unit procedure (2186)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Batch recipe unit procedure

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Rup (Recipe unit procedure) element of the BATCH standard block parameter as per the
PROFIBUS profiles.

User entry 0 to 216 - 1

Out value (2194)

142 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Navigation Expert → Discrete inputs → Discrete input 1...4 → Out value

Read permission Operator

Write permission • For Mode block actual = Man:


Operator
• In all other cases:
Read-only (display parameter)

Operation via FieldCare Online/offline

Description Value element of the OUT_D standard parameter in the Discrete Input block as per the
PROFIBUS profiles.
Displays the output value of the Analog Input block.

User interface Two-digit hexadecimal number.


• Out value = 00 Þ FALSE
• Out value ¹ 00 Þ TRUE

Out status (2203)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Out status

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Status element of the OUT_D standard parameter in the Analog Input block as per the
PROFIBUS profiles. Only the two quality bits are evaluated in this parameter.

User interface • Good


• Uncertain
• Bad

Out status HEX (2193)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Out status HEX

Read permission Operator

Write permission • For Mode block actual = Man:


Operator
• In all other cases:
Read-only (display parameter)

Operation via FieldCare Online/offline

Endress+Hauser 143
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. The complete status byte is displayed as a two-digit hexadecimal
number in this parameter.

Channel (2187)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Channel

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description CHANNEL standard parameter of the Analog Input block as per the PROFIBUS profiles.
Assigns a switching variable to the Discrete Input block.

Options • None
• Switch output
• Digital output Advanced Diagnostics 1
• Digital output Advanced Diagnostics 2

Factory setting None

Invert (2188)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Invert

Read permission Operator

Write permission Operator

Operation via FieldCare Online/offline

Description INVERT standard parameter of the Discrete Input block as per the PROFIBUS profile.
Enables the inversion of the discrete output signal (the logical states FALSE and TRUE are
swapped).

Options • Off
No inversion
• On
The switching signal is inverted before being transmitted to the bus.

Factory setting Off (i.e. no inversion)

Fail safe type (2189)

144 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Navigation Expert → Discrete inputs → Discrete input 1...4 → Fail safe type

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description FSAFE_TYPE standard parameter of the Discrete Input block as per the PROFIBUS profiles.
Specifies the output value of the block in the event of an error.

Options • Fail safe value


The value output in the event of an error is defined in the Fail safe value parameter.
• Fallback value
The last output value that was valid before the error occurred is retained.
• Off
The output value follows the current measured value. The status is set to BAD.

Factory setting Off

Fail safe value (2189)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Fail safe value

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Prerequisite Only visible if Fail safe type = Fail safe value

Description FSAFE_VAL_D standard parameter of the Discrete Input block as per the PROFIBUS
profiles. Specifies the output value of the Discrete Input block in the event of an error.

Value range Two-digit hexadecimal number


• Fail safe value = 00 Þ FALSE
• Fail safe value ¹ 00 Þ TRUE

Factory setting 00 (FALSE)

Simulate enabled (2196)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Simulate enabled

Read permission Operator

Write permission Maintenance

Endress+Hauser 145
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Operation via FieldCare Online/offline

Description Simulate_Enabled element of the SIMULATE_D standard parameter in the Discrete Input
block as per the PROFIBUS profiles. Enables or disables the simulation of the Analog Input
block. If simulation is enabled, the Analog Input block uses a constant switching variable
instead of the switching variable selected in Channel. This value is specified in Simulate
value. The associated status is specified in Simulate status.

Options • Disable
• Enable

Factory setting Disable

Simulate value (2198)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Simulate value

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Simulate_Value element of the SIMULATE_D standard parameter in the Discrete Input
block as per the PROFIBUS profiles. Specifies the simulation value.

User entry Two-digit hexadecimal number

Factory setting 00

Simulate status (2197)

Navigation Expert → Discrete inputs → Discrete input 1...4 → Simulate status

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description Simulate_Status element of the SIMULATE_D standard parameter in the Discrete Input
block as per the PROFIBUS profiles. Specifies the status of the simulation value.

User entry 0 to 255

146 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.7 Expert → Analog outputs → Analog output N

3.7.1 Overview
There is an Analog output submenu for each Analog Output block in the device. This
submenu contains the parameters of the individual block. The parameters of the Analog
Output block are described in the PROFIBUS profile. The most important characteristics of
the parameters are summarized below.
The device uses the Analog Output block to read in a value, which has been measured
externally, via the bus. This value can be used
• for display on the display module (Expert → System → Display)
• for automatic gas phase compensation in the case of a pressure value (Expert →
Sensor → Gas phase compensation → External pressure selector)

2
ENDRESS + HAUSER

A0016304

 14 The level transmitter reads the externally measured pressure via the Analog output block.
1 Level tranmsitter
2 Segment coupler
3 PLC
4 Absolute pressure transmitter

Endress+Hauser 147
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Data processing in the Analog Output block

PV scale
upper range

Set point value Out value


Set point status Out status

PV scale
lower range

Out scale Out scale


lower range upper range

A0016954

The diagram describes the function of the Analog Output block in the normal
operational state (Mode block actual = Auto). The block's behavior in other
operational states is described in the Profibus profiles of the Profibus User
Organization (PNO).

The parameters of the "Analog output N" submenu


The Analog Output blocks correspond to the Profibus profiles of the Profibus User
Organization (PNO). Accordingly, they contain all the parameters provided in the
profiles. The device only uses some of these parameters, however. Any parameters
that are not relevant for the device are marked "not used" in the following table.

Parameter Parameter name Comments Parameter description


according to PROFIBUS
profile

Standard block parameters

Tag description TAG_DESC Standard block parameter

Static revision ST_REV Standard block parameter

Strategy STRATEGY Standard block parameter

Alert key ALERT_KEY Standard block parameter

Target mode TARGET_MODE Standard block parameter

Mode block actual MODE_BLK Standard block parameter

Mode block permitted MODE_BLK Standard block parameter

Mode block normal MODE_BLK Standard block parameter

Alarm summary ALARM_SUM Standard block parameter

Batch ID BATCH Standard block parameter

Batch operation BATCH Standard block parameter

Batch phase BATCH Standard block parameter

Batch recipe unit BATCH Standard block parameter


procedure

Parameters of the input value (set point)

Set point value SP External value


Value element

Set point status SP Status of the external value


Status element

Input scaling

PV scale lower range PV_SCALE 0% mark for the input value

148 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Parameter Parameter name Comments Parameter description


according to PROFIBUS
profile

PV scale upper range PV_SCALE 100% mark for the input value

Block-specific parameters

Readback value READBACK Not used -

Readback status READBACK Not used -

RCAS in value RCAS_IN Not used -

RCAS in status RCAS_IN Not used -

Input channel IN_CHANNEL Not used -

Output channel OUT_CHANNEL Not used -

Error handling

Fail safe time FSAFE_TIME Time after which the block


responds to an error in the input
value (set point)

Fail safe type FSAFE_TYPE Specifies the response if an error


is detected.

Fail safe value FSAFE_VALUE Specifies the output value if an


error is detected.

Block-specific parameters

RCAS out value RCAS_OUT Not used -

RCAS out status RCAS_OUT Not used -

Position value POS_D Not used -

Position status POS_D Not used -

Setpoint deviation SETP_DEVIATION Not used -

Check back CHECK_BACK Not used -

Check back mask CHECK_BACK_MASK Not used -

Simulate enabled SIMULATE Not used -

Simulate value SIMULATE Not used -

Simulate status SIMULATE Not used -

Increase close INCREASE_CLOSE Not used -

Output value

Out value OUT Output value of block

Out status OUT Status of the output value


(quality bits as per PROFIBUS
profile)

Out status HEX OUT Status of the output value (full


representation by two-digit
hexadecimal number as per
PROFIBUS profile)

Output scaling

Out scale upper range OUT_SCALE 100% mark for the output value

Out scale lower range OUT_SCALE 0% mark for the output value

Endress+Hauser 149
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.7.2 The parameters

Tag description (1667)

Navigation Expert → Analog outputs → Analog output 1...4→ Tag description

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TAG_DESC standard block parameter as per the PROFIBUS profiles.

