User’s Manual
PROFIBUS-DP Adapter Module
RPBA-01
PROFIBUS-DP Adapter Module
RPBA-01
User’s Manual
EFFECTIVE: 13.10.2003
Safety instructions
Overview
This chapter states the general safety instructions that must be
followed when installing and operating the RPBA-01 PROFIBUS-
DP Adapter module.
The material in this chapter must be studied before attempting any
work on, or with, the unit.
In addition to the safety instructions given below, read the
complete safety instructions of the specific drive you are working
on.
Safety instructions
6
Safety instructions
7
Table of contents
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Intended audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
What this manual contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Terms used in this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Further information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
PROFIBUS standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
The RPBA-01 PROFIBUS-DP Adapter module . . . . . . . . . . . . . . . . . . . . . . 14
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Warranty and liability information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mechanical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
General cabling instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table of contents
8
Node selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
PROFIBUS connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Configuring the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
PROFIBUS connection configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Control locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
PROFIBUS-DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Service Access Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Communication start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
PPO message types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
The Control Word and the Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . 36
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Actual Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Parameter handling in cyclic communication (DP) . . . . . . . . . . . . . . . . . . . . 41
Fault tracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
LED indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
PROFIdrive parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
RPBA-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
PROFIBUS link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table of contents
9
Introduction
Intended audience
The manual is intended for the people who are responsible for
commissioning and using an RPBA-01 PROFIBUS-DP Adapter
module. The reader is expected to have a basic knowledge of
electrical fundamentals, electrical wiring practices and how to
operate the drive.
Introduction
10
Introduction
11
Further information
Further information is available on the World Wide Web from
www.profibus.com.
Introduction
12
Introduction
13
Overview
Overview
This chapter contains a short description of the PROFIBUS
standard and the RPBA-01 Adapter module, a delivery checklist
and warranty information.
PROFIBUS standard
PROFIBUS is an open serial communication standard that
enables data exchange between all kinds of automation
components. There are three main variations of PROFIBUS:
PROFIBUS-FMS (Fieldbus Message Specification), PROFIBUS-
DP (Decentralised Periphery) and PROFIBUS-PA (Process
Automation). The RPBA-01 PROFIBUS-DP Adapter module
supports the PROFIBUS-DP protocol only.
The physical transmission medium of the bus is a twisted pair
cable (according to the RS-485 standard). The maximum length of
the bus cable is 100 to 1200 metres, depending on the selected
transmission rate (see Technical data chapter). Up to 31 nodes
can be connected to the same PROFIBUS network segment
without the use of repeaters. With repeaters, it is possible to
connect 127 nodes (including repeaters and master station) to the
network.
In PROFIBUS communication, the master station – usually a
programmable logic controller (PLC) – polls the nodes which
respond and take the actions requested by the master. It is also
possible to send a command to several nodes at the same
broadcast; in this case the nodes do not send a response
message to the master. Communication between nodes is not
possible on a PROFIBUS network.
The PROFIBUS protocol family is specified in the EN 50170
standard. The communication with a drive is defined in the
PROFIDRIVE-PROFILE – The PROFIBUS Profile for Adjustable
Overview
14
Overview
15
address
selection switches
Diagnostic LEDs
Top view (See chapter Side view
Fault tracing)
Compatibility
The RPBA-01 is compatible with all master stations that support
the PROFIBUS-DP protocol.
Delivery check
The option package for the RPBA-01 PROFIBUS-DP Adapter
module contains:
• PROFIBUS-DP Adapter module, type RPBA-01
• two screws (M3x10)
• this manual.
Overview
16
Overview
17
Mechanical installation
Mounting
The RPBA-01 is to be inserted into its specific position in the drive.
The module is held in place with plastic retaining clips and two
screws. The screws also provide the earthing of the I/O cable
shield connected to the module, and interconnect the GND signals
of the module and the control board of the drive.
On installation of the module, the signal and power connection to
the drive is automatically made through a 34-pin connector.
Mounting procedure:
• Insert the module carefully into its position inside the drive until
the retaining clips lock the module into position.
• Fasten the two screws (included) to the stand-offs.
• Set the bus termination switch of the module to the required
position.
