ACUD PROJECT - EGYPT / PROCESS MAIN EQUIPMENT SCHEDULE for each DCP-1 & DCP-2 Rev.

01

Motor Power
S/N Service Duty Voltage (V) Starter Type Phase Brief on Capacity Description Remarks
(KW)
6,000 TR per module at zero tolerance conditions, Series counter flow arrangement,
1 Chiller -1 Lead (Hot Side) Continuous 3,300 RVSS 1 CHW 39.20 / 55.20 F in/out, 9,000 gpm flow rate & CW 87 / 99.5 F in/out, 14,000
3800 (total, R 513A or R 1233zde single of twin compressors / motors (2 or 4
gpm flow rate, compressors & motors sizes selected at stretched condensers +3 F
arranged in 2 or compressors / motors per module according to manufacturer
inlet conditions without capacity reduction. Module Minimum efficiency at zero
4 motors) selection).
2 Chiller -2 Lag (Cold Side) Continuous 3,300 RVSS 1 tolerance conditions 0.59 KW/TR. Maximum DP-Evaporator = 16 ft. at design flow &
26 ft. at 130 % flow and DP-Condenser = 20 ft. per Chiller .
6,000 TR per module at zero tolerance conditions, Series counter flow arrangement,
3 Chiller -3 Lead (Hot Side) Continuous 3,300 RVSS 1 CHW 39.20 / 55.20 F in/out, 9,000 gpm flow rate & CW 87 / 99.5 F in/out, 14,000
3800 (total, R 513A or R 1233zde single of twin compressors / motors (2 or 4
gpm flow rate, compressors & motors sizes selected at stretched condensers +3 F
arranged in 2 or compressors / motors per module according to manufacturer
inlet conditions without capacity reduction. Module Minimum efficiency at zero
4 motors) selection).
4 Chiller -4 Lag (Cold Side) Continuous 3,300 RVSS 1 tolerance conditions 0.59 KW/TR. Maximum DP-Evaporator = 16 ft. at design flow &
26 ft. at 130 % flow and DP-Condenser = 20 ft. per Chiller .
6,000 TR per module at zero tolerance conditions, Series counter flow arrangement,
5 Chiller -5 Lead (Hot Side) Continuous 3,300 RVSS 1 CHW 39.20 / 55.20 F in/out, 9,000 gpm flow rate & CW 87 / 99.5 F in/out, 14,000
3800 (total, R 513A or R 1233zde single of twin compressors / motors (2 or 4
gpm flow rate, compressors & motors sizes selected at stretched condensers +3 F
arranged in 2 or compressors / motors per module according to manufacturer
inlet conditions without capacity reduction. Module Minimum efficiency at zero
4 motors) selection).
6 Chiller -6 Lag (Cold Side) Continuous 3,300 RVSS 1 tolerance conditions 0.59 KW/TR. Maximum DP-Evaporator = 16 ft. at design flow &
26 ft. at 130 % flow and DP-Condenser = 20 ft. per Chiller .
6,000 TR per module at zero tolerance conditions, Series counter flow arrangement,
7 Chiller -7 Lead (Hot Side) Continuous 3,300 RVSS 2 CHW 39.20 / 55.20 F in/out, 9,000 gpm flow rate & CW 87 / 99.5 F in/out, 14,000
3800 (total, R 513A or R 1233zde single of twin compressors / motors (2 or 4
gpm flow rate, compressors & motors sizes selected at stretched condensers +3 F
arranged in 2 or compressors / motors per module according to manufacturer
inlet conditions without capacity reduction. Module Minimum efficiency at zero
4 motors) selection).
8 Chiller -8 Lag (Cold Side) Continuous 3,300 RVSS 2 tolerance conditions 0.59 KW/TR. Maximum DP-Evaporator = 16 ft. at design flow &
26 ft. at 130 % flow and DP-Condenser = 20 ft. per Chiller .
6,000 TR per module at zero tolerance conditions, Series counter flow arrangement,
9 Chiller -9 Lead (Hot Side) Continuous 3,300 RVSS 2 CHW 39.20 / 55.20 F in/out, 9,000 gpm flow rate & CW 87 / 99.5 F in/out, 14,000
3800 (total, R 513A or R 1233zde single of twin compressors / motors (2 or 4
gpm flow rate, compressors & motors sizes selected at stretched condensers +3 F
arranged in 2 or compressors / motors per module according to manufacturer
inlet conditions without capacity reduction. Module Minimum efficiency at zero
4 motors) selection).
10 Chiller -10 Lag (Cold Side) Continuous 3,300 RVSS 2 tolerance conditions 0.59 KW/TR. Maximum DP-Evaporator = 16 ft. at design flow &
26 ft. at 130 % flow and DP-Condenser = 20 ft. per Chiller .
6,000 TR per module at zero tolerance conditions, Series counter flow arrangement,
11 Chiller -11 Lead (Hot Side) Continuous 3,300 RVSS 2 CHW 39.20 / 55.20 F in/out, 9,000 gpm flow rate & CW 87 / 99.5 F in/out, 14,000
3800 (total, R 513A or R 1233zde single of twin compressors / motors (2 or 4
gpm flow rate, compressors & motors sizes selected at stretched condensers +3 F
arranged in 2 or compressors / motors per module according to manufacturer
inlet conditions without capacity reduction. Module Minimum efficiency at zero
4 motors) selection).
12 Chiller -12 Lag (Cold Side) Continuous 3,300 RVSS 2 tolerance conditions 0.59 KW/TR. Maximum DP-Evaporator = 16 ft. at design flow &
26 ft. at 130 % flow and DP-Condenser = 20 ft. per Chiller .
6,000 TR per module at zero tolerance conditions, Series counter flow arrangement,
13 Chiller -13 Lead (Hot Side) Continuous 3,300 RVSS 2 CHW 39.20 / 55.20 F in/out, 9,000 gpm flow rate & CW 87 / 99.5 F in/out, 14,000
3800 (total, R 513A or R 1233zde single of twin compressors / motors (2 or 4
gpm flow rate, compressors & motors sizes selected at stretched condensers +3 F
arranged in 2 or compressors / motors per module according to manufacturer
inlet conditions without capacity reduction. Module Minimum efficiency at zero