User entry Up to 32 alphanumeric characters

Static revision (1666)

Navigation Expert → Analog outputs → Analog output 1...4 → Static revision

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ST_REV standard block parameter as per the PROFIBUS profiles

Strategy (1665)

Navigation Expert → Analog outputs → Analog output 1...4 → Strategy

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description STRATEGY standard block parameter as per the PROFIBUS profiles

Alert key (1632)

Navigation Expert → Analog outputs → Analog output 1...4 → Alert key

150 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description ALERT_KEY standard block parameter as per the PROFIBUS profiles

Target mode (1668)

Navigation Expert → Analog outputs → Analog output 1...4 → Target mode

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TARGET_MODE standard block parameter as per the PROFIBUS profiles

Mode block actual (1631)

Navigation Expert → Analog outputs → Analog output 1...4 → Mode block actual

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles

Mode block permitted (1648)

Navigation Expert → Analog outputs → Analog output 1...4 → Mode block permitted

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

Endress+Hauser 151
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Mode block normal (1643)

Navigation Expert → Analog outputs → Analog output 1...4 → Mode block normal

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

Alarm summary (1642)

Navigation Expert → Analog outputs → Analog output 1...4 → Alarm summary

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.

User interface • Discrete alarm


• Alarm state HiHi limit
• Alarm state Hi limit
• Alarm state LoLo limit
• Alarm state Lo limit
• Update Event

Batch ID (1633)

Navigation Expert → Analog outputs → Analog output 1...4 → Batch ID

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Batch_ID element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 232 - 1

152 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Batch operation (1639)

Navigation Expert → Analog outputs → Analog output 1...4 → Batch operation

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Operation element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 216 - 1

Batch phase (1640)

Navigation Expert → Analog outputs → Analog output 1...4 → Batch phase

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Phase element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 216 - 1

Batch recipe unit procedure (1641)

Navigation Expert → Analog outputs → Analog output 1...4 → Batch recipe unit procedure

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Rup (Recipe unit procedure) element of the BATCH standard block parameter as per the
PROFIBUS profiles.

User entry 0 ... 216 - 1

Set point value (1661)

Endress+Hauser 153
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Expert → Analog outputs → Analog output 1...4 → Set point value

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description Input value of AO block.


This value comes from a linked device (e.g. a pressure transmitter) via PROFIBUS. It can be
subsequently scaled in the AO block before it is forwarded to Out value and used by the
device for display purposes or for calculating other values.

Set point status (1660)

Navigation Expert → Analog outputs → Analog output 1...4 → Set point status

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description Hexadecimal-encoded status of the input value.

PV scale lower range (1651)

Navigation Expert → Analog outputs → Analog output 1...4 → PV scale lower range

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description EU_at_0% element of the PV_SCALE standard parameter in the Analog Output block as
per the PROFIBUS profiles.
Defines the 0% mark for the input value.

User entry IEEE floating point number

PV scale upper range (1652)

Navigation Expert → Analog outputs → Analog output 1...4 → PV scale upper range

154 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description EU_at_100% element of the PV_SCALE standard parameter in the Analog Output block
as per the PROFIBUS profiles.
Defines the 100% mark for the input value.

User entry IEEE floating point number

Fail safe time (1635)

Navigation Expert → Analog outputs → Analog output 1...4 → Fail safe time

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description FSAFE_TIME standard parameter of the Analog Output block as per the PROFIBUS
profiles.
Defines the time (in seconds) between the occurrence of a set point error (set point status
= BAD) and the corresponding response of the AO block.

User entry 0 to 999.0 s

Factory setting 0

Fail safe type (1636)

Navigation Expert → Analog outputs → Analog output 1...4 → Fail safe type

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description FSAFE_TYPE standard parameter of the Analog Input block as per the PROFIBUS profiles.
Specifies the output value of the Analog Input block in the event of an error.

Endress+Hauser 155
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Options • Fail safe value


The value output in the event of an error is defined in the Fail safe value parameter.
• Fallback value
The last output value that was valid before the error occurred is retained.
• Off
The output value follows the current measured value. The status is set to BAD.

Factory setting Fallback value

Fail safe value (1637)

Navigation Expert → Analog outputs → Analog output 1...4 → Fail safe value

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description FSAFE_VALUE standard parameter of the Analog Input block as per the PROFIBUS
profiles. Specifies the output value of the Analog Output block in the event of an error.

Value range IEEE floating point number

Factory setting 0

Out value (1647)

Navigation Expert → Analog outputs → Analog output 1...4 → Out value

Read permission Operator

Write permission • For Mode block actual = Man:


Operator
• In all other cases:
Read-only (display parameter)

Operation via FieldCare Online

Description Value element of the OUT standard parameter in the Analog Output block as per the
PROFIBUS profiles.
Displays the output value of the Analog Input block.

Out status (1669)

Navigation Expert → Analog outputs → Analog output 1...4 → Out status

156 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online/offline

Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. Only the two quality bits are evaluated in this parameter.

User interface • Good


• Uncertain
• Bad

Out status HEX (1645)

Navigation Expert → Analog outputs → Analog output 1...4 → Out status HEX

Read permission Operator

Write permission • For Mode block actual = Man:


Operator
• In all other cases:
Read-only (display parameter)

Operation via FieldCare Online

Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. The complete status byte is displayed as a two-digit hexadecimal
number in this parameter.

Out scale upper range (1646)

Navigation Expert → Analog outputs → Analog output 1...4 → Out scale upper range

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description EU_at_100% element of the OUT_SCALE standard parameter in the Analog Output block
as per the PROFIBUS profiles.
Defines the 100% mark for the output value.

User entry IEEE floating point number

Endress+Hauser 157
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Out scale lower range (1644)

Navigation Expert → Analog outputs → Analog output 1...4 → Out scale lower range

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description EU_at_0% element of the OUT_SCALE standard parameter in the Analog Input block as
per the PROFIBUS profiles.
Defines the 0% mark for the output value.

User entry IEEE floating point number

158 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.8 Expert → Discrete outputs → Discrete output N

3.8.1 Overview
There is an Discrete output submenu for each Discrete Output block in the device. This
submenu contains the parameters of the individual block. The parameters of the Discrete
Output block are described in the PROFIBUS profile. The most important characteristics of
the parameters are summarized below.
The device uses the Discrete Output block to read in a discrete value (0-False / 1-
TRUE). This discrete value can be used:
• for transmission via the switch output (terminals 3 and 4 in the connection
compartment). See the operating menu: Expert → Output → Switch output →
Assign status
• for switching the measurement on and off (Expert → Sensor → External input →
Control measurement)
• for transmitting a permanently defined level or interface value, regardless of the
measurement (Expert → Sensor → External input → Level external input /
interface external input)

+

3 4 +

1 2
Out Value
PROFIBUS

Set point value 3+

1 2 3
4-

A0017059

 15 Transmission of an external discrete value via the switch output of the device
1 PLC
2 Discrete Output block (part of transmitter software)
3 Transmitter

Data processing in the Discrete Output block


The diagram describes the function of the Discrete Output block in the normal
operational state (Mode block actual = Auto). The block's behavior in other
operational states is described in the Profibus profiles of the Profibus User
Organization (PNO).

Simulate value Enable


Simulate status
off TRUE TRUE
FALSE FALSE
Simulate Invert Out value
enable Out state
TRUE FALSE
on FALSE TRUE
Set point value
Set point status Disable

A0017057

Endress+Hauser 159
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

The parameters of the "Discrete output N" submenu


The Discrete Output blocks correspond to the Profibus profiles of the Profibus User
Organization (PNO). Accordingly, they contain all the parameters provided in the
profiles. The device only uses some of these parameters, however. Any parameters
that are not relevant for the device are marked "not used" in the following table.

Parameter Parameter name Comments Parameter description


according to PROFIBUS
profile

Standard block parameters

Tag description TAG_DESC Standard block parameter

Static revision ST_REV Standard block parameter

Strategy STRATEGY Standard block parameter

Alert key ALERT_KEY Standard block parameter

Target mode TARGET_MODE Standard block parameter

Mode block actual MODE_BLK Standard block parameter

Mode block permitted MODE_BLK Standard block parameter

Mode block normal MODE_BLK Standard block parameter

Alarm summary ALARM_SUM Standard block parameter

Batch ID BATCH Standard block parameter

Batch operation BATCH Standard block parameter

Batch phase BATCH Standard block parameter

Batch recipe unit BATCH Standard block parameter


procedure

Parameters of the input value (set point)

Set point value SP External value


Value element

Set point status SP Status of the external value


Status element

Parameters of the output value

Out value OUT Output value of block

Out status OUT Status of the output value


(quality bits as per PROFIBUS
profile)

Out status HEX OUT Status of the output value (full


representation by two-digit
hexadecimal number as per
PROFIBUS profile)

Block-specific parameters

Readback value READBACK Not used -

Readback status READBACK Not used -

RCAS in value RCAS_IN Not used -

RCAS in status RCAS_IN Not used -

Input channel IN_CHANNEL Not used -

Output channel OUT_CHANNEL Not used -

Signal inversion

Invert INVERT Inversion of the switch value


that is read in: 0 → 1
1→0

160 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Parameter Parameter name Comments Parameter description


according to PROFIBUS
profile

Error handling

Fail safe time FSAFE_TIME Time after which the block


responds to an error in the input
value (set point)

Fail safe type FSAFE_TYPE Specifies the response if an error


is detected.

