Anda di halaman 1dari 11

Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.

org

A Survey of Arc Flash


Computation Methods and
Mitigation Strategies
By Dr. Carl J. Spezia

ABSTRACT industrial accident. Proper system


A robust, reliable, and safe electric design and work rules can minimize the
power system is essential to productive impact of an arc flash incident on both
Carl J. Spezia is an Assistant Professor in the industrial operations. Plant personnel workers and equipment (Hill, Bruehler,
Electrical Engineering Technology Program in must maintain and operate the electric & Chmura, 2004).
the Department of Technology at Southern Il- power system without exposure to
linois University Carbondale (SIUC). He joined
the program in1998 as a Visiting Assistant Pro- dangerous electrical hazards. The arc Arc flash analysis determines the inci-
fessor. He has eight years of utility experience flash that accompanies electrical system dent energy exposure workers encounter
as a power systems engineer and is a licensed faults and operator errors exposes at various locations in an industrial
professional engineer in Illinois. His industrial electric power system. Incident energy
assignments included power system modeling,
workers to high temperature plasma,
power systems protection, and substation design. pressure shock waves, toxic gases, and values determine the level of personal
He received his M.S. and Ph.D. from SIUC in 1991 blast fragments. Arc flash can be dead- protective equipment (PPE) that work-
and 2002 respectively. He teaches courses in ly to personnel, cost millions of dollars ers require to prevent serious burns.
electric power and machinery, industrial automa- Analysis methods must produce reli-
tion, and electric circuits. He won outstanding to repair, and idle industrial facilities.
departmental teaching awards two of the last Without arc flash analysis and mitiga- able values of arc energies that do not
five years. His research interests include power tion strategies, workers must wear cum- grossly overestimate actual conditions.
systems economics, power markets, and electric Over protecting workers limits their
energy management.
bersome personal protective equipment
that can resist maximum arc energy or ability to operate and maintain electrical
work only on de-energized equipment. systems efficiently, but under protection
This paper surveys the computation exposes them to unnecessary risks. Arc
methods and mitigation technologies flash mitigation uses modified electri-
used to quantify and control arc flash cal equipment, protective device set-
hazards in industrial power systems. A tings, and work rules to restrict worker
review of analysis techniques compares exposure to high energy levels. These
algorithms used currently to determine modifications reduce the required level
incident energy. A presentation of cur- of PPE. The goal of arc flash analysis
rent mitigation technologies identifies and mitigation is to provide a safe work
their advantages and disadvantages in environment while operating and main-
the control of incident energy. A final taining industrial electrical systems with
section proposes future directions for minimal disruption.
research and development on arc flash
safety. Arc flash is a significant safety hazard
addressed by the Occupational Safety
INTRODUCTION TO ARC and Health Administration (OSHA)
FLASH HAZARDS standards since its inception in the
Arc flash is an electrical fault (short 1970’s. These standards evolved over
circuit) that propagates through air the last 33 years into NFPA 70E-2004
producing high temperature plasma. and IEEE 1584-2002. One standard,
Arc flash temperatures exceed 5000° NFPA 70E-2004, sets protective cloth-
F creating an intense light, a pressure ing requirements, defines the flash-pro-
shock wave, toxic gases, and blast frag- tection boundary, and includes calcula-
ments. Arc flashes produce concentrat- tion procedures for incident energy.
ed radiant energy that can cause severe The second standard, IEEE 1584-2002:
burns to unprotected workers (Fischer, “Guide for Performing Arc-Flash
2004). The numerous physical hazards Hazard Calculations”, presents math-
and high energies associated with arc ematical models and formulas derived
flash make it a dangerous and costly from empirical data for determining

