A seismic

switch
RENATO PICCARDO, ANNUNZIO REGANTINI, DAVIDE CATTANEO, LUCIANO
Certified switchgear DI MAIO – A nuclear power plant must be able to manage an enormous

for nuclear power amount of energy in extremely safe conditions. All system functions
must be controlled with absolute reliability and guaranteed operation.
plants is providing a The equipment used must be able to withstand degradation over time
caused by exposure to environmental extremes of temperature, pres-
critical link in the sure, humidity, radiation and vibration, including earthquakes. ABB has
developed the UniGear ZS1 medium-voltage certified switchgear with
chain the aim of satisfying all critical requirements.

24 ABB review 1|11


1 Example of required response spectrum (RRS)

Acceleration (g)
1

0
10 20 30 40 50
Frequency (Hz)

operating basic earthquake (OBE) or, in and vibration, can hasten common-
case of a very strong earthquake, it must cause failures of qualified equipment. For
be able to shut down the reactor, known this reason it is necessary to establish a
as a safe shutdown earthquake (SSE). An “qualified life” for equipment with signifi-
additional requirement is verifying the cant aging mechanisms. Qualified life is
functionality of each component under the period of time before the start of a
very intense environmental conditions in design basis event for which equipment
terms of temperature/humidity and after has demonstrated that it meets the de-
a thermal/radiation aging process. sign requirements for the specified ser-
vice conditions [1].

P
eople working on nuclear proj- According to both IEEE and IEC stan-
ects know that attention to de- dards the following methods can be Climatic qualification (cyclic damp heat)
tail and only using equipment used to qualify system components The purpose of climatic qualification is to
that has been certified is cru- (alone or in combination): prove that the switchgear will continue to
cial: It is never acceptable to turn the key – Type testing: A type test subjects a perform its safety function before, during
of a nuclear plant until it is certain that representative sample of equipment, and after variation of the humidity and
every component playing a safety func- including interfaces, to a series of temperature levels in the environment
tion has been fully tested and certified. tests, simulating the effects of where the equipment will be installed. The
Detailed parameters for certification are significant aging mechanisms during test determines the suitability of equip-
specified in American IEEE 1 and Euro- normal operation. ment under conditions of high humidity
pean IEC 2 standards. – Operating experience: Performance combined with cyclic temperature chang-
data from the equipment in question es and production of condensation on the
The qualification process or from equip-
Every supplier of products for the safety ment of similar
chain of a nuclear power plant (NPP) design that has The system must be able to
must go through a specific qualification successfully
process, the purpose of which is to verify operated under continue functioning during
and certify complete reliability of system
components.
known service
conditions may
a so-called operating basic
be used in earthquake (OBE) or, in case
Some of the equipment in a NPP may qualifying other
also be required to operate under very equipment of a very strong earthquake,
intense conditions. This is why the main
purpose of a qualification process is to
under equal or
less severe
it must be able to shut down
verify the ability to operate during various conditions. the reactor
and well-defined environmental settings. – Analysis:
Qualification by
The critical scenario is the possibility of a analysis requires a logical as sessment surface of the equipment being tested.
seismic event: The system must be able or a valid mathematical model of the In medium-voltage (MV) switchgear, con-
to continue functioning during a so-called equipment. densation produced during humidity-tem-
perature cycles can cause a reduction in
Degradation over time, along with expo- the isolating properties.
Footnotes
1 Institute of Electrical and Electronics Engineers sure to environmental extremes of tem-
2 International Electrotechnical Commission perature, pressure, humidity, radiation

A seismic switch 25
maintain it in a safe shutdown condition,
2 The climatic testing cycle of the Doel NPP qualification
are designed to remain functional.
cycle 6
100 EMC qualification
Ur% max
95
The equipment must also be qualified to
90
Ur% min Ur% ensure full availability of the safety func-
85
80 Ur% max tion in case of high electromagnetic
75 Ur% min stress, which may occur during accident
70 conditions. Two types of testing, which
Ta°C/Ur%

65
Ta
reproduce the actual configuration of the
60
instrumentation and control (I&C) devic-
55
50 es installed in the primary equipment,
Ta
45 including wiring, are performed on all of
Ta max
40 the equipment.
35 Ta min
30
Immunity testing: Electromagnetic com-
25 Ta
20 patibility (EMC) qualification tests are
performed in order to verify the level of
3/2/09 9.10 AM

3/2/09 10.10 AM

3/2/09 11.10 AM

3/2/09 12.10 AM

3/2/09 1.10 PM

3/2/09 2.10 PM

3/2/09 3.10 PM

3/2/09 4.10 PM

3/2/09 5.10 PM

3/2/09 6.10 PM

3/2/09 7.10 PM

3/2/09 8.10 PM

3/2/09 9.10 PM

3/2/09 10.10 PM

3/2/09 11.10 PM

4/2/09 12.10 AM

4/2/09 1.10 AM

4/2/09 2.10 AM

4/2/09 3.10 AM

4/2/09 4.10 AM

4/2/09 5.10 AM

4/2/09 6.10 AM

4/2/09 7.10 AM

4/2/09 8.10 AM

4/2/09 9.10 AM
immunity of the equipment from electro-
magnetic disturbance in a broad fre-
time
quency range.

