Anda di halaman 1dari 3

SWIMMING POOL

DEHUMIDIFICATION CALC

305 Sport Activity Building

Scenario 1: sweem meet

Pool evaporation
Wp = 4 E-5 A (pw - pa) Fa
Reference: 2011 Ashrae Handbook Applications 5.6
Water temperature (C) 27
Air temperature (C) 28
Relative humidity (%) 50
A: area of pool surface (m2) 325
pw: saturation vapor pressure taken at surface water
temperature, kPa 3.567
pa: saturation pressure at dew point, kPa 1.898
Fa: activity factor 1 Public
Wp: evaporation of water (kg/s) 0.021697
Wp: evaporation of water (kg/h) 78.1

Occupant load + Outdoor air


Occupation (Spectators) 156
Ventilation rate (Ashrae Standard 62.1 Table 6-1) (l/s/m2) 2.4
Swimming pool area (pool + deck) 770
Ventilation rate (Ashrae Standard 62.1 Table 6-1) (l/s/person) 3.8
Swimming pool Spectator area (Ashrae Standard 62.1 Table 6-1) (l/s/m2) 0.3
Spectator area (m2) 160
Outdoor ventilation (l/s) 2488.8

Humidification needed according to HAP calculation (kg/h) HR 44% (Winter) 77.67

Humidity balance
Evaporation - Occupant load - Outdoor air load (kg/h) 0.4

Conclusion scenario 1
Relative humidity 44%
SWIMMING POOL

DEHUMIDIFICATION CALC

305 Sport Activity Building

Scenario 2: occupation only with swimmers

Pool evaporation
Wp = 4 E-5 A (pw - pa) Fa
Reference: 2011 Ashrae Handbook Applications 5.6
Water temperature (C) 27
Air temperature (C) 28
Relative humidity (%) 50
A: area of pool surface (m2) 325
pw: saturation vapor pressure taken at surface water
temperature, kPa 3.567
pa: saturation pressure at dew point, kPa 1.898
Fa: activity factor 1
Wp: evaporation of water (kg/s) 0.021697
Wp: evaporation of water (kg/h) 78.1

Occupant load + Outdoor air


Occupation (Spectators) 12
Ventilation rate (Ashrae Standard 62.1 Table 6-1) (l/s/m2) 2.4
Swimming pool area (pool + deck) 770
Ventilation rate (Ashrae Standard 62.1 Table 6-1) (l/s/person) 3.8
Swimming pool Spectator area (Ashrae Standard 62.1 Table 6-1) (l/s/m2) 0.3
Spectator area (m2) 160
Outdoor ventilation (l/s) 1941.6

Humidification needed according to HAP calculation (kg/h) 53%HR (Winter) 77.9

Humidity balance
Evaporation - Occupant load - Outdoor air load (kg/h) 0.2

Conclusion scenario 2
Relative humidity 53%
Data references

Anda mungkin juga menyukai