2
Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.org

incident energy levels. In 2002, the Na- Table 1. Protective Clothing Classes
tional Electrical Code (NEC) included Description Class Weight ATPV
labeling requirements for electrical (HRC) (oz/yd2) (cal/cm2)
equipment to warn workers of the arc
flash hazard and list protective cloth- Untreated cotton 0 4.5-7 N/A
ing requirements (Ammerman, Sen Flame retardant (FR) shirt and pants 1 4.5-8 5
& Nelson, 2007). All these standards Cotton underwear plus FR shirt and pants 2 9-12 8
have the same goal of reducing worker
injuries due to arc flash burns. Cotton underwear plus FR shirt, pants and 3 16-20 25
coveralls
Arc flash accidents are high-cost/ Cotton underwear plus FR shirt, pants, coveralls 4 24-30 40
low probability events that make cost and multilayer flash suit
justifications for detailed studies and
extensive retrofitting difficult (Fischer, (Excerpt from Table 3-3.913 NFPA 70E-2004. ATPV is the incident energy that just
2004). A review of OSHA incidents causes the onset of a second degree burn.)
shows that human error causes up to 80
percent of electrical incidents. (In-
shaw, & Wilson, 2005) The policies Arc mitigation schemes should increase cation labeling throughout industrial
and procedures included in arc flash worker safety without compromising power systems.
standards give industrial managers the the reliability of the electrical system.
framework to promote safety by defin- Practical mitigation schemes may System voltage, fault current levels,
ing the training, tools, warning labels, temporarily sacrifice system reliability time, and proximity are all factors in
and PPE required to minimize injuries to lower incident energy levels and determining arc flash intensities. (Buff
and comply with OSHA guidelines. relax worker PPE requirements. The and Zimmerman, 2008) Relays, fuses,
Even though arc flash accidents are goal of arc flash analysis and mitigation molded-case (MCCB) and low-voltage
unlikely, they are costly when they is to find incident energies throughout power circuit breakers (LVPCB) pro-
occur. Analyzing and mitigating the the industrial power system and then vide fault protection in most industrial
arc flash hazard makes economic sense reduce these values to the lowest level. power systems. In radial systems,
when the analysis includes the costs of This will allow workers to maintain and fault current magnitudes diminish as
lost production, equipment repair, and operate plant electrical systems without the fault location moves further from
company liability. Arc flash analysis excessive PPE. High classes of PPE the source. System designers achieve
and mitigation schemes limit personal restrict mobility and visibility. The protection coordination by selecting
injury and electrical equipment dam- heavy weight fabrics and the full flash devices that have time-current char-
age to reduce repair and lost produc- suit specified for class 4 PPE locations acteristics that intentionally introduce
tion costs (Wilson, Harju, Keisala, & rapidly fatigue workers due to retained delay in device operation.
Ganesan, 2007). body heat (Doan, 2009).
Figure 2 shows fault current decay in a
Arc flash standards set PPE guidelines ARC FLASH ENERGY radial system as a function of distance
based on the incident energy levels COMPUTATION METHODS from a source. Proper protection coor-
near the arc flash. These guidelines Industrial electric power systems are dination requires that the highest cur-
define how workers should be clothed typically radial connected and fed rent levels at breaker 1 have the longest
to protect them from burns (Das, 2005). from medium voltage (15 kV class) time delay (Mason, 1956).
The threshold limit is 1.2 cal/cm2 , the systems. Transformers reduce this
onset of a second-degree burn. Table 1 voltage to secondary medium voltages ARC HAZARD ANALYSIS
shows arc thermal performance values (4.16 and 2.4 kV) for operating large USING NFPA-70E-2004
(ATPV) of protective clothing classes motors and further distribution to low Both arc flash standards include algo-
required for increasing levels of inci- voltage motor control centers (MCC’s). rithms for computing incident energy.
dent arc flash energy. The standards Industrial low voltage is typically 480 The detailed algorithms in each stan-
do not define PPE for incident energy V. Industrial power systems have low dard require short circuit calculations
levels greater than 40 cal/cm2. Incident impedance and operate at low voltage and protective device settings to deter-
energy levels at or above this level resulting in high fault currents and arc mine incident energy levels. The NFPA
require work on de-energized electrical energies. Figure 1 shows a one-line 70E-2004 standard includes tables of
equipment. These guidelines are only diagram of a simple industrial power common tasks and simple formulas to
for burn protection and do not address system with a three-phase fault located determine the PPE category without
other hazards of arc flash. at point F1. Current standards require detailed calculations.
arc flash analysis and hazard classifi-

3
Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.org

The first step in the NFPA-70E-2004 Figure 1. Typical Industrial Power System Showing Protective Devices.
algorithm is to determine the task per-
sonnel will perform. The next step is
to calculate the flash protection bound-
ary and determine if work on energized
equipment falls within this distance.
This standard uses the product of bolted
three-phase fault current and the total
clearing time to determine the flash
protection boundary. If the time-current
product is less than 300 kA-cycles then
the flash-protection distance is 4 feet.
Equations 1 and 2 compute the flash-
protection boundary for electrical sys-
tem and transformer faults respectively.