4 motors) selection).
14 Chiller -14 Lag (Cold Side) Continuous 3,300 RVSS 2 tolerance conditions 0.59 KW/TR. Maximum DP-Evaporator = 16 ft. at design flow &
26 ft. at 130 % flow and DP-Condenser = 20 ft. per Chiller .
6,000 TR per module at zero tolerance conditions, Series counter flow arrangement,
15 Chiller -15 Lead (Hot Side) Continuous 3,300 RVSS 2 CHW 39.20 / 55.20 F in/out, 9,000 gpm flow rate & CW 87 / 99.5 F in/out, 14,000
3800 (total, R 513A or R 1233zde single of twin compressors / motors (2 or 4
gpm flow rate, compressors & motors sizes selected at stretched condensers +3 F
arranged in 2 or compressors / motors per module according to manufacturer
inlet conditions without capacity reduction. Module Minimum efficiency at zero
4 motors) selection).
16 Chiller -16 Lag (Cold Side) Continuous 3,300 RVSS 2 tolerance conditions 0.59 KW/TR. Maximum DP-Evaporator = 16 ft. at design flow &
26 ft. at 130 % flow and DP-Condenser = 20 ft. per Chiller .
11,700 gpm @ 120 ft. Horizontal split case double suction impeller, minimum Motors equipped with insulated bearings at non-drive end side and
17 Chilled Water Primary Pump -1 395 Continuous 400 VFD 1
hydraulic efficiency = 85% and motor minimum efficiency 95%, motor SF 1.15. grounding ring at drive end side.
11,700 gpm @ 120 ft. Horizontal split case double suction impeller, minimum Motors equipped with insulated bearings at non-drive end side and
18 Chilled Water Primary Pump -2 395 Continuous 400 VFD 1
hydraulic efficiency = 85% and motor minimum efficiency 95%, motor SF 1.15. grounding ring at drive end side.
11,700 gpm @ 120 ft. Horizontal split case double suction impeller, minimum Motors equipped with insulated bearings at non-drive end side and
19 Chilled Water Primary Pump -3 395 Continuous 400 VFD 1
hydraulic efficiency = 85% and motor minimum efficiency 95%, motor SF 1.15. grounding ring at drive end side.
11,700 gpm @ 120 ft. Horizontal split case double suction impeller, minimum Motors equipped with insulated bearings at non-drive end side and
20 Chilled Water Primary Pump -4 395 Continuous 400 VFD 2
hydraulic efficiency = 85% and motor minimum efficiency 95%, motor SF 1.15. grounding ring at drive end side.
11,700 gpm @ 120 ft. Horizontal split case double suction impeller, minimum Motors equipped with insulated bearings at non-drive end side and
21 Chilled Water Primary Pump -5 395 Continuous 400 VFD 2
hydraulic efficiency = 85% and motor minimum efficiency 95%, motor SF 1.15. grounding ring at drive end side.
11,700 gpm @ 120 ft. Horizontal split case double suction impeller, minimum Motors equipped with insulated bearings at non-drive end side and
22 Chilled Water Primary Pump -6 395 Continuous 400 VFD 2
hydraulic efficiency = 85% and motor minimum efficiency 95%, motor SF 1.15. grounding ring at drive end side.
11,700 gpm @ 120 ft. Horizontal split case double suction impeller, minimum Motors equipped with insulated bearings at non-drive end side and
23 Chilled Water Primary Pump -7 395 Continuous 400 VFD 2
hydraulic efficiency = 85% and motor minimum efficiency 95%, motor SF 1.15. grounding ring at drive end side.
11,700 gpm @ 120 ft. Horizontal split case double suction impeller, minimum Motors equipped with insulated bearings at non-drive end side and
24 Chilled Water Primary Pump -8 395 Continuous 400 VFD 2
hydraulic efficiency = 85% and motor minimum efficiency 95%, motor SF 1.15. grounding ring at drive end side.
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
25 Chilled Water Secondary Pump -1 660 Continuous 400 VFD 1 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
26 Chilled Water Secondary Pump -2 660 Continuous 400 VFD 1 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
27 Chilled Water Secondary Pump -3 660 Continuous 400 VFD 1 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
28 Chilled Water Secondary Pump -4 660 Continuous 400 VFD 1 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
29 Chilled Water Secondary Pump -5 660 Continuous 400 VFD 1 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
30 Chilled Water Secondary Pump -6 660 Continuous 400 VFD 2 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
31 Chilled Water Secondary Pump -7 660 Continuous 400 VFD 2 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
32 Chilled Water Secondary Pump -8 660 Continuous 400 VFD 2 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
33 Chilled Water Secondary Pump -9 660 Continuous 400 VFD 2 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
34 Chilled Water Secondary Pump -10 660 Continuous 400 VFD 2 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
35 Chilled Water Secondary Pump -11 660 Continuous 400 VFD 2 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)
Motors equipped with insulated bearings at non-drive end side and
7,500 gpm @ 297 ft. Horizontal split case double suction impeller, minimum hydraulic
36 Chilled Water Secondary Pump -12 660 Continuous 400 VFD 2 grounding ring at drive end side. Network differential pressure
efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
considered 230 ft. (TBC by ACUDE)