Fail safe value FSAFE_VALUE Specifies the output value if an


error is detected.

Block-specific parameters

RCAS out value RCAS_OUT Not used -

RCAS out status RCAS_OUT Not used -

Simulate enabled SIMULATE Not used -

Simulate value SIMULATE Not used -

Simulate status SIMULATE Not used -

Check back CHECK_BACK Not used -

Check back mask CHECK_BACK_MASK Not used -

Endress+Hauser 161
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.8.2 The parameters

Tag description (1721)

Navigation Expert → Discrete outputs → Discrete output 1...4→ Tag description

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TAG_DESC standard block parameter as per the PROFIBUS profiles.

User entry Up to 32 alphanumeric characters

Static revision (1720)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Static revision

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ST_REV standard block parameter as per the PROFIBUS profiles

Strategy (1719)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Strategy

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description STRATEGY standard block parameter as per the PROFIBUS profiles

Alert key (1694)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Alert key

162 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description ALERT_KEY standard block parameter as per the PROFIBUS profiles

Target mode (1722)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Target mode

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description TARGET_MODE standard block parameter as per the PROFIBUS profiles

Mode block actual (1691)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Mode block actual

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Actual element of the MODE_BLK standard block parameter as per the PROFIBUS profiles

Mode block permitted (1705)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Mode block permitted

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Permitted element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

Endress+Hauser 163
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Mode block normal (1702)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Mode block normal

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description Normal element of the MODE_BLK standard block parameter as per the PROFIBUS
profiles

Alarm summary (1701)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Alarm summary

Read permission Operator

Write permission Read-only (display parameter)

Operation via FieldCare Online

Description ALARM_SUM standard block parameter as per the PROFIBUS profiles. Indicates the type
of alarm that has occurred.

User interface • Discrete alarm


• Alarm state HiHi limit
• Alarm state Hi limit
• Alarm state LoLo limit
• Alarm state Lo limit
• Update Event

Batch ID (1695)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Batch ID

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Batch_ID element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 232 - 1

164 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Batch operation (1698)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Batch operation

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Operation element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 216 - 1

Batch phase (1699)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Batch phase

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Phase element of the BATCH standard block parameter as per the PROFIBUS profiles.

User entry 0 to 216 - 1

Batch recipe unit procedure (1700)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Batch recipe unit procedure

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Rup (Recipe unit procedure) element of the BATCH standard block parameter as per the
PROFIBUS profiles.

User entry 0 to 216 - 1

Set point value (1715)

Endress+Hauser 165
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Expert → Discrete outputs → Discrete output 1...4 → Set point value

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Input value of DO block.


This value is transmitted from a PLC to the device via PROFIBUS.

Set point status (1714)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Set point status

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online/offline

Description Hexadecimal-encoded status of the input value.

Out value (1704)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Out value

Read permission Operator

Write permission • For Mode block actual = Man:


Operator
• In all other cases:
Read-only (display parameter)

Operation via FieldCare Online

Description Value element of the OUT standard parameter in the Discrete Output block as per the
PROFIBUS profiles.
Displays the output value of the Discrete Input block (0=FALSE or 1=TRUE).

Out status (1723)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Out status

Read permission Operator

166 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Write permission Read-only (display parameter)

Operation via FieldCare Online/offline

Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. Only the two quality bits are evaluated in this parameter.

User interface • Good


• Uncertain
• Bad

Out status HEX (1703)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Out status HEX

Read permission Operator

Write permission • For Mode block actual = Man:


Operator
• In all other cases:
Read-only (display parameter)

Operation via FieldCare Online

Description Status element of the OUT standard parameter in the Analog Input block as per the
PROFIBUS profiles. The complete status byte is displayed as a two-digit hexadecimal
number in this parameter.

Invert (1692)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Invert

Read permission Operator

Write permission Operator

Operation via FieldCare Online/offline

Description INVERT standard parameter of the Discrete Output block as per the PROFIBUS profile.
Enables the inversion of the discrete output signal (the logical states FALSE and TRUE are
swapped).

Options • Off
No inversion
• On
The switching signal is inverted before being used in the device.

Factory setting Off (i.e. no inversion)

Endress+Hauser 167
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Fail safe time (1697)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Fail safe time

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description FSAFE_TIME standard parameter of the Discrete Output block as per the PROFIBUS
profiles.
Defines the time (in seconds) between the occurrence of a set point error (set point status
= BAD) and the corresponding response of the DO block.

User entry 0 to 999.0 s

Factory setting 0

Fail safe type (1696)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Fail safe type

Read permission Operator

Write permission Maintenance

Operation via FieldCare Online

Description FSAFE_TYPE standard parameter of the Analog Input block as per the PROFIBUS profiles.
Specifies the output value of the Discrete Input block in the event of an error.

Options • Fail safe value


The value output in the event of an error is defined in the Fail safe value parameter.
• Fallback value
The last output value that was valid before the error occurred is retained.
• Off
The output value follows the current measured value. The status is set to BAD.

Factory setting Fallback value

Fail safe value (1693)

Navigation Expert → Discrete outputs → Discrete output 1...4 → Fail safe value

Read permission Operator

168 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Write permission Maintenance

Operation via FieldCare Online

Description FSAFE_VALUE standard parameter of the Discrete Input block as per the PROFIBUS
profiles. Specifies the output value of the Discrete Output block in the event of an error.

Value range • 0: FALSE


• 1: TRUE

Factory setting 0

Endress+Hauser 169
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.9 Expert → Diagnostics

Actual diagnostics (0691)

Write access Read-only parameter

Navigation Expert → Diagnostics → Actual diagnostics

Description Use this function to display the current diagnostics message. If two or more messages
occur simultaneously, the message with the highest priority is shown on the display.
Information on what is causing the message, and remedy measures, can be viewed via
the symbol on the display.

User interface Symbol for event behavior, diagnostics event, time the event occurred and event text

Additional information User interface


Example for display format:
S441 01d4h12min30s
Current output 1

Previous diagnostics (0690)

Write access Read-only parameter

Navigation Expert → Diagnostics → Previous diagnostics

Description Use this function to display the diagnostics message last displayed before the current
message. This condition can still apply.
Information on what is causing the message, and remedy measures, can be viewed via
the symbol on the display.

User interface Symbol for event behavior, diagnostics event, time the event occurred and event text

Additional information User interface


Example for display format:
C411 01d5h14min20s
Upload/download active

Operating time from restart (0653)

Write access Read-only parameter

Navigation Expert → Diagnostics → Operating time from restart

170 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Description Use this function to display the time the device has been in operation since the last device
restart.

User interface Days (d), hours (h), minutes (m) and seconds (s)

Operating time (0652)

Endress+Hauser 171
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.9.1 Expert → Diagnostics → Diagnostics list

Diagnostics 1 - 5 (0692 - 0696)

Write access Read-only parameters

Navigation Expert → Diagnostics → Diagnostics list → Diagnostics 1


Expert → Diagnostics → Diagnostics list → Diagnostics 2
Expert → Diagnostics → Diagnostics list → Diagnostics 3
Expert → Diagnostics → Diagnostics list → Diagnostics 4
Expert → Diagnostics → Diagnostics list → Diagnostics 5

Description Use this function to display the current diagnostics messages with the highest priority to
the fifth-highest priority.

Unser interface Symbol for event behavior, diagnostics event and event text

Additional information User interface


Example 1 for display format:
S441 01d4h12min30s
Current output 1

Example 2 for display format:


F276 10d8h12min22s
I/O module error

172 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.9.2 Expert → Diagnostics → Event logbook

Filter options (0705)

Write access Maintenance

Navigation Expert → Diagnostics → Event logbook → Filter options

Description Use this function to select the category whose event messages are displayed in the events
list.
The status signals are categorized according to NAMUR NE 107: F = failure, M =
maintenance request, C = function check, S = out of specification

Options • All
• Failure (F)
• Mainenance required (M)
• Function check (C)
• Out of specification (S)
• Information (I)

Factory setting All

Event list

Navigation Expert → Diagnostics → Event logbook → Event list

Description Use this function to display the history of event messages of the category selected in the
Filter options parameter (→  173). A maximum of 20 event messges are displayed in
chronological order. If the advanced HistoROM function is enabled in the device, the event
list can contain up to 100 entries.
The following symbols indicate whether an event has occurred or has ended:
• : Event has occurred
• : Event has ended
Information on what is causing the message, and remedy measures, can be viewed via
the -button.

User interface • For event messages in category I: information event, event text, "recording event" symbol
and time event occurred
• For event messages in category F, M, C, S (status signal): diagnostic event, event text,
"recording event" symbol and time event occurred

Endress+Hauser 173
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Additional information User interface


Example 1 for display format:
I 1091 24d12h13m00s
Configuration modified

Example 2 for display format:


S441 01d4h12min30s
Current output 1

HistoROM
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.

