Anda di halaman 1dari 10

MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

RELIABLE UNDERGROUNDING OF ELECTRICITY SUPPLY IN ASIA

Ken. W. BARBER & Hilary MARAZZATO


Olex Australia Pty Ltd
kbarber@olex.com.au & hmarazza@olex.com.au

ABSTRACT Selecting the best cable and installation 3.1.1 Conductors are required to carry the “Current” and
conditions taking account of the environment and customer hence these are Copper or Aluminium. In most cases
needs, is a key challenge for cable designers and utility asset conductors are stranded but for LV distribution, solid
managers. aluminium sector shaped conductors are often used. The
In South East Asia there has been a ready acceptance of question of whether these conductors need to be “water-
XLPE for Power Distribution and Transmission cables but the blocked” will be addressed in this paper. The choice of
‘in-service’ performance has not been without problems. copper or aluminium depends on the economics of the system
With the increasing demands by consumers for a better and connections required.
environment and much greater system reliability of supply,
utilities throughout the region are grappling with the 3.1.2 Insulation is required to maintain the “Voltage” and
inevitable increase in demand for undergrounding and the today the predominant material for nearly all Distribution and
need to improve the overall performance of this expensive Transmission voltages is XLPE. We will discuss the type of
asset. The challenge is how to do this in the most cost XLPE available. For Medium and High Voltage cables the
effective manner but avoid the mistakes made with some insulation is sandwiched between layers of semi-conductive
underground installations having limited service life. material to avoid ionisation and premature breakdown of the
This paper proposes to outline a number of issues and insulation under the influence of electrical stress.
solutions in this regard with particular emphasis on the South
East Asian region where the performance of underground 3.1.3 Protection is required for the “Environment” and
cable systems is currently under review. operation of the cable. This includes the provision of screens
to carry earth fault currents and “sheathing” or “jacketing” to
1.0 INTRODUCTION protect the cable during installation and service under various
operating conditions and environments.
In the past, the higher costs for underground services and the
restrictions on the use of overhead lines, limited demand for 3.2 XLPE Cables
underground power cables. The rapid growth in After the introduction of XLPE cables in the USA, there
infrastructure throughout South East Asia has been the were very serious problems with cable failures in the late
catalyst for change. During the past twenty (20) years there 1960’s and early 1970’s. Whilst some were due to
has been major use of XLPE insulated underground cable. incompatible semi-conductive materials and lack of triple
However, despite having had the advantage of learning from extrusion, most were due to water ingress, and treeing in
the mistakes made in the USA in the 60’s and 70’s, and the steam cured XLPE. Because XLPE cables were not
access to modern plants and materials, performance has in introduced into Australasia and South East Asia region until
some cases, been less than expected. the late 1970’s, we were very fortunate to be able to learn
from problems encountered in the USA and cable experts
2.0 FACTORS AFFECTING PERFORMANCE OF visiting from the USA are often surprised to learn of the good
CABLES IN SERVICE performance of the underground XLPE cables in this region
[10,11].
There are four main factors affecting performance of Most cable manufactured
underground cables, they are:- in the region has been
• Design, materials and processes produced on dry cure cable
• Testing and Quality Control manufacturing facilities
• Installation and accessories using highly effective cable
• Service conditions designs incorporating high
In the following sections it is proposed to address these issues performance cable sheaths.
and make recommendations for improved underground cable The excellent electrical
performance. Typical state-of-the-art performance of XLPE is the
Catenary Continuous reason it is now used
3.0 DESIGN, MATERIAL AND PROCESS ISSUES Vulcanisation (CCV) Line almost exclusively for the
insulation of all LV, HV
3.1 Cable Design Insulated power cables are constructed and EHV distribution and transmission cables. However,
with 3 basic components. whilst XLPE has far better resistance to moisture permeation
than Paper insulation or PVC, moisture can affect long term
performance of XLPE
MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