Dc =
2.65 ⋅ MVA bf ⋅ t (1)

Dc =
53 ⋅ MVA ⋅ t (2)

where:
Dc = distance that will just cause a
second-degree burn on a person (ft),

MVAbf = bolted three-phase fault power


(MVA),

MVA = power rating of transformer


(MVA). For transformers with
power ratings below 750 kVA,
multiply transformer power rating
by 1.25 Figure 2. Current-Distance Relationship in Radial Systems and Associated
Coordination Curves.
t = total clearing time (Sec)

Once the flash boundary is computed,


one of three methods finds the neces-
sary level of PPE for workers within
this distance. Figure 3 shows the basic
steps in these methods. Methods 1 and
2 are tabular techniques for finding the
hazard risk category (HRC). Method 1
uses Table 130-7(C)(9)(a) in the NFPA
70E-2004 to associate common work
tasks with an HRC (0-4). Method 2
uses a simplified table that determines
the appropriate level of PPE. These
tabular methods can substitute for more
detailed arc flash analyses but they
must be applied carefully.

4
Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.org

Figure 3. Steps for Finding the HRC Using the NFPA-70E-2004 Standard.

The tables only apply to listed tasks under the specified assumptions and cannot be extrapolated to other situations and circum-
stances (Graham, Hodder, & Gates, 2008). These assumptions place limits on fault current and protective device operating time.
Analysis using method three is necessary when fault currents and device operating time violate these limits.

The third method for conducting an arc flash analysis in NFPA 70E-2004 requires detailed system data but gives the most pre-
cise results. This algorithm finds the incident energy level in calories/cm2. The resulting incident energy then determines the
PPE category from Table 1. The steps for detailed arc flash analysis using the NFPA 70E-2004 standard are:
1. Use Equations (1) or (2) to determine the flash-protection boundary.
2. Determine the minimum worker approach distance to electrical equipment for the designated task. If the minimum
approach is within the boundary then continue with the analysis.
3. Find the bolted three-phase fault current at the work location. Use maximum and minimum arc-sustaining current values for
the remaining steps. (NFPA 70E-2004 defines minimum arc sustaining current at 480V as 38% of available fault current.)
4. Find total fault clearing time for the values in step 3.
5. Determine if work will be done in open air or inside an enclosure. Use the appropriate formula below to compute incident
energy.

Open air: E MA = 5271D A−1.9593 t A (0.0016F2 − 0.0076F + 0.8938) (3) (3)


Enclosure: E MB = 1038.7 D B−1.4738 t A (0.0093F 2 − 0.3453F + 5.9675) (4) (4)

Where: EMA = incident energy in open air (calories/cm2)


EMB = incident energy for enclosed box (calories/cm2)
DA = distance from electrodes (inches)
tA = maximum arc clearing time (Sec)
F = short circuit current (kA, range 16-50 kA)

6. If incident energy calculated from above is less than 1.2 Cal/cm2, flame retardant clothing may not be required to prevent
burns although protection may be needed for other hazards (Graham, Hodder, & Gates, 2008).
7. Determine the HRC and select the proper level of PPE from the incident calculations.

Calculations for the NFPA 70E-2004 standard produce conservative results for incident energy that tend to over-protect workers (Am-
merman, Sen, & Nelson, 2007). Equations (3) and (4) are based on theoretical concepts and models derived from a small test data set.
Electric arcs are complex phenomena that are difficult to model precisely (Stokes & Oppenlander, 1991), The standard is based on
research conducted using simplifying assumptions (Lee, 1982) that may not be suitable in general application.

5
Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.org

Figure 4. IEEE 1584-2002 Algorithm for Finding Arc Flash Hazards. The following formula computes
the actual incident energy for specific
Collect System
Determine Perform Short
Compute Arc
arcing time and personnel distance.
System Circuit Analysis
Data Fault Currents
Operating Modes (Bolted Faults)
 t  610 
x
E = 4.184C f E n 
 x  (7)
 0.2  D 
Determine Work Document Find Protective
Distance for Voltage and Equipment Where:
Equipment and Equipment Operating Times E = incident energy (J/ cm2)
Voltage Classes and Arc Duration
En = normalized incident energy
(J/ cm2)
Cf = calculation factor
Set PPE from t = arcing time (seconds)
Find Flash
Calculate Computed
Incident Energies
Protection
Incident Energies D = distance from arc point to person
Boundries
and HRC (mm)
x = distance exponent from table in
standard
ARC HAZARD ANALYSIS USING IEEE-1584-2002
The IEEE 1584-2002 standard presents another method for detailed arc flash analy- 8. Determine flash protection
sis. Figure 4 shows the steps in this algorithm with the following explanation. boundary using equation (8)

