Anda di halaman 1dari 8

Engineering Practice

Air Coolers Versus


Shell-and-Tube Water Coolers
as shown here, economical cooling is often achieved with a combination oi ooth air
and water cooling. Design considerations are also presented here
Ml-i'"fl5 K""1a" Ma"da' TABLE 1. FEBFURMAIIBE tIltl'fl-"Al=l|5D|ll lllt Ala coouaa
Flum Daniel lndia pvt" Ltd Particulars Air in counter-curranttc Air in co-currauttc |:iro- Air in cu-current
process fluid in finned cess fluid in finned tube to process fluid in
or the last 4lIIl years, air- J‘-Ill“ {Ell-’=P ll ___{Ste|l 2] J hare tullelfitep 3]
cooled heat exchangers I
|"iltl .lIl .-til ‘-_°iil 'l l}.lZl |Il1l ‘l IIllES 4
4; ,-, ;.¢_' 3 A5l5:-:2 A-Ellflxl
have become an indispens- l'llt1l.UllUllB pasecsltlc. ‘lElB l2l'B 'lElB
able part of many chemical, _ cf rows ‘I I
Heat Duly, llilllll 12.-l 12.4 12.4
petroleum-refining, petrochemical, MTD, “C E? . E
4

5? 4
4

E4
gas processing and power plants, as _Hyi:lrocarhori velccity,mls V _ 1 l] ._E5 U 4?
I

I] 41
well as oft-shore platforms. In loca- Surface area rec uiremerit, secs ll1arel,35,35it
-r I |_| I

3,Ei?lIl there}, 46,201


1

' 5490
-

tions such as the Middle East, where m? Jfinnelill Jfinnedl A


the availability of cooling water is Hydrocarbon NH E, inlout 3,3l'El-3El‘l 2,41 l-222 3,3l]l}-1'00
limited end expensive, air-cooled ex- _ Tulle slim Temp, ic , soc -l
51.5 ,l':i1.5
-r

changers may be a preferred choice. Exchanger cost, million $ ill?- l-Cl Hot estimated
However, even there, due to vari- _[g_gproltlmale_l y
ous process constraints, air cooling Installation cost, million 5 [l.E-3 l c.s l ilix estimated
_ @_Epl‘fl-Lltl l‘l'lt':l'[E]
alone may not always suffice. so Elperating cost, mlllitln E l]-2=l
‘I

0-3

Hot estimated
water cooling may also be required. laggroximalel g
Similarly, where cooling water is Total cost, million 5 1.5? 1 2.1 1 Hot estimated
plentiful, shell-and-tube coolers may lggproximatel — -r