174 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.9.3 Expert → Diagnostics → Device information

Device (0011)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Device

Description Use this function to view the device designation.

Serial number (0009)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Serial number

Description Use this function to view the serial number of the device. It can also be found on the
nameplate.
Uses of the serial number
• To identify the device quickly, e.g. when contacting Endress+Hauser.
• To obtain specific information on the device using the Device Viewer:
www.endress.com/deviceviewer

User interface Max. 11-digit character string comprising letters and numbers

Firmware version (0010)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Firmware version

Description Use this function to view the device firmware version installed.

Anzeige Max. 6-digit character string in the format xx.yy.zz

Device name (0013)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Device name

Description Use this function to view the name of the device. It can also be found on the nameplate.

Endress+Hauser 175
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Order code (0008)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Order code

Description Use this function to view the order code of the device. It can also be found on the
nameplate. The order code is generated fronm the extended roder code, which defines all
the device features of the product structure. In contrast, only some of the device features
can be read directly from the order code.
Uses of the order code
• To order an identical spare device.
• To identify the device quickly and easily, e.g. when contacting Endress+Hauser.

Extended order code 1 - 3 (0021 - 0023)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device information → Extended order code 1


Expert → Diagnostics → Device information → Extended order code 2
Expert → Diagnostics → Device information → Extended order code 3

Description Use these paameters to display the fist, second or third part of the extended order code. On
account of length restrictions, the extended order code is split into a maximum of 3
parameters.
The extended order code indicates the version of all the features of the preoduct structure
for the device and thus uniaquely identifies the device. It canalso be found on the
nameplate.
Uses of the extended order code
• To order an identical spare device
• To check the ordered device features against the shipping note.

ENP version (0012)

Write access Read-only parameter

Navigation Expert→ Diagnostics → Device information→ ENP version

Description Use this function to view the version of the electroni nameplate (ENP).

User interface 6-digit number in the format xx.yy.zz

176 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.9.4 Expert → Diagnostics → Data logging


The menu is only displayed if the extended function of the HistoROM is enabled in the
device.

Assign channel 1 -4 (0851 - 0854)

Write access Maintenance

Navigation Expert → Diagnostics → Data logging → Assign channel 1


Expert → Diagnostics → Data logging → Assign channel 2
Expert → Diagnostics → Data logging → Assign channel 3
Expert → Diagnostics → Data logging → Assign channel 4

Description Use this functionto assign a process variable to the data logging channel.
A total of 500 measured values can be logged. This means:
• 500 data points if 1 logging channel is used
• 250 data points if 2 logging channels are used
• 166 data points if 3 logging channels are used
• 125 data points if 4 logging channels are used
Once the maximum number of data points is reached, the oldest data points in the data log
are cyclically overwritten in such a way that the last 500, 250, 166 or 125 measured
values are always in the log (ring memory principle).
The log contents are cleared if the option selected is changed.

Auswahl • Off
• Level
• Distance
• Current output 1
• Measured current
• Terminal voltage
• Electronics temperature
• Absolute echo amplitude
• Relative echo amplitude
• Signal noise

Factory setting Off

Logging interval (0856)

Write access Maintenance

Navigation Expert → Diagnostics → Data logging → Logging interval

Endress+Hauser 177
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Description Definition of the logging interval tlog for data logging. This defines the interval between
the individual data points in the data log, and thus the maximum loggable process time
Tlog.
• If 1 logging channel is used: T log = 500 ⋅ t log
• If 2 logging channels are used: T log = 250 ⋅ t log
• If 3 logging channels are used: T log = 166 ⋅ t log
• If 4 logging channels are used: T log = 125 ⋅ t log
Once this time elapses, the oldest data points in the data log are cyclically overwritten such
that a time of Tlog always remains in the meory (ring memory principle).
Nach Ablauf dieser Zeit werden die ältesten im Speicher vorhandenen Datenpunkte
zyklisch überschrieben, so dass immer eine Zeit von Tlog im Speicher bleibt (Ringspeicher-
Prinzip).
The log contents are cleared if the length of the logging interval is changed.

Input range 1 to 3600 s

Factory setting 10 s

Additional information Example


If 1 logging channel is used:
• Tlog = 500 ⋅ 1 s = 500 s ≈ 8.5 min
• Tlog = 500 ⋅ 10 s = 5 000 s ≈ 1.5 h
• Tlog = 500 ⋅ 80 s = 40 000 s ≈ 11 h
• Tlog = 500 ⋅ 3 600 s = 1 800 000 s ≈ 20 d

Clear logging data (0855)

Write access Maintenance

Navigation Expert → Diagnostics → Data logging → Clear logging data

Description Use this function to clear the entire logging data.

Options • Cancel
The data are not cleared. All the data are retained.
• Clear data
The logging data are cleared. The logging process starts from scratch.

Factory setting Cancel

Display channel 1 - Display channel 4

Navigation Expert → Diagnostics → Data logging → Display channel 1


Expert → Diagnostics → Data logging → Display channel 2
Expert → Diagnostics → Data logging → Display channel 3
Expert → Diagnostics → Data logging → Display channel 4

178 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Description Use this function to view the measured value trend for the logging channel in the form of a
chart.

A0013859

• x-axis: depending on the number of channels selected displays 250 to 1000 measured
values of a process variable.
• y-axis: displays the approximate measured value span and constantly adapts this to the
ongoing measurement.
The process variable whose measured valu curve is displayed is specified in the Assign
channel 1 - Assign channel 4 parameters .

Endress+Hauser 179
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

3.9.5 Expert → Diagnostics → Min/max values

Max. level value (2357)

Write access Display-only parameter

Navigation Expert → Diagnostics → Min/max values → Max. level value

Description Use this parameter to view the maximum level measured until now (drag indicator).

Time max. level (2385)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Time max. level

Description Use this parameter to view the operating time at which the maximum level has been
measured.

Min. level value (2358)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Min. level value

Description Use this parameter to view the minimum level measured until now (drag indicator).

Time min. level (2386)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Time min. level

Description Use this parameter to view the operating time at which the minimum level has been
measured.

Max. draining speed (2320)

Write access Read-only parameter

180 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Navigation Expert → Diagnostics → Min/max values → Max. draining speed

Description Use this parameter to view the maximum draining speed measured until now (drag
indicator).

Max. filling speed (2360)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Max. filling speed

Description Use this parameter to view the maximum filling speed measured until now (drag
indicator).

Reset min./max. (2324)

Write access Service

Navigation Expert → Diagnostics → Min/max values → Reset min./max.

Description Resets the drag indicator of the selected process variable.


Access to this parameter is reserved to the Endress+Hauser service staff. It can only be
accessed after entering the service code.

Max. electronics temperature (1031)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Max. electronics temperature

Description Use this parameter to view the maximum electronics temperature measured until now
(drag indicator).

Time max. electronics temperature (1204)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Time max. electronics temperature

Description Use this parameter to view the operating time at which the maximum electronics
temperature has been measured.

Endress+Hauser 181
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Min. electronics temperature (1040)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Min. electronics temperature

Description Use this parameter to view the minimum electronics temperature measured until now
(drag indicator).

Time min. electronics temperature (1205)

Write access Read-only parameter

Navigation Expert → Diagnostics → Min/max values → Time min. electronics temperature

Description Use this parameter to view the operating time at which the minimum electronics
temperature has been measured.

Reset min./max. temperature (1173)

Write access Service

Navigation Expert → Diagnostics → Min/max values → Reset min./max. temperature

Description Resets the drag indicator of the electronics temperature.


Access to this parameter is reserved to the Endress+Hauser service staff. It can only be
accessed after entering the service code.

182 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.9.6 Expert → Diagnostics → Simulation

Assign simulation process variable (2328)

Write access Maintenance

Navigation Expert → Diagnostics → Simulation → Assign proc. var.

Description Use this function to select a process variable for the simulation process that is activated.
The display alternates between the measured value and a diagnostics message of the
"function check" category (C) while simulation is in progress.
The simulation value of the selected process variable is defined in the Value process
variable parameter.

Options • Off
• Level
• Level linearized

Factory setting Off

Value process variable (2329)

Write access Maintenance

Navigation Expert → Diagnostics → Simulation → Value proc. var.

Prerequisite One of the following options is selected in the Assign simulation process variable
parameter:
• Level
• Level linearized

Beschreibung Use this function to enter a simulation value for the selected process variable. Subsequent
measured value processing and the signal output use this simulation value. In this way,
users can verify whether the measuring device has been configured correctly.

Input range Depends on the process variable selected

Factory setting The current value of the selected process variable at the moment the simulation is
activated.