14,000 gpm @ 120 ft. Horizontal split case double suction impeller, minimum
37 Condenser Water Pump -1 450 Continuous 400 RVSS 1
hydraulic efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.

14,000 gpm @ 120 ft. Horizontal split case double suction impeller, minimum
38 Condenser Water Pump -2 450 Continuous 400 RVSS 1
hydraulic efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.

14,000 gpm @ 120 ft. Horizontal split case double suction impeller, minimum
39 Condenser Water Pump -3 450 Continuous 400 RVSS 1
hydraulic efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.

14,000 gpm @ 120 ft. Horizontal split case double suction impeller, minimum
40 Condenser Water Pump -4 450 Continuous 400 RVSS 2
hydraulic efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.
14,000 gpm @ 120 ft. Horizontal split case double suction impeller, minimum
41 Condenser Water Pump -5 450 Continuous 400 RVSS 2
hydraulic efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.

14,000 gpm @ 120 ft. Horizontal split case double suction impeller, minimum
42 Condenser Water Pump -6 450 Continuous 400 RVSS 2
hydraulic efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.

14,000 gpm @ 120 ft. Horizontal split case double suction impeller, minimum
43 Condenser Water Pump -7 450 Continuous 400 RVSS 2
hydraulic efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.

14,000 gpm @ 120 ft. Horizontal split case double suction impeller, minimum
44 Condenser Water Pump -8 450 Continuous 400 RVSS 2
hydraulic efficiency = 86% and motor minimum efficiency 95%, motor SF 1.15.