not always be a straightforward so-


lution. Due to the need for elaborate water, the heat-transfer coefficient Fouling. The costs associated with
cooling-water piping circuits, a cool- will be about one third that of a fouling are usually lower for air cool-
ing tower, large cooling-water circu- water-cooled exchanger, leading to ing compared to water cooling.
lation pumps and water-conditioning higher heat-transfer area in air cool- Shell-and-tube coolers, the cooling-
systems, the complexity and capital ers. ln addition, an air cooler requires tower basin and other peripheral
requirements are generally very high, elaborate structures, which further equipment require regular mainte-
leading to a preference for air cool- increases fixed costs by anywhere nance due to extensive fouling and
ers over shell-and-tube coolers. In from three to ten times that of a shell- scaling, and also biological treatment
this article, with the help of a case and-tube water cooler, depending on is required, without which the perfor-
study, the author discusses situa- materials of construction. Neverthe- mance of the operating plant drops
tions where the combination of both less. an air cooler is usually preferred substantially due to deposition or
air cooler and water coolers can be to avoid. completely or partially, the fouling in the shell-and-tube coolers.
used, including considerations for requirement of elaborate cooling- Air coolers may also become fouled
better overall project economics. water piping circuits, cooling tower, on the outside due to the accumula-
cooling-water circulation pumps and tion of dust, insects and other debris
Why use air coolers‘? water-conditioning systems and so on the finned surface, but less main-
Even though overall economics play on, because such additional equip- tenance is required to handle this.
a major role, an air-cooled heat ex- ment incurs much larger fixed costs. Where shell-and-tube overhead con-
changer is used extensively in all In addition to that, the operating cost densers or trim condensers are used
kinds of on-shore plants and oft- of pumping raw water, make-up for cooling or condensing column
shore platforms as a first choice of water and power for cooling-tower overhead vapor, any drop in perfor-
cooling mechanism for one of the fans makes the TIG of water-cooling mance due to fouling can mean loss
following reasons: system much higher than an air-cool- in processing material lhydrocarbon.
Total installed cost (TIC). The TlG ing system, which only requires op- chemical} and thermal energy. As a
of an air-cooling system is less than erating costs for the fan power and result, the column pressure can be
that of a cooling water system. Due some controls. such as variable fre- affected and the hydrocarbon mate-
to lower thermal conductivity and quency drive, louver and so on {see rial is lost in slop, or flared, or the pro-
specific heat of air compared to the case study. below}. duction of lower-grade material.
CHEMICAL ENGINEERING 'W"Lflifi.ltl.CHEMENG'UNLlNE-CClM FEBFlLJAFl"r' EEJ19
Flexibility. An air cooler offers more air cooler, an economical approach
flexibility for controlling the process- temperature between the outlet of
fluid outlet temperature. There are process fluid and the ambient air
various ways to safe energy by con- temperature is generally 15-25%},
trolling the process-fluid outlet tem- whereas for shell-and-tube water
perature in an air cooler, as follows coolers, the approach temperature
[see also the case study below}: can be as low as 5‘"’C.
1- Switching one fan off during winter Winterization. In cold climates, air
months or during the night time coolers require extensive winterize-
1- Using variable-speed drive motors tion arrangements to protect against
having lU—ilZlU% operable range congealing ldue to low pour point of
1' Using auto variable-pitch fans process fluid] or freezing for very low
where blade angles change to air-inlet design temperature. Elabo-
draw more or less air {power} rate ducting with louvers, actuators,
Such operational flexibility is non- steam coil or heating fans under
existent in shell-and-tube coolers. as each fan can increase the capital
rarely any control is provided for the cost many times. In shell-and-tube
cooling water side of water coolers. water coolers. simply switching the
Location. No specific location is re- cooling medium to a tempered water
quired for air coolers. However, any system can prevent freezing of the
process plant that uses a shell-and- process fluid.
tube cooler together with a water- Plot areas. Air coolers require a
cooling system will be preferred large plot area due to the larger
when the location is near a source of heat-transfer area requirement. in
water, such as river, lal<:e or the sea. contrast, a shell-and-tube cooler is
Power: in the event of a power failure. very compact and requires much
cooling can continue in an air cooler less space.
by natural convection. When fan mo- Location and performance. The
tors fail to run due to mechanical or perlormance of air coolers is affected
electrical problems, an air cooler can by the proximity of other structures.
still provide cooling of 10-15% of the The efficiency of air coolers goes
design heat duty by natural convec- down drastically when the wind di-
tion. Loss of power or other mechani- rection changes seasonally, affecting
cal issues in a shell-and-tube cooler air inlet temperature to the bundles
can cause the water to be heated up due to the presence of furnace
more than the desired outlet temper- staclt, columns and other equipment
ature, causing scaling and fouling. in the path of the changing air-flow
direction. Because these equip-
Why shell-and-tube coolers’? ment cannot be positioned very far
Cooling range. Air coolers can be from other structures due to space
used mostly as primary coolers for constraints in the operating plant,
process fluid that requires cooling the air temperature may increase by
before storage- if a process fluid is to few degrees. also, if sufficient space
be cooled or condensed from 100°C is not allocated between air coolers
or above, to ¢l5"C or below, an air and columns, furnaces and buildings
cooler can tirst cool the process fluid in the same unit, hot-air dispersion
down to 65—i'iIi'='tI, then further cool- gets hampered, leading to hot-air re-
ing is provided by a shell-and-tube circulating to the fresh intaite air- This
water-trim cooler for final cooling be- lowers the mean temperature differ-
fore lt proceeds for rundown or stor- ence (lylTEl}, and the area for cooling
age. A shell-and-tube cooler or con- becomes inadequate.
denser may not be a direct choice Maintenance. Air coolers gener-
due to the probability of high tube- ally have higher maintenance re-
sl-iin temperature, which can lead to quirements than shell-and-tube
scaling in the tubes. Where process condensers. An air cooler consists
cooling is in a lower range (to--115‘-‘Cl of many static and rotating com-
obviously air coolers cannot be used ponents that may have mainte-
at all, and shell-and-tube water cool- nance issues, such as: ll fan-shaft
ers are the only choice. misalignment, leading to high fani
Approach temperature. Shell-and motor vibration which stops fan; 2]
tube water coolers can accept a high fariimotor bearing tempera-
lower approach temperature. For an ture, resulting in failure of coupling
gnnllni canal?

CHEMICAL ENGINEERING l.l'tl'l.l'l.|"'iftl.l:I-lEl\JlENlI'_%l:.'lNLlNE.C"-Cll'la'1 FEESHU.-i'tFt”r’ EH19


Frollll llllllll drool sills Mg_ai|, Tulle Prearlul:-c sheet side FFIJITIZ lJ.lIJE $llli!E1 tt|'E -
5 Avg. til Avg. Tuore HEB’ mm “H 5"!“ than one row per pass, and should
side sltin
tIIeIiI|io “ll Twm III:
I PT-.'r:r_'_'c_; ll.rr! |'I|_|.v __ Fhflmmflmbme IIIImIII' IIIII IIIMII IIII .- rue onloniroluoo
preferably have at least two passes
Prooom luld c E23. "Flr.rl:lc:olisfrcm1ulrc . .. _ cog, ' ' 1 oer per row, so that the fluid flowing in
'H1=i=Ifv-1-is-= -- "'i"i-Y
i
not-ll,':""““'= -H_-|:_:';5g_gIl'=-‘E5
'-it as '1'
two rows due to pass distribution, is
M_k_I.%___ ....-é2.?. Pm .
|

Flo'r'|'3r=-ares Tar flows g=n=t- . ' gg_gII sis rsss1o,ra'c'


i.""I“"II ..59'9_i.52. . _t=u=.II'I. mg ' I
mixed in later passes after exchang-
'ri'ali'i'"iF"I’“_==- i....""ii;i' ll”
I'IT
l-Fl
3

