Anda di halaman 1dari 7

Company: Project: Engineering Contractor:

OFFSITES ENGINEERING WORKS


FOR THE ERBIL REFINERY
40,000 B/D EXPANSION PROJECT

Contract no.: 10J01762-01


Company doc. no.: Job no.: 10J01762 Engineering doc. no.:
N/A Sheet 1 of 7 10J01762-ICT-LS-000-002

OFFSITES ENGINEERING WORKS FOR THE


ERBIL REFINERY 40,000 B/D EXPANSION PROJECT

CONTROL SYSTEM I-O LIST

D4 06-06-2012 Re-Approved for Design Nikhilesh Joy Benvenuti


D3 23-12-2011 Re-Approved for Design Lucarelli Pagliardini Cilia
D2 19-09-2011 Re-Approved for Design Lucarelli Pagliardini Cilia
D1 31-08-2011 Re-Approved for Design Lucarelli Pagliardini Cilia
D0 29-07-2011 Approved for Design Lucarelli Pagliardini Cilia
C0 15-04-2011 Issued for Company approval Mariotti Pagliardini Cilia
REV. DATE REVISION TITLE PREPARED CHECKED APPROVED

File name: 10J01762-ICT-LS-000-002-D4 Printed on 6/6/2012


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
CONTROL SYSTEM I-O LIST
Company doc. no.: Rev.: C0 D0 D1 D2 D3 D4 Engineering doc. no.:
Sheet 2 of 7 10J01762-ICT-LS-000-002

System HH, H, L, LL
DCS_1 3#-DCS_LCP-001 (OSBL field I/O cabinet) High High, High, Low, Low Low Thresholds.
Corresponding alarms to be considered
where these fields are filled (i.e. for
Serial a pressure transmitter PAHH, PAH, PAL or
SAO Analog value transferred to an external system PALL alarms).
SDO Digital value transferred to an external system
SAI Analog value received from an external system PID
SDI Digital value received from an external system I Input signal for a control loop
O Output signal for a control loop
Serial To/From
System originating or receiving the serial data Logic
L Signal involved in a logic diagram
Interface
4 - 20 mA 4 - 20 mA Loop Powered 2 wires Alarm
4 - 20 mA LNP 4 - 20 mA 2 wire Loop Not Powered A Signal generating alarm
VFC 1 Voltage Free Contact 24 Vdc 2A A=0 Alarm on contact opened
VFC 2 Voltage Free Contact 230 Vdc 2A A=1 Alarm on contact closed
24 Vdc 24 Vdc Output
230 Vac 230 Vac Output Trip
P.S. Proximity Switch T Signal generating a trip
RTD Three wires RTD
Status
Mode 0=Action/Status
P Permanent Output/Input Indicated action/status corresponds to an
M Momentary Output/Input open contact or not energized condition
1=Action/Status
SPDT Indicated action/status correspond to a
NC Normally Closed Input/Output closed contact or energized condition
NO Normally Opened Input/Output
Examples
Power 1=Open Valve
Instrument or actuator rated power The valve is opened when the output
is energized
Protection
I.S. Intrinsically Safe 1=Valve Opened
A closed contact indicates that the
Loop Conditioning valve is opened
I.R. Interface Relay
L.M. Line Monitoring
G.S. Galvanic separation Logic\loop diagram - Cause & Effect
Reference to relevant drawings (P&ids &
Range Process Control Narrative)
Calibrated range in engineering units

Unit
Signal measurement Units

Notes:

1) All instrument and system tag numbers are preceded by a "3#" prefix.

2) The following Control System I-O list is in accordance with the Rev. D0-D1-D2-D3 of project P&Ids.

File name: 10J01762-ICT-LS-000-002-D4 Printed on 6/6/2012


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
CONTROL SYSTEM I-O LIST
Company doc. no. : Rev.: C0 D0 D1 D2 D3 D4 Engineering doc. no. :
sheet 3 7 of 10J01762-ICT-LS-000-002

Interface
To/From

Protect.

Condit.

Status
Range
Power
Serial

Alarm
Logic
Serial

SPDT
Mode

Loop

Unit

Trip
PID
Index SystemTag InstrumentTag Equipment Service P&ID System DI DO AI AO LL L H HH Logic Diagram Loop Diagram Notes Rev.

1 LI-01E LIT-01E TK-01E crude oil tank level measurement 10J01762-PRO-DW-000-002_1 DCS_1 AI 4-20 mA 0-100 % 3000 3400 13600 14500 L A T I-050; I-051 Threshold values in mm
2 LI-01F LIT-01F TK-01F crude oil tank level measurement 10J01762-PRO-DW-000-002_1 DCS_1 AI 4-20 mA 0-100 % 3000 3400 13600 14500 L A T I-050; I-051 Threshold values in mm

Set point will be defined by Company based


control signal for valve on crude oil B-P- set point = HOLD on tank operating level and pump
3 PIC-053B PV-053B 101A/B recycle line 10J01762-PRO-DW-000-002_1 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
4 PI-053B PIT-053B crude oil pump disch. pressure indic. 10J01762-PRO-DW-000-002_1 DCS_1 AI 4-20 mA 0-30 bar g note) note) I A characteristic curve

MCC-IRP-B101 relay cabinet


5 HSL-101BA (see note) pump B-P-101A, STOP 10J01762-PRO-DW-000-002_1 (see note) DO 24 Vdc P, M ≤2W I.R. 0=STOP I-050 By Ventech D3

B-MCC-007 panel VFC 1 P NO


6 XL-101BA (see note) pump B-P-101A, RUNNING STATUS 10J01762-PRO-DW-000-002_1 (see note) DI 1=RUNNING By Ventech D3

B-MCC-007 panel VFC 1 P NC


7 XA-101BA (see note) pump B-P-101A, FAULT 10J01762-PRO-DW-000-002_1 (see note) DI A 0=FAULT By Ventech D3

8 PAH-101BA PSH-101BA pump B-P-101A sealing system sealing system high pressure (see note) 10J01762-PRO-DW-000-002_1 (see note) DI VFC 1 P NC A 0=ALARM By Ventech D3