under the influence of high electrical stress so the overall is significantly better than the PVC, tests showing a moisture
features in the cable design are vitally important. level found after days in water with PVC is only achieved
with HDPE after many years [1].
3.3 Description of moisture mode of failure
We all know that Paper/Oil insulation must be kept dry, but Nevertheless, moisture vapour does eventually penetrate into
many people initially felt that special precautions were not cables, so it is recommended that moisture swellable tapes be
necessary for XLPE insulation. used under the sheath. These water-blocking tapes are often
The very first XLPE cables were produced on Steam Cure made out of a one-layer non-woven carrier, a layer of
CV (Continuous Vulcanisation) lines where moisture swellable powder and a water-soluble binder. All the
saturated the insulation due to the temperature and pressure swelling powder is bound into the tape thereby reducing the
of the steam (~200 degC, 200 psi). Pressure is required when risk of airborne dust.
cross-linking polyethylene
with dicumyl peroxide to Only when under the influence of moisture, does the water-
prevent void formation due soluble binder release the water-blocking powder. In this way
to the formation of volatile the super-absorbent material is free to swell and move into
cross-linking by-products. voids and interstices of the cable extremely quickly.
While steam was an Different grades of swellable powders have different degrees
obvious provider of both of response to water, affected by the time taken for the
temperature and pressure, material to swell and hence block the passage of water.
the saturation of the insulation actually created “micro voids”.
The level of moisture in the insulation of cables made by this For power cables, it is important to know that the high
process can be up to 3,000 ppm. Many of these early cables viscosity gel ensures that water-blocking characteristics are
are now showing signs of water trees. For at least the last 25 retained during temperature cycling and that for these tapes,
years, all of the XLPE insulated cables produced in South when used in conjunction with extruded metal sheaths at high
East Asia and Australasia have been processed in a manner temperature and pressure, the water-blocking characteristics
(called ‘Dry Cure’) that ensures that the maximum possible are retained.
water absorption is less than 200 ppm. Very few of these
cables have significant water treeing unless water has been 3.4.2 Preventing the water running along the length of the
allowed to enter into the conductor. cable – ‘Longitudinal Protection’
The subject of water treeing, electrical treeing and subsequent Regardless of the measures taken in the manufacture of the
breakdown is a complex subject , but it can be briefly stated cable, it is not uncommon to find that water has been allowed
that under the influence of electrical stress and the water to enter the cable during installation. This either occurs by
absorbed by the insulation, water trees can grow. Whilst as accident, whereby the pulling end of a cable has been
water trees they may not cause breakdown, in cases where damaged, or by the more common circumstance where the
there is a high stress point or a space charge developed during cable end is simply allowed to rest on site, in the trench, in
DC testing, such trees may develop into electrical trees which ducts, in water, without being capped.
subsequently cause premature breakdown.
Of course, the best way to protect the cable from moisture is
3.4 Modes of protection/prevention to prevent its ingress but there may be occasions when the
There are several modes of preventing the water and moisture cable is damaged by external means or a joint fails in service
penetrating into the cable and travelling within it along the and then water enters the cable at that point. Once the water
length. There are also alternative cable materials that may be has penetrated the cable, the easiest path is for the water to
used. In each case, different measures may be used to protect travel along the cable. Spaces are present in the area of the
the cable. screen wires, in the middle of multicore cables, within the
fillers of multicore cables or even down the conductor.
3.4.1 Prevention of water getting into the cable-“Radial
Protection” The most effective prevention is by filling up those spaces
To prevent water permeating through the cable sheath into used by the water and some cables are made with solid fillers
the cable, the most obvious design technique is the inclusion completely filling all voids. It is common practice in the
of a metal sheath on the cable. The metal sheath provides an USA to also fill any voids in the conductor between the wires.
impervious barrier to entry and provides an extremely dry This practice of using solid fillers has not been adopted
cable for the entire life. Metal sheaths are expensive so are elsewhere as it is quite expensive and typically means a
usually only provided for Transmission, Sub-transmission or significant increase in cost. The use of solid blocking
Submarine cables. materials in conductors also makes conventional connection
In the absence of the metal barrier, there are plastic sheath methods difficult to use.
options but these exhibit significantly different properties.
The most common plastic material in sheathing of cables is
the PVC, but this material allows too much permeation of The lower cost alternative is to use the water swellable tapes,
moisture into the cable. The High Density Polythene (HDPE) which will fill the spaces when the water is present and they
material, chosen by almost all the ESI companies in Australia, then prevent the longitudinal progress of any further water.
MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

This typically only adds 2 - 10% to the cable cost. The


measures have been successful in effectively blocking tears in The most recent information from the USA is that the TR-
the sheaths of cables and limiting any water ingress to the XLPE has improved to the point that the selection of EPR has
immediate area around the tear [2]. Using swellable tapes, been limited to applications where cable flexibility is
yarns or powder to fill conductors is also now widely essential/desirable. An example of such an instance, is where
accepted. However, in this context it is important to consider load-break disconnectors are used and the flexibility of the
the impact of such materials on the type of accessories and cable provides an advantage for the disconnection. The
method of installation of same. economics of TR-XLPE versus EPR show that the TR-XLPE
is a lower cost material. Our information is that the EPR
Another alternative is to adopt solid conductors in place of usage has decreased in the last five years in favour of the TR-
stranded conductors. XLPE.