Switch output simulation (0462)

Navigation Expert → Diagnostics → Simulation → Switch output simulation

Description Use this parameter to activate or deactivate the simulation of the switch output.

Endress+Hauser 183
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Auswahl • Off
• On

Werkseinstellung Off (i.e. no simulation)

Switch status (0463)

Navigation Expert → Diagnostics → Simulation → Switch status

Prerequisite Only visible for Switch output simulation = On.

Description Use this parameter to define the switch status for the simulation.

Auswahl • Open
• Closed

Werkseinstellung Open

Simulation device alarm (0654)

Navigation Expert → Diagnostics → Simulation → Simulation device alarm

Description Use this function to switch the device alarm on and off. In this way, users can verify the
correct adjustment of the current output and the correct function of downstream switching
units.
The display alternates between the measured value and a diagnostics message of the
"function check" category (C) while simulation is in progress:

Options • On
• Off

Factory setting Off

3.9.7 Expert → Diagnostics → Device check

Start device check (1013)

Write access Maintenance

Navigation Expert → Diagnostics → Device check → Start device check

Description Start of a device check.

184 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Selection • No
No device check is performed.
• Yes
A device check is performed.
If the error S941 "Echo lost" is present, a device check is not possible. First you have to
eliminte the cause of this error.

Factory setting No

Result device check (1014)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device check → Result device check

Description Indicates the result of the device check.

Display • Installation ok
• Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the
signal amplitudes.
• Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check
the mounting position of the device and the dielectric constant of the medium.
• Check not done

Last check time (1203)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device check → Last check time

Description Displays the operating time at which the last device check has been performed.

Additional information Display format


Days (d), hours (h), minutes (m), seconds (s): 0000d00h00m00s

Level signal (1016)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device check → Level signal

Prerequisite Only visible if a device check has been performed.

Description Displays the result of the device check for the level signal.

Endress+Hauser 185
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Display • Check not done


• Check not ok
Check the mounting position of the device and the dielectric constant of the medium.
• Check ok

Area of incoupling (1186)

Write access Read-only parameter

Navigation Expert → Diagnostics → Device check → Area of incoupling

Description Indicates the area of ringing zone.

186 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

3.9.8 Expert → Diagnostics → Advanced diagnostics 1/2

Basic principles
The Advanced Diagnostics offers additional options to monitor the process. The device
contains two Advanced Diagnostics Blocks which can be used separately or in combination.
A measuring variable can be assigned to the input of each Advanced Diagnostics Block.
Based on a freely configurable time interval, the variable can be submitted to a statistical
function (e.g. maximum, minimum, mean, slope). Finally, a limit detection can be
parametrized and its result can be transmitted to a digital output.
The result can be displayed and evaluated by a DCS or PLC. If required, it can also be linked
to the second Advanced Diagnostics block and thus it is possible to combine the two results
by the logical operators AND or OR.

Endress+Hauser 187
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Application example: Foam detection


Preconditions
• The process runs at a fixed level (in the example: 80 %)
• If foam occurs during the operation, the vessel should automatically be sprinkled with
water from the top or an antifoam agent should be added to dissolve the foam.
Reaction of the radar signal in the case of foam formation
The echo amplitude decreases in the case of foam formation. This can be used by the
Advanced Diagnostics to detect the foam. The foam detection, however, should only be
active as long as the level is between 75 % and 85 %.

A A

85%

75%

A0019640

 16 Decrease of the amplitude in case of foam formation


A Amplitude threshold for foam detection

Step 1: Determination of the amplitude threshold


Observe the echo amplitude while the process is running at the given level (in the example:
80 %) and determine the lower limit for the amplitude (in the example: 10 dB).
The Maximum value 1/2 (→  196) and Minimum value 1/2 (→  196) parameters
can be used for this.

Step 2: Configuration of the level monitoring
In order to ensure that the level actually is in the vicinity of the given value: Configure
Advanced Diagnostics 1 as follows:
• Assign diagnostic signal 1 = Level linearized
• Check mode 1 = Out of range
Out of range checks whether the level is outside a defined range. As long as this is the
case, the block outputs "0" (INACTIVE). If the level gets into the defined range, the block
outputs "1" (ACTIVE).
• Upper limit 1 = 85 %
• Lower limit 1 = 75 %
With this setting, the output of Advanced Diagnostics 1 assumes the following value:
• 0 (INACTIVE) - if the level is outside the defined range (out of range).
• 1 (ACTIVE) - if the level is within the defined range. The foam detection should only be
active in this case.

188 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Step 3: Configuration of the foam detection.


Configure Advanced Diagnostics 2 as follows:
• Assign diagnostic signal 2 = Relative echo amplitude
• Calculation type 2 = Mean
• Sample time 2 = 60 s
• Check mode 2 = Lower limit
• Lower limit 2 = 10 dB
With this setting Advanced Diagnostics 2 (internally) assumes the following value:
• 0 (INACTIVE) - if the amplitude exceeds 10 dB (i.e.: there is no foam)
• 1 (ACTIVE) - if the amplitude is below 10 dB (i.e.: foam detected).

Step 4: Configuration of the logic block linking
Configure Advanced Diagnostics 2 as follows:
• Link AD 2 to = Digital output AD 1
• Linking logic AD 2 = AND
With this setting, the output of Advanced Diagnostics 2 assumes the following value:
• 0 (INACTIVE) - if at least one of the two blocks is in the "0" (INACTIVE) status.
• 1 (ACTIVE) - if both blocks are in the "1" (ACTIVE) status.
For the example this means:
– A diagnostic signal is output, if the level is within the defined range and the signal
amplitude is below 10 dB. This signal can be linked to the status output of the device
(→  98).
– If, on the other hand, the level is out of the defined range or if the signal amplitude
exceeds 10 dB, no diagnostic signal is transmitted via the switch output.
The status can also be linked to the DI block and transmitted to the fieldbus.

Endress+Hauser 189
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

A L

1
1.2 1.5 2.7 2.8
1.3 2.6
L 1.1
1.4

2
2.2 2.4

A 2.1 2.5

2.3

A0019641

 17 Configuration of the Advanced Diagnostics for foam detection


L Level
A Amplitude
1 Advanced diagnostics 1: Monitoring the level
1.1 "Assign diagnostic signal 1" = "Level linearized"
1.2 "Check mode 1" = "In range"
1.3 "Upper limit" = 85 %
1.4 "Lower limit" = 75 %
1.5 Digital output of Advanced Diagnostics 1
2 Advanced Diagnostics 2: Monitoring the amplitude
2.1 "Assign diagnostic signal 2" = "Relative echo amplitude"
2.2 "Calculation type 2" = "Mean"
2.3 "Sample time" = 60 s
2.4 "Check mode" = "Lower limit"
2.5 "Lower limit" = 10 dB
2.6 "Link AD 2 to" = "Digital output AD1"
2.7 "Linking logic AD 2" = "AND"
2.8 Digital output of Advanced Diagnostics 2

190 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Overview of the parameters

Parameter Description

Assign diagnotic signal 1/2 (→  192)

Link AD 1/2 to (→  192)

Linking logic AD 1/2 (→  192)

Sample time 1/2 (→  193)

Calculation type 1/2 (→  193)

Check mode 1/2 (→  193)

Calculation unit 1/2 (→  194)

Upper limit 1/2 (→  194)

Lower limit 1/2 (→  195)

Hysteresis1/2 (→  195)

Maximum value 1/2 (→  196)

Minimum value 1/2 (→  196)

Reset Min./Max. 1/2 (→  196)

Assign status signal to AD event 1/2 (→  196)

Assign event behaviour 1/2 (→  197)

Alarm delay 1/2 (→  197)

Endress+Hauser 191
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

The parameters

Assign diagnostic signal 1/2 (11179)

Navigation Expert → Diagnostics → Advanced diagnostics → Assign diagnostic signal 1/2

Write access Maintenance

Descriptions Assigns a measuring variable, which is needed for diagnostic purposes, to the Advanced
Diagnostics Block.

Options • None
• Level linearized
• Unfiltered distance
• Relative echo amplitude
• Electronic temperature
• Measured current
• Terminal voltage
• Area of incoupling

Factory setting None

Link AD 1/2 to (11180)

Navigation Expert → Diagnostics → Advanced diagnostics → Link AD 1/2 to

Write access Maintenance

Descriptions Links the Advanced Diagnostics Block 1 or 2 to the other Advanced Diagnostics Block in
order to include the linking logic into the configuration (→  187).

Options • None
• Digital output AD 1
• Digital output AD 2

Factory setting None

Linking logic AD 1/2 (11181)

Navigation Expert → Diagnostics → Advanced diagnostics → Linking logic AD 1/2

Write access Maintenance

Prerequisite Only visible if the Advanced Diagnostics Block has been linked to the digital oputput of the
other Advanced Diagnostics Block via the Link AD 1/2 to parameter.