MCC-IRP-B101 relay cabinet


9 HSL-101BB (see note) pump B-P-101B, STOP 10J01762-PRO-DW-000-002_1 (see note) DO 24 Vdc P, M ≤2W I.R. 0=STOP I-050 By Ventech D3
B-MCC-008 panel VFC 1 P NO 1=RUNNING
10 XL-101BB (see note) pump B-P-101B, RUNNING STATUS 10J01762-PRO-DW-000-002_1 (see note) DI I-050 By Ventech D3
B-MCC-008 panel VFC 1 P NC 0=FAULT
11 XA-101BB (see note) pump B-P-101B, FAULT 10J01762-PRO-DW-000-002_1 (see note) DI A I-050 By Ventech D3

12 PAH-101BB PSH-101BB pump B-P-101B sealing system sealing system high pressure (see note) 10J01762-PRO-DW-000-002_1 (see note) DI VFC 1 P NC A 0=ALARM I-050 By Ventech D3

MCC-IRP-B101 relay cabinet


13 HSL-101BC (see note) pump B-P-101C, STOP 10J01762-PRO-DW-000-002_1 (see note) DO 24 Vdc P, M ≤2W I.R. 0=STOP I-050 By Ventech D4
B-MCC-008 panel VFC 1 P NO 1=RUNNING
14 XL-101BC (see note) pump B-P-101C, RUNNING STATUS 10J01762-PRO-DW-000-002_1 (see note) DI I-050 By Ventech D4
B-MCC-008 panel VFC 1 P NC 0=FAULT
15 XA-101BC (see note) pump B-P-101C, FAULT 10J01762-PRO-DW-000-002_1 (see note) DI A I-050 By Ventech D4

16 PAH-101BC PSH-101BC pump B-P-101C sealing system sealing system high pressure (see note) 10J01762-PRO-DW-000-002_1 (see note) DI VFC 1 P NC A 0=ALARM I-050 By Ventech D4
17
18 LI-01G LIT-01G TK-01G crude oil tank level measurement 10J01762-PRO-DW-000-002_2 DCS_1 AI 4-20 mA 0-100 % 3000 3400 13600 14500 L A T I-052; I-051 Threshold values in mm
19 LI-01H LIT-01H TK-01H crude oil tank level measurement 10J01762-PRO-DW-000-002_2 DCS_1 AI 4-20 mA 0-100 % 3000 3400 13600 14500 L A T I-052; I-051 Threshold values in mm

Set point will be defined by Company based


control signal for valve on crude oil C-P- set point = HOLD on tank operating level and pump
20 PIC-053C PV-053C 101A/B recycle line 10J01762-PRO-DW-000-002_2 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
21 PI-053C PIT-053C crude oil pump disch. pressure indic. 10J01762-PRO-DW-000-002_2 DCS_1 AI 4-20 mA 0-30 bar g note) note) I A characteristic curve

MCC-IRP-C101 relay cabinet


22 HSL-101CA (see note) pump C-P-101A, STOP 10J01762-PRO-DW-000-002_2 (see note) DO 24 Vdc P, M ≤2W I.R. 0=STOP I-052 By Ventech D3

C-MCC-001 panel VFC 1 P NO 1=RUNNING


23 XL-101CA (see note) pump C-P-101A, RUNNING STATUS 10J01762-PRO-DW-000-002_2 (see note) DI By Ventech D3

C-MCC-001 panel VFC 1 P NC 0=FAULT


24 XA-101CA (see note) pump C-P-101A, FAULT 10J01762-PRO-DW-000-002_2 (see note) DI A By Ventech D3

25 PAH-101CA PSH-101CA pump C-P-101A sealing system sealing system high pressure (see note) 10J01762-PRO-DW-000-002_2 (see note) DI VFC 1 P NC A 0=ALARM By Ventech D3

MCC-IRP-C101 relay cabinet


26 HSL-101CB (see note) pump C-P-101B, STOP 10J01762-PRO-DW-000-002_2 (see note) DO 24 Vdc P, M ≤2W I.R. 0=STOP I-052 By Ventech D3

C-MCC-002 panel VFC 1 P NO 1=RUNNING


27 XL-101CB (see note) pump C-P-101B, RUNNING STATUS 10J01762-PRO-DW-000-002_2 (see note) DI By Ventech D3

C-MCC-002 panel VFC 1 P NC 0=FAULT


28 XA-101CB (see note) pump C-P-101B, FAULT 10J01762-PRO-DW-000-002_2 (see note) DI A By Ventech D3

29 PAH-101CB PSH-101CB pump C-P-101B sealing system sealing system high pressure (see note) 10J01762-PRO-DW-000-002_2 (see note) DI VFC 1 P NC A 0=ALARM By Ventech D3

MCC-IRP-C101 relay cabinet


30 HSL-101CC (see note) pump C-P-101C, STOP 10J01762-PRO-DW-000-002_2 (see note) DO 24 Vdc P, M ≤2W I.R. 0=STOP I-052 By Ventech D4
C-MCC-002 panel VFC 1 P NO 1=RUNNING
31 XL-101CC (see note) pump C-P-101C, RUNNING STATUS 10J01762-PRO-DW-000-002_2 (see note) DI I-052 By Ventech D4
C-MCC-002 panel VFC 1 P NC 0=FAULT
32 XA-101CC (see note) pump C-P-101C, FAULT 10J01762-PRO-DW-000-002_2 (see note) DI A I-052 By Ventech D4

File name: 10J01762-ICT-LS-000-002-D4 Printed on 6/6/2012


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
CONTROL SYSTEM I-O LIST
Company doc. no. : Rev.: C0 D0 D1 D2 D3 D4 Engineering doc. no. :
sheet 4 7 of 10J01762-ICT-LS-000-002

Interface
To/From

Protect.