Emission testing: Electromagnetic emis-


Seismic and airplane impact test qualification sions radiated and conducted on the wires
The ABB Compe- IEC 60980 [2] and IEEE 344 [3] standards by each piece of electrical equipment are
represent the two main reference stan- measured over a broad spectrum.
tence Center dards for the seismic qualification of

l ocated in Dalmine, safety electrical equipment for nuclear


power stations. The response spectra
Detailed functional tests are performed on
all of the I&C functions, such as protec-
Italy, has several are not defined in either standard, since tion or control functions integrated into a
they can vary depending on the geo- single piece of equipment. The software
recent references graphic area and building structure. They qualification process follows IEC stan-
are therefore normally defined in techni- dards specifically developed for NPPs;
for medium voltage cal project specifications. these are described in IEC 60780 [4].
switchgear for
A time-history seismic test usually con- The ABB answer
nuclear plants in sists of a tri-axial independent multifre- ABB has the products, the expertise and
quency test performed on the basis of the technical means to ensure that all
Europe: Tihange time histories (plots of the acceleration NPP requirements are met. The ABB
and Doel in Bel- as a function of time) artificially synthe-
sized from a given required response
Competence Center located in Dalmine,
Italy, has several recent references for
gium, Cernavoda spectrum (RRS). The RRS takes into ac- MV NPP switchgear in Europe: Tihange
count the characteristics of the geo- and Doel in Belgium, Cernavoda in Ro-
in Romania, Oskar- graphic location and of the supporting mania, Oskarsham in Sweden and Leib-
sham in Sweden structure or building £ 1. The time-his-
tory method is considered the best way
stadt in Switzerland. For each of these
projects, ABB’s products underwent a
and Leibstadt in to simulate seismic loads during the rigorous qualification procedure. This
qualification of equipment. process verified equipment functionality
Switzerland. in the case of seismic events and severe
During the seismic test the following environmental conditions.
earthquakes are simulated:
OBE/S1: an earthquake that produces In addition to ABB’s own products, labo-
accelerations where features for contin- ratories and know-how, the company also
ued operation without risks to public can rely on a dedicated partnership with
safety are designed to remain functional. state-of-the-art laboratories located near-
SSE/S2: an earthquake that produces by containing, for example, a triaxial
accelerations for which certain struc- shake table; in addition, ABB can call on
tures, systems and components neces- a team of experts on structures for seis-
sary to ensure the integrity of the reactor mic events. Software simulations of seis-
coolant pressure boundary as well as the mic events can provide many advantages
capability to shut down the reactor and for nuclear projects since no prototype is

26 ABB review 1|11


3 Seismic test arrangement on UniGear ZS1 4 Example of numerical evaluation of the struc- 5 Example of amplified deformation on
during Doel NPP qualification ture used for analytical seismic qualification UniGear ZS1 structure