1. Gather power system and electrical equipment data. 1
2. Review system topology to determine different operating modes.   t  610  x
x

3. Calculate minimum and maximum fault currents and X/R ratios at work B = 4.184C f E n 
D   (8)
locations.   0.2  E B 
4. Find arc fault currents. This value is different from fault currents due to arc
resistance. Equations (5a) and (5b) compute this value for system voltages Where:
under 1 kV. DB = Boundary distance from arc (mm)
EB = Incident energy level at boundary
log10 ( I arc ) = K A + 0.662 log10 (I BF ) + 0.0966V...
(5a) (J/ cm2). This is usually set to the value
... + 0.000526g + 0.5588V log10 (I BF ) − 0.00304g log10 (I BF ) of 5(5a)
J/ cm2, which is the burn threshold
energy.
log10 ( I BF )
I arc = 10
(5b) (5proper
9. Select b) PPE category based
on incident energy and flash
Where: KA = -0.153 for open air or -0.097 for enclosure protection boundary.
IBF = bolted three-phase fault current (kA)
V = system voltage, (kV) The IEEE 1584-2002 method is quite
g = electrode gap (mm) complex and requires extensive cal-
culations. The standard comes with
5. Use protective device characteristics to find total arc clearing time. spreadsheet software for making these
6. Determine working distance to energized equipment. calculations.
7. Equations (6a) and (6b) determine normalized incident energy at each work
location. The equations are normalized to an arc time of .200 second and a The equations in IEEE-1584-2002
working distance of 610 mm. derive from fitting extensive test data
statistically to a model. The relation-
log10 ( E n ) = K1 + K 2 + 1.081 log10 ( I arc ) + 0.0011g (6a)(6a) ship of the variables produces a good fit
to the data but also results in anomalous
E n = 10log10 ( E n ) (J/cm2) (6b)(6b) results for certain ranges of parameters
(Wilkins, Allison, & Lang, 2005).
Where: K1 = -0.792 for open air and -0.555 for enclosure
K2 = 0 for grounded and -0.113 for ungrounded systems Both detailed analysis techniques pre-
sented above use approximations and
Applying specific case values of clearing time and working distance converts this simplifications of the problem to arrive
value to actual incident energy values. Distance exponents for different types of at the incident energy. The electric
equipment model energy dissipation with distance (Buff & Zimmerman, 2008). arc in open air is difficult to represent

6
Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.org

mathematically (Stokes, & Oppenland- Table 2. Arc Fault Analysis Comparison


er, 1991). A mathematical model must
include randomness, arc interruptions, Analysis Method Data Computational Limitations
and plasma characteristics to represent Requirement Effort
accurately an electrical arc in air. The NFPA-70E-2004 Method Must not violate given
standards use a combination of theoret- 1 - Matrix Table Low No Calculation assumptions. Does not
ical models (Lee, 1982) and laboratory Required cover all work tasks
tests. The algorithms omit contribu- NFPA-70E-2004 Method Must not violate given
tions from induction and synchronous 2 - Simplified Table Low No Calculation assumptions. Does not
motors. They also use symmetrical Required cover all work tasks.
fault current values that ignore DC NFPA-70E-2004 Must apply energy
offsets. The existing algorithms rely on Method 3 – Detailed formulas within speci-
symmetrical, three-phase fault current, Analysis Moderate Moderate fied fault current ranges.
but most faults start as line-to-ground Need total device
faults and progress into a three-phase operating time and work
fault. Significant energy dissipates distance
during the transition that is damaging to
IEEE-1584-2002 Voltage range: 208V to
equipment and dangerous to personnel.
Arc Hazard Analysis Moderate High 15 kV.
Current range: 700 –
COMPARISON OF 106,000 A
METHODS AND
CONTINUING RESEARCH
Tables 2 and 3 compare the methods Table 3. Comparison of Required Variables for Arc Analysis Methods
of determining HRC presented in the
NFPA-70E-2004 and IEEE-1584-2002 Required Variable NFPA- NFPA- NFPA- IEEE
standards based on data requirements, 70E-2004 70E-2004 70E-2004 1584-2002
required variables and computational Method 1 Method 2 Method 3
effort and limitations. System Voltage, V, V (kV) X X X X
The two tabular methods presented in Fault Current, F, Ibf (kA) X X X X
the NFPA standard require no calcula- Arcing Time tA, t (seconds) X X X X
tions to find the incident energies but
do require information from fault and Working distance (mm) X X
protection studies. The tabular methods Open/enclosed Equipment X
only apply within specified limits of
operating time and fault currents, which Conductor gap, G (mm) X
restricts their application. The de- System Grounding factor, K X
tailed analysis from the NFPA standard
computes arc flash energies with some Calculation factor, Cf X
additional data requirements above the Distance Factor, x X
tabular methods. This method requires
working distances, protective device
operating times and fault currents. The computations to find incident energy the fault current range of 20-30 kA.
method requires two calculations for and boundary distances for a single Beyond this range, the NFPA method
each work location and only applies to work location. over-estimates the incident energies
fault currents ranging from 16 – 50 kA. with respect to the IEEE method. This
Figures 5 and 6 compare the two over-estimate leads to conservative
The IEEE standard covers a wide range computations methods from the NFPA values of HRC and tends to overprotect
of voltages and fault current levels but and IEEE standards for a range of fault workers.
requires several computational steps to currents on a 480 volt solidly grounded
determine the incident energy levels. system. Working distance is 24 inches Figure 6 compares the arc flash protec-
This method requires conductor gap and conductor gap distance 25 mm. The tion boundaries produced by the NFPA
distances, system grounding, and work- total protective device operating time and IEEE methods. The boundary val-
ing distance values along with fault and is 0.3 seconds. Figure 5 compares the ues from the IEEE computations are all
protection data to compute the incident incident energy calculations for a fault significantly larger than corresponding
energy. The IEEE method requires six current range of 16-46 kA. The method value from the NFPA methods. This
produces nearly the same results over gives the IEEE method a more con-