Condit.

Status
Range
Power
Serial

Alarm
Logic
Serial

SPDT
Mode

Loop

Unit

Trip
PID
Index SystemTag InstrumentTag Equipment Service P&ID System DI DO AI AO LL L H HH Logic Diagram Loop Diagram Notes Rev.

33 PAH-101CC PSH-101CC pump C-P-101C sealing system sealing system high pressure (see note) 10J01762-PRO-DW-000-002_2 (see note) DI VFC 1 P NC A 0=ALARM I-052 By Ventech D4
34
35 LI-02D LIT-02D TK-02D fuel oil tank level measurement 10J01762-PRO-DW-000-003 DCS_1 AI 4-20 mA 0-100 % 900 1200 12800 13600 L A T I-053 Threshold values in mm
36 LI-02E LIT-02E TK-02E fuel oil tank level measurement 10J01762-PRO-DW-000-003 DCS_1 AI 4-20 mA 0-100 % 900 1200 12800 13600 L A T I-053 Threshold values in mm
37 LI-02F LIT-02F TK-02F fuel oil tank level measurement 10J01762-PRO-DW-000-003 DCS_1 AI 4-20 mA 0-100 % 900 1200 12800 13600 L A T I-053 Threshold values in mm

Set point will be defined by Company based


control signal for valve on fuel oil P-2315 set point = HOLD on tank operating level and pump
38 PIC-057 PV-057 A/B/C recycle line 10J01762-PRO-DW-000-003 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
39 PI-057 PIT-057 fuel oil pump disch. pressure indic. 10J01762-PRO-DW-000-003 DCS_1 AI 4-20 mA 0-10 bar g note) note) I A characteristic curve
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
40 HSL-2315A MCC-020 panel pump P-2315A, STOP 10J01762-PRO-DW-000-003 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-053 (0.8...1.1) U N

41 XL-2315A MCC-020 panel pump P-2315A, RUNNING STATUS 10J01762-PRO-DW-000-003 DCS_1 DI VFC 1 P NO 1=RUNNING
42 XA-2315A MCC-020 panel pump P-2315A, FAULT 10J01762-PRO-DW-000-003 DCS_1 DI VFC 1 P NC A 0=FAULT

43 LAH-2315A LSH-2315A pump P-2315A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-003 DCS_1 DI VFC 1 P NC A 0=ALARM

interposing relais provided with MCC panel (coil nominal


voltage rating UN=24VDC; coil normal operating range
44 HSL-2315B MCC-020 panel pump P-2315B, STOP 10J01762-PRO-DW-000-003 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-053 (0.8...1.1) U N

45 XL-2315B MCC-020 panel pump P-2315B, RUNNING STATUS 10J01762-PRO-DW-000-003 DCS_1 DI VFC 1 P NO 1=RUNNING
46 XA-2315B MCC-020 panel pump P-2315B, FAULT 10J01762-PRO-DW-000-003 DCS_1 DI VFC 1 P NC A 0=FAULT
47 LAH-2315B LSH-2315B pump P-2315B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-003 DCS_1 DI VFC 1 P NC A 0=ALARM
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
48 HSL-2315C MCC-020 panel pump P-2315C, STOP 10J01762-PRO-DW-000-003 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-053 (0.8...1.1) U N

49 XL-2315C MCC-020 panel pump P-2315C, RUNNING STATUS 10J01762-PRO-DW-000-003 DCS_1 DI VFC 1 P NO 1=RUNNING
50 XA-2315C MCC-020 panel pump P-2315C, FAULT 10J01762-PRO-DW-000-003 DCS_1 DI VFC 1 P NC A 0=FAULT
51 LAH-2315C LSH-2315C pump P-2315C sealing system sealing system reservoir high level 10J01762-PRO-DW-000-003 DCS_1 DI VFC 1 P NC A 0=ALARM
52
53 HS-050 SOV-050 HV-050 open/close command for valve HV-050 10J01762-PRO-DW-000-004 DCS_1 DO 24 Vdc P ≤8W 1=OPEN VALVE I-051; I-054
54 ZLH-050 ZSH-050 HV-050 limit switch, valve opened 10J01762-PRO-DW-000-004 DCS_1 DI VFC 1 P NO 1=VALVE OPENED
55 ZLL-050 ZSL-050 HV-050 limit switch, valve closed 10J01762-PRO-DW-000-004 DCS_1 DI VFC 1 P NO 1=VALVE CLOSED
crude oil metering system flow FQI-050A Flow
56 FI-050A FIT-050A measurement/totalisation 10J01762-PRO-DW-000-004 DCS_1 AI 4-20 mA see note m3/h totalizer To be defined by Coriolis flowmeter MFR
crude oil metering system flow FQI-050B Flow
57 FI-050B FIT-050B measurement/totalisation 10J01762-PRO-DW-000-004 DCS_1 AI 4-20 mA see note m3/h totalizer To be defined by Coriolis flowmeter MFR
crude oil metering system flow FQI-050C Flow
58 FI-050C FIT-050C measurement/totalisation 10J01762-PRO-DW-000-004 DCS_1 AI 4-20 mA see note m3/h totalizer To be defined by Coriolis flowmeter MFR
PY-058 max signal
59 PI-058A PIT-058A crude oil pressure indication 10J01762-PRO-DW-000-004 DCS_1 AI 4-20 mA 0-4 bar g hold hold hold I L A I-054 (see note) selector voting 1oo2
PY-058 max signal
60 PI-058B PIT-058B crude oil pressure indication 10J01762-PRO-DW-000-004 DCS_1 AI 4-20 mA 0-4 bar g hold hold hold I L A I-054 (see note) selector voting 1oo2