In the case of single core cables, the application of water It must however be appreciated that putting any fillers or
swellable tapes in the screen area is very effective and does additives, such as those required for tree retardancy, into an
achieve a total cable "block". Even with cables using a insulation is similar to adding a contaminant. Therefore,
corrugated sheath, they can be blocked using current fast whilst the stresses adopted in the design of Medium Voltage
acting swellable materials. cables (6 - 40 kV) enable the use of materials such as TR-
For three core cables, it has been XLPE or EPR, these insulation materials may not be suitable
found that the water swellable tapes for the high stresses required for cables rated for higher
applied at the area of the screens voltages. This is also why those manufacturers experienced
does not limit the progress of water in making HV and EHV Cables with Super clean XLPE,
along the cable as well as it does for continue to supply good quality MV Cables without using
the single core designs, so more TR-XLPE.
material is often required.
3.5 Solutions for various cable types

3.5.1 Low Voltage Cables


Cables designed to function at voltage levels up to 1000 V,
have insulation thicknesses that are well above those required
for purely electrical function. The thicknesses are in fact
increased to provide adequate levels of mechanical robustness
and protection. Given these circumstances, the voltage
stresses in the insulation are very small and inadequate to
3.4.3 Use an insulation material that is not affected by promote the growth of water trees that lead to electrical
moisture / water failure of the cable. Thus, no protection is required from the
The alternative approach to the problem is to use an insulation effects of water or moisture.
system that is not as significantly affected by water trees, so The design life of these cables is 40 years, and the cables are
that electrical trees do not form. The early alternative expected to last much longer when they are installed in
material was the EPR. Due to its opacity, for many years it protected areas. The main cause of failure of such cables is
was thought that water tree growth was not present. More mechanical damage and localised failure.
critical and advanced methods of analysis show that the water
trees do exist [3,4,5]. 3.5.2 Distribution Cables
The electrical stresses in cables designed for operation in
Due to the inherent presence of fillers in the material, it was excess of 5kV is sufficient to promote water tree growth.
found that the water tree was not allowed to progress through Tests on cable samples of 6.35/11kV cables that are known to
the material, once it had reached the interface to such fillers. have had water for some years in the area of the screen wires,
The ingredients therefore acted as limiting constraints on the show a number of water trees present in the insulation,
growth of the water trees. More modern developments in however, in all cases the water trees are small and do not yet
material technology have resulted in the development of Tree present a threat to the electrical stability of the cable. In other
Retardant XLPE, TR-XLPE. This material uses a similar words the stresses are such that electrical trees do not develop
technique as the EPR, in that targeted and effective unless there is a localised cause of high electrical stresses.
ingredients are added to the basic XLPE to act as limiting
constraints to the growth of the water trees. Tests on 12.7/22kV cables that had failed electrically have
revealed an abundance of water trees. These cables were
The examination and analysis of 'tree growth' is far more buried in very wet environments for 10 years to 15 years.
easily done within the transparent XLPE. The extra After 17-19 years in service, the cables had failed electrically.
ingredients have been optimised and perfected so they are DC testing was a regular occurrence as part of maintenance
now effective in the control of water tree growth. Papers, procedures and space charges left by such testing may have
which describe the advantages of TR-XLPE, include some been a significant factor in the failure. Mostly, such cables
interesting comparisons to EPR and 'normal' XLPE [6]. have been produced by the steam curing process, but it can be
MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