Mechanical installation
18
Mechanical installation
19
Electrical installation
Overview
This chapter contains:
• general cabling instructions
• instructions for setting module node address number and bus
termination
• instructions for connecting the module to the PROFIBUS-DP
network.
Bus termination
The DIP switch on the front of the RPBA-01 module is used to
switch on bus termination. Bus termination prevents signal
reflections from the cable ends. Bus termination must be set to ON
if the module is the last or first module on the network. When using
PROFIBUS specific D-sub connectors with built-in termination, the
RPBA-01 termination must be switched off.
Electrical installation
20
ON ON
Node selection
Use the rotary node address selectors on the module to select the
node address number. The node address number is a decimal
number ranging from 01 to 99. The left selector represents the first
digit and the right selector the second digit. The node address can
be changed during operation, but the module must be re-initialised
for changes to take effect.
10x 1x
901 901
23
23
78
78
45 6 45 6
Electrical installation
21
PROFIBUS connection
The bus cable is connected to connector X1 on the RPBA-01.
The connector pin allocation described below follows the
PROFIBUS standard.
5 1
X1
9 6
X1 Description
1 Not used
2 Not used
3 B Data positive (Conductor 1 in twisted pair).
4 RTS Request To Send
5 GND Isolated ground
BUS
6 +5V Isolated 5V DC voltage supply
7 Not used
8 A Data negative (Conductor 2 in twisted pair).
9 Not used
Housing SHLD PROFIBUS cable shield. Internally connected
to GND BUS via an RC filter and directly to
CHGND.
+5V and GND BUS are used for bus termination. Some devices,
like optical transceivers (RS485 to fibre optics) might require
external power supply from these pins.
Electrical installation
22
X1 SHLD X1 SHLD
A 1 A 1
RPBA-01 RPBA-01
B 2 B 2
A 3 A 3
PROFIBUS B 4 B 4
MASTER
A
B
GND
Electrical installation
23
Programming
Overview
This chapter gives information on configuring the PROFIBUS
master station and the drive for communication through the
RPBA-01 PROFIBUS-DP Adapter module.
Note: The new settings take effect only when the module is
powered up the next time or when the module receives a ‘Fieldbus
Adapter parameter refresh’ command from the drive.
Programming
24
Programming
25
Note: Set also the extended Parameter Data (see page 31) to
ensure proper operation of the RPBA-01 with the drive.
1 MODULE TYPE
This parameter shows the module type as detected by the drive.
The value cannot be adjusted by the user.
If this parameter is undefined, the communication between the
drive and the module has not been established.
2 Node address
Each device on the PROFIBUS network must have a unique node
number. This parameter is used to define a node number for the
drive it is connected to, if the node address selection switches are
set to the zero position. When the node address selector switches
are used to define the node address (node address selectors not
in zero position) this parameter indicates the set node address.
3 Baud rate
The speed of communication. The value is given in kbit/s:
12000 = 12 Mbit/s
6000 = 6 Mbit/s
3000 = 3 Mbit/s
1500 = 1.5 Mbit/s
500 = 500 kbit/s
187 = 187.5 kbit/s
93 = 93.75 kbit/s
45 = 45.45 kbit/s
19 = 19.2 kbit/s
9 = 9.6 kbit/s
4 PPO-type
This parameter indicates the selected PPO message type for the
PROFIBUS communication. See Figure 6 in chapter
Communication for the supported PPO message types.
Programming
26
5 PZD3 OUT
This parameter represents process data word 3 of the PPO type
received by the drive over the PROFIBUS network. The content is
defined by a decimal number in the range of 0 to 32767 as follows:
0 not used
1 - 99 data set area of the drive
101 - 9999 parameter area of the drive
10000 - 32767 not supported by the drive
Programming
27
6 PZD3 IN
Process data word 3 of the PPO type sent from the drive to the
PROFIBUS network.
The content is defined by a decimal number in the range of 0 to
32767. See parameter PZD3 OUT for description of decimal
number allocation.
7 to 20 PZD4 OUT to PZD10 IN
See parameters PZD3 OUT and PZD3 IN.
Control locations
ABB drives can receive control information from multiple sources
including digital inputs, analogue inputs, the drive control panel
and a communication module (e.g. RPBA-01). ABB drives allow
the user to separately determine the source for each type of
control information (Start, Stop, Direction, Reference, Fault Reset,
etc.). In order to give the fieldbus master station the most
complete control over the drive, the communication module must
be selected as source for this information. See the user
documentation of the drive for information on the selection
parameters.