Signal from PY-058 Max signal selector (PI-


058A/ B). Set point will be defined by
control signal for valve on crude oil set point = HOLD Company based on crude oil tank operating
61 PIC-058 PV-058 PY-058 (See note) metering system outlet 10J01762-PRO-DW-000-004 DCS_1 AO 4-20 mA 0-100 % O (see note) level
62
63 LI-04E LIT-04E TK-04E diesel tank level measurement 10J01762-PRO-DW-000-005_1 DCS_1 AI 4-20 mA 0-100 % 800 1200 9600 10200 L A T I-055 Threshold values in mm
64 LI-04F LIT-04F TK-04F diesel tank level measurement 10J01762-PRO-DW-000-005_1 DCS_1 AI 4-20 mA 0-100 % 800 1200 9600 10200 L A T I-055 Threshold values in mm

Set point will be defined by Company based


control signal for valve on diesel fuel P- set point = HOLD on tank operating level and pump
65 PIC-064 PV-064 2314 A/B recycle line 10J01762-PRO-DW-000-005_1 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
66 PI-064 PIT-064 diesel fuel pump disch. pressure indic. 10J01762-PRO-DW-000-005_1 DCS_1 AI 4-20 mA 0-10 bar g note) note) I A characteristic curve
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
67 HSL-2314A MCC-020 panel pump P-2314A, STOP 10J01762-PRO-DW-000-005_1 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-055 (0.8...1.1) U N

68 XL-2314A MCC-020 panel pump P-2314A, RUNNING STATUS 10J01762-PRO-DW-000-005_1 DCS_1 DI VFC 1 P NO 1=RUNNING
69 XA-2314A MCC-020 panel pump P-2314A, FAULT 10J01762-PRO-DW-000-005_1 DCS_1 DI VFC 1 P NC A 0=FAULT

70 LAH-2314A LSH-2314A pump P-2314A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-005_1 DCS_1 DI VFC 1 P NC A 0=ALARM
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
71 HSL-2314B MCC-020 panel pump P-2314B, STOP 10J01762-PRO-DW-000-005_1 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-055 (0.8...1.1) U N

72 XL-2314B MCC-020 panel pump P-2314B, RUNNING STATUS 10J01762-PRO-DW-000-005_1 DCS_1 DI VFC 1 P NO 1=RUNNING
73 XA-2314B MCC-020 panel pump P-2314B, FAULT 10J01762-PRO-DW-000-005_1 DCS_1 DI VFC 1 P NC A 0=FAULT
74 LAH-2314B LSH-2314B pump P-2314B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-005_1 DCS_1 DI VFC 1 P NC A 0=ALARM
75
76 LI-04G LIT-04G TK-04G diesel tank level measurement 10J01762-PRO-DW-000-005_2 DCS_1 AI 4-20 mA 0-100 % 800 1200 10400 11000 L A T I-055 Threshold values in mm
77 LI-04H LIT-04H TK-04H diesel tank level measurement 10J01762-PRO-DW-000-005_2 DCS_1 AI 4-20 mA 0-100 % 800 1200 10400 11000 L A T I-055 Threshold values in mm
78
79 LI-05D LIT-05D TK-05D kero/jet fuel tank level measurement 10J01762-PRO-DW-000-006 DCS_1 AI 4-20 mA 0-100 % 800 1200 9600 10200 L A T I-056 Threshold values in mm
80 LI-05E LIT-05E TK-05E kero/jet fuel tank level measurement 10J01762-PRO-DW-000-006 DCS_1 AI 4-20 mA 0-100 % 800 1200 9600 10200 L A T I-056 Threshold values in mm
81 LI-05F LIT-05F TK-05F kero/jet fuel tank level measurement 10J01762-PRO-DW-000-006 DCS_1 AI 4-20 mA 0-100 % 800 1200 9600 10200 L A T I-065 Threshold values in mm

Set point will be defined by Company based


control signal for valve on kero/jet fuel P- set point = HOLD on tank operating level and pump
82 PIC-068 PV-068 2313 A/B recycle line 10J01762-PRO-DW-000-006 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
83 PI-068 PIT-068 kero/jet fuel pump disch. pressure indic. 10J01762-PRO-DW-000-006 DCS_1 AI 4-20 mA 0-10 bar g note) note) I A characteristic curve

File name: 10J01762-ICT-LS-000-002-D4 Printed on 6/6/2012


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
CONTROL SYSTEM I-O LIST
Company doc. no. : Rev.: C0 D0 D1 D2 D3 D4 Engineering doc. no. :
sheet 5 7 of 10J01762-ICT-LS-000-002

Interface
To/From

Protect.

Condit.

Status
Range
Power
Serial

Alarm
Logic
Serial

SPDT
Mode

Loop

Unit

Trip
PID
Index SystemTag InstrumentTag Equipment Service P&ID System DI DO AI AO LL L H HH Logic Diagram Loop Diagram Notes Rev.

interposing relais provided with MCC panel (coil nominal


voltage rating UN=24VDC; coil normal operating range
84 HSL-2313A MCC-020 panel pump P-2313A, STOP 10J01762-PRO-DW-000-006 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-056 (0.8...1.1) U N

85 XL-2313A MCC-020 panel pump P-2313A, RUNNING STATUS 10J01762-PRO-DW-000-006 DCS_1 DI VFC 1 P NO 1=RUNNING
86 XA-2313A MCC-020 panel pump P-2313A, FAULT 10J01762-PRO-DW-000-006 DCS_1 DI VFC 1 P NC A 0=FAULT
87 LAH-2313A LSH-2313A pump P-2313A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-006 DCS_1 DI VFC 1 P NC A 0=ALARM
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
88 HSL-2313B MCC-020 panel pump P-2313B, STOP 10J01762-PRO-DW-000-006 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-056 (0.8...1.1) U N