taken that electrical stress at this working voltage is sufficient satisfactory for moisture protection in telecommunication
to develop electrical trees. cables and for some distribution cables but its performance on
HV & EHV cables may be questioned, particularly where
3.5.3 Cable Life these cables are installed directly in the ground or in conduits
It is commonly accepted that these XLPE cables are designed or pipes.
for a 40-year life. Provided adverse water and moisture
conditions do not impact on the cable, such a life can be In such cases, there are already reports of extensive water
reasonably expected. In the case of providing an estimate of trees in 132kV cables installed some 15-20 years ago using
cable life where water and moisture adverse conditions may that type of protection. Naturally there may be many causes,
present themselves, then the cable without any protection has but a conservative approach is to specify welded sheaths
a life expectancy of 15-25 years. rather than relying on overlapped tape, unless cables are
installed in dry situations such as tunnels.
When water swellable tapes are used in the region of the
screens, then a greater life expectancy of 20-30 years can be In the early days it was not possible to reliably weld
applied. By the use of insulation materials that resist water aluminium, copper and stainless steels so there was a
tree growth, i.e. by the use of TR-XLPE, then life expectancy preference to specify seamless or extruded aluminium
can be further increased to 30-35 years. The combination of sheaths. However, because it has
the TR-XLPE plus water swellable tapes increases life been found that there are many
expectancy to 35-40 years. cases where these extruded
Aluminium Sheathed cables were
The more secure design option for the cable is to add a metal badly corroded, they are often not
moisture barrier such as a Lead Sheath. This option, XLPE specified. Nowadays, with high
protected by a Lead Sheath, has a life expectancy of 60 years. quality welding technology,
welded corrugated sheaths are
3.5.4 Sub-Transmission & Transmission Cables much more superior having the
It is clear that at voltages of 33kV and above, the voltage advantage that stronger, more
stress on the insulation is quite sufficient to induce the water corrosion resistant materials, can
tree and electrical tree growth. Actual electrical failures for be adopted. Corrugated stainless steel
cables rated 33-275kV have not been seen where and copper are popular for the new
water/moisture protection is specified for such cables. environmentally friendly EHV
transmission cables [7,8]. Welded
At 33kV there is a wide divergence of opinion as to the net Aluminium sheathed cables are being
commercial benefits of adopting the expensive metal sheathed used extensively in China,
designs. As an example, in South Australia 33kV cables have particularly when cables are installed
water swellable tapes in the screen area whereas similar cable in cable ways and tunnels. The
circuits installed in Queensland use Lead Sheathed cable. On welding process is more suited to the
the other hand, most cable at 33kV and below in New design of XLPE Cable as the process
Zealand, are made with the use of TR-XLPE, whereas 33kV avoids the high temperatures which are unavoidable with the
Cables in Malaysia are provided with an Aluminium moisture extrusion process which was originally developed for Paper
barrier tape. Oil Cables. For transmission cable, the more secure design
With the advances in XLPE option therefore, is to add a metal moisture barrier such as
material technology it is extruded lead sheath or a welded sheath to ensure a life
possible to design and expectancy of 50-60 years.
manufacture distribution
cables with thinner wall 4.0 TESTING & QUALITY CONTROL
thicknesses, and consequently
higher stresses, than those Strict Quality Assurance procedures are an essential part of
specified in the current the manufacture of MV, HV and EHV Cables. The slightest
Standards. Currently, it is difficult to take advantage of the contamination, defect or process damage can have a
possible savings for distribution cables because it is not significant effect on the performance of XLPE cables. In the
always possible to produce low cost joints and terminations case of Paper Insulated Cable, any defects in the quality of
which operate reliably with such reduced wall thickness. On materials or processing, is often mitigated by the oil. Whilst
the other hand, for cables rated for 66kV and above, where not understating the importance of ‘in-process’ Quality
more sophisticated joints and terminations are used, and Control and the use of Inspection and Test plans at all stages,
installation is performed by higher skilled staff, it is possible one should not under estimate the value of the final test and
to take advantage of reduced wall thicknesses and we are fortunate today to have very advanced testing
consequently, high stresses. equipment, which when used in a screened room
Nearly all 66 kV cables in Australia are supplied with lead environment, can detect very minor defects.
sheaths. In some countries a moisture barrier of polythene
laminated Aluminium tape is adopted. This has proved very
MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