'I'“"""' "““'“I°-I _. .5?‘-ii??? ___ ing heat with air at different tempera-
tures in different rows. This phenom-
:Flwr
$I:I I:I I3I I.-;it'I l_l". - - iii it. flgwfi Pro.-to
Ilwll -_ ___ __.-Ft’--ti.s.t -___ 'Passe
51.15533 get ;i_=_ir=i=ic.ss‘c
?‘1f.‘.-'?‘.‘“l enon is shown in Figure 1.
Floir_eP=s11'--‘l>'"
as-itat '
f" - I3?
IT:IIIIP
"5s=' Iit-Ii
f:
F". til.“ ‘"3-‘HI?
|:h,|||||]|Iljll1-'l-i.'l.1-‘il?I|I §|;;‘fi5 I-3-3.5IEil'
oi
To avoid such a situation, and if
"'“"*"-""“" Air llow
Flllid le111|;l-erelure in hoot header side
Fluid llerriueraturc in rear
lreaoorsido
""°“=“"-""‘“ "“I' I-In‘-'-' Process lllearchallel side the tube-skin temperature cannot
Fronlotraholsidolluidtornperaluro l'llI=tl llorr lltlltl lcmoclalurc
be achieved in conventional flow ar-
FIGURE 1. As seen by flrese two examples, the tube sl-tin temperature in an air cooler is linlteo to the rangement lhot fluid entering from
direction of the air flow
top nozzles}, a co-current arrange-
and belt; 3} dustidebrisrpollen built tube-side pressure drop, which can ment is tried out where process
up on tubes, leading to increased be justified economically because fluid enters from bottom nozzles
air pressure drop in the bundle and the increase in the operating and and moves up the bundle. Elue to
reduction of airflow (some reverse capital cost of the pump is small lower lylTD in such an arrangement,
flow also can be seen] leading to compared to surface area and cost the required surface area goes up
loss in cooling capacity; 4] corro- of air cooler saved. in general, this further. as is usually the case. this
sion of finned tubes due to salty at- design has a relatively higher surface kind of design is tube-side resis-
mosphere or mishandling by water area requirement- Adopting a deep tance contrclling, and a bare-tube
washing and so on; 5} breaitage bundle design also helps improve design instead of finned tube will be
or stuck louver or the failure of the the air-flow distribution in the bun- less expensive. Even after all these
louver positioner, causing restriction dle. Bundles should have no more alternatives are considered, if the
in air flow and reduction of cooling
capacity; and at mat-operation of
auto-variable pitch fan blades. as Process fluid is same as as stated in the Hydrocarbon cooling hjl tempered water in a shell-and-
they can get stuck and then air flow case study tulle cooler and cooling of same tempered weter cooling
cannot be adjusted by variable- in an air cooler
blade pitch angle. Type of exchanger I shell-and-tube Air cooler
_ Fluid Tgle J Eiacltwash oitf Tempered water Tempered wateri Air
Case study _ Temp. to, lrviiiii j soil-torso-so _ soieo
its an example, we discuss the chal- _ Heat duly, Irlliirl _ 12 . 4 12 4
lenges in handling a high-viscosity, _lvrro, “C _4s.s
high-fouling and low-pour-point hy- Hydrocarbon flollilrate, ltgflt 152,105 Hll
___Te@p-eretl wateLflo_wr_a_t_i_e, ltgflt I 5135.553 _5E5,Ef.‘iE _
drocarbon in an air cooler.
Ho. of bundlesishells required _ - is in series 4 i-
A residue-upgrading project in Shell-and-tutre areal air cooler care area, mi‘ i,ooo 1,5lIliIl
a petroleum refinery has a bach- IIIII|;tE!I'IlZlIlIE3 l'II.ll'l'lIIiIH' I In-III-II-II—- I‘ IIII I
wash oil cooler where hydrocarbon Exchangercost,millions[ggproximete} _ o - as o er
is cooled from 2o4 to rotc. The oil _ Installation cost, mil.ion $ lggproximate} , 11-32 lIl.El
viscosity is in the range of 1.4 to 40 _ Total installed cost, million S lggoroximate} I l]. so l 12
cF' and the pour point is 38°C. in this
project. the engineer has restricted TABLE 3. FEHFDRHIAHBE WITH GUMEIHED AIR DHULEB MID TEMFEBED WATER
the Reynolds number to a minimum SHELI.-Mil]-TIIBE GIIIILEII
of 2,000. The design ambient-air Process fluld is same as used In Hydrocarlron cooling oarfly by an alr cooler ' Cooling of same
temperature is 47°C. The location of Talrle 2 followed by tempered water in a shell-and- tempered water in
tulle cooler _ an air cooler
the refinery does not require exten- eof exclran er Pill‘ cooler shell-and-tuhe Air cooler
sive winterization for such a liquid. Huio Type Baclrwash olliltir Backwash oiliTem|:lered ' Tempered wateri
The design target for handling 1 water g Ajr
high-viscosity, high-fouling and con- _ Temp, “C, lnrout 2lIl4i11El A no-torso-so ‘Billed
gealing (low pour point} hydrocarbon Heat dtl , MW 9.01 3.4 3.4
is to achieve a tube shin temperature MTD, T E15 -l
15.2 15
of at least 15°C above pour point, Hydrocarbon flowrate, ltglh 152,1 [I15 A isaroc full
maximizing the tube velocity and the _ Tempered water flowrate, ltgrh lllil g 143,T5T 1 1irs,rsr
heat-transfer coefficient such that ..Brioole.ttsoells_asuireo__ 21- . _,_t!t_e__io.series.._ fil-
the Reynolds number lies in the tur- Elare area, m3 est soo _ is
bulent region. _ Reynolds number roses-e.ero Asst at midpoint J-
To get a reasonably high velocity Exchanger cost, million 5 o . es o . re lllfi
lggproximatel
in the tube side for such fluid re- Installation cost , million 5 0.29 0.23 o.2e
quires increasing the number of tube a roxlmatel
passes in a deep bundle of B to 12 Total installed cost. million 3 I153 0.39 I o.sa
rows. But this also leads to a higher legproximatel -l -r