89 XL-2313B MCC-020 panel pump P-2313B, RUNNING STATUS 10J01762-PRO-DW-000-006 DCS_1 DI VFC 1 P NO 1=RUNNING
90 XA-2313B MCC-020 panel pump P-2313B, FAULT 10J01762-PRO-DW-000-006 DCS_1 DI VFC 1 P NC A 0=FAULT
91 LAH-2313B LSH-2313B pump P-2313B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-006 DCS_1 DI VFC 1 P NC A 0=ALARM

Set point will be defined by Company based


control signal for valve on kero/jet fuel P- set point = HOLD on tank operating level and pump
92 PIC-116 PV-116 2313C recycle line 10J01762-PRO-DW-000-006 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
93 PI-116 PIT-116 kero/jet fuel pump disch. pressure indic. 10J01762-PRO-DW-000-006 DCS_1 AI 4-20 mA 0-10 bar g note) note) I A characteristic curve
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
94 HSL-2313C MCC-020 panel pump P-2313C, STOP 10J01762-PRO-DW-000-006 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-065 (0.8...1.1) U N

95 XL-2313C MCC-020 panel pump P-2313C, RUNNING STATUS 10J01762-PRO-DW-000-006 DCS_1 DI VFC 1 P NO 1=RUNNING
96 XA-2313C MCC-020 panel pump P-2313C, FAULT 10J01762-PRO-DW-000-006 DCS_1 DI VFC 1 P NC A 0=FAULT
97 LAH-2313C LSH-2313C pump P-2313C sealing system sealing system reservoir high level 10J01762-PRO-DW-000-006 DCS_1 DI VFC 1 P NC A 0=ALARM
98
99 LI-03D LIT-03D TK-03D naphtha tank level measurement 10J01762-PRO-DW-000-007 DCS_1 AI 4-20 mA 0-100 % 800 1200 9600 10200 L A T I-057 Threshold values in mm
100 LI-03E LIT-03E TK-03E naphtha tank level measurement 10J01762-PRO-DW-000-007 DCS_1 AI 4-20 mA 0-100 % 800 1200 9600 10200 L A T I-057 Threshold values in mm

Set point will be defined by Company based


control signal for valve on naphtha P- set point = HOLD on tank operating level and pump
101 PIC-072 PV-072 2212A/B recycle line 10J01762-PRO-DW-000-007 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
102 PI-072 PIT-072 naphtha pump disch. pressure indic. 10J01762-PRO-DW-000-007 DCS_1 AI 4-20 mA 0-20 bar g note) note) I A characteristic curve
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
103 HSL-2212A MCC-020 panel pump P-2212A, STOP 10J01762-PRO-DW-000-007 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-057 (0.8...1.1) U N

104 XL-2212A MCC-020 panel pump P-2212A, RUNNING STATUS 10J01762-PRO-DW-000-007 DCS_1 DI VFC 1 P NO 1=RUNNING
105 XA-2212A MCC-020 panel pump P-2212A, FAULT 10J01762-PRO-DW-000-007 DCS_1 DI VFC 1 P NC A 0=FAULT
106 LAH-2212A LSH-2212A pump P-2212A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-007 DCS_1 DI VFC 1 P NC A 0=ALARM
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
107 HSL-2212B MCC-020 panel pump P-2212B, STOP 10J01762-PRO-DW-000-007 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-057 (0.8...1.1) U N

108 XL-2212B MCC-020 panel pump P-2212B, RUNNING STATUS 10J01762-PRO-DW-000-007 DCS_1 DI VFC 1 P NO 1=RUNNING
109 XA-2212B MCC-020 panel pump P-2212B, FAULT 10J01762-PRO-DW-000-007 DCS_1 DI VFC 1 P NC A 0=FAULT
110 LAH-2212B LSH-2212B pump P-2212B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-007 DCS_1 DI VFC 1 P NC A 0=ALARM
111
112 LI-03F LIT-03F TK-03F HDT naphtha tank level measurement 10J01762-PRO-DW-000-008 DCS_1 AI 4-20 mA 0-100 % 2000 2400 9600 10200 L A T I-058 Threshold values in mm

Set point will be defined by Company based


control signal for valve on HDT naphtha P- set point = HOLD on tank operating level and pump
113 PIC-076 PV-076 2213A/B recycle line 10J01762-PRO-DW-000-008 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
114 PI-076 PIT-076 HDT naphtha pump disch. pressure indic. 10J01762-PRO-DW-000-008 DCS_1 AI 4-20 mA 0-20 bar g note) note) I A characteristic curve
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
115 HSL-2213A MCC-020 panel pump P-2213A, STOP 10J01762-PRO-DW-000-008 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-058 (0.8...1.1) U N

116 XL-2213A MCC-020 panel pump P-2213A, RUNNING STATUS 10J01762-PRO-DW-000-008 DCS_1 DI VFC 1 P NO 1=RUNNING
117 XA-2213A MCC-020 panel pump P-2213A, FAULT 10J01762-PRO-DW-000-008 DCS_1 DI VFC 1 P NC A 0=FAULT
118 PAH-2213A PSH-2213A pump P-2213A sealing system sealing system high pressure 10J01762-PRO-DW-000-008 DCS_1 DI VFC 1 P NC A 0=ALARM
119 LAH-2213A LSH-2213A pump P-2213A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-008 DCS_1 DI VFC 1 P NC A 0=ALARM
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
120 HSL-2213B MCC-020 panel pump P-2213B, STOP 10J01762-PRO-DW-000-008 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-058 (0.8...1.1) U N