4.1 H.V. Testing including online temperature monitoring and site facilitation.
In accordance with National and International Standards, Overall costs are reducing with the growing emphasis on
every length of cable must be subjected to HV AC Testing “trench-less” technology, circuit optimisation, improved
and the test levels specified in the IEC (60502 and 60840) backfills, mechanised laying/handling and shared services.
have recently been upgraded. Some manufacturers in Japan, Utilities are increasingly constructing underground common
Australia and Europe, have their own internal Standards with service tunnels or trenches as a means to address growing
higher test levels based on design stress levels. HV AC demand for underground cable infrastructure services.
Testing is a very effective means of determining if a cable is
defect free, but only if the test voltage is of a sufficient level 5.2 Installation methods
depending on the design stress of the cable. Using direct buried cables provides the lowest cost and best
possible ratings. In many countries, particularly in Asia, the
4.2 Partial Discharge Testing restriction on access to roads is such that the only way that
Partial Discharge levels and test procedures in IEC Standards cables can be installed is to first install plastic pipes
should be considered the minimum requirement, based on the (nowadays Polythene for environmental reasons) during the
variability of testing conditions. Some manufacturers night so that cables can be pulled in once a section length is
measure P.D. over the full HV Test range and reject any cable completed. Even in Australia and New Zealand where access
with the slightest indication of P.D. Cables which are tested to roads is not as difficult, the high cost of traffic management
to higher standards rarely fail in service. which is required when a trench is left open often makes the
During routine testing, due to the wall thickness of MV and cost of installing pipe an attractive solution even though a
HV Cable being higher than the minimum for design stresses larger size and thus more expensive cable has to be selected.
of XLPE, most defects are detected by P.D. rather than by HV It is also sometimes argued that by installing pipe or conduit,
failure. As an example, a small cut or contaminate on the a cheaper, less reliable cable design can be adopted as the
surface of an MV cable will not cause HV failure but can be cable can be easily replaced in the event of failure. If cables
detected as a few P.D. and the position located. In practice, are installed in conduits, the conduits may be filled with water
the majority of P.D. defects found during production testing for much of the time and at other times the air space in the
of MV cable, are related to damage during handling and conduit reduces the current rating. In some countries the
processing. conduits are filled with special slurry to restore the rating to
that closer to the direct buried situation but that process is
5.0 CABLE INSTALLATION AND SELECTION OF nowadays not favoured as it introduces many other problems.
ACCESSORIES Overall, it is suggested that it is generally better to select the
correct cable design for the environment and install correctly
In 1993, the Electric Power Research Institute in the USA set to obtain and exceed the cable design life.
as a goal the lowering of the cost of undergrounding both
transmission and distribution cables. The target was a 50% 5.3 Selection of Accessories and their Installation
reduction in cost by the year 2000. This target has been It is found that the weakest link in a circuit is always the
easily achieved with the ratio of overhead to underground accessory and installation.
cost, which was typically 1:20 some 10-12 years ago, now The design materials and manufacture of accessories is
more often less than 1:5. In fact, at the Institute of Electrical essentially different to the cable. Accessories are designed
and Electronic Engineers’ Winter Meeting in Singapore for compatibility with the cable but care must be taken in the
several years ago there was a lively debate on the cost of preparation and fitting so that adequate training is essential.
undergrounding compared to overhead lines. Views from After installation one needs to consider the appropriateness of
around the world varied with representatives from the United testing the circuit. An example is the previous practice of
Kingdom suggesting 16 to 20 times and those from using a DC test, where such a test is totally incapable of
Scandinavia suggesting it was closer to two times. Clearly the reproducing the same field in the accessory and the cable as
ratio is dependent on the voltage level, the power an AC voltage produces, and leads to undesirable space
transmission requirement and length of line, thus it is vital to charges being left at the accessory/cable interface, which may
consider all factors when making such an assessment. In cause damage when the circuit is later energised with A.C.
most cases, because of the slower time/temperature response Most circuit failures initially occur at accessories. These
of underground cables, it is not necessary to rate failed accessories may then allow water to enter the cable
underground line at the same full continuous rating as which may promote failure to the cable after new accessories
overhead line. are fitted.

5.1 Undergrounding now more cost-effective 6.0 SERVICE CONDITIONS WHICH REDUCE CABLE
So what are the factors which are driving down the cost of LIFE
underground cabling? First, cable costs have reduced in real
terms with the development of cheaper high quality materials, 6.1 Voltage surges
faster processing and reduced insulation thickness. Typically As with any electrical insulation, life expectancy is reduced
cable costs made up 50% of the cost for transmission cable when the insulation is subjected to ‘over voltage’, in the form
projects and 25% of distribution projects. Today, the key of surges and impulses. It is recommended that appropriate
factors are construction methods coupled with system design protection devices be installed and the nature and frequency
MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