CHEMICAL ENGINEERING W“I.flioN.CHEMENGCNLlNE-CCM FEBFlLJAFl“r’ 2519


design target is a higher tube-sl-tin qi -
temperature and a higher tube-side
velocity, the Fieynolds number in FIGURE 2. For applications where the fluid is botll ti st.‘ __
the transition zone is not achieved, viscous and clean, twisted tape turtrulators can ire
so other alternatives must be con- inserted into the tubes to increase heat transfer i ___;__;‘ '%"*"- _ I _'l:,‘olumn
sidered, such es cooling with tem- fluid starts congealing.
I -,,g_-Piperacltwi_IIII _;-
pered water- The following five design steps
ln the actual situation, the viscosity were considered for using an air I 1to|iIII'

of the process fluid increases as the cooler (Steps 1-3}, using a tem-
temperature of the process fluid falls pered water shell-and-tube cooler
while progressing in the tube bundle. {Step 4) and a combination of the FIGURE 3. shown here is a computer model of an
Also, if there is mal-distribution in the two (Step 5}. The results of the per- air cooler mounted on flre pipe raclt
air side of the multi-pass air cool- formance characteristics are sum-
ers, invariably the process fluid cools marized in Tables 1-3. Several l-tey Step 2. By arranging the process
more in some of tubes than in others- observations are pointed out in the fluid flow co-currently to air flow, the
This will further increase the viscos- following paragraphs: MTD goes down from diff} (coun-
ity in the cooler tubes and therefore Step 1'. The first attempt in thermal ter-current} to 57'“lS and therefore,
reduce flow through the tubes, which design, using a conventional coun- the surface area requirement goes
causes further cooling and more flow ter-current flow arrangement in an air up. The existing design of four bays
reduction. This process continues cooler, results in a Fleynolds number becomes inadequate in surface
at the outlet of soo {deep laminar area. so one more bay is added to
until ultimately, we may notice that
fluid has stooped flowing in many flow} and a tube-sltin temperature of total]. as the number of bays is in-
of the tubes, and is only flowing in 5lIl.6"’C- The design also has a high creased, the tube-side velocity goes
a very few tubes with higher veloc- tube-side pressure drop and a low down further (0.4? mist and so does
ity and turbulent flow regime. Pres- tube-side velocity, in spite of 12 tube the overall heat-transfer coefficient,
sure drop may be substantially higher passes in an eight-tube row bundle, as tube side resistance is control-
and. unless the pump can deliver the and therefore high surface area re- ling by S5‘iti. Even if the tube-st-tin
needed head, flow may stop and quirement lhigh cost}. temperature is improved, there is not

r**-"-=-"-
If s

POWTECH fli I
||_ .I'

'ri'v'orid-Lt'-Lltllog T:-it-ill; Full lur Erotcss Hg. -I 1 I


"‘
I -
.iI
lfitn.-'rlj,.-:.is_ ._'|r‘[l ll._‘nu;ll:i'ig of Po-.~,-tit;-r ant: Etnli. so iris rs -"' .I
‘ '!;-it-'*
*rt“ I.
‘F

,, "4'? . - -P
I -_‘ -is |l'I
1 .

.I
I‘

_ -oil‘ - -_

PB0I3E55E5
To
. itiiEli“s°iiitEiiililt’itii.
UPTIHISE PROCESSES
First comes the experience, then the success: discover

4 SOLUT|0N$ ""'
the entire spectrum and dynamic energy of mechanical
process engineering. PfItl.ll.lTECH is the trade fair event
for built solids - and the place where process

060 F-
H optimisation begins.
hlew strategies are needed for "green chemistry"- in the
Expert Forum Chemistry, you’lI learn about sustainable
h concepts for procurement, production and sales, loT,
‘l ‘F mixed reality and new processes in solids production.
- I J ‘l - ,',' Directly from the experts — for everyone who wants
cg; ~
to matte their processes more efficient-

utirtroesets russsrt
lnei.con'll?3B51 -"I 4
toil!“
1‘ -an ggs>“"_ _fl-
gee“ inside the tubes. The swirling fluid
r%II‘1III' x
Ix rI";IIIIIIIIII promotes greater contact with the
II[':_-‘I \ "'1 5--H-‘iii 1%