121 XL-2213B MCC-020 panel pump P-2213B, RUNNING STATUS 10J01762-PRO-DW-000-008 DCS_1 DI VFC 1 P NO 1=RUNNING
122 XA-2213B MCC-020 panel pump P-2213B, FAULT 10J01762-PRO-DW-000-008 DCS_1 DI VFC 1 P NC A 0=FAULT
123 PAH-2213B PSH-2213B pump P-2213B sealing system sealing system high pressure 10J01762-PRO-DW-000-008 DCS_1 DI VFC 1 P NC A 0=ALARM
124 LAH-2213B LSH-2213B pump P-2213B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-008 DCS_1 DI VFC 1 P NC A 0=ALARM
125
126 LI-012E LIT-012E TK-012E gasoline tank level measurement 10J01762-PRO-DW-000-009_1 DCS_1 AI 4-20 mA 0-100 % 2000 2400 9600 10200 L A T I-059 Threshold values in mm
127 LI-012F LIT-012F TK-012F gasoline tank level measurement 10J01762-PRO-DW-000-009_1 DCS_1 AI 4-20 mA 0-100 % 2000 2400 9600 10200 L A T I-059 Threshold values in mm

Set point will be defined by Company based


control signal for valve on gasoline P- set point = HOLD on tank operating level and pump
128 PIC-080 PV-080 2312A/B recycle line 10J01762-PRO-DW-000-009_1 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
129 PI-080 PIT-080 gasoline pump disch. pressure indic. 10J01762-PRO-DW-000-009_1 DCS_1 AI 4-20 mA 0-10 bar g note) note) I A characteristic curve
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
130 HSL-2312A MCC-020 panel pump P-2312A, STOP 10J01762-PRO-DW-000-009_1 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-059 (0.8...1.1) U N

131 XL-2312A MCC-020 panel pump P-2312A, RUNNING STATUS 10J01762-PRO-DW-000-009_1 DCS_1 DI VFC 1 P NO 1=RUNNING
132 XA-2312A MCC-020 panel pump P-2312A, FAULT 10J01762-PRO-DW-000-009_1 DCS_1 DI VFC 1 P NC A 0=FAULT
133 PAH-2312A PSH-2312A pump P-2312A sealing system sealing system high pressure 10J01762-PRO-DW-000-009_1 DCS_1 DI VFC 1 P NC A 0=ALARM
134 LAH-2312A LSH-2312A pump P-2312A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-009_1 DCS_1 DI VFC 1 P NC A 0=ALARM

File name: 10J01762-ICT-LS-000-002-D4 Printed on 6/6/2012


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
CONTROL SYSTEM I-O LIST
Company doc. no. : Rev.: C0 D0 D1 D2 D3 D4 Engineering doc. no. :
sheet 6 7 of 10J01762-ICT-LS-000-002

Interface
To/From

Protect.

Condit.

Status
Range
Power
Serial

Alarm
Logic
Serial

SPDT
Mode

Loop

Unit

Trip
PID
Index SystemTag InstrumentTag Equipment Service P&ID System DI DO AI AO LL L H HH Logic Diagram Loop Diagram Notes Rev.

interposing relais provided with MCC panel (coil nominal


voltage rating UN=24VDC; coil normal operating range
135 HSL-2312B MCC-020 panel pump P-2312B, STOP 10J01762-PRO-DW-000-009_1 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-059 (0.8...1.1) U N

136 XL-2312B MCC-020 panel pump P-2312B, RUNNING STATUS 10J01762-PRO-DW-000-009_1 DCS_1 DI VFC 1 P NO 1=RUNNING
137 XA-2312B MCC-020 panel pump P-2312B, FAULT 10J01762-PRO-DW-000-009_1 DCS_1 DI VFC 1 P NC A 0=FAULT
138 PAH-2312B PSH-2312B pump P-2312B sealing system sealing system high pressure 10J01762-PRO-DW-000-009_1 DCS_1 DI VFC 1 P NC A 0=ALARM
139 LAH-2312B LSH-2312B pump P-2312B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-009_1 DCS_1 DI VFC 1 P NC A 0=ALARM
140
141 LI-012G LIT-012G TK-012G gasoline tank level measurement 10J01762-PRO-DW-000-009_2 DCS_1 AI 4-20 mA 0-100 % 2000 2400 9600 10200 L A T I-059 Threshold values in mm
142 LI-012H LIT-012H TK-012H gasoline tank level measurement 10J01762-PRO-DW-000-009_2 DCS_1 AI 4-20 mA 0-100 % 2000 2400 9600 10200 L A T I-059 Threshold values in mm
143
144 LI-06C LIT-06C TK-06C slop tank level measurement 10J01762-PRO-DW-000-010 DCS_1 AI 4-20 mA 0-100 % 800 1200 9600 10200 L A T I-060 Threshold values in mm
145 LI-06D LIT-06D TK-06D slop tank level measurement 10J01762-PRO-DW-000-010 DCS_1 AI 4-20 mA 0-100 % 800 1200 9600 10200 L A T I-060 Threshold values in mm

Set point will be defined by Company based


control signal for valve on slop tank recycle set point = HOLD on tank operating level and pump
146 PIC-084 PV-084 line 10J01762-PRO-DW-000-010 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
147 PI-084 PIT-084 slop pump disch. pressure indic. 10J01762-PRO-DW-000-010 DCS_1 AI 4-20 mA 0-10 bar g note) note) I A characteristic curve
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
148 HSL-2613A MCC-020 panel pump P-2613A, STOP 10J01762-PRO-DW-000-010 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-060 (0.8...1.1) U N