Programming
28
Programming
29
Communication
Overview
This chapter describes the PROFIBUS messaging used in the
communication with the drive.
PROFIBUS-DP
The RPBA-01 module supports the PROFIBUS-DP protocol
according to EN 50170 standard. PROFIBUS-DP is a distributed
I/O system which enables the master to use a large number of
peripheral modules and field devices. The data transfer is mainly
cyclic: the master reads the input information from the slaves and
sends the output information back to the slaves.
The PROFIBUS-DP protocol uses so-called PPOs
(Parameter/Process Data Objects) in cyclic communication. See
Figure 6 for the different PPO types and their composition.
Communication
30
Communication start-up
The following Service Access Points (SAPs) are used to initiate
DP communication:
SAP no. Short Name Name
61 Set_Prm Send Parameter Data
62 Chk_Cfg Check Configuration Data
60 Slave_Diag Read Slave Diagnostic
128 Data_Exch Transfer Input and Output Data
SAP 61 (Set_Prm)
This SAP is used in the parameterisation of the drive.
Prm_Data (Parameter Data Standard)
Type: Octet String - Length: 8
Byte Value Description
0 B8h Station_Status
1 0 1 1 1 0 0 0
Reserved
WD_On
1 = Watchdog on
Freeze_Req
1 = Slave is requested to process in freeze mode
Sync_Req
1 = Slave is requested to process in SYNC mode
00 = Min TSDR and slave-related
Unlock_Req parameters may be overwritten
10 = Slave locked for other masters. All
Lock_Req parameters can be carried over
x1 = Slave released for other masters
Communication
31
Reserved
Communication
32
Communication
33
SAP 60 (Slave_Diag)
This SAP gives diagnostic information on the slave station.
Diag_Data (Diagnostic Data)
Type: Octet String - Length: 6 (Standard) + 2 (Extended Diagnosis)
Byte Description
1 Station_Status_1
x x x x x x x x
Diag.Station_Non_Existent (Set by Master, reset by Slave)
Slave not found
Diag.Stagion_Not_Ready (Set by Slave)
Slave not ready for data exchange
Diag.Cfg_Fault (Set by Slave)
Received configuration data does not match original configuration data
Diag.Ext_Diag (Set by Slave)
Diagnostic entry present in slave-specific diagnostic area
Diag.Not_Supported (Set by Slave)
Service not supported by slave
Diag.Invalid_Slave_Response (Set by Master, reset by Slave)
Invalid response by slave
Diag.Prm_Fault (Set by Slave)
Invalid parameter or parameter value
Diag.Master_Lock (Set by Master, reset by Slave)
Slave is parameterised by another master
2 Station_Status_2
x 0 x x x 1 x x
Diag.Prm_Req (Set by Slave)
Slave requires re-configuration and re-parameterisation
Diag.Stat_Diag (Set by Slave)
Static diagnosis. Slave (temporarily) unable to provide valid
data
Communication
34
Reserved
4 Diag.Master_Add
The address of the master that parameterised this slave
5 - 6 Ident_Number (for RPBA-01: 0812h)
7 Ext_Diag_Data
The number of bytes reserved for Extended Diagnosis
(including this byte)
Fixed to 2
8 Ext_Diag_Data
Bit 0 = Communication temporarily lost
Bit 1 = Communication permanently lost
Bit 2 - 7 = Not used
Communication
35
Type 1
Type 2
Type 3
Type 4
Type 5
Parameter Identification:
ID – Parameter Identification
IND – Index for Arrays
VALUE – Parameter Value (Max. 4 bytes)
Process Data:
CW – Control Word (see Table 7.)
SW – Status Word (see Table 8.)
REF – Reference
ACT – Actual Value
PZD – Process Data (application-specific)
DS – Data Set
DW – Data Word
Communication
36
References
References are 16-bit words containing a sign bit and a 15-bit
integer. A negative reference (indicating reversed direction of
rotation) is formed by calculating the two’s complement from the
corresponding positive reference.