3- _
tube wall {increasing shear stress
H-I'l--

Header for
-I.
'1
E
-III

IIIIIT s E --cg
-'-|.
-l_,_ H-
at the walls many times more} en-
tech bay tTyo.} 1‘--.-,___g__ hancing tube-side convective heat
-. III -. _lI_I_‘lI1= IIII"'- transfer efficiency. The increase in
‘T IIT"'tl-- -lI
values of hlusselt number, F-‘reynolds
I
rt- ii’
r- lg
"' .
number, Praridtl number, pressure
I I I ‘-.I i1~;I 1..-I’I_|_-.Ii1ri':t--,3, drop and friction factor will depend
1"‘
Ir’

| .-
I
'I
_
_

upon the configuration of twisted


Fll‘.itlftE 4. tilormally, the inlet piping of an air
FIGURE 5. When a perfectly symmetrical disince- tape {twisted ratio. pitch ratio, tape
tion is not possible tas in Figure 4}, an equivalent width, wire diameter and so on}.
cooler requires t1 symmetrical dislnbulion distribution of headers can be designed
much improvement in the Fteynolds perature {11tIi'“'Cl from the air cooler Structural considerations
number, and because it is outside is high enough to have a Fieynolds Support options. For an air-cooled
the users requirement. this method number above 2.000. The rest of the exchanger, there are two support
is also not adequate. heat duty can be cooled in a closed- options: 1] to place it on pipe rack or
Step 3. From the above, since loop tempered water system, as 2) to place it on a separate structure
tube-side film coefficients are very shown in Table 3. supported from the ground. Even
low and become controlling, there By opting for a combined system, though air-cooled exchangers re-
is generally no advantage in using the surface area is optimized sub- quire more space than water-cooled
fins on the air side to increase the stantially and the total installed cost exchangers, the majority of space
overall heat-transfer rate. Bare tube is lower. an air cooler can handle a problems can be resolved if they
bundles with a large number of rows higher inlet temperature, and a high are placed on a pipe rack (Figure
and split passes are more practical, Reynolds number can be maintained S}. Normally the tube bundle length
as shown above. The bare surface by limiting the outlet temperature of is fixed, based on the width of the
area calculated by the software is the air cooler. Then hydrocarbon pipe rack. If the pipe rack width is B
not very high, and the power re- is passed through the shell side m, the tube length could be 9.5 to
quirement is also similar to the first of a downstream tempered water 9-? m. The supporting legs of the air-
two designs. The real advantage of shell-and-tube cooler where higher cooler bundle are fixed on the main
using bare tube bundles is that the viscosity can be tackled better by civil or structural beams, which sim-
number of bundles is reduced from considering rotated-square (45 deg} plifies the pipe rack design. At the
10 to 8, while maintaining a skin tube arrangement. As the bulk tem- same time, it is desirable to adjust
temperature of B1 .5"’l3- perature in the shell is above 65°C, the pipe rack or the structure lon-
Step 4- lvlost of the challenges seen despite the low Beynolds number, gitudinal column spacing, based on
in the designs of Steps 1-3 can be heat transfer coefficient and shell the width of the air-cooler bundle, so
avoided if we bring tempered water side velocity are acceptable- that the bundle legs sit straight on
as a coolant. since normal cooling 111erefore, we see that a combina- top of the columns. Sometimes, it
water is not suitable for cooling a tion of both shell-and-tube and air may not be possible to adjust spac-
process fluid with high viscosity, low cooler play a definite role in the over- ing, since each tube bundle might
pour point and a limited tube-skin all cost economics. and together they have different widths, depending on
temperature. When the total heat achieve more benefits when com- service condition. Therefore, adjust-
duty is cooled in a shell-and-tube. bined than when used separately. ing the pipe rack columns for differ-
tempered water cooler, the capital ent widths may not be feasible from
cost is very attractive, as shown in Handling lube oil in air coolers a structural design and detailing
Table 2- However, because an air In off-shore platforms where space point of view.
cooler is required for cooling tem- is at a premium, air coolers are lltrafltways. There will be walkways
pered water, the costs balance out- used for cooling lubricant oil. Lube between sets of air coolers across
lf a tempered water system is used oil is both viscous and clean, and the length and near the headers for
elsewhere in the plant that can be therefore it is possible to use turbu- facilitating operators to inspect the
tweaked and ramped up to accom- fence promoters (Figure 2} or tube bundle or operate the valves. The
modate this cooler, the scheme can inserts {turbulators} in this type of width of these walkways is gener-
definitely be made attractive. How- air cooler. Such inserts can increase ally 1.5—2.o m. air coolers must
ever, in spite of more turbulence due the tube-side heat-transfer coeffi- have access platforms mounted all
to baffling in the shell side, the Fieyn- cient by 1[ltIl—25U% over bare tube around on the structure to provide
olds number is poor, because the exchangers, with an increase in maintenance. Air coolers have mo-
bulk temperature of the process fluid pressure drop. but without much tors hanging at the bottom of the
is B1“G in the coldest shell. increase in velocity. Twisted tape air-cooler plenum. Hence, it is re-
Step 5. We can split the total cool- turbulators are formed into a heli- quired to have access platforms un-
ing load into two stages and use an cal fashion and they increase heat- derneath the cooler for maintenance
air cooler in a series with a tempered transfer efficiency by breaking up of the motors. A regular staircase
water trim cooler. The outlet tem- the laminar flow pattern of fluids should be provided for accessing
CHEMICAL ENGINEERING 'ififW'y'tl.GHEMENGCNLlNE-CCM FEBRl..JAR“r' E519
the air cooler platforms or motor where a total often bays are divided have to be considered. The length
maintenance platforms. lvlonkey lad- into five bays both sides and vapor is of all branch pipes for all tube
ders are also provided in addition to distributed equally to both sides. The bundles from its header has to be
a staircase from the structure. piping of the air cooler needs to be more or less similar to keep the
Piping considerations. For a mini- supported. so either the structural pressure drop the same: this will
mum of two fans per bay, the height columns or the pipe-rack structural ensure equal distribution of fluids
of the underside of the fan inlet bell columns need to be extended up- to all bundles.
[for forced-draft units} or of the un- wards to properly support the pip- 2. Normally, the inlet-side header
derside of the bundle {for induced- ing. Such data have to be given at a box is considered as fixed for the
draft units} should be at least 2 m or very early stage in the project, since piping connection and the other
one fan diameter (whichever is the this needs to be considered during header is floating. But the bundle
greater} above the ground level, el- the design of the pipe rack- can move in transverse direction
evated floor or pipe bridge- The air The air coolers for an overhead of tubes by a few millimeters lsay.
coolers on the pipe rack should be system are normally used when a B mm minimum} or if it is fixed at
located in such a way that the bun- large quantity of vapor is required for one edge, then it can move by a
dles are accessible with a crane — condensation or a huge quantity of higher margin (say, 12-? mm mini-
at least from one side. gas or liquid needs to be cooled. The mum} in the other direction, as per
Normally, the inlet piping of an major points that need to be taken American Petroleum institute lAF'l.
air cooler requires a symmetrical care of when routing the inlet and ?th edition} recommendations.
distribution for condensers. There- outlet pipes are as follows: Usually, this value can be any-
fore, the number of baysrbundles 1- If the supply line has a very low where between 5 and so mm. This
is based on 2"‘ = 2, 4, B, 1B, B2 operating pressure, which is usu- header displacement is necessary
[Figure 4). When such an exact sym- ally the case for connecting a to compensate for piping inletiout-
metry is not possible due to some distillation column, care needs to let header expansion. The value
constraint, such as pressure drop be taken to keep the number of decided upon should be con-
or structural limitation, efforts should bends or elbows leading to the air firmed with the vendor of the air
be made to maximize an equivalent cooler at e minimum. But func- cooler, since the vendor may use
symmetry, as shown in Figure 5, tionality and stress requirements a different displacement provision.