Descriptions Defines the linking logic between the two Advanced Diagnostics Blocks AD1 and AD2.

192 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Options • AND
• OR

Factory setting AND

Sample time 1/2 (11187)

Navigation Expert → Diagnostics → Advanced diagnostics → Sample time 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Defines the scanning time in seconds for the calculation.

Input range 1 to 3 600 s

Factory setting 10 s

Calculation type 1/2 (11174)

Navigation Expert → Diagnostics → Advanced diagnostics → Calculation type 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Defines, which quantity is derived from the assigned measured variable.

Options • Off
• Maximum
• Minimum
• Mean
• Standard deviation
• Difference Max. - Min.
• Slope

Factory setting Off

Additional information The calculation is performed based on the defined Sample time. (I.e. the maximum,
minimum, mean, standard deviation, difference max.-min. or average slope within the
sample time are calculated.)

Check mode 1/2 (11175)

Endress+Hauser 193
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Navigation Expert → Diagnostics → Advanced diagnostics → Check mode 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Defines the check mode.

Options • Off
• Upper limit
• Lower limit
• In range
• Out of range

Factory setting Off

Additional information If a calculation has been selected in the Calculation type parameter, the check does not
refer to the assigned measuring variable but to the quantity calculated from it.

Calculation unit 1/2 (11188)

Navigation Expert → Diagnostics → Advanced diagnostics → Calculation unit 1/2

Write access Operator

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Defines the unit for the selected Calculation type.

Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Upper limit 1/2 (11182)

Navigation Expert → Diagnostics → Advanced diagnostics → Upper limit 1/2

Write access Maintenance

Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Upper limit
• In range
• Out of range

194 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Descriptions Defines the upper limit for the selected check mode.

Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Lower limit 1/2 (11184)

Navigation Expert → Diagnostics → Advanced diagnostics → Lower limit 1/2

Write access Maintenance

Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Lower limit
• In range
• Out of range

Descriptions Defines the lower limit for the selected check mode.

Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Hysteresis 1/2 (11178)

Navigation Expert → Diagnostics → Advanced diagnostics → Hysteresis 1/2

Write access Maintenance

Prerequisite Only visible if one of the following options has been selected in the Check mode
parameter:
• Upper limit
• Lower limit
• In range
• Out of range

Descriptions Defines the hysteresis for the selected check mode.

Options Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Factory setting Depending on the selected Calculation type and the measuring variable selected in Assign
diagnostic signal.

Endress+Hauser 195
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Maximum value 1/2 (11183)

Navigation Expert → Diagnostics → Advanced diagnostics → Maximum value 1/2

Write access Read-only parameter

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Indicates the maximum value the assigned measuring variable has attained (dragging
indicator).

Minimum value 1/2 (11185)

Navigation Expert → Diagnostics → Advanced diagnostics → Minimum value 1/2

Write access Read-only parameter

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Descriptions Indicates the minimum value the assigned measuring variable has attained (dragging
indicator).

Reset min./max. 1/2 (11186)

Navigation Expert → Diagnostics → Advanced diagnostics → Reset min./max. 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Description Resets the Maximum value and Minimum value dragging indicators.

Options • Off
• Reset max.
• Reset min.
• Reset min./max.

Factory setting Off

Assign status signal to AD event 1/2 (11176)

196 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 The "Expert" menu

Navigation Expert → Diagnostics → Advanced diagnostics → Assign status signal to AD event


1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Description Assigns an event category according to NAMUR NE107 to the event of the Advanced
Diagnostics Block.

Options • Failure (F)


• Maintenance required (M)
• Function check (C)
• Out of specification (S)

Factory setting Maintenance required (M)

Assign event behaviour 1/2 (11177)

Navigation Expert → Diagnostics → Advanced diagnostics → Assign event behaviour 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Description Assigns an event behavior to the event of the Advanced Diagnostics Block.

Options • Off
• Alarm
• Warning
• Logbook entry only

Factory setting Warning

Alarm delay 1/2 (11171)

Navigation Expert → Diagnostics → Advanced diagnostics → Alarm delay 1/2

Write access Maintenance

Prerequisite Only visible if a measuring variable has been assigned to the Advanced Diagnostics Block
via the Assign diagnostic signal 1/2 parameter.

Description Assigns an event behavior to the event of the Advanced Diagnostics Block.

Input range 0 to 3 600 s

Endress+Hauser 197
The "Expert" menu Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Factory setting 10 s

198 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Index

Index
A Configuration management (Parameter) . . . . . . . . . . 30
Absolute echo amplitude (Parameter) . . . . . . . . . . . . 64 Confirm access code (Parameter) . . . . . . . . . . . . . . . . 34
Access status display (Parameter) . . . . . . . . . . . . . . . 17 Confirm distance (Parameter) . . . . . . . . . . . . . . . . . . 91
Access status tooling (Parameter) . . . . . . . . . . . . . . . 18 Const. GPC factor (Parameter) . . . . . . . . . . . . . . . . . . 84
Acknowledge alarm (Parameter) . . . . . . . . . . . . . . . . 88 Contrast display (Parameter) . . . . . . . . . . . . . . . . . . . 28
Activate SW option (Parameter) . . . . . . . . . . . . . . . . 35 Control measurement (parameter) . . . . . . . . . . . . . . . 97
Activate table (Parameter) . . . . . . . . . . . . . . . . . . . . . 62 CRC count failed (parameter) . . . . . . . . . . . . . . . . . . 107
Actual diagnostics (Parameter) . . . . . . . . . . . . . . . . 170 CRC count OK (parameter) . . . . . . . . . . . . . . . . . . . . 107
Address mode (parameter) . . . . . . . . . . . . . . . . . . . 103 Customer value (Parameter) . . . . . . . . . . . . . . . . . . . 62
Advanced process conditions (Parameter) . . . . . . . . . 40
Alarm delay 1 (Parameter) . . . . . . . . . . . . . . . . . . . 197 D
Alarm delay 2 (Parameter) . . . . . . . . . . . . . . . . . . . 197 Dead time (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 73
Alarm hysteresis (parameter) . . . . . . . . . . . . . . . . . 130 Decimal places 1 (Parameter) . . . . . . . . . . . . . . . . . . 24
Alarm summary (parameter) . . 112, 123, 141, 152, 164 Decimal places 2 (Parameter) . . . . . . . . . . . . . . . . . . 24
Alert key (parameter) . . . . . . . 110, 121, 139, 150, 162 Decimal places 3 (Parameter) . . . . . . . . . . . . . . . . . . 24
Application parameter (Parameter) . . . . . . . . . . . . . . 41 Decimal places 4 (Parameter) . . . . . . . . . . . . . . . . . . 24
Area of incoupling (Parameter) . . . . . . . . . . . . . . . . 186 Decimal places menu (Parameter) . . . . . . . . . . . . . . . 27
Assign channel 1 (Parameter) . . . . . . . . . . . . . . . . . 177 Define access code (Parameter) . . . . . . . . . . . . . . . . . 34
Assign channel 2 (Parameter) . . . . . . . . . . . . . . . . . 177 Delay echo lost (Parameter) (Parameter) . . . . . . . . . . 87
Assign channel 3 (Parameter) . . . . . . . . . . . . . . . . . 177 Descriptor (parameter) . . . . . . . . . . . . . . . . . . . . . . 115
Assign channel 4 (Parameter) . . . . . . . . . . . . . . . . . 177 Device (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . . 175
Assign diagnostic level (Parameter) . . . . . . . . . . . . . . 98 Device address (parameter) . . . . . . . . . . . . . . . . . . . 104
Assign diagnostic signal 1 (Parameter) . . . . . . . . . . 192 Device certification (parameter) . . . . . . . . . . . . . . . . 114
Assign diagnostic signal 2 (Parameter) . . . . . . . . . . 192 Device ID (parameter) . . . . . . . . . . . . . . . . . . . . . . . 113
Assign event behaviour 1 (Parameter) . . . . . . . . . . . 197 Device install date (parameter) . . . . . . . . . . . . . . . . 116
Assign event behaviour 2 (Parameter) . . . . . . . . . . . 197 Device message (parameter) . . . . . . . . . . . . . . . . . . 115
Assign limit (Parameter) . . . . . . . . . . . . . . . . . . . . . . 98 Device name (Parameter) . . . . . . . . . . . . . . . . . . . . 175
Assign simulation process variable (Parameter) . . . . 183 Device reset (Parameter) . . . . . . . . . . . . . . . . . . . . . . 35
Assign status (Parameter) . . . . . . . . . . . . . . . . . . . . 100 Diagnostics (parameter) . . . . . . . . . . . . . . . . . . . . . 114
Assign status signal to AD event 1 (Parameter) . . . . 196 Diagnostics 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
Assign status signal to AD event 2 (Parameter) . . . . 196 Diagnostics 2 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
Diagnostics 3 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
B Diagnostics 4 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
Backlight (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 28 Diagnostics 5 (Parameter) . . . . . . . . . . . . . . . . . . . . 172
Backup state (Parameter) . . . . . . . . . . . . . . . . . . . . . 31 Diagnostics extension (parameter) . . . . . . . . . . . . . . 114
Base current (parameter) . . . . . . . . . . . . . . . . . . . . . 108 Diagnostics mask (parameter) . . . . . . . . . . . . . . . . . 114
Batch ID (parameter) . . . . . . . . . . . . 123, 141, 152, 164 Diameter (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 59
Batch operation (parameter) . . . . . . 124, 142, 153, 165 Direct access (Parameter) . . . . . . . . . . . . . . . . . . . . . 17
Batch phase (parameter) . . . . . . . . . 124, 142, 153, 165 Display channel 1 (Parameter) . . . . . . . . . . . . . . . . . 178
Batch recipe unit procedure (parameter) 124, 142, Display channel 2 (Parameter) . . . . . . . . . . . . . . . . . 178
153, 165 Display channel 3 (Parameter) . . . . . . . . . . . . . . . . . 178
Bin property (Parameter) . . . . . . . . . . . . . . . . . . . . . . 38 Display channel 4 (Parameter) . . . . . . . . . . . . . . . . . 178
Blocking distance (Parameter) . . . . . . . . . . . . . . . . . . 77 Display damping (Parameter) . . . . . . . . . . . . . . . . . . 25
Display interval (Parameter) . . . . . . . . . . . . . . . . . . . 25
C Distance (Parameter) . . . . . . . . . . . . . . . . . . . 45, 72, 91
Calculated DC value (Parameter) . . . . . . . . . . . . . . . . 43 Distance offset (Parameter) . . . . . . . . . . . . . . . . . . . . 45
Calculation type 1 (Parameter) . . . . . . . . . . . . . . . . 193 Distance unit (Parameter) . . . . . . . . . . . . . . . . . . . . . 37
Calculation type 2 (Parameter) . . . . . . . . . . . . . . . . 193 Document
Calculation unit 1 (Parameter) . . . . . . . . . . . . . . . . . 194 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Calculation unit 2 (Parameter) . . . . . . . . . . . . . . . . . 194 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Channel (parameter) . . . . . . . . . . . . . . . . . . . . 127, 144
Check mode 1 (Parameter) . . . . . . . . . . . . . . . . . . . 193 E
Check mode 2 (Parameter) . . . . . . . . . . . . . . . . . . . 193 Electronic temperature (Parameter) . . . . . . . . . . . . . . 67
Clear logging data (Parameter) . . . . . . . . . . . . . . . . 178 Empty calibration (Parameter) . . . . . . . . . . . . . . . . . . 46
Comparison result (Parameter) . . . . . . . . . . . . . . . . . 31 ENP version (Parameter) . . . . . . . . . . . . . . . . . . . . . 176
Condensed status diagnose (parameter) . . . . . . . . . . 117 Enter access code (Parameter) . . . . . . . . . . . . . . . . . . 18