Gear Box equipped with anti rotation stop mechanism. Motors


Field erected, 14,000 gpm, 87/99.5 F CW in/out, 80 F design WBT, 12 x 14 Mts. cell
equipped with insulated bearings at non-drive end side and
size, 11.4 Mt deck height, 2.0 Mts. fill height (4-layers), 9.144 Mt fan dia., no of fan
grounding ring at drive end side. EC motor to be considered (as per
blades 10, thermal selection to exclude rain and spray zone, motor at +3 degree blade
RFP). Fire resistance partition as per NFPA 214 and deluge system (to
45 Cooling Tower -1 275 Continuous 400 VFD 1 angle, additional 50 pa external static pressure for louvers, minimum efficiency 95%,
be checked with local code if required). Ultra noise fan and sound
motor SF 1.15. Noise level not to exceed 75 dBA @ 1 m and
matting (optional to be advised, as could be used during detailed
not to exceed 55 dBA at site boundary (i.e. ground floor - 10 m away from cooling
design as RFP request for restricted noise level). Basin to be 1.5 Mt
towers).
height concrete with GRP lined.
Gear Box equipped with anti rotation stop mechanism. Motors
Field erected, 14,000 gpm, 87/99.5 F CW in/out, 80 F design WBT, 12 x 14 Mts. cell
equipped with insulated bearings at non-drive end side and
size, 11.4 Mt deck height, 2.0 Mts. fill height (4-layers), 9.144 Mt fan dia., no of fan
grounding ring at drive end side. EC motor to be considered (as per
blades 10, thermal selection to exclude rain and spray zone, motor at +3 degree blade
RFP). Fire resistance partition as per NFPA 214 and deluge system (to
46 Cooling Tower -2 275 Continuous 400 VFD 1 angle, additional 50 pa external static pressure for louvers, minimum efficiency 95%,
be checked with local code if required). Ultra noise fan and sound
motor SF 1.15. Noise level not to exceed 75 dBA @ 1 m and
matting (optional to be advised, as could be used during detailed
not to exceed 55 dBA at site boundary (i.e. ground floor - 10 m away from cooling
design as RFP request for restricted noise level). Basin to be 1.5 Mt
towers).
height concrete with GRP lined.
Gear Box equipped with anti rotation stop mechanism. Motors
Field erected, 14,000 gpm, 87/99.5 F CW in/out, 80 F design WBT, 12 x 14 Mts. cell
equipped with insulated bearings at non-drive end side and
size, 11.4 Mt deck height, 2.0 Mts. fill height (4-layers), 9.144 Mt fan dia., no of fan
grounding ring at drive end side. EC motor to be considered (as per
blades 10, thermal selection to exclude rain and spray zone, motor at +3 degree blade
RFP). Fire resistance partition as per NFPA 214 and deluge system (to
47 Cooling Tower -3 275 Continuous 400 VFD 1 angle, additional 50 pa external static pressure for louvers, minimum efficiency 95%,
be checked with local code if required). Ultra noise fan and sound
motor SF 1.15. Noise level not to exceed 75 dBA @ 1 m and
matting (optional to be advised, as could be used during detailed
not to exceed 55 dBA at site boundary (i.e. ground floor - 10 m away from cooling
design as RFP request for restricted noise level). Basin to be 1.5 Mt
towers).
height concrete with GRP lined.
Gear Box equipped with anti rotation stop mechanism. Motors
Field erected, 14,000 gpm, 87/99.5 F CW in/out, 80 F design WBT, 12 x 14 Mts. cell
equipped with insulated bearings at non-drive end side and
size, 11.4 Mt deck height, 2.0 Mts. fill height (4-layers), 9.144 Mt fan dia., no of fan
grounding ring at drive end side. EC motor to be considered (as per
blades 10, thermal selection to exclude rain and spray zone, motor at +3 degree blade
RFP). Fire resistance partition as per NFPA 214 and deluge system (to
48 Cooling Tower -4 275 Continuous 400 VFD 2 angle, additional 50 pa external static pressure for louvers, minimum efficiency 95%,
be checked with local code if required). Ultra noise fan and sound
motor SF 1.15. Noise level not to exceed 75 dBA @ 1 m and
matting (optional to be advised, as could be used during detailed
not to exceed 55 dBA at site boundary (i.e. ground floor - 10 m away from cooling
design as RFP request for restricted noise level). Basin to be 1.5 Mt
towers).
height concrete with GRP lined.
Gear Box equipped with anti rotation stop mechanism. Motors
Field erected, 14,000 gpm, 87/99.5 F CW in/out, 80 F design WBT, 12 x 14 Mts. cell
equipped with insulated bearings at non-drive end side and
size, 11.4 Mt deck height, 2.0 Mts. fill height (4-layers), 9.144 Mt fan dia., no of fan
grounding ring at drive end side. EC motor to be considered (as per
blades 10, thermal selection to exclude rain and spray zone, motor at +3 degree blade
RFP). Fire resistance partition as per NFPA 214 and deluge system (to
49 Cooling Tower -5 275 Continuous 400 VFD 2 angle, additional 50 pa external static pressure for louvers, minimum efficiency 95%,
be checked with local code if required). Ultra noise fan and sound