7
Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.org

servative result with respect to worker Figure 5. Incident Energy Computation Comparison.
safety. The flash protection boundary
30
distance sets the minimum approach
distance of unprotected workers to
the electrical work zone. The NFPA HRC 3 E>25 cal/cm2
25
method uses the flash protection bound-
ary to determine if any further analysis

Incident Energy (cal/cm2)


must take place. If personnel perform 20
work within this distance, the standard Over-estimate
specifies application of one of the three Of Incident E
methods to determine the HRC and
15
level of PPE required.

Several researchers address issues 10


related to the analysis algorithms pre-
sented in the current standards. The al- HRC 2 8<E<25
gorithm in IEEE 1584-2002 is complex 5
and requires a computer spreadsheet
provided with the standard for effec-
tive use. Ammerman, Sen, and Nelson 0
(2007) conducted a sensitivity analysis 15 20 25 30 35 40 45 50
on the IEEE 1584-2002 equations. The Three Phase Bolted Fault Current (kA)
results were simplified regression equa-
tions that are ideal for prescreening NFPA-70E Method
work locations. Wu (2008) addressed IEEE-1584 Method
the absence of contributions from rotat-
ing machines in medium voltage arc
flash analysis by developing modified
equations that include fault current
decay factors. These equations com-
Figure 6. Comparison of Arc Flash Boundaries Produced by NFPA and
pute lower values of incident energy IEEE Methods.
than the IEEE 1584-2002 method. The
equations find fault current magnitudes 10
that decay over time which reduces arc
energy.

Time domain analysis gives detailed


solutions of faults and includes factors 8
omitted from the standards. Wilkins,
Allison, and Lang (2005) developed
a time domain model that includes
current limiting fuses. Their work
6
modeled the arc with a non-linear V-I
characteristic. Computations using
this model combined with system time
domain formulas give circuit currents,
voltages, powers, and energy. The 4
model results correlate well with ex-
perimental data.

ARC FLASH MITIGATION


TECHNIQUES 2
15 20 25 30 35 40 45 50
Arc flash energy depends on three key
factors: system voltage, fault current Three Phase Bolted Fault Current (kA)
magnitude and arc time. Industrial
power system owners have limited con- NFPA Method
trol over the first two factors, leaving IEEE Method