DRY RUNNING r CAVITATION - BEARING FAILURE - OVERLOAD

MUHITDB Pl.Illl'lP PIJIHEH BDHIPAST EAST tlllt'Il.lNTlltt'i


I Best Sensitivity Dnly 3-35" x 15.35" x 3"
I Digital Display ' Starter Boot I Panel .---{Fm
two Ao.rusrrter.s set sururs ' Hiiiwai ' “"3"
A Belay outputs LINIUUE FILANEE FINDER SENSDFI __,
s Adjustable Belay timers 1- Works on Wide-range of lrlotors r ,. .
[E _-

* simplifies installation
4-iltt IIIILLIAIIIIP ANALOG OUTPUT

WHY MONITOR POWER INSTEAD OF JUST AMPS? PUMP POWER


_ _ VALVE CLOHNG

E E -1}Z iLrWMPl Il\


Q g :_- q_,g5,,,gy,,,g I VALVEOFEHIHG ,
Pov-e'is Lireer-Eoorrl sensitivity , ._.r"i,.._.._s=~"--/‘--“*"‘—l
all-3-r.llfll.l2I'rl'-raldl-iglrLrIlal;ts IIIUIIILMIII ' II""II I
HO LOAD FULL LOAD NO LOAD Ft.ILL LOAD- lI

M ALL PRODUCTS
2 MADE IN USA

LOAD CONTROLS
EINCORPORATED
lr'll'W'llll.LOADCONT ltOLS.COl'vl
Fur details rrisit acllinlc5.r:heme|'rgr:r-nline.c:crII1l"r"3S5‘I-13

GHEMIGAL ENGINEERING lAB.APv"J.CHEMENGClNLlNE.CCM FEBRLJARW’ SO19


substantial, as shown in Table 4.
Such flexibility is not possible
Air cooler used alone at lower ambient tem eraturcl using only shell-and-tube coolers.
Air aln tlient
._-_ tam ‘*0
-._._ll~-_-_ 50"‘[I -. 4111!-'3 ._t4"i3 _ where operators only very rarely will
Process fluid temp, to E5 53.? 42.0 adjust the cooling water flowrate by
Heal ogjy. MW 55.3 58.? __-‘ll operating exchanger valves (manu-
shaft er re uiremerit. kill 390 320 350 ally or automatically}. Therefore, we
Air cooler and trim cooler combination er design} with air flow optimized for lower ambient temperature see that shell-and-tube and air cool-
Heat duly, ritw ss-s so-a ss-s ers both have definite roles in the
_rirr rr_irr.vrste. xgg y s.goe,sss _4,r-121,012 lists} _ 3,4liiT,B2E tests} overall cost economics.
shalt power requirement, kill sec 130 1o4
saving in shalt power per year
r