of all such occurrences should be monitored and recorded, so combination of cable design and system design features,
that protective measures can be installed. installation methods and the myriad of operating
circumstances that the system is exposed to throughout its
6.2 Excess operating temperatures lifetime, as well as the criteria used for defining end of life.
Cables are designed for a maximum operating temperature of
90°C with limited overload periods as defined in the relevant Overloading (overheating), over voltage, ground or support
Standard. Changes in the environment, for example, depth of movement, vibration, mechanical abuse/damage, water
cover, adjacent services and micro biological effects in the immersion etc., will all have a deleterious effect, which will
soil, can increase operating temperatures and thus reduce possibly be cumulative and may, depending on severity, cause
cable life. The circuit protection system also needs to ensure immediate failure in one extreme, or an imperceptible
adequate protection from excess current loading. The nature shortening of life on the other.
of frequency of all such occurrences should be monitored and
recorded. We would confidently predict cable lifetimes of at least 40
years for any modern XLPE insulated cable, and would
To protect the investment and ensure the life of the cable, suggest that 60 years is not an unreasonable expectation if the
continuous monitoring of all key circuits using DTS should be cables are correctly designed, installed and operated. This is
adopted whenever the reliability of these circuits is a critical particularly so for those cable designs utilising water blocking
issue [9,12]. measures or where there is a welded or extruded corrosion
resistant moisture barrier.
6.3 Adverse environmental conditions
Environmental conditions can adversely affect the conditions Condition monitoring by DTS and the adoption of other
for the cable. As mentioned above, microbiological effects condition monitoring technologies as they become available,
from fungus and bacteria can induce increases in soil are recommended as they will help ensure maximum lifetime
temperature thus affecting the temperature of the cable and is achieved.
causing unseen overloads. Increases in the thermal
conductivity of the soil must be monitored and recorded. Cable manufacturer’s today are often able to offer a complete
service in terms of cable and accessory supply, system design,
6.4 Poor installation practices project management, installation and on-line remote
The lifetime of cables is very much dependant on the cable monitoring all focused on providing long term performance of
being installed correctly. Supervision/management and the cable system, and are keen to provide recommendations
adverse installation conditions may cause the cable to be for any specific installation. In the attached Appendix 1, we
damaged, over tensioned, twisted, bending radii exceeded, have listed some of the many questions that may need to be
excessive sidewall pressure induced, over compaction of addressed in selecting the best cable design for a project [13].
backfill and other life threatening factors.
REFERENCES
6.5 Compatibility of design for cable and accessories
Poor co-ordination of designs will result in incorrect or [1] Guerts, Steennis, Poorts, Meijer, Kema Netherlands,
incompatible accessories, fixing methods, stresses induced by “Water diffusion through sheaths and its effects on
mechanical vibration, thermal movement and lack of cable constructions”, JICABLE, Versailles, 1995.
compensation for seismic conditions.
[2] Barber, Olex Australia, “Underground MV Cable
Although the materials used are selected to ensure their long Design”, Workshop 19, D2000, Sydney, November
term resistance to UV and environmental stress cracking, it is 1997.
essential that correct methods of fixing and environmental
assessment be undertaken to ensure the materials are not [3] Katz, Walker, Cable Technology Laboratories, New
subjected to unforseen or unexpected stresses in service. Jersey, “Evaluation of service aged EPR cables”,
International Wire and Cable Symposium
7.0 CONCLUSION Proceedings, 1994.

XLPE insulated cables have only been in existence for a [4] Xu, Gorton, University of Conneticut, “The
relatively short time, so a guaranteed lifetime is difficult to chemical composition of water trees in EPR cable
assign without a clear knowledge of operating conditions. As insulation”, IEEE Transactions on Dielectrics and
indicated above, defining an end of life for such cable Electrical Insulation, Volume 1 No:1, 1994.
systems is subject to many factors and questions. Most of
these questions do not have a definitive answer, but we [5] Uematsu, Iwata, Irie, Fujii, The Furukawa Electric
certainly can say that technology has greatly improved since Co., Japan “Bow-tie-tree in EPR cables after
the early XLPE insulated cables, and the problems these early accelerated water treeing test”, IEEE Transactions
cables began to exhibit after 20 years or so in service have on Power Delivery, Volume 7 No:4, 1992.
been addressed. New designs will not experience such
problems. Ultimately, cable lifetime will be determined by a
MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