motor SF 1.15. Noise level not to exceed 75 dBA @ 1m and
matting (optional to be advised, as could be used during detailed
not to exceed 55dBA at site boundary (i.e. ground floor - 10m away from cooling
design as RFP request for restricted noise level). Basin to be 1.5 Mt
towers.
height concrete with GRP lined.
Gear Box equipped with anti rotation stop mechanism. Motors
Field erected, 14,000 gpm, 87/99.5 F CW in/out, 80 F design WBT, 12 x 14 Mts. cell
equipped with insulated bearings at non-drive end side and
size, 11.4 Mt deck height, 2.0 Mts. fill height (4-layers), 9.144 Mt fan dia., no of fan
grounding ring at drive end side. EC motor to be considered (as per
blades 10, thermal selection to exclude rain and spray zone, motor at +3 degree blade
RFP). Fire resistance partition as per NFPA 214 and deluge system (to
50 Cooling Tower -6 275 Continuous 400 VFD 2 angle, additional 50 pa external static pressure for louvers, minimum efficiency 95%,
be checked with local code if required). Ultra noise fan and sound
motor SF 1.15. Noise level not to exceed 75 dBA @ 1 m and
matting (optional to be advised, as could be used during detailed
not to exceed 55 dBA at site boundary (i.e. ground floor - 10 m away from cooling
design as RFP request for restricted noise level). Basin to be 1.5 Mt
towers).
height concrete with GRP lined.
Gear Box equipped with anti rotation stop mechanism. Motors
Field erected, 14,000 gpm, 87/99.5 F CW in/out, 80 F design WBT, 12 x 14 Mts. cell
equipped with insulated bearings at non-drive end side and
size, 11.4 Mt deck height, 2.0 Mts. fill height (4-layers), 9.144 Mt fan dia., no of fan
grounding ring at drive end side. EC motor to be considered (as per
blades 10, thermal selection to exclude rain and spray zone, motor at +3 degree blade
RFP). Fire resistance partition as per NFPA 214 and deluge system (to
51 Cooling Tower -7 275 Continuous 400 VFD 2 angle, additional 50 pa external static pressure for louvers, minimum efficiency 95%,
be checked with local code if required). Ultra noise fan and sound
motor SF 1.15. Noise level not to exceed 75 dBA @ 1 m and
matting (optional to be advised, as could be used during detailed
not to exceed 55 dBA at site boundary (i.e. ground floor - 10 m away from cooling
design as RFP request for restricted noise level). Basin to be 1.5 Mt
towers).
height concrete with GRP lined.
Gear Box equipped with anti rotation stop mechanism. Motors
Field erected, 14,000 gpm, 87/99.5 F CW in/out, 80 F design WBT, 12 x 14 Mts. cell
equipped with insulated bearings at non-drive end side and
size, 11.4 Mt deck height, 2.0 Mts. fill height (4-layers), 9.144 Mt fan dia., no of fan
grounding ring at drive end side. EC motor to be considered (as per
blades 10, thermal selection to exclude rain and spray zone, motor at +3 degree blade
RFP). Fire resistance partition as per NFPA 214 and deluge system (to
52 Cooling Tower -8 275 Continuous 400 VFD 2 angle, additional 50 pa external static pressure for louvers, minimum efficiency 95%,
be checked with local code if required). Ultra noise fan and sound
motor SF 1.15. Noise level not to exceed 75 dBA @ 1m and
matting (optional to be advised, as could be used during detailed
not to exceed 55dBA at site boundary (i.e. ground floor - 10m away from cooling
design as RFP request for restricted noise level). Basin to be 1.5 Mt
towers.
height concrete with GRP lined.
Thermal stratification of water thermal storage tank, 39.20 / 55.20 F CHW in/out,
Tank diameter 24 Mts. water level 31.5 Mts. and shell height 32 Mts.
53 DCP-1 Thermal Energy Storage Tank-1 N/A Continuous N/A N/A 1 FOM 0.85, total storage capacity 35,750 TR.Hrs, peak charge / discharge flow 9,750
( to be confirmed by vendor)
gpm, total hydraulic head loss 2 psi.
Thermal stratification of water thermal storage tank, 39.20 / 55.20 F CHW in/out,
Tank diameter 23 Mts. water level 31.5 Mts. and shell height 32 Mts.
54 DCP-1 Thermal Energy Storage Tank-2 N/A Continuous N/A N/A 2 FOM 0.85, total storage capacity 30,250 TR.Hrs, peak charge / discharge flow 8,250
( to be confirmed by vendor)
gpm, total hydraulic head loss 2 psi.
Thermal stratification of water thermal storage tank, 39.20 / 55.20 F CHW in/out,
Tank diameter 25 Mts. water level 31.5 Mts. and shell height 32 Mts.
55 DCP-2 Thermal Energy Storage Tank-1 N/A Continuous N/A N/A 1 FOM 0.85, total storage capacity 38,500 TR.Hrs, peak charge / discharge flow10,500
( to be confirmed by vendor)
gpm, total hydraulic head loss 2 psi.
Thermal stratification of water thermal storage tank, 39.20 / 55.20 F CHW in/out,
Tank diameter 22 Mts. water level 31.5 Mts. and shell height 32 Mts.
56 DCP-2 Thermal Energy Storage Tank-2 N/A Continuous N/A N/A 2 FOM 0.85, total storage capacity 27,500 TR.Hrs, peak charge / discharge flow 7,500
( to be confirmed by vendor)
gpm, total hydraulic head loss 2 psi.

