i4 Series Combination Carbon Monoxide(CO)/Photoelectric Smoke Detector

COSMO-2W (2-wire) Wiring Diagram

(2-wire)
PANEL
ALL CIRCUITS ARE SUPERVISED
i MODULE*
(EXCEPT4 TRIGGERS) AND MUST i4 DETECTOR
SMOKE BE POWER LIMITED

AUXPOWER
(resettable) **

Panel
SMOKE EOL
Resistors
ZONE
3.9k
RESISTOR
(supplied
with module)
CO
ZONE

MAINT. LOOP STYLE D / CLASS A WIRING


ZONE COSMOD2W
Panel
EOL COSMO-2W
Resistor
BELL
i4 MODULE TERMINALS
OR
SMOKE
TRIGGER OUT

CO POWER IN + SMOKE ZONE EOL RESISTOR


POWER IN – (VALUE DEFINED BY PANEL)
TRIGGER
CO ZONE EOL RESISTOR
OUT *** SMOKE ALARM CONTACT
(VALUE DEFINED BY PANEL)

MAINTENANCE TROUBLE RELAY CONTACT IDC +


(COSMOD2W ONLY)
DIP SWITCH CONFIGURATIONS IDC –
STYLE D/CLASS A + (4-WIRE DETECTOR POWER +)
DIP SWITCH # 1 DIP SWITCH # 2 DIP SWITCH # 3 CO ALARM CONTACT
STYLE D/CLASS A – (4-WIRE DETECTOR POWER –)
Smoke Maint on Smoke Trouble CO TRIGGER
ON SMOKE TRIGGER / BELL IN
Bell In and Form-B Maint Relay Unused
(DEFAULT) (COSMOD2W only)
Smoke Maint on Form-B
OFF Smoke Trigger Smoke maintenance Relay only Unused
(COSMOD2W only)
COSMOD2W
* Module is also compatible with 2WTA-B Smoke Detector
** Module requires resettable smoke power
***Triggers are optional and can be used to interconnect multiple modules with a bell output or positive voltage from the panel.
Please consult panel manufacturer for programming outputs
****Up to 12 detectors per module; models COSMO-2W or 2WTA-B only. Module interconnects sounders of both devices (RSS-MOD not needed).
 ©2013 System Sensor. COFL8102 • 7/13
i4 Series Combination Carbon Monoxide(CO)/Photoelectric Smoke Detector
COSMO-4W (4-wire) Wiring Diagram

(4-wire)
PANEL
ALL CIRCUITS ARE SUPERVISED
(EXCEPT4 TRIGGERS) AND MUST
i MODULE* i4 DETECTOR
SMOKE BE POWER LIMITED

POWER
(resettable)
Panel
SMOKE
EOL
EOL RELAY

Resistors
#EOLR-1

ZONE

3.9k
RESISTOR
CO (supplied
with module)
ZONE

COSMOD4W COSMO-4W

BELL
OR i4 MODULE TERMINALS
SMOKE
TRIGGER OUT

CO POWER IN + SMOKE ZONE EOL RESISTOR


POWER IN – (VALUE DEFINED BY PANEL)
TRIGGER
CO ZONE EOL RESISTOR
OUT ** SMOKE ALARM CONTACT
(VALUE DEFINED BY PANEL)

MAINTENANCE TROUBLE RELAY CONTACT IDC +


(COSMOD2W ONLY) IDC –
DIP SWITCH CONFIGURATIONS
STYLE D/CLASS A + (4-WIRE DETECTOR POWER +)
DIP SWITCH # 1 DIP SWITCH # 2 DIP SWITCH # 3 CO ALARM CONTACT
STYLE D/CLASS A – (4-WIRE DETECTOR POWER –)
Smoke Maint on Smoke Trouble CO TRIGGER SMOKE TRIGGER / BELL IN
ON
Bell In and Form-B Maint Relay Unused
(DEFAULT) (COSMOD2W only)
Smoke Maint on Form-B
OFF Smoke Trigger Smoke maintenance Relay only Unused
(COSMOD2W only)
COSMOD4W
* Module is also compatible with 4WTA-B Smoke Detector
** T
 riggers are optional and can be used to interconnect multiple modules with a bell output or positive voltage from the panel.
Please consult panel manufacturer for programming outputs
***Up to 12 detectors per module; models COSMO-4W or 4WTA-B only. Module interconnects sounders of both devices (RSS-MOD not needed). ©2013 System Sensor. COFL8102 • 7/13