149 XL-2613A MCC-020 panel pump P-2613A, RUNNING STATUS 10J01762-PRO-DW-000-010 DCS_1 DI VFC 1 P NO 1=RUNNING
150 XA-2613A MCC-020 panel pump P-2613A, FAULT 10J01762-PRO-DW-000-010 DCS_1 DI VFC 1 P NC A 0=FAULT
151 LAH-2613A LSH-2613A pump P-2613A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-010 DCS_1 DI VFC 1 P NC A 0=ALARM
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
152 HSL-2613B MCC-020 panel pump P-2613B, STOP 10J01762-PRO-DW-000-010 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-060 (0.8...1.1) U N

153 XL-2613B MCC-020 panel pump P-2613B, RUNNING STATUS 10J01762-PRO-DW-000-010 DCS_1 DI VFC 1 P NO 1=RUNNING
154 XA-2613B MCC-020 panel pump P-2613B, FAULT 10J01762-PRO-DW-000-010 DCS_1 DI VFC 1 P NC A 0=FAULT
155 LAH-2613B LSH-2613B pump P-2613B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-010 DCS_1 DI VFC 1 P NC A 0=ALARM

156
Threshold values in mm. Where two values
are given for a threshold, the former is
12000 / 12400 / relevant to utility water service, the latter to
157 LI-2511 LIT-2511 TK-2511 firewater tank level measurement 10J01762-PRO-DW-000-012_1 DCS_1 AI 4-20 mA 0-100 % 1200 11500 15000 L A T I-066 firewater service.
158 XL-2513 MCC-020 panel pump P-2513, RUNNING STATUS 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NO 1=RUNNING
159 XA-2513 MCC-020 panel pump P-2513, FAULT 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NC A 0=FAULT
hold hold Set point will be defined by Company based
control signal for valve on firewater tank (see (see set point = HOLD on tank operating level and pump
160 PIC-120 PV-120 recycle line 10J01762-PRO-DW-000-012_1 DCS_1 AO 4-20 mA 0-100 % note) note) O (see note) characteristic curve
hold hold Set point will be defined by Company based
(see (see on tank operating level and pump
161 PI-120 PIT-120 utility water pump disch. pressure indic. 10J01762-PRO-DW-000-012_1 DCS_1 AI 4-20 mA 0-20 bar g note) note) I A characteristic curve
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
162 HSL-2401A MCC-020 panel pump B-P-2401A, STOP 10J01762-PRO-DW-000-012_1 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-066 (0.8...1.1) U N

163 XL-2401A MCC-020 panel pump B-P-2401A, RUNNING STATUS 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NO 1=RUNNING
164 XA-2401A MCC-020 panel pump B-P-2401A, FAULT 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NC A 0=FAULT

To be confirmed later, once pump sealing


system typology will be defined from
165 PAH-2401A PSH-2401A pump B-P-2401A sealing system sealing system high pressure 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NC A 0=ALARM Company

To be confirmed later, once pump sealing


system typology will be defined from
166 LAH-2401A LSH-2401A pump B-P-2401A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NC A 0=ALARM Company
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
167 HSL-2401B MCC-020 panel pump B-P-2401B, STOP 10J01762-PRO-DW-000-012_1 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-066 (0.8...1.1) U N

168 XL-2401B MCC-020 panel pump B-P-2401B, RUNNING STATUS 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NO 1=RUNNING
169 XA-2401B MCC-020 panel pump B-P-2401B, FAULT 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NC A 0=FAULT

To be confirmed later, once pump sealing


system typology will be defined from
170 PAH-2401B PSH-2401B pump B-P-2401B sealing system sealing system high pressure 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NC A 0=ALARM Company

To be confirmed later, once pump sealing


system typology will be defined from
171 LAH-2401B LSH-2401B pump B-P-2401B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-012_1 DCS_1 DI VFC 1 P NC A 0=ALARM Company
172
173 XL-2512A LCP-2512A jockey p. P-2512A, RUNNING STATUS 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=RUNNING
174 XA-2512A LCP-2512A jockey p. P-2512A, FAULT 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NC A 0=FAULT
175 YI-2512A LCP-2512A jockey P-2512A, AUTO START/STOP 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=AUTO
176 XL-2512B LCP-2512B jockey p. P-2512B, RUNNING STATUS 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=RUNNING
177 XA-2512B LCP-2512B jockey p. P-2512B, FAULT 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NC A 0=FAULT
178 YI-2512B LCP-2512B jockey P-2512B, AUTO START/STOP 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=AUTO
firewater diesel main pump P-2122A,
179 XL-2122A LCP-2122A RUNNING STATUS 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=RUNNING
firewater diesel main pump P-2122A,
180 XA-2122A LCP-2122A FAULT 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NC A 0=FAULT

181 YI-2122A LCP-2122A firewater diesel main pump P-2122A, TEST 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=TEST
firewater diesel main pump P-2122B,
182 XL-2122B LCP-2122B RUNNING STATUS 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=RUNNING

File name: 10J01762-ICT-LS-000-002-D4 Printed on 6/6/2012


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
CONTROL SYSTEM I-O LIST
Company doc. no. : Rev.: C0 D0 D1 D2 D3 D4 Engineering doc. no. :
sheet 7 7 of 10J01762-ICT-LS-000-002

Interface
To/From

Protect.

Condit.