ABB drives can receive control information from multiple sources
including analogue and digital inputs, the drive control panel and a
communication module (e.g. RPBA-01). In order to have the drive
controlled through PROFIBUS, the communication module must
be defined as the source for control information, e.g. Reference.
In the Vendor Specific mode, the scaling of the integer received
from the master as Reference is drive-specific. See its
programming manual for available control source selections and
Reference scaling factors.
In PROFIdrive mode, the speed reference (REF) in hexadecimal
(0…4000h) corresponds to 0…‘motor nominal speed’.
Actual Values
Actual Values are 16-bit words containing information on the
operation of the drive. The functions to be monitored are selected
by a drive parameter. The scaling of the integers sent to the
Communication
37
Communication
38
Communication
39
Communication
40
SWITCH-ON
MAINS OFF INHIBIT (SW Bit6=1)
C D ENABLE
OPERATION (SW Bit2=1)
A (CW Bit4=0 Bit5=0 Bit6=0)
(CW Bit5=0) (CW Bit4=1)
Inching 1 or 2 ON
(CW Bit8=1 or Bit9=1)
D RFG: ENABLE
OUTPUT INCHING 1
B or
(CW Bit6=0) (CW Bit5=1) INCHING 2
ACTIVE
RFG: ENABLE Inching 1 or 2 OFF
state ACCELERATION (CW Bit8=0 or Bit9=0)
C
(CW Bit6=1) Inching pause
condition
rising edge OPERATING ‘n=0 or f =0’ and ‘I=0’
of the bit (SW Bit8=1) and inching pause expired
D
Communication
41
Parameter
Identification Process Data
CW REF
ID IND VALUE SW ACT (PD1, PD2...)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Request Label
Response Label Parameter Number (PNU)
*Request Signal
*Not used (=0)
Communication
42
Communication
43
Drive parameters
Range Example
Index Sub-index Request Label
(Decimal) No.
0h 65h 101
0h 66h 102
R/W 6/7 1, 2
•••
27h 0Fh 9999
Communication
44
PROFIdrive parameters
Range Example
Index Sub-index Request Label
(Decimal) No.
2h 2
3h 3
393h 915 R/W 6/7 6
••• •••
9h 9
2h 2
3h 3
394h 916 R/W 6/7 7
••• •••
9h 9
396h 0h 918 R/W 1/2 3, 4
•••
0h 1
9h 9
11h 17
3B3h 947 R 6 5
19h 25
21h 33
29h 41
•••
3CCh 0h 972 R/W 1/2 3,4
Communication
45
Req 60 20 DB 00 00 00 00 00 04 7F 34 15 00 00 00 00 00 00 00 00
Resp 60 20 DB 00 00 00 00 64 03 37 34 15 00 00 00 00 00 00 00 00
Communication
46
Req 70 04 B2 00 00 00 00 64 04 7F 34 15 00 00 00 00 00 00 00 00
Resp 40 04 B2 00 00 00 00 64 03 37 34 15 00 00 00 00 00 00 00 00
Communication
47
Request 13 96 00 00 00 00 00 00 04 7F 34 15
Read:
Response 13 96 00 00 00 00 00 02 03 37 34 15
Communication
48
Request 23 CB 00 00 00 00 00 01 04 7F 34 15
Write:
Response 13 CB 00 00 00 00 00 00 03 37 34 15
Communication
49
Request 63 B1 09 00 00 00 00 00 04 7F 34 15
Read:
Response 43 B1 09 00 00 00 23 00 03 37 34 15
Communication
50
Req 73 93 03 00 00 00 04 B2 04 7F 34 15 00 00 00 00 00 00 00 00
Resp 43 93 03 00 00 00 04 B2 03 37 34 15 00 00 00 00 00 00 00 00
Communication
51
Req 73 94 03 00 00 00 00 68 04 7F 34 15 00 00 00 00 00 00 00 00
Resp 43 94 03 00 00 00 00 68 03 37 34 15 00 00 00 00 00 00 00 00
Communication
52
Communication
53
Fault tracing
LED indications
The RPBA-01 module is equipped with three diagnostic LEDs.
The description of the LEDs is below.
Host
ERROR
Indication
Off-line On-line
Green possible.
Off - Module is not On-Line
Lit - Module is Off-Line and no data exchange is
Red possible.
