3. For all Pump Stations, Use the same Type of Fence instead of using different type for each pump station. The fence agreement greed priviously with Eng.Kinawi
General Notes (Structural):
Soil investigatoin report for shafts not for the building ,design
1. For Concrete Construction, Concrete compressive strength should be 300KG/cm2 as per the Soil Investigation procced on compressive strength in tender docoments refer
report. attachment.
3. Please clarify the use of two types of fence. Single type can be used or not as per Tender. The fence agreement greed priviously with Eng.Kinawi
SSEM COMMENT RAM REPLY
columns and footing arangment for fence and guard room pro
1. Please provide a layout showing the location of Guard House & other foundation for fence near to the Guard SEE DWG. NO RH1414-S-ML-FN-300 ,
House. RH1414-S-ML-GH-300,
2. Please also show the orientation of the Guard House by putting the North arrow. north direction alraeady provided for all building
3. Same size of fence columns is shown up the foundation while the up to Ground the size is OK. Below Ground for size of pedestal see see DWG. NO RH1414-S-ML-FN-300, the
level, was done based on details structural calculations, if you have
the column size should be bigger with a pocket at top to fix the precast fence column. Sample drawing is amendment calculation please provide us
attached.
columns and footing arangment for fence and sec room prov
1. Please provide a layout showing the location of SEC Room & other foundation for fence near to the SEC SEE DWG. NO RH1414-S-ML-FN-300 ,
Room. RH1414-S-ML-SEC-300
3. Please mark the north arrow to show the orientation of the room. north direction alraeady provided for all building
columns and footing arangment for fence and sec room prov
4. Please show the fence foundations near to the SEC room. SEE DWG. NO RH1414-S-ML-FN-300 ,
RH1414-S-ML-SEC-300
1. For the pads at roof, Please make it a part of roof slab instead of providing isolation joint b/w the pad & roof provided ,mechanical pad already monolithic with roof slab f
slab. building, see typical detail in DWG RH1414-s-ML-PH-304,
1. Please provide a layout showing the location of Tanks along with the Fence Foundations & check if there is Columns and footing arangment for fence ad other building alr
any conflict b/w foundations & tanks. provided ,see DWG. NO RH1414-S-ML-FN-300
2. Please provide the reinforcement details for the top slab as it will be casted at site. Noted
SSEM COMMENT RAM REPLY
3. Section – B, Provided reinforcement & dimensions are not correct. Please update as per plan & section – A. Noted
4. Details for protection below base slab, 100mm blinding concrete & 4mm thick waterproofing membrane is the layers agreed with Eng.Kinawi and we followed the layers pr
required while in the details, one additional layer of blinding concrete is provided above the waterproofing by whom in date 27-1-2019
membrane. Please update.
5. Top slab of Fuel Pump Pit, is it concrete slab or checkered plate. Please mention it & provide the details. Noted ,it will be checkered plate.
1. For the Pump House, monorail arrangement should be b/w Grid A&C instead of B&C as per Tender Document already modeifed see DWG No.DWg. No.RH1414-S-ML-PS-3
Page # 1184.
2. Please provide the complete connection details for the steel structure. already modeifed see DWg. No.RH1414-S-ML-PS-305
3. Section – 1, mentioned wall reinforcement @ Grid – B, T25@150, Please check as there is a conflict. All reinforcment in the said sectoin is T32 not T25 ,please clari
4. Please provide the fixing details of steel column to the concrete column. Provided, See DWg. No.RH1414-S-ML-PS-305 -Steel Connections
5. Please provide the details of concrete columns at Grid – B. Provided, See DWg. No.RH1414-S-ML-PS-305 -Planted column
the height of the internal walls exceeds than 3 meters, so from
6. Water stopper for the internal walls is not required, Please update the sections. technical point of view ,water stop must be used if you insiste
remove it please confirm this issue to be under your responsib
7. In sections the Reinforcement for the Base Slab is different (e.g. Section 4 & 10). Please check & correct. we don't have section 4 of section 10, please clarify ??
columns and footing arangment for fence and other building alraeady
provided ,see DWG. No RH1414-S-ML-FN-300
Soil investigatoin report for shafts not for the building ,design was
procced on compressive strength in tender docoments refer to
attachment.
columns and footing arangment for fence and other building alraeady
provided ,see DWG. No RH1414-S-MLl-FN-300
columns and footing arangment for fence and other building alraeady
provided ,see DWG. No RH1414-S-MLl-FN-300
columns and footing arangment for fence , sec and guard rooms
provided
See DWG. No RH1414-S-ML-FN-300 ,
DWG. No RH1414-S-ML-GH-300
DWG. No RH1414-S-ML-SEC-300
columns and footing arangment for fence and guard room provided
SEE DWG. NO RH1414-S-ML-FN-300 ,
RH1414-S-ML-GH-300,
provided ,mechanical pad already monolithic with roof slab for all
building, see typical detail in DWG RH1414-s-ML-GH-303,
RAM REPLY
columns and footing arangment for fence and sec room provided
SEE DWG. NO RH1414-S-ML-FN-300 ,
RH1414-S-ML-SEC-300
columns and footing arangment for fence and sec room provided
SEE DWG. NO RH1414-S-ML-FN-300 ,
RH1414-S-ML-SEC-300
provided ,mechanical pad already monolithic with roof slab for all
building, see typical detail in DWG RH1414-s-ML-PH-304,
Noted
:
Noted
RAM REPLY
Noted
the layers agreed with Eng.Kinawi and we followed the layers provided
by whom in date 27-1-2019
ral):
All reinforcment in the said sectoin is T32 not T25 ,please clarify ??
Provided, See DWg. No.RH1414-S-ML-PS-305 -Steel Connections Details
Provided, See DWg. No.RH1414-S-ML-PS-305 -Planted column detail
the height of the internal walls exceeds than 3 meters, so from our
technical point of view ,water stop must be used if you insisted to
remove it please confirm this issue to be under your responsibility
we don't have section 4 of section 10, please clarify ??
the design is optimized for durability and safty ,see calculation reports
and models , let us know if you have any justification
the design is optimized for durability and safty ,see calculation reports
and models , let us know if you have any justification