8
Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.org

only arc time as a controllable variable. Table 4. Arc Flash Mitigation Techniques
Protective relays, fuses, LVPCB, and
MCCB are the devices commonly used Technique Advantages Disadvantages
to provide fault protection in industrial
power systems. These devices all have High impedance Limits fault currents on Lowering fault currents
an inverse time relationship where grounding line-to-ground faults. without changing protection
higher currents cause the devices to (Wilson, Harju, Kei- Lowers fault currents. settings slows device response
operate faster (Gregory, Lyttle, & Well- sala, & Ganesan, 2007) and leads to higher arc ener-
man, 2003). gies. Has no impact on three-
phase faults.
A properly designed protection scheme Current-limiting fuses Very fast clearing Fuses are only current-limiting
will clear system faults with minimum (Doughty, Neal, Ma- time. Less than 8.3 ms. within specific range. Limited
interruption to electric supply. This calady, Saporita, & Interrupting fuse adds number of current-limiting
requires a time delay between pro- Borgwald, 2000). resistance and lowers arc fuse types.
tective devices that increases as the current.
device nears the fault current source. A
properly coordinated protection system Arc resistant switch- Special design redirects Must be included in design.
has the longest time delays nearest the gear (Hopper & Etzel, arc blast away from Expensive to retrofit.
utility source, which is where the high- 2008) workers.
est fault currents occur. Figure 2 shows
the relationship between fault current Reducing relay coordi- No changes in equip- Expenses are associated with
magnitudes and protection system time nation times ment or design. Uses coordination study. Cost high
delay. High fault currents produce (Buff & Zimmerman, existing protective relative to trip time decrease.
large incident energies and require the 2008) devices Could be unpractical for
most stringent level of arc flash PPE. LVPCP’s and MCCB’s due to
trip time uncertainty.
Table 4 summarizes arc flash mitiga-
Increase working dis- Requires no changes in May be impractical for some
tion techniques commonly applied in
tance electrical equipment. Re- cases. Expenses associated
industrial power systems (Buff & Zim-
(Inshaw & Wilson, duces arc energy as the with special tools and equip-
merman, 2007). Most of these tech-
2005) square of the distance ment. Longer times required
niques reduce arc flash incident energy
change. to complete tasks due to work-
exposure by shortening the protection
ing at distance.
system response time to the fault cur-
rent. Bus differential relaying, fast bus Arc flash detectors Very fast tripping times. Must be supervised by instan-
tripping, current limiting fuses, and (Inshaw & Wilson, (2-9 ms) Respond to taneous tripping device. Only
arc flash detectors all reduce incident 2005) high-intensity light applies to enclosed switch-
energy by shortening the tripping time produced by arcs. Oper- gear. Requires communica-
for a fault current. Arc flash detectors ates independently of tion between flash detectors
respond to the high intensity light emit- overcurrent protection. and existing protection.
ted from arc flashes and give the fastest
response of all these schemes. Current Bus differential relay- Fast response (< 24 ms). Requires additional relays,
limiting fuses can reduce fault-clearing ing Operates for any type of current transformers and wir-
times to 8.3 ms or less, but only within (Buff & Zimmerman, fault. ing. Expensive.
a specified range of fault currents 2008)
(Doughty, Neal, Macalady, Saporita, &
Borgwald, 2000). Fast bus tripping Uses overcurrent protec- Requires communication
(Buff & Zimmerman, tion and a communica- channels and special relays.
Other techniques in Table 4 modify 2008) tion channel to block Expensive
work rules or equipment settings to downstream faults but
reduce the energy exposure a worker applies fast tripping to
encounters. Increasing the distance bus faults.
between the worker and live electri- Maintains sensitivity and
cal protective equipment reduces the security of protection.
incident energy as the square of the Enable special protec- Operators enable instan- Risk of larger system outages
distance. “Hot sticks,” remote control tion settings during taneous tripping. Low due to higher relay sensitivity
tripping, and racking of breakers are all maintenance cost modification to during maintenance.
methods that reduce arc flash hazards. existing systems.