Off - Module is not Off-Line
Fault tracing
54
Host
ERROR
Indication
Off-line On-line
Fault tracing
55
PROFIdrive parameters
PROFIdrive parameters
56
PROFIdrive parameters
57
PROFIdrive parameters
58
PROFIdrive parameters
59
PROFIdrive parameters
60
PROFIdrive parameters
61
PROFIBUS definitions
Acyclic Communication in which messages are sent only once
Communication on request
Array Parameter consisting of data fields of equal data type
Broadcast Non-acknowledged message from master to all bus
participants (compare Multicast)
Command Word See Control Word
Communication Any object of a real device that can be communicated
Object with (variable, program, data range, etc.). Stored locally
in the Object Dictionary.
Control Word 16-bit word from master to slave with bit-coded control
signals (sometimes called the Command Word).
Cyclic Communication in which Parameter-/Process Data-
Communication Objects are sent cyclically at pre-defined intervals
Device Class Classification according to the number of profile
functions included in the device
Drivecast Broad- and Multicast, a special message frame for
drives
Fault Event that leads to tripping of the device
GSD File ASCII-format device description file in a specified form.
Each device (active & passive stations) on PROFIBUS
has to have its own GSD File.
Index Access reference for Objects in PROFIBUS
Information Report Non-acknowledged message from master to one or all
groups of bus participants
PROFIBUS abbreviations
The text in italics is the original German term.
.con Confirmation
.ind Indication
.req Request
.res Response
ACT Actual Value
Istwert
AK Request Label/Response Label
Auftragskennung/Antwortkennung
ALI Application Layer Interface
CR Communication Reference
Kommunikationsreferenz (Kommunikationsbeziehung)
DP Decentralised Periphery
Dezentrale Peripherie
DP-ALI Application Layer Interface for DP
DPV1 PROFIBUS-DP Extensions to the EN 50170 standard,
including e.g. acyclic data exchange
FDL Fieldbus Data Link
FMS Fieldbus Message Specification
FSU Manufacturer Specific Interface
Firmenspezifischer Umsetzer
HIW Main Actual Value
Hauptistwert
HSW Main Reference
Hauptsollwert
Technical data
RPBA-01
Enclosure:
34 mm
95 mm
20 62 mm
mm
Mounting: Into the option slot on the control board of the drive.
Degree of protection: IP 20
Ambient conditions: The applicable ambient conditions specified
for the drive in its Hardware Manual are in effect.
Hardware settings:
• Rotary switches for node address selection (address range
00 to 99)
• DIP switch for bus termination selection
Software settings:
• Input/Output/User Parameter data/Diagnostics format
• Maximum cyclic I/O data size: 244 bytes in, max 244 bytes out,
max. 416 bytes total
• Maximum User Parameter data/Diagnostics length: 237 bytes
Technical data
66
Connectors:
• 34-pin parallel bus connector
• 9-pin female DSUB connector
Current consumption:
• 350 mA max. (5 V), supplied by the control board of the drive
General:
• Estimated min. lifetime: 100 000 h
• All materials UL/CSA-approved
• Complies with EMC standards EN 50081-2 and EN 50082-2
Technical data
67
PROFIBUS link
Compatible devices: All devices compatible with the PROFIBUS-
DP protocol
Size of the link: 127 stations including repeaters (31 stations and
1 repeater per segment)
Medium: Shielded, twisted pair RS-485 cable
• Termination: built in the module
• Specifications:
Line A Line B
Parameter Unit
PROFIBUS-DP DIN 19245 Part 1
Impedance 135 to 165 100 to 130 W
(3 to 20 MHz) (f > 100 kHz)
Capacitance < 30 < 60 pF/m
Resistance < 110 – Ω/km
Topology: Multi-drop
Serial communication type: Asynchronous, half Duplex
Transfer rate: 9.6 kbit/s, 19.2 kbit/s, 45.45 kbit/s, 93.75 kbit/s,
187.5 kbit/s, 500 kbit/s, 1.5 Mbit/s, 3 Mbit/s, 6 Mbit/s, or 12 Mbit/s
(automatically detected by RPBA-01)
Protocol: PROFIBUS-DP
Technical data
68
Technical data
3AFE 64504215 REV E EN
EFFECTIVE: 13.10.2003