Ken Barber, General Manager –Engineering and


[6] Caronia, Furno, Pong, Szaniszlo, Union Carbide International Sales - Olex Australia
Corp, New Jersey, “Advances in TR- XLPE Ken Barber has been directly involved
insulation", IEEE Transmission and Distribution in the cable sector for almost 40 years,
Conference, New Orleans, 1999 having worked in the United Kingdom,
India, Malaysia and Australia. He has
[7] Barber, Olex Australia, “Moisture Barrier been responsible for Olex Cables’
Protection Screening & Armouring for HV & EHV development program in the past 28
Cable”, presented at IPEC, Singapore 1993. years, including EHV cable
manufacture/installation. He has been
[8] Barber, Olex Australia, ‘Environmentally friendly actively involved in the preparation of
HV transmission systems”, 11th CEPSI cable standards for most of that time
Conference, Malaysia 1996. and since 1984 has been Chairman of the Australian
Standards Committee for Insulated cables. Ken has for many
[9] Barber, Olex Australia, “New Technology in years, been a member of various international organizations
Transmission Networks provides greater capacity supporting the cable industry and is currently the Australian
with better system reliability”, presented at representative on CIGRE Study Committee B1 - High
AESIEAP CEO’s Conference, Cebu, Philippines, Voltage Cables and company representative on other
1999. organizations such as AESIEAP.
He can be contacted at kbarber@olex.com.au
[10] Barber, Olex Australia, “Undergrounding
Transmission and Distribution Lines” Hilary Marazzato, Engineering Manager - Cable Design
Australian Power Transmission & Distribution and Applications – Olex Australia
Magazine, 2002. Hilary started with Olex Cables in
1979 within the Technical
[11] Barber, Marazzato, Olex Australia, “Designs & Department, and has held a range of
Reliability of Underground Cables and positions in the Technical and
Systems” Australian Power Transmission & Engineering functions, including
Distribution Magazine, 2003. software development, production
process development, management of the Electrical Test
[12] Barber, Barnewall, Olex Australia, “Condition facilities, and supervision of the QA functions. He has also
Monitoring” Australian Power Transmission &
held the positions of Logistics Manager and Customer
Distribution Magazine, April 2003.
Services Manager. During the 1990's, Hilary was the
Engineering Manager for Energy Cables with responsibility
[13] Barber, Olex Australia, “The Challenge for
Undergrounding Electricity Supply” Pacific to manage product design and development. Since 1998,
Power Association, Fiji August 2004. Hilary has had the responsibility for Cable Design and
Applications.
Throughout this time Hilary has been involved with
Standards Australia in the preparation of cable standards for
high voltage and industrial/mining cables and is the
Australian member of the IEC Working Group for power
cables.
Hilary is author of several papers covering high voltage cable
design and applications, both for underground and for aerial
installations.
Hilary is an Electrical Engineer who has also completed a
Graduate Diploma in Manufacturing Management and an
MBA with RMIT.
MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

APPENDIX 1.
(Issues should be discussed at a cable workshop or project review)

Review of specific cable and accessory designs to achieve better performance

1. Waterblocking of Conductors

Question: Should conductors for underground cables be water-blocked to avoid water travelling
along the cable?

Problem appears to be at the time of installation when the cable is cut but appropriate end caps are not
fitted. Also, if a cable fault occurs due to damage or failure of a joint. This is a serious problem in
tropical areas. This has not been of concern to Supply Authorities in the past because appropriate work
practices have insisted on cables having special mastic filled heat shrink caps applied, however problems
are occurring with increasing use of contractors, or poorly trained staff. Similar problems have occurred
in the USA which has lead to significant demand for water-blocking of underground cables in that
country. This applies to both copper and aluminium conductors.

Issues:-
(a) What is the extent of the problem, or likelihood, of water in conductors?
(b) Effect on cable cost of inclusion of water-blocking.
(c) Effect on jointing, termination, accessories, changed work practices.
(d) What are the problems with solid conductors?

2. Cable Design – Single or Three Core

Question: Should cables be single core or 3-core?

There is an increasing emphasis on reducing costs of cable for underground distribution. In the USA where
circuit isolation is carried out using load break elbows and padmount equipment, single core cables are
standard practice, however, this is not standard practice in this region.

Single core cables can be cost-effective where impedance earthed systems are used which require relatively small
screens sizes so that the cost for three core cables is economical. This is also true for large conductor sized cables.
Single core cables are more easily water-blocked.

For 11kV systems, trend is to 3-phase cables. At higher voltages and higher fault levels, this issue of
circulatory current in large screens of single core cable is a significant factor. The subject therefore of 3-core vs
single core is an important issue.

Issues:-
(a) For LV cables, what is the best design – Stranded or solid conductor?
(b) Where should 3 core cables be specified – 11-33kV?
(c) Is there a need to use filler materials to make 3-core cables circular?

3. Direct-Buried or In-Conduit Systems

Question: Which is best system, direct-buried or in-conduit and what is the impact on cable design?

