Tabel 2.

perhitungan Tingkat Pencahayaan


Kp Kd E A E A F1 n N total Nlampu = W1 Wtotal =
Ftotal 
kp  kd (lumen) Narmatur x n (Wa Nlampu x
Ruangan Ftotal
(Lux) (m2)  tt) W1
(lumen) F1  n (Watt) PHILIPS
1. Sortasi dan Loading
ramp 0.95 0.8 400 350 1800 2 18 36 26 936 PL-C
2. Pengelola
a. Pengelola 1 0.9 0.8 350 76.8 37333.33 3250 2 6 12 36 432 TL-D Super 80
b. Pengelola 2 0.9 0.8 350 76.8 37333.33 3250 2 6 12 36 432 TL-D Super 80
3. Bank
a. Bank 1 0.95 0.8 350 26.88 12378.94 3000 1 4 4 45 180 ECOTONE HL
b. Bank 2 0.95 0.8 350 26.88 12378.94 3000 1 4 4 45 180 ECOTONE HL
4. Lavatory 1
a. Lavatory Pria
ECOTONE
-toilet 1 0.9 0.8 250 3.36 1166.66 900 1 1 1 15 15 PLE-U
ECOTONE
-toilet 2 0.9 0.8 250 3.36 1166.66 900 1 1 1 15 15 PLE-U
-pedestal 0.9 0.8 250 15.6 5416.66 1750 1 3 3 25 75 ALTO
b. Lavatory Wanita
ECOTONE
-toilet 1 0.9 0.8 250 3.36 1166.66 900 1 1 1 15 15 PLE-U
ECOTONE
-toilet 2 0.9 0.8 250 3.36 1166.66 900 1 1 1 15 15 PLE-U
-pedestal 0.9 0.8 250 15.6 5416.66 1750 1 3 3 25 75 ALTO
Tabel 3. tabel katalog lampu Philips
Product Description Volt Watt Cap Color Lumen CRI
(V) Temp (lm) (Ra)
(K)
PL-C 220 26 G24 2700 1800 83
PL-C 220 20 G24 2700 600 87
ECOTONE PLE-U 220 15 G24 2700 900 83
ECOTONE PLE-U 220 20 G24 2700 1350 83
ECOTONE HL 220 45 G24 3000 3000 83
ECOTONE HL 220 65 G10 3000 4200 83
PL-L 220 36 2G1 3500 2900 82
PL-L 220 40 2G1 3500 3500 82
ALTO 220 25 GX2 2700 1750 82
ESENSIAL 220 25 G23 2700 1500 83
ESENSIAL 220 20 G23 2700 1250 83
TORNADO 220 20 G21 2700 1250 82
DECOTWIST 220 25 G21 2700 1700 83
TL-D Super 80 220 36 G13 5000 3250 83
TL-5 220 35 G13 5000 3300 83
ARENA VISION 220 1000 G40 5000 90000 87
Sumber: Philips;2008