Endress+Hauser 199
Index Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57

Envelope curve (Parameter) . . . . . . . . . . . . . . . . . . . . 90 Level (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 51, 61


Evaluation mode (Parameter) . . . . . . . . . . . . . . . . . . 95 Level correction (Parameter) . . . . . . . . . . . . . . . . . . . 50
Event list (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 173 Level external input (parameter) . . . . . . . . . . . . . . . . 96
Extended order code 1 (Parameter) . . . . . . . . . . . . . 176 Level limit mode (Parameter) . . . . . . . . . . . . . . . . . . . 49
Extended order code 2 (Parameter) . . . . . . . . . . . . . 176 Level linearized (Parameter) . . . . . . . . . . . . . . . . . . . 52
Extended order code 3 (Parameter) . . . . . . . . . . . . . 176 Level signal (Parameter) . . . . . . . . . . . . . . . . . . . . . 185
External pressure (Parameter) . . . . . . . . . . . . . . . . . . 83 Level unit (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 48
External pressure selector (Parameter) . . . . . . . . . . . . 82 Lin type (parameter) . . . . . . . . . . . . . . . . . . . . . . . . 127
Linearization type (Parameter) . . . . . . . . . . . . . . . . . 56
F Link AD 1 to (Parameter) . . . . . . . . . . . . . . . . . . . . 192
Factory reset (parameter) . . . . . . . . . . . . . . . . . . . . 115 Link AD 2 to (Parameter) . . . . . . . . . . . . . . . . . . . . 192
Fail safe time (parameter) . . . . . . . . . . . . . . . . 155, 168 Linking logic AD 1 (Parameter) . . . . . . . . . . . . . . . . 192
Fail safe type (parameter) . . . . . . . . 129, 144, 155, 168 Linking logic AD 2 (Parameter) . . . . . . . . . . . . . . . . 192
Fail safe value (parameter) . . . . . . . . 129, 145, 156, 168 Lo alarm state (parameter) . . . . . . . . . . . . . . . . . . . 133
Feature enabled (parameter) . . . . . . . . . . . . . . . . . . 116 Lo alarm value (parameter) . . . . . . . . . . . . . . . . . . . 133
Feature supported (parameter) . . . . . . . . . . . . . . . . 117 Lo lim (parameter) . . . . . . . . . . . . . . . . . . . . . . . . . 131
Filter options (Parameter) . . . . . . . . . . . . . . . . . . . . 173 Lo Lo alarm state (parameter) . . . . . . . . . . . . . . . . . 134
Firmware version (Parameter) . . . . . . . . . . . . . . . . . 175 Lo Lo alarm value (parameter) . . . . . . . . . . . . . . . . . 133
Fixed value input 1/2 (parameter) . . . . . . . . . . . . . . . 96 Lo Lo lim (parameter) . . . . . . . . . . . . . . . . . . . . . . . 131
Format display (Parameter) . . . . . . . . . . . . . . . . . . . . 22 Locking status (Parameter) . . . . . . . . . . . . . . . . . . . . 17
Found echoes (Parameter) . . . . . . . . . . . . . . . . . . . . . 66 Logging interval (Parameter) . . . . . . . . . . . . . . . . . . 177
Free field special (Parameter) . . . . . . . . . . . . . . . . . . 68 Low limit (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 50
Free text (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 58 Lower limit 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 195
Full calibration (Parameter) . . . . . . . . . . . . . . . . . . . . 47 Lower limit 2 (Parameter) . . . . . . . . . . . . . . . . . . . . 195
Function input 1/2 level (parameter) . . . . . . . . . . . . . 96
M
G Manufacturer ID (parameter) . . . . . . . . . . . . . . . . . . 113
Gas layer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Mapping end point (Parameter) . . . . . . . . . . . . . . . . . 92
Gas phase compensation factor (Parameter) . . . . . . . . 83 Max. draining speed (Parameter) . . . . . . . . . . . . . . . 180
Good telegrams (parameter) . . . . . . . . . . . . . . . . . . 107 Max. draining speed liquid (Parameter) . . . . . . . . . . . 39
GPC mode (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 82 Max. draining speed solid (Parameter) . . . . . . . . . . . . 40
Max. electronics temperature (Parameter) . . . . . . . . 181
H Max. filling speed (Parameter) . . . . . . . . . . . . . . . . . 181
Hardware lock (parameter) . . . . . . . . . . . . . . . . . . . 116 Max. filling speed liquid (Parameter) . . . . . . . . . . . . . 39
Hardware revision (parameter) . . . . . . . . . . . . . . . . 112 Max. filling speed solid (Parameter) . . . . . . . . . . . . . . 39
Header (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Max. level value (Parameter) . . . . . . . . . . . . . . . . . . 180
Header text (Parameter) . . . . . . . . . . . . . . . . . . . . . . 26 Maximum value (Parameter) . . . . . . . . . . . . . . . . . . . 59
Hi alarm state (parameter) . . . . . . . . . . . . . . . . . . . 132 Maximum value 1 (Parameter) . . . . . . . . . . . . . . . . 196
Hi alarm value (parameter) . . . . . . . . . . . . . . . . . . . 132 Maximum value 2 (Parameter) . . . . . . . . . . . . . . . . 196
Hi Hi alarm state (parameter) . . . . . . . . . . . . . . . . . 132 Measurement (parameter) . . . . . . . . . . . . . . . . . . . . . 97
Hi Hi alarm value (parameter) . . . . . . . . . . . . . . . . . 131 Measurement frequency (Parameter) . . . . . . . . . . . . . 67
Hi Hi lim (parameter) . . . . . . . . . . . . . . . . . . . . . . . 130 Medium group (Parameter) . . . . . . . . . . . . . . . . . . . . 42
Hi lim (parameter) . . . . . . . . . . . . . . . . . . . . . . . . . 130 Medium property (Parameter) . . . . . . . . . . . . . . . . . . 43
High limit (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 49 Medium type (Parameter) . . . . . . . . . . . . . . . . . . . . . 42
History reset (Parameter) . . . . . . . . . . . . . . . . . . . . . 95 Min. electronics temperature (Parameter) . . . . . . . . 182
Hysteresis 1 (Parameter) . . . . . . . . . . . . . . . . . . . . . 195 Min. level value (Parameter) . . . . . . . . . . . . . . . . . . 180
Hysteresis 2 (Parameter) . . . . . . . . . . . . . . . . . . . . . 195 Minimum value 1 (Parameter) . . . . . . . . . . . . . . . . . 196
Minimum value 2 (Parameter) . . . . . . . . . . . . . . . . . 196
I Mode block actual (parameter) 111, 122, 140, 151, 163
Ident number selector (parameter) . . . . . . . . . . . . . . 105 Mode block normal (parameter) 112, 123, 141, 152,
In safety distance (Parameter) . . . . . . . . . . . . . . . . . . 88 164
Integration time (Parameter) . . . . . . . . . . . . . . . . . . . 75 Mode block permitted (parameter) 111, 122, 140,
Intermediate height (Parameter) . . . . . . . . . . . . . . . . 59 151, 163
Invert (parameter) . . . . . . . . . . . . . . . . . . . . . . 144, 167
Invert output signal (Parameter) . . . . . . . . . . . . . . . 102 N
Noise of signal (Parameter) . . . . . . . . . . . . . . . . . . . . 85
L Number format (Parameter) . . . . . . . . . . . . . . . . . . . 27
Language (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 22
Last backup (Parameter) . . . . . . . . . . . . . . . . . . . . . . 30
Last check time (Parameter) . . . . . . . . . . . . . . . . . . 185