Should one adopt direct-buried or an in-conduit system? In-conduit systems might enable simpler, low
cost cable designs to be used. In many densely populated cities conduit systems are the only appropriate
form of cabling, as it is impossible to take advantage of longer drum lengths with direct-buried systems.
Due to frequent presence of water in ducts, perhaps it becomes necessary to apply water barriers into the
cable.
On the other hand, there is an increasing interest in direct-burying using modern installation methods.
MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

Issues:-
(a) Appropriate designs of cable for the particular method of installation.
(b) Cost difference in cables for the different applications, e.g. tough cables for direct-buried and lighter
cables for in-conduit applications.
(c) Possibility of lower design performance suitable for direct ploughing in or long lengths of cable for
rural Electrification.
(d) Experience with cables used with direct plough or directional boring.
(f) What is the effect of water in conduits?
(g) Would it be better to apply water barriers in cable to be installed in conduits?

4. Cable Accessories

Question: What factors need to be considered when selecting cable accessories?

With increasing variation in cable designs, accessories need to accommodate these changes. Examples are
transition from conventional paper cables to XLPE cables and from various designs of XLPE cable
including transition from Copper to Aluminium. In particular, cases where two different installation
techniques are used, e.g., connection of submarine to land cables, EPR to XLPE, 3-core to single core.

Issues:-
(a) Experience with performance of cable accessories in harsh operating environments common in Asia
and Australia (i.e. UV, humidity and rainfall, temperature, high water tables, airborne pollution).
(b) Transition jointing
(c) Performance testing
(d) Connector design
(e) Water blocking at joints

5. Tree-Retardant Polymeric Insulation

Question: Should tree-retardant XLPE or EPR be specified for cable insulation?

With the high degree of concern that has been experienced with water-treeing in some parts of the world, in
particular, the USA, there is a trend in specifications to call up either tree-retardant XLPE or EPR. What
are the various merits of specifying tree-retardant XLPE compared with standard XLPE for medium
voltage underground cables? There are economic and technical issues in respect of these insulants.
Experience in New Zealand, using TR-XLPE in single and three core cable, shows no detrimental effects
nor special precautions necessary.

Issues:-
(a) Application of these materials at this time.
(b) Field experience
(c) Cost impact of these materials ?

6. Design of Cables for Wet Environments

Question: What type of sheathing and/or other protection should be applied to cable where ground
conditions are known to be wet?

In many parts of this region cables are being installed on reclaimed land with a high water table or in flood
prone areas. There are concerns about the poor performance of cables sheathed only with PVC. The use of
water swellable tapes under the sheath and replacement of PVC by Polyethylene is now more common.
Should metallic moisture barriers be used for MV cables and what is the practical performance of PVC and
Polyethylene sheathed cables in these environments?

Issues:-
(a) What are the current practices in the region for cabling in these environments?
(b) Are there any clear trends from international experience?
MNC-CIRED Asia Pacific Conference on MV Power Cable Technologies 6-8 September 05

7. Armouring

Question: Is metallic armouring required for MV cable in other than submarine applications?

Past practice was to armour all MV cables and this was done to protect the lead sheath of paper insulated
cables during installation and provide protection from damage predominantly by persons with hand held
equipment.

With the introduction of mechanical plant, many authorities do not now specify armouring for underground cables.
This practice is not, however, uniform throughout the region.

Issues:-
(a) Cases where armouring is still required
(b) Type of armouring now considered appropriate for various applications where armouring is essential
(c) Use of armouring a screening medium

8. Field Testing

Question: Should D.C. be used for testing of polymeric MV cables after installation?

There is now considerable concern about the possible damage caused to otherwise sound polymeric cable by D.C.
testing. Research has shown that space charges caused by D.C. testing may induce cable and accessory failures.

Issues:-
(a) What test methods should be used for testing MV cable after installation or after specific service life?
(b) Practical experience with D.C. testing
(c) Are any diagnostic testing solutions for assessing cables currently in service?

9. Cable Identification

Question: How can cables be identified and traced to identify manufacturing records?

There is a greater interest in having available, complete details for cables for purposes of traceability.

Issues:-
(a) Cable identification is provided either on the cable;
(b) On the cable drum
(c) How information can be retained for future reference

10. Combined Communication and Power Cables

Question: Can, or should, optical fibres be included in power cables?

With the greater trend for deregulation there are calls for inclusion of optical fibre cables within power cables.
Previously such trends were avoided due to difficulties with jointing of optical fibre cables at places where the power
cables are jointed. There are now possible solutions which may make the inclusion of optical fibre cables in power
cables attractive so that single cable may be attractive.

Issues:-
(a) What are typical applications?
(b) Experience to date

Anda mungkin juga menyukai