9
Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.org

Modifying system protection settings workers. A time domain representa- and retrofitting protection schemes.
either permanently or temporarily to tion that uses non-linear time-varying Implementing impedance relays using
reduce operating times also reduces the resistance to model arcs can give more this technology in low voltage systems
arc flash energy (Buff & Zimmerman, precise estimates of arc currents and can achieve high speed tripping over
2008). The use of maintenance settings incident energies. 80 to 90 percent of distribution feeders
on protective devices gives instan- at low cost. Hall-effect current sensors
taneous (<20 ms) tripping of break- Computer simulation programs such that do not saturate when subjected to
ers while workers are near energized as the Alternative Transients Program high currents can take the place of cur-
electrical equipment. Reducing device (ATP) (Canadian/American EMTP rent transformers with reduced cost and
coordination times can also reduce User Group, 2008) and MatLab with greater flexibility in retrofitting.
incident energy but may produce small Simulink (Mathworks, 2009) allow en-
reductions relative to the cost. gineers to build complex time-domain Technology cannot take the place of
representations of electrical networks. worker training and skill. Reducing
Lowering fault currents by using high These tools also have control systems the high percentage of electrical ac-
impedance grounding can increase modeling capabilities to represent pro- cidents attributed to personnel errors
rather than decrease arc energies. tective device behaviors. It is possible must be a priority. All maintenance
Reduced fault currents increase the to create a time domain models of an personnel and system operators must
response time of inverse time protective arc flash and system protective devices have continuing training on electrical
devices. This increased time causes using these tools, but field-testing must safety procedures and current industry
increased incident energies that can verify the results. Work should focus on practices regarding locking and tagging
lead to greater worker hazards. This the evolution of line-to-ground faults of industrial electrical equipment for
technique must be accompanied by a into three phase faults so that fault de-energized service. Worker training
detailed analysis of protective device exposure time can be minimized. should emphasize completing tasks in
coordination times. the safest way, not the easiest or fast-
Increasing the working distance is a est. Industrial maintenance supervisors
New or redesigned industrial power simply way of reducing the incident and management must make electri-
systems can employ new equipment energy in an industrial electric system. cal safety a priority. Industries should
technologies that reduce arc flash Secure wireless operation of breakers maintain electrical system diagrams in
hazards. Arc resistant switchgear would allow maintenance workers to an “as-build” or “as-operating” state
redirects arc blasts away from workers. stay outside the flash protection bound- to prevent accidents due to undocu-
Installing main breakers in MCC’s adds ary while operating energized electri- mented system changes. These draw-
another level of protection and reduces cal equipment with incident energies ings should be available to workers
fault-clearing times, resulting in lower greater than 40 cal/cm2. These devices as needed. Communication between
incident energy levels (Hopper & Etzel, will be part of the next generation of maintenance, operations and engineer-
2008). Incorporating arc flash safety electrical maintenance tools. ing personnel on the current state of the
into new designs and retrofits of exist- electrical system should promote a safe
ing systems gives the best results with Many of the mitigation techniques and efficient industrial operation and
the least cost. must have communication channels to reduce the risk of arc flash accidents.
transfer tripping and trip-blocking in-
FUTURE TRENDS IN ARC formation to other parts of the electrical This paper surveys the available
FLASH ANALYSIS AND system. Innovations in secure wireless literature on arc flash hazard analysis
MITIGATION communications between protective and mitigation techniques. This topic
The goal of arc flash analysis and devices will help reduce the costs of produces a large number of articles and
mitigation is to provide workers with implementing these schemes. Using research each year. This paper covers
enough protection to prevent second- ad hoc wireless networking would al- the main topics and a fraction of the on-
degree burns but to avoid over-protect- low low cost expansion of protection going work in the field. A comprehen-
ing workers so that they do not encoun- schemes with less set-up time. sive review of all topics and research is
ter a greater risk of heat stress and other beyond the scope of this paper.
injuries due to poor visibility and lim- Continued development of digital
ited movements. The current standards relays can extend to LVPCB’s and CONCLUSION
use algorithms based on experimental MCCB’s that have greater capabili- Arc flash accidents are very dangerous
data acquired from laboratory tests. ties and more flexibility than today’s industrial safety hazards that subject
These algorithms include simplifying models. Application of low-cost plant personnel to life-threaten levels
assumptions to make the problem trac- microcontrollers to produce alterna- of energy. These energy levels can
table and tend to over-estimate incident tives to time-overcurrent protection produce severe burns leading to death
energy levels. This results in selecting in industrial power systems will give for those within close proximity of the
higher PPE categories that over-protect designers more choices in designing arc flash. Two industry standards ad-