Status
Range
Power
Serial

Alarm
Logic
Serial

SPDT
Mode

Loop

Unit

Trip
PID
Index SystemTag InstrumentTag Equipment Service P&ID System DI DO AI AO LL L H HH Logic Diagram Loop Diagram Notes Rev.

firewater diesel main pump P-2122B,


183 XA-2122B LCP-2122B FAULT 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NC A 0=FAULT

184 YI-2122B LCP-2122B firewater diesel main pump P-2122B, TEST 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=TEST
firewater diesel main pump P-2122A,
185 YA-2122A LCP-2122A GENERAL ALARM 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NC 0= GENERAL ALARM
firewater diesel main pump P-2122B,
186 YA-2122B LCP-2122B GENERAL ALARM 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NC 0= GENERAL ALARM
firewater diesel main pump P-2122C,
187 YA-2122C LCP-2122C GENERAL ALARM 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NC 0= GENERAL ALARM
firewater diesel main pump P-2122C,
188 XL-2122C LCP-2122C RUNNING STATUS 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=RUNNING
firewater diesel main pump P-2122C,
189 XA-2122C LCP-2122C FAULT 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NC A 0=FAULT
firewater diesel main pump P-2122C,
190 YI-2122C LCP-2122C TEST 10J01762-PRO-DW-000-012_2 DCS_1 DI VFC 1 P NO 1=TEST
191
192 LI-1101 LIT-1101 TK-1101 sour water tank level measurement 10J01762-PRO-DW-000-015 DCS_1 AI 4-20 mA 0-100 % 600 800 3200 3400 L A T I-064 Threshold values in mm

hold hold Set point will be defined by Company based


(see (see on tank operating level and pump
193 PI-113 PIT-113 sour water pump disch. pressure indic. 10J01762-PRO-DW-000-015 DCS_1 AI 4-20 mA 0-10 bar g note) note) A characteristic curve

Set point will be defined by Company based


control signal for valve on sour water tank set point = HOLD on tank operating level and pump
194 PIC-113 PV-113 recycle line 10J01762-PRO-DW-000-015 DCS_1 AO 4-20 mA 0-100 % O (see note) characteristic curve
hold hold
(see (see Set point will be defined by Company based
195 PI-114 PIT-114 sour water tank pressure indic. 10J01762-PRO-DW-000-015 DCS_1 AI 4-20 mA 0-0.6 bar g note) note) A on tank operating level
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
196 HSL-1105A MCC-020 panel pump P-1105A, STOP 10J01762-PRO-DW-000-015 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-064 (0.8...1.1) U N

197 XL-1105A MCC-020 panel pump P-1105A, RUNNING STATUS 10J01762-PRO-DW-000-015 DCS_1 DI VFC 1 P NO 1=RUNNING
198 XA-1105A MCC-020 panel pump P-1105A, FAULT 10J01762-PRO-DW-000-015 DCS_1 DI VFC 1 P NC A 0=FAULT
199 PAH-1105A PSH-1105A pump P-1105A sealing system sealing system high pressure 10J01762-PRO-DW-000-015 DCS_1 DI VFC 1 P NC A 0=ALARM
200 LAH-1105A LSH-1105A pump P-1105A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-015 DCS_1 DI VFC 1 P NC A 0=ALARM
interposing relais provided with MCC panel (coil nominal
voltage rating UN=24VDC; coil normal operating range
201 HSL-1105B MCC-020 panel pump P-1105B, STOP 10J01762-PRO-DW-000-015 DCS_1 DO 24 Vdc P, M ≤2W I.R. (see note) 0=STOP I-064 (0.8...1.1) U N

202 XL-1105B MCC-020 panel pump P-1105B, RUNNING STATUS 10J01762-PRO-DW-000-015 DCS_1 DI VFC 1 P NO 1=RUNNING
203 XA-1105B MCC-020 panel pump P-1105B, FAULT 10J01762-PRO-DW-000-015 DCS_1 DI VFC 1 P NC A 0=FAULT
204 PAH-1105B PSH-1105B pump P-1105B sealing system sealing system high pressure 10J01762-PRO-DW-000-015 DCS_1 DI VFC 1 P NC A 0=ALARM
205 LAH-1105B LSH-1105B pump P-1105B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-015 DCS_1 DI VFC 1 P NC A 0=ALARM
206

207 XL-2617A MCC-020 panel pump P-2617A, RUNNING STATUS 10J01762-PRO-DW-000-016 DCS_1 DI VFC 1 P NO 1=RUNNING

208 XA-2617A MCC-020 panel pump P-2617A, FAULT 10J01762-PRO-DW-000-016 DCS_1 DI VFC 1 P NC A 0=FAULT

209 XL-2617B MCC-020 panel pump P-2617B, RUNNING STATUS 10J01762-PRO-DW-000-016 DCS_1 DI VFC 1 P NO 1=RUNNING

210 XA-2617B MCC-020 panel pump P-2617B, FAULT 10J01762-PRO-DW-000-016 DCS_1 DI VFC 1 P NC A 0=FAULT

211 XL-2617C MCC-020 panel pump P-2617C, RUNNING STATUS 10J01762-PRO-DW-000-016 DCS_1 DI VFC 1 P NO 1=RUNNING

212 XA-2617C MCC-020 panel pump P-2617C, FAULT 10J01762-PRO-DW-000-016 DCS_1 DI VFC 1 P NC A 0=FAULT
213 LAH-2617A LSH-2617A pump P-2617A sealing system sealing system reservoir high level 10J01762-PRO-DW-000-016 DCS_1 DI VFC 1 P NC A 0=ALARM
214 LAH-2617B LSH-2617B pump P-2617B sealing system sealing system reservoir high level 10J01762-PRO-DW-000-016 DCS_1 DI VFC 1 P NC A 0=ALARM
215 LAH-2617C LSH-2617C pump P-2617C sealing system sealing system reservoir high level 10J01762-PRO-DW-000-016 DCS_1 DI VFC 1 P NC A 0=ALARM
216
217 LI-2414 LIT-2414 TK-2414 plant fuel tank level measurement 10J01762-PRO-DW-000-018 DCS_1 AI 4-20 mA 0-100 % 600 1000 6400 6800 A Threshold values in mm
218 LI-2416 LIT-2416 TK-2416 plant fuel tank level measurement 10J01762-PRO-DW-000-018 DCS_1 AI 4-20 mA 0-100 % 600 1000 6400 6800 A Threshold values in mm
219
220
221
222
223
224

File name: 10J01762-ICT-LS-000-002-D4 Printed on 6/6/2012

Anda mungkin juga menyukai