Tank List Requirement for Kijing Port

No Description Capacity (m3) Material


1 Storage HSD Fuel for Filling Station 16 ASTM A36
2 Treated Water Tank 200 SS400
3 Drinking Water Tank 11.25 Stainless Steel
4 Roof Tank 10 FRP
5 Roof Tank 5 FRP
Qty
2
2
1
1
5
DATA PROPERTIES TANK DERMAGA KIJING

#REF!
Dimension ( m )
No Description / Document Title Code Used Type of Tank Roof Type Stair Type Qty Fluida Temperature deg Capacity Capacity + 10%
C m3 Diameter High Dia. Head

Tank List

1 Storage HSD Fuel for Filling Station ASME SECT. VIII or DIN 6616/D Horizontal Elliptical Head Ladder c/w top handrail 2 HSD oil Ambient 16 17.60 2.20 3.90 2.20
or DIN 6624 or Equal

2 Treated Water Tank AWWA D100 / API 650 Vertical with Conical Roof Conical Roof Ladder c/w top handrail 2 Water Ambient 200 220.00 6.20 7.28

3 Drinking Water Tank AWWA D100 / API 650 Vertical with Conical Roof Conical Roof Ladder c/w top handrail 1 Water Ambient 11.25 12.38 2.08 3.64

4 Roof Tank manufacture standard manufacture standard - 1 Water Ambient 10 11 2.20 2.65

5 Roof Tank manufacture standard manufacture standard - 5 Water Ambient 2 2.2 1.36 1.38

Note:

1 : Sight glass HT = Hydro Test


2 : Level indicator (Dial type) LT = Leak Test
3 : Temperature transmitter LP = Liquid Penetrant Test
4 : Relief valve MS = Manufacture Std
5 : dip stick level
6 : pressure transmitter
7 : Level transmitter
8 :All dimensions are for reference only

NOZZLE
Dimension nozzle ( inch )
No Description / Document Title Pressure / Level Thickness
Shell manhole Roof manhole Filling Outlet Over flow Drain PSV Sampling Temp. Venting
Ind.

Tank List
1 Storage HSD Fuel for Filling Station 24" - 4" / sch.40 3" / sch.40 4" / sch.40 3" / sch.40 3'' / sch. 40 1'' / sch. 40 2'' / sch. 40 3" / sch.40 2'' / sch. 40 as per code
2 Treated Water Tank 24" 24" 4" / sch.40 3" / sch.40 3" / sch.40 3" / sch.40 3" / sch.40 2'' / sch. 40 as per code
3 Drinking Water Tank 24" 24" 4" / sch.40 3" / sch.40 3" / sch.40 3" / sch.40 3" / sch.40 2'' / sch. 40 as per code
4 Roof Tank Manufacture Standard
5 Roof Tank Manufacture Standard

Note:
All nozzle dimensions are for reference only

EXTERNAL PAINTING
EXTERNAL PAINTING
No Description / Document Title Surface Prep' (workshop) Surface Prep' (site) Code Used Total DFT
1st 2nd 3rd (site)

Tank List
SSPC-SP1 - Solvent or
1 Storage HSD Fuel for Filling Station SSPC-SP10 - Blast clean or Sa. SSPC-SP3-63 - wire brush BS EN ISO 12944-1 350 µm
2,5

SSPC-SP1 - Solvent or
2 Treated Water Tank SSPC-SP10 - Blast clean or Sa. SSPC-SP3-63 - wire brush BS EN ISO 12944-1 as per code
2,5
3 Drinking Water Tank N/A N/A N/A
Thickness (mm) Material Est. Empty Est. Hydro Weight min. Accessories Min. Test. Req.
Weight (ton) (ton)

Shell plate= min.5 mm Shell plate = ASTM A36


Head plate = ASTM A36 1.6 19.20 3, 4, 5, 6 HT, LT, LP
Head plate = min.5 mm Saddle = ASTM A36

Bottom plate = 8 mm
Shell plate 1 = 6 mm Bottom plate = SS400
Shell plate 2 = min.5 mm Shell plate = SS400 10.906 230.91 2, 7 HT, LT, LP
Shell plate 3 = min.5 mm Roof plate = SS400
Shell plate 4 = min.5 mm
Roof plate = min.6 mm

Bottom plate = min.5 mm Bottom plate = SUS316


Shell plate 1 = min. 5 mm Shell plate = SUS316 2, 7 HT, LT, LP
Shell plate 2 = min.5 mm Roof plate = SUS316
Roof plate = min.5 mm

manufacture std FRP manufacture std

manufacture std FRP manufacture std

Material pipe

ANSI B16.5
ANSI B16.5
ANSI B16.5