200 Endress+Hauser
Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 Index

O Switch output failure mode (Parameter) . . . . . . . . . . 101


Operating time (Parameter) . . . . . . . . . . . . . . . . . . . . 30 Switch output function (Parameter) . . . . . . . . . . . . . . 98
Operating time from restart (Parameter) . . . . . . . . . 170 Switch output simulation (Parameter) . . . . . . . . . . . 183
Order code (Parameter) . . . . . . . . . . . . . . . . . . . . . . 176 Switch status (Parameter) . . . . . . . . . . . . . . . . 102, 184
Out decimal point (parameter) . . . . . . . . . . . . . . . . . 128 Switch-off delay (Parameter) . . . . . . . . . . . . . . . . . . 101
Out scale lower range (parameter) . . . . . . . . . . 126, 158 Switch-off value (Parameter) . . . . . . . . . . . . . . . . . . . 99
Out scale upper range (parameter) . . . . . . . . . . 127, 157 Switch-on delay (Parameter) . . . . . . . . . . . . . . . . . . 101
Out status (parameter) . . . . . . . . . . . 125, 143, 156, 166 Switch-on value (Parameter) . . . . . . . . . . . . . . . . . . . 99
Out status HEX (parameter) . . . . . . . 125, 143, 157, 167
Out unit (parameter) . . . . . . . . . . . . . . . . . . . . . . . . 128 T
Out unit text (parameter) . . . . . . . . . . . . . . . . . . . . 135 Table mode (Parameter) . . . . . . . . . . . . . . . . . . . . . . 60
Out value (parameter) . . . . . . . . . . . 124, 142, 156, 166 Table number (Parameter) . . . . . . . . . . . . . . . . . . . . . 61
Output echo lost (Parameter) . . . . . . . . . . . . . . . . . . . 86 Tag description (parameter) . . . 110, 121, 139, 150, 162
Output mode (Parameter) . . . . . . . . . . . . . . . . . . . . . 51 Tank bottom echo amplitude (Parameter) . . . . . . . . . 66
Tank bottom range (Parameter) . . . . . . . . . . . . . . . . . 94
P Tank trace state (Parameter) . . . . . . . . . . . . . . . . . . . 66
Present mapping (Parameter) . . . . . . . . . . . . . . . . . . 92 Tank type (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 37
Present reference distance (Parameter) . . . . . . . . . . . 83 Tank/silo height (Parameter) . . . . . . . . . . . . . . . . . . 52
Previous diagnostics (Parameter) . . . . . . . . . . . . . . . 170 Target mode (parameter) . . . . . 111, 122, 140, 151, 163
PROFIBUS ident number (parameter) . . . . . . . . . . . . 106 Temperature unit (Parameter) . . . . . . . . . . . . . . . . . . 37
Profile version (parameter) . . . . . . . . . . . . . . . . . . . 107 Terminal voltage 1 (parameter) . . . . . . . . . . . . . . . . 108
PV filter time (parameter) . . . . . . . . . . . . . . . . . . . . 128 Time max. electronics temperature (Parameter) . . . . 181
PV scale lower range (parameter) . . . . . . . . . . 126, 154 Time max. level (Parameter) . . . . . . . . . . . . . . . . . . 180
PV scale upper range (parameter) . . . . . . . . . . 126, 154 Time min. electronics temperature (Parameter) . . . . 182
Time min. level (Parameter) . . . . . . . . . . . . . . . . . . 180
R Tube diameter (Parameter) . . . . . . . . . . . . . . . . . . . . 38
Ramp at echo lost (Parameter) . . . . . . . . . . . . . . . . . . 86
Record map (Parameter) . . . . . . . . . . . . . . . . . . . . . . 92 U
Reference distance (Parameter) . . . . . . . . . . . . . . . . . 83 Unit after linearization (Parameter) . . . . . . . . . . . . . . 57
Reference echo threshold (Parameter) . . . . . . . . . . . . 84 Upper limit 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 194
Relative echo amplitude (Parameter) . . . . . . . . . . . . . 65 Upper limit 2 (Parameter) . . . . . . . . . . . . . . . . . . . . 194
Reset min./max. (Parameter) . . . . . . . . . . . . . . . . . . 181 Used calculation (Parameter) . . . . . . . . . . . . . . . . . . . 66
Reset min./max. 1 (Parameter) . . . . . . . . . . . . . . . . 196
Reset min./max. 2 (Parameter) . . . . . . . . . . . . . . . . 196 V
Reset min./max. temperature (Parameter) . . . . . . . . 182 Value 1 display (Parameter) . . . . . . . . . . . . . . . . . . . 24
Result device check (Parameter) . . . . . . . . . . . . . . . . 185 Value 2 display (Parameter) . . . . . . . . . . . . . . . . . . . 24
Result self check (Parameter) . . . . . . . . . . . . . . . . . . . 85 Value 3 display (Parameter) . . . . . . . . . . . . . . . . . . . 24
Value 4 display (Parameter) . . . . . . . . . . . . . . . . . . . 24
S Value echo lost (Parameter) . . . . . . . . . . . . . . . . . . . . 86
Safety distance (Parameter) . . . . . . . . . . . . . . . . . . . . 88 Value process variable (Parameter) . . . . . . . . . . . . . 183
Sample time 1 (Parameter) . . . . . . . . . . . . . . . . . . . 193
Sample time 2 (Parameter) . . . . . . . . . . . . . . . . . . . 193
Sensor module (Parameter) . . . . . . . . . . . . . . . . . . . . 68
Separator (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 26
Serial number (parameter) . . . . . . . . . . . . . . . . . . . 113
Serial number (Parameter) . . . . . . . . . . . . . . . . . . . 175
Set point status (parameter) . . . . . . . . . . . . . . 154, 166
Set point value (parameter) . . . . . . . . . . . . . . . 153, 165
Signal quality (Parameter) . . . . . . . . . . . . . . . . . . . . . 64
Simulate enabled (parameter) . . . . . . . . . . . . . 134, 145
Simulate status (parameter) . . . . . . . . . . . . . . . 135, 146
Simulate value (parameter) . . . . . . . . . . . . . . . 135, 146
Simulation device alarm (Parameter) . . . . . . . . . . . . 184
Software revision (parameter) . . . . . . . . . . . . . . . . . 112
Start device check (Parameter) . . . . . . . . . . . . . . . . . 184
Start self check (Parameter) . . . . . . . . . . . . . . . . . . . . 85
Static revision (parameter) . . . . 110, 121, 139, 150, 162
Status PROFIBUS Master Config (parameter) . . . . . . 106
Strategy (parameter) . . . . . . . . 110, 121, 139, 150, 162

Endress+Hauser 201
*71217608*
71217608

www.addresses.endress.com