10
Journal of Industrial Technology • Volume 26, Number 2 • April 2010 through June 2010 • www.atmae.org

dress these hazards and give guidelines Buff, J., & Zimmerman, K., (2007). Hill, D. J., Bruehler L. W., & Chmura,
for computing incident energy, select- Application of existing technologies P.E. (2004). Designing, operat-
ing personal protective equipment, and to reduce arc-flash hazards, Power ing, and maintenance strategies to
labeling equipment to alert workers of Systems Conference: Advanced Me- limit arc flash energy exposure, 51st
arc flash dangers. Different levels of tering, Protection, Control, Commu- Annual Petroleum and Chemical
analysis exist for computing arc flash nication, and Distributed Resources, Industry Technical Conference, San
incident energy. The algorithms pre- Clemson, SC, March 13-16, 2007, Francisco, CA, Sept. 13-15, 2004,
sented in the standards derive from test 8-15. 339-349.
data and tend to produce conservative Canadian/American EMTP User Group, Hopper, W. S., & Etzel, B. L. (2008).
values. The goal of arc flash analysis (2008). Alternative transients pro- Distribution equipment moderniza-
and mitigation is to limit worker energy gram. Retrieved from http://www. tion to reduce arc flash hazards, IEEE
exposure through the use of appropriate emtp.org/ Trans. on Industry Applications,
levels of protective equipment. Overly Das, J. C. (2005). Design aspects of 44(3), 940-948.
conservative values lead to over-pro- industrial distribution systems to Inshaw, C., & Wilson, R. A. (2005). Arc
tected worker who are at risk of other limit arc flash hazard, IEEE Trans. on flash hazard and mitigation, 58th An-
injuries due to heat, visibility, or mobil- Industry Applications, 41(6), 1467- nual Conference for Protective Relay
ity. Future work on arc flash analysis 1475. Engineers, College Station, TX, April
should include further development of Doan, D. R. (2009). Designing a site 5-7, 2005, 145- 157.
time-domain models of system faults electrical system with arc flash Lee, R. (1982). The other electrical haz-
supported by high-power test data. energy under 20 cal/cm2, IEEE Trans. ard: electrical arc blast burns, IEEE
New models should produce better esti- on Industry Applications, 45(3) Trans. on Industry Applications, IA-
mates of incident energy values, which 1180-1183. 18(3), 246-351.
will provide workers with adequate Doughty, R.L., Neal, T. E., Macalady, T. MathWorks (2009). The MathWorks.
protection without requiring exces- L., Saporita, V., Borgwald, K. (2000). Retrieved from http://www.math-
sive PPE. Designing industrial power The use of low-voltage current-limit- works.com
systems for arc flash safety is the least ing fuses to reduce arc-flash energy, Mason, C. R. (1956). The Art and sci-
expensive method of complying with IEEE Trans. on Industry Applica- ence of protective relaying. New
current safety standards. Continued tions, 36(6), 1741-1749. York: John Wiley & Sons, Inc..
development of innovative low-cost, Electrical safety requirements for Stokes, A. B., & Oppenlander, W. T.
digital communication and protective employee workplaces, NFPA 70E. (1991). Electric arcs in open air,
devices will give plant management (2004). Quincy, MA: National Fire Journal of Physics D: Applied Phys-
lower cost alternatives for retrofitting Protection Association. ics, 24(1), 26-35.
existing systems to achieve compliance. Fischer, L. K. (2004). The dangers of arc Wilkins, R., Allison, M., & Lang, M.
flash incidents, Maintenance Tech- (2005). An improved method for arc-
REFERENCES nology, 17(2), 41-47. flash hazard analysis, IEEE Industry
Ammerman, R. F., Sen, P. K., & Nelson, Graham, A.M., Hodder, M. & Gates, G. Applications Magazine, 11(3), 40-48.
J. P. (2007). Arc flash hazard inci- (2008). Current method for conduct- Wilson, R. A., Harju, R., Keisala, J., &
dent energy calculations a historical ing an arc-flash hazard analysis, Ganesan, S. (2007). Tripping with
perspective and comparative study of IEEE Trans. on Industry Applica- the speed of light: arc flash protec-
the standards: IEEE 1584 and NFPA tions, 44(6), 902-1909. tion, 60th Annual Conference for
70E, 54th Annual Technical Confer- Gregory, G. D., Lyttle, I., &Wellman, Protective Relay Engineers, College
ence of the Petroleum and Chemi- C. M. (2003). Arc flash calculations Station TX, March 27-29, 2007,
cal Industry Committee, Calgary, in systems protected by low-voltage 226-238.
Alberta, Canada Sept. 17 - 19, 2007, circuit breakers, IEEE Trans. on Wu, A.Y. (2008). Modified medium
1-13. Industry Applications, 39(4), 1193- voltage arc flash incident energy
Buff, J. & Zimmerman, K. (2008). 1199. calculation method, 54th Annual Pulp
Reducing arc-flash hazards, IEEE Guide for arc flash hazard calculations, and Paper Industry Technical Confer-
Industry Applications Magazine, IEEE Standard 1584-2002. (2002). ence, Seattle, WA, June 22-27, 2008,
14(3), 40-47. New York, New York: The Institute 131-139.
of Electrical and Electronics Engi-
neers, Inc..

11
Copyright of Journal of Industrial Technology is the property of National Association of Industrial Technology
and its content may not be copied or emailed to multiple sites or posted to a listserv without the copyright
holder's express written permission. However, users may print, download, or email articles for individual use.

Anda mungkin juga menyukai