57 Make-up water pump -1 (CW) 20 Continuous 400 S/D 1 450 gpm @ 120 ft.

58 Make-up water pump -2 (CW) 20 Continuous 400 S/D 1 450 gpm @ 120 ft.

59 Make-up water pump -3 (CW) 20 Stand-BY 400 S/D 1 450 gpm @ 120 ft.

60 Make-up water pump -4 (CW) 20 Continuous 400 S/D 2 450 gpm @ 120 ft.

61 Make-up water pump -5 (CW) 20 Continuous 400 S/D 2 450 gpm @ 120 ft.

62 Make-up water pump -1 (CHW) 4 Intermittent 400 S/D 1 50 gpm @ 110 ft.

63 Make-up water pump -2 (CHW) 4 Intermittent 400 S/D 1 50 gpm @ 110 ft.

64 Expansion Tank-1 N/A N/A N/A N/A 1 5 Cu. Mt. bladder type

65 Expansion Tank-2 N/A N/A N/A N/A 2 5 Cu. Mt. bladder type

Concrete tank with GRP Lining (based on 12 Hrs. peak consumption,


66 Make-up water storage tank-1 (permeate) N/A N/A N/A N/A 1 Net water Volume 750 Cu. Mt.
to be confirmed as per local conditions - Clarification raised)

Concrete tank with GRP Lining (based on 12 Hrs. peak consumption,


67 Make-up water storage tank-2 (permeate) N/A N/A N/A N/A 1 Net water Volume 550 Cu. Mt.
to be confirmed as per local conditions - Clarification raised)

Concrete tank with GRP Lining (based on 12 Hrs. peak consumption,


68 Make-up water storage tank-3 (permeate) N/A N/A N/A N/A 1 Net water Volume 550 Cu. Mt.
to be confirmed as per local conditions - Clarification raised)

