FLAMMABLE AND COMBUSTIBLE LIQUIDS:
3404.29.66. The use ofa float vent valve shall be pro-
hibited
3404.2.9 Above-ground tanks. Above-ground storage of
lammable and combustible Fiquids in tanks shall comply
with Section 34062 and Sections 3404.2.9.1 dhrough
3404.29.6.10,
3404,2.9.1 Fire protection, Fire protection for
above-ground tanks shall comply with Sections
3404,2.9.1.1 through 3404.2.9.1.4,
3404.2.9.1.1 Required foam fire protection sys-
tems. When required by the fie code official, foam
fire protection shall be provided for above-ground
tanks, other than pressure tanks operating at or above
1 pound per square inch gauge tpsig) (6.89 KPa) when
such tank, or group of tanks spaced less than 50 feet
(15 240 nim) apart measured shell 0 shell as a lig-
uid surface area in excess of 1,500 square feet (139
and isin accordance with one of the following:
1, Used forthe storage of Class Lor I iquids.
2, Used for the storage of erude oil
3. Used for in-process produets and
within 100 feet (30 480 mm) of a
beater, related fractioning or processing apps
rats or similar device ata processing plant or
petroleum refinery as herein defined.
4, Considered by the fire code official as posing
‘an unusual exposure hazard because of topo=
raphical conditions: nature of occupancy,
proximity on the same or adjoining propery,
and beight and character of Fiquids to be stored:
degree of private fire protection to be provided:
and facilities of the fire department to cope with
lammable liquid fre.
34044.2.9.1.2 Foam fire protection system installa-
tion. Where foam fire protection is requited, it shall,
be installed in accondance with NEPA TL and NEPA,
nA.
3404,2.9.1.2.1 Foam storage. Where foain fice
protection is required, foan- producing materials
Shall be storod on the premises,
Exception: Storage of foam-producing materi~
als off the premises is allowed as follows:
1. Such materials stored off the premises
shall heof the proper type suitable for use
With the equipment at the installation
where require.
2. Such materials sll be readily available
athe storage location at all times.
3. Adequate loading and transportation
tailities shal! be provided.
1 time required 1 deliver such materi-
als to the required location i the event oF
Tire shall he consistent with the hazards
and fire seenarios for which the foam
supply is intended,
a8
5. Attbe time of a fire, these off-premises
Supplies shall be accumplated sn suffi
cient quantities before placing the equip-
ment in operation to ensure foam
production at an adequate rate without
interruption until extinguishment is,
accomplished,
3404,2.9.1.3 Fire protection of supports. Supports
‘or pilings for above-ground tanks storing Class, Hor
IITA igaids elevated more than 12 inches (305 mm)
above grade shall have a fire-resistance rating of not
less chan 2 hours in accordance with the fire exposure
itera specified in ASTM F 1529,
Except
1. Structural supports tested as part of a pro=
tected above-ground tank in accordance
‘with UL 2085.
2. Stationary tanks located ouside of buildings
hea protected by an approved water-sprty
system designed inaceardance with Chapter
and NEPA 1S,
3, Stationary tanks located inside of buildings
‘equipped throughout with an approved auto-
‘matic sprinkler system designed in acco
dance with Section 903.3.1.1
3404.2.9.1.4 Inerting of tanks with boilover liq-
tuids. Liquids with boilover characteristics shall not
be stored in fixed roof tanks larger than 150 fet (4S
"720 mun) in diameter unless an approved pos entich-
‘nent or inerting system is provided on the tank,
Exception: Crude oil storage tanks in production
fields with no ther exposures adjacent to the sto
age tank,
3404.2.9.2 Supports, foundations and anchorage.
Supports, foundations and anchorages for above-ground
tanks shall be designed and constructed in accordance
With NEPA 30 and the International Building Code,
3404.29.3 Stairs, platforms and walkways. Si
platforms and walkways shall eof noncombustiblecon-
Struction and shall be designed sad consteueted in aeeor-
‘dance with NFPA 30 and the Jmernational Building
Code.
3404.2.9.4 Above-ground tanks inside of buildings.
‘Tanks storing Class and ITA liquids inside buildings
shall be equipped with adeviee or other means to prevent
‘overflow into the building including, but not limited to: &
float valve:a preset meter onthe fill line; a valve actuated
by the weight of the tanks contents; a low head pump
Which is incapable of producing overflow: or a lig
uig-tight overflow pipe at least one pipe size larger than
the fll pipe and discharging by gravity back to the out
side source of liquid oF to an approved location
3404.2.9.5 Above-ground tanks outside of buildings.
‘Above-ground tanks outside of buildings shall eomply
with Sections 3404.2.9.5.1 through 408.2.9.5.3,