1,030
-r

2,233
Weatherizing for colder climates.
_i3-I322 "ll MW ln some parts of the world, where
ambient conditions are such that in
The movement of tube bundles and sometimes power is required winter, air temperature dips below
in the transverse direction could for heating coils in cold climates. freezing, temperature control of the
occur only when the piping con- Normatly, the design of the cooler process streams at the air-cooler
nected to equipment nozzles gen- will be such to accommodate the outlet is required to prevent freezing
erates enough force to overcome highest expected ambient tempera- of low pour-point hydrocarbons. This
the friction at the bundle supports. ture lfor example, 50°C}, but be- leads to a more complicated design
That is why it is a common prac- cause of seasonal changes, such a for the air cooler.
tice to provide stainless steel. strategy would be wasteful during When a minimum tube-wall tem-
polytetrafluoroethylene lPTFE} or the periods when the ambient tem- perature has to be maintained in the
other type of plate at the support perature is lower {for example, 40“'C} air cooler, a recirculation system is
point to ease the movement. But — which can be as much as 50% employed whereby automatic lou-
this must be done in consultation for the year. Operating power costs vers at the top and sides of the air
with the vendor- can therefore be much lower than cooler housing (containing the entire
3. The loads created on the bundle the installed power costs by using assembly of tube bundles. ducting,
nozzle -- due to thermal expan- two-speed motors, auto-variable steam coils, plenums and fan mo-
sion, the weights of the pipe, in- pitch fans and variable frequency tors} control the extent of recircula-
sulation and fluid. and the inside drive rvrol fan-motor control to re- tion. The recirculation is possible in
pressure of piping — should be duce the air flow. In temperate cli- forced-draft air coolers, since hot ex-
less than the limits given by API. mates, as much as 50% or more haust air can be recirculated through
Sometimes the vendor allows a of the design power may be saved a duct-and-louver system.
higher allowable load [normally over the course of a year with auto A steam coil is generally a sepa-
two times the code value}. variable-pitch fans. rate tube bundle of one or two rows
Locating shell-and-tube coolers. Nowadays, VFD technology has having a length and width similar to
The standalone water condenser become popular and more com- the main air cooler, that is placed
and shell-and-tube trim water mon rather than auto variable-pitch below the main air cooler bundle. if
cooler can be placed above the fans, which are problematic for a an electric fan heater is to be pro-
condenser drum on a structural number of reasons. The air require- vided in place of a steam-heated
platform supported from grade. ment can be adjusted from 10 to bundle, the same is placed below
Even though a shell-and-tube water 100% through VFD control. Table each air cooler fan. Low-pressure
cooler will require less space than 4 presents the potential savings (LP) steam being inside finned tubes.
an air cooler, some area allocation that can be expected by adjusting the steam-heated bundle and lou-
is needed on the ground for on the power requirements to different ver will involve additional pressure
the platform for off-shore applica- ambient-air temperatures, for both drop in the fan design. Closing the
lions}. The pressure of the cooling a standalone air cooler, and for a louver on top of a bundle allows the
water reaching to the tube side of combination of air cooler and trim healing coil to warm the bundle dur-
condensers and trim coolers {when cooler. When the ambient tempera- ing slart up in freezing weather, so
on a platform} is very important for ture drops to below 34°C — which that the material in the bundle will
proper functioning of the condenser can occur during 5 to B months not freeze or solidify. A steam coil is
and the trim cooler. If the pressure over the year, the trim cooler may also used to temper very cold air to
drop in the cooling water circuit is not even be required at all, since the bundles in continuous operation
not properly calculated while de- the total heat duty can be handled while the fan is operating and the
signing the inletloutlet piping, the by air cooler alone. So in addition to exhaust louver is open. When two
actual cooling water flowrate will be the power savings, there will be ad- fans are operated per bay, an auto-
lower than that of the design cal- ditional savings for not using cooling variable-pitch fan or fan with l.-‘Fiji is
culation, and the performance may water, which can cost around $0.4 kept at rear end of the bundle, so
suffer as a result. millionryr. If a refinery decides to that the process fluid outlet temper-
Flexibility. The operating costs for keep both air coolers and trirn cool- ature can be controlled.
the air cooler include the electrical ers on line, power saving through C.-‘onfrolling recirculation. A part
power required to operate the fans reduction of air flow via ‘v'FD is very of the air leaving from the top of the
CHEMICAL ENGINEERING 'v'dl.h0r‘v.CHEMENGCNLlNE-CCM FEBRLJAR“r' SO19
--I: ~';_=._r,- l _ -.r =.: - l.-. L... r r -l- r |
I---- -.r
system is recirculated and mixes regulate the opening and closing .. . 1 | '!_: '
' 'lr-- =.-::-!--:-
with fresh air entering from the sides of the outlet louver. The duct sizing
so that the combined temperature is calculation and differential pres- ‘..'

:-'-::-:l'.r.
|:_'- .I.|o. ll |.|I .I'l'

._I;-:s'::'r l-'5rr':::.::.':'-.
I-I.‘-.II ||' ll:l:: I ‘II

:rl='." ' " I


.I|. I ::I::

