aumia (india) pvt itd Operation instruction SA 3 -SA 100 SAR 3 - SAR 100 ae t Ga Aste rely o ne Ne no NC CAUTION Thermo switches are provided to protect Motor windings, These should be connected in panel control circuit (Refer Terminal Plan) else our warranty in void. Electric connection or 3 phase AC - motors: Check whether terminal inks are fitted 0 suit tape of motor and power supply (Ra. 1). Connect wires ReS-1 to terminal pias U,-V;-W, (fa. 2). for lame proof enclosure at clip-on terminals. or single - phase or DC - motors seo instructions in terminal compartment Connect controt wires according to wiring diagram. Terminal plan s inside the terminal comparment. Note: The two cireuts of each suttch fia. 3).are suitable only for the same potential, Remove cover at switch compartment (fg. #). Check whether limit-switck has tipped (ig. 5). Valve completely dosed: W5R tripped Valve completely opened : WOL érippedt Engage manual drive ‘Pusk decluich lever as indicated by arrow (fi. 6). resistance is felt turn handwheet slowly white lover is procsed tll manual drive engages. Operate oalve to incermediate postion manuadly (Ae. 7) Direction OPEN (=) vurn hendwheel ante-clockuise, Direction CLOSED (XE) turn handwheet clockwise. Switeh cam at 1) or “= (0) should rotate 90" aud release the Switch (fg. 8). f set property, Ensure sealing faces at control plug are clean and check whether O-ring is ok apply thin film of ron- facie greese to sealing faces, then replace plug cover Gig. 9.