needed, therefore achieving shorter ment is used for distribution of energy piece of equipment that has voltage
scheduling times and a reduction in costs. supplied by diesel emergency generators. transformers fitted onto removable
trucks. As required in the contract, the
In 2009, Areva NP, an engineering, pro- The equipment supplied was qualified replacement of all circuit breakers and
curement and construction (EPC) leader according to IEEE 323 and 344 stan- VT trucks took place within 2010; the
in NPPs, certified that the ABB Compe- dards and customer specifications, site activity was performed along two
tence Center satisfies the conditions for which included a request for climatic and years, during the annual routine mainte-
“planning and production of medium volt- seismic tests £ 2. A specimen switch- nance shut-downs.
age switchgear for nuclear power plants.” gear was identified so that all of the char-
acteristics that were part of the supply The qualification process was conceived
MV Switchgear – UniGear ZS1 were included. A qualification program in two different steps. Industrial and
Medium-voltage switchgear is one of the was implemented on these proto- nuclear qualifications were based on IEC
most important links in the power distri- types £ 3, achiev-
bution chain. ABB has developed the ing a successful
UniGear ZS1 switchgear with the aim of outcome. Medium-voltage switchgear
satisfying all users’ requirements. Uni-
Gear ZS1 is a combination of consoli- The Tihange Nu- is one of the most important
dated solutions and innovative compo-
nents from ABB. The MV switchgear is
clear Plant is the
other large-scale
links in the power distribution
suitable for indoor installations. Metal NPP in Belgium. chain. ABB’s UniGear ZS1
partitions segregate the compartments The primary stake-
from each other and the live parts are holder in the plant switchgear is a combination
air-insulated. The range of apparatus for is again the Bel-
UniGear ZS1 switchgear is the most gian energy com-
of consolidated solutions and
complete available on the market, and pany Electrabel. innovative components from
includes vacuum and gas circuit break- The plant has three
ers and vacuum contactors with fuses. pressurized water ABB.
reactors (PWRs),
Industry applications has a total capa city of 2,985 MWe and and IEEE standards for MV apparatus
Doel is one of two large-scale NPPs in makes up 52 percent of the total Belgian and switchgear, as well as on the cus-
Belgium. The Belgian energy corporation nuclear generating capacity. tomer’s technical specifications. Seismic
Electrabel, part of the GDF SUEZ group, is tests were performed according to IEEE
its largest stakeholder. In 2009 ABB sup- ABB has retrofitted 344 breakers made standards at CESI-ISMES laboratories.
plied MV switchgear comprising 18 Uni- by CEM Gardy, with HD4 SF6 breakers.
Gear ZS1 panels with 12 kV / 1,600 A / On site there are 354 circuit breakers The Oskarshamn nuclear power station
50 kA ratings and equipped with ABB HD4 (including 35 spares) and 34 VT trucks is one of ten active nuclear power sta-
SF6 insulated circuit breakers. ABB equip- (including seven spares). A VT truck is a tions in Sweden. With three reactors, the

A seismic switch 27
Because circuit breakers operate open-
ZS1 switchgear
ing and closing currents, as opposed to
other switchgear components that are
static, in most cases breakers are the
equipment most prone to aging. There-
fore breakers are the components that
are generally in the worst condition and
replacing them with new ones is the best
solution.

ABB has already performed retrofits on


its own as well as competitors’ breakers.
The most extensive job was performed
at the Tihange NPP where ABB retrofit-
ted 344 CEM Gardy breakers with HD4
SF6 breakers.

plant produces about 10 percent of the


In addition to electricity needs of Sweden and its reac-
tors use boiling water reactor (BWR)
ABB’s own prod- technology.
ucts, laboratories In 2009 ABB supplied four MV switch-
and know-how, gear installations, each of them com-
prising seven UniGear ZS1 panels with Renato Piccardo
the company also a 12 kV / 1,600 A / 50 kA rating and Annunzio Regantini

can rely on a dedi- equipped with ABB HD4 SF 6 breakers.


As at Doel, ABB equipment is used for
Davide Cattaneo
Luciano Di Maio
cated partnership power distribution supplied by diesel ABB Power Products, Medium Voltage Products
generators for emergencies and the Dalmine, Italy
with state-of-the- equipment supplied was qualified ac- renato.piccardo@it.abb.com

art laboratories. cording to IEEE 323 and IEEE 344 stan-


dards, as well as the customer’s speci-
annunzio.regantini@it.abb.com
davide.cattaneo@it.abb.com
fications, which required seismic luciano.di_maio@it.abb.com
qualification.
References
Seismic qualification of the MV switch- [1] IEEE 323 IEEE standard for qualifying class 1E
gear was performed by both analytical equipment for nuclear power generating
and testing methods. Both of these stations.
[2] IEEE 344 Recommended practices for seismic
were carried out in collaboration with the
qualification of class 1E equipment for nuclear
CESI-ISMES laboratories located a few power generating stations.
kilometers from the ABB MV switchgear [3] IEC 60780 Nuclear power plants – Electrical
factory £ 4, £ 5. equipment of the safety system – Qualification.
[4] IEC 60980 Recommended practices for seismic
qualification of electrical equipment of the safety
Modernization of existing NPPs system for nuclear generating stations.
Retrofitting is the implementation of
modern components (primary switching
Further Reading
devices and digital protection/control EN 61000-4 Series Electromagnetic compatibility
technology) in existing MV installations. – Testing and measurement techniques.
The aim of this modernization is to
replace only those components that are
Title picture
planned for replacement according to Seismographs are used to record both real
their expected life cycle. earthquakes and to monitor shake-table testing.

28 ABB review 1|11