‘ 1-ii-iii
precisely the design ambient tem- sure drop across the dampers is lf;'i:=;:r': s ;':fiil:'I-. !:':' --l;. l ll t
perature. The lower the ambient carefully done to avoid failure of -:_:" r 1 51l':_:-j_-' lI‘:;'.':r_:_ I :':" ~,'.':;_:‘_i
temperature, the greater will be the the system. The vendors scope of -II::""=i -- ' -iIiI==II-'= ==I--=':"I'==';r-II-'-
extent of recirculation. work will include the design of the -7- i:'-;r""i-l'-l_;i_iI f!:r!'l': :--;:_':if'.'..;-.'l& '=_ll".-r':;."::"r l-l-_-Iii l._:"'
For startup, when ambient tem- louvers. -n general, air-cooler tube- ‘ii-' l-'=="i-;-::-zr=t:": l":&.i Zr-.i-:1: liilil i'i5r'.'1r'-I-Iii‘. low. *"r
--..- -_'.- .- .-|.-I.-.-..-I. I" I
.::.-::'.l.. .=. ..,:. I.-,1: : . .-
perature is lower than design am- skin temperature is kept 15—20°C
bient temperature, ambient air can above the tube-side fluid pour-
be passed through a live-steam point temperature through this Author
coil, located below the bundle, elaborate system. lllahas ll lilandal is a principal
such that air approaching the bun- Aithough the cost of such an air desigll errgiileer for Fluor Elailiel
Indra Pvt. ltd. Itilh Floor, infinity
dle is heated up to the design tem- cooler is quite high, it is still pre- Tower B. 0,'ber' City. BLF Elly
perature. The recirculation of exit ferred in colder climates to prevent Phase ll, Surgeon 122 002- fiery-
air is gradually increased, which icing or frosting. I ons, lrrdia: Phone --Ell-l24-
reduces the steam requirement. Eoiled by Gerald 0ndrey 45i0r00: Fax: +B1-124-
4203-P00: Email; mantis-
Eventually, the steam supply can l rnandsl@fiuor.corrrl- He has more
be stopped altogether. Fteferences i than I-‘i4 years of experience in the
The air cooler is fitted with a duct I-_=:._; '2 tr ll l-- I :_;"r:: :-._= I .l-'|_--.:_:i l_. -1 l._. __ .r: lieltl of process heat transfer. cost optimization studies.
| .I process des:gn and operalrorrs. process revamp, pro;ect
leading from the top outlet to the -'1 '-I-I::.:::=r::::- ll~;:-iii l II'."ii"=lII"""' -I-52:2-2
lII"' =:""'I |'l:'|ii:'|'-': i;‘I'. I-I"II'iII"II|
l" "Iii",-' i'Ii'I'-E!II'-".‘tI""
control and energy managemerit- Prior to l-lrior, he
bottom inlet. Louvers are placed in -| 1.. ‘I . I . ' _..
wort-red at Errginaers lntlia Ltd. Delhi anti Hindustan Pa-
ul-;- '..'r ..' ‘Jr. --ll.-.'l --'-I! I---if
the bypass duct. at the air inlet and II--I"'|:'I!.‘-ii‘ lit: =l;:':r:l:::-rI-.- ii"-r'l -.1: "r: l..-::- I
:---r-":2-l
troleum ll-Iumbai Flelinery- lvlarldaf has presented many
papers in various seminars on heal transfer. energy
at the air outlet. The temperature of -.Ii l'--::.::- .-::- I..I' -- '-..-I.-L utl "-.r-.l'. l.'-I.. =rI' I.-I-r'I:~. - -;:'I..'..-ul -.'l-:1 nlorragerrrerrt anti process irnproverrrem lvlerrtlal holds
air just below the tube bundles will “.:l..l
. ..-
'.l' .l-.- l..i:-..-:- I.---.r
. '_.... _' _ ' ' _._
a B-Tech degree tn chemical engineering from the In-
regulate the opening and closing of |
--
|
'..li:'i_l"!i-;i .'
.--r. . I
__._2':r_l l.l;_i'"zlr_r:' -l
I .- .
-.~'::;_:'= ._-:;-:;!x tliorr lnslilrrle of Teclrrrolcgy Belhi on-ti Masters tlegree
inlet and bypass louvers, whereas lI'II':-::-:'rr:e:"- r --I‘-IL l'l:.==.2 l:~-::i'za' .r -I=-:-.:;:;': ll;=r"::- ll1 lrrrarrcral nlarragerlrenl from -_li]lTlf‘lf_IlEil Bajaj lrrslilule
of lvlanagemenl Sllrrlies. l".lumhai- India-
the process outlet temperature will l.III'ir5. III.‘ l3‘..-:"' I; III:-': '--i'l"iE*i

i—r—ji

-in
_?//'1'; AFPM 2019 Annual Meeting
rt‘ Leading Industry Sustainability S innovation
lvlarr:l‘l I? — 'l‘5", .T'lfi'lSi Tilt‘? POIIS rllitttlirlg '~.viII lltj: lt‘lt':l;st'1t'l on illnnvalivtt st‘:-lillitjirls, fit'ltlt'IiTllt'I-IT, -21 nil
h.-'larriott I-?iiver"centel' cr_rrrrr"r"r,rnity. Learn the latest orn the issues you care most about and Iouilcl
San Antonio, lit strategic re ationships with over 'l,1il_ii_l industry leaders-

irls-;=.ti=;:.t_i;:-" l_t_'lf_l.I;1'-_,-" l:t;iEltLl-"l|'1glI_ll'1fjl'Tt;il1‘rl'1B|IlE,'.Elltt;ll"1:-Lt-l'1l1il1I'lf£'f.£:.7i-ElRIII-i.€:.OtIbiI"l ‘Secretary to.‘ E-late of


alprri-or";--:1--"t:o"ice ti"-e Linitecl States and keynote spea-tel" Gary" I lerninger; CLO, -I‘vlar'athor1-
Fcrr details visit: acllin1c5.r::heme-ngnnlinre.c:cr-ml?3B51-D3

Anda mungkin juga menyukai