Concrete tank with GRP Lining (based on 12 Hrs. peak consumption,


69 Make-up water storage tank-4 (permeate) N/A N/A N/A N/A 2 Net water Volume 750 Cu. Mt.
to be confirmed as per local conditions - Clarification raised)
Concrete tank with GRP Lining (based on 12 Hrs. peak consumption,
70 Make-up water storage tank-5 (permeate) N/A N/A N/A N/A 2 Net water Volume 750 Cu. Mt.
to be confirmed as per local conditions - Clarification raised)

Concrete tank with GRP Lining (based on 12 Hrs. peak consumption,


71 Make-up water storage tank-6 (permeate) N/A N/A N/A N/A 2 Net water Volume 750 Cu. Mt.
to be confirmed as per local conditions - Clarification raised)

Concrete tank with GRP Lining (based on 12 Hrs. peak consumption,


72 Make-up water storage tank-7 (permeate) N/A N/A N/A N/A 2 Net water Volume 750 Cu. Mt.
to be confirmed as per local conditions - Clarification raised)

Concrete tank with GRP Lining (Capacity to be confirmed according


73 Domestic Water and Fire water storage N/A N/A N/A N/A 1 Net water Volume 500 Cu. Mt. (To be confirmed according to local code)
to local code and civil defense requirements)

74 Air Compressor 5 Intermittent 400 S/D 1 12 bar @ 10 l/s & receiver tank capacity 500 L Complete system with piping valves and accessories.

75 Water cooled refrigerant recovery unit 1.5 Intermittent 230 S/D 1 Complete system with piping valves and accessories.

76 RRU Cooling pump 1 Intermittent 230 S/D 1

77 Refrigerant leak detection system TBA Continuous 230 N/A 1 Complete system with sensors, control panels, wiring, conduits, etc.

78 Chemical Treatment Panel CW 4 Continuous 230 N/A 1 Complete system,

79 Chemical Treatment Panel CHW 0.05 Continuous 230 N/A 1 Complete system,

80 Domestic water booster pump-1 TBA Intermittent 230 TBA 1

81 Domestic water booster pump-2 TBA Stand-BY 230 TBA 1

82 Domestic water heater 1.5 Continuous 230 TBA 1


83 Fire pump (Electrical) TBA Intermittent 400 TBA 1 To be checked with local code and regulation of civil defense.
84 Fire pump (Diesel) TBA Intermittent 400 TBA 1 To be checked with local code and regulation of civil defense.
85 Fire jockey pump (Diesel) TBA Intermittent 400 TBA 1 To be checked with local code and regulation of civil defense.

86 Monorail for CHW Primary pumps 11 Intermittent 400 TBA 1 Electrical Hoist 7.5 Ton (to be confirmed by vendor based on selected model)

87 Monorail for CHW Secondary pumps 11 Intermittent 400 TBA 1 Electrical Hoist 7.5 Ton (to be confirmed by vendor based on selected model)

88 Monorail for CW pumps 11 Intermittent 400 TBA 1 Electrical Hoist 7.5 Ton (to be confirmed by vendor based on selected model)
Each with Electrical Hoist 10 Ton (to be confirmed by vendor based on selected Sized to carry chiller's heaviest part at a time, capacity to be
89 Set of 6 Monorail beam above each Chiller 12.5 Intermittent 400 TBA 1
model) confirmed upon equipment selection.
Each with Electrical Hoist 10 Ton (to be confirmed by vendor based on selected Sized to carry chiller's heaviest part at a time, capacity to be
90 Set of 10 Monorail beam above each Chiller 12.5 Intermittent 400 TBA 2
model) confirmed upon equipment selection.
Electrical Hoist 7.5 Ton (to be confirmed by vendor based on selected heaviest
91 Building Monorail 11 Intermittent 400 TBA 1
component)
Electrical Hoist 7.5 Ton (to be confirmed by vendor based on selected heaviest
92 Building Monorail 11 Intermittent 400 TBA 2
component)
Manual Hoist 3 Ton (to be confirmed by vendor based on selected heaviest
93 Manual Jib Crane on roof for CT motors N/A Intermittent N/A N/A 1
component)
Complete system with all accessories include 24 Hrs. diesel storage
94 Emergency diesel generator with accessories 1000 Intermittent 400 N/A 1 For one secondary pump and plant important components power supply.
tank, diesel pumps, ATS, control panel, etc.