Anda di halaman 1dari 32

Product 16LJ

Single-Effect,
Data Low Temperature Hot Water
Hermetic Absorption
Liquid Chiller
75 to 525 Nominal Tons

Carrier-Sanyo’s 16LJ single-effect


hermetic absorption liquid chiller is an
efficient and functional alternative to
traditional electric driven chillers. The
16LJ absorption chiller uses low tem-
perature hot water as its energy
source; as it eliminates the need for
high cost electricity, it may qualify for
financial incentives as a gas cooling
product. The 16LJ absorption chiller
offers functional flexibility in a variety
of installations:
• no CFCs; environmentally sound
• single stage design for simple,
dependable operation
• high reliability with few moving parts
• nominal coefficient of performance
(COP) of .70
• quiet, vibration-free operation
• Direct Digital Controls (DDC) for
optimum chiller performance

Features/Benefits
Single-effect absorption
cycle provides efficient,
economical water chilling
with minimal use of
electricity.
Cost-effective cooling
Alternative-energy chiller — The
16LJ chiller is a solution for building
owners who want to avoid high operat-
ing costs associated with electric-driven
chillers. Powered by low temperature
hot water, the Carrier-Sanyo 16LJ
absorption chiller reduces or eliminates
electric demand and/or ratchet
charges while allowing the owner to
take advantage of gas cooling incen-
tives when offered by local utility
companies.

Copyright 2005 Carrier Corporation Form 16LJ-1PD


Features/Benefits (cont)
Simple, reliable operation — The Computerized performance ratings al- machine during the factory fabrication
16LJ chiller’s single generator provides low the appropriately sized machine to and sectioning process.
one stage of solution reconcentration, be selected in order to meet exact job Small footprint — Compared to
which makes the 16LJ chiller one of requirements. All machine selections other single-effect chillers, the 16LJ
the most basic cycles currently avail- are rated in accordance with the latest chiller is significantly smaller in overall
able. The 16LJ chiller’s simple design, edition of ARI-560. physical size and weight, saving valu-
in addition to its other quality features, Combine absorption and electric- able space in the equipment room as
equates to inherently high reliability. driven chillers — Utilizing both well as reducing the rigging and instal-
Few moving parts and simple, depend- absorption and electric chillers in a lation cost of the machine.
able operation reduce downtime, as central plant offers the flexibility to Flanged waterbox nozzles — All
well as service and maintenance costs. base load one chiller, while using the 16LJ chillers incorporate ANSI
Exceptional efficiency — The 16LJ other to handle peak load require- (American National Standards Institute)
chiller offers full-load COPs of .70 at ments. Hybrid chiller systems have raised face flanges as standard on all
standard ARI (Air Conditioning and proven to be an economical solution external piping connections, simplify-
Refrigeration Institute) operating con- for many chilled water plants. In many ing chiller installation and field piping.
ditions. The 16LJ chiller provides effi- geographical areas, operating the
Low sound and vibration levels
cient performance for a low tempera- electric chiller as the base loaded
allow location flexibility — Absorp-
ture hot water absorber. Incorporated machine while using the absorption
tion chillers are distinguishable by their
into the standard machine design is a chiller during peak load conditions
low sound and vibration levels, primari-
solution heat exchanger, intended to provides the most economical operat-
ly because the only rotating parts are
preheat the weak lithium bromide solu- ing cost scenario. The reverse may
the refrigerant and absorbent pumps.
tion being pumped to the generator by also be true, depending on utility rate
The overall sound level of the Carrier-
precooling the strong solution from the structures and other job specifics.
Sanyo 16LJ chiller is typically 80 dbA,
generator. Either way, a 16LJ single-effect
absorption chiller used in conjunction therefore the machine may easily be
Superior part-load performance — installed near occupied spaces or in ar-
The concentration control system of the with an electric-driven chiller may be
eas with strict sound requirements.
16LJ chiller allows stable, part-load the most efficient and cost-effective
combination available. Low vibration levels also make it possi-
operation at cooling water tempera- ble to install the chiller on upper floors
tures as low as 64 F exclusive of the Location and installation without special consideration for vibra-
need for a cooling tower bypass. A con- savings tion dampening systems.
trol valve integral to the machine guar-
Ease of installation — All machines Microprocessor control
antees stable, continuous refrigerant
pump operation at part-load conditions. are completely fabricated, assembled, features/benefits
The 16LJ chiller has a continuous wired and tested in the factory as
single-piece units. Units are customari- Each 16LJ single-effect chiller in-
operating range from 100% to 10% of cludes a pre-programmed, factory-
rated machine capacity. ly shipped in one piece for all model
sizes, but shipment in multiple sections mounted and factory-wired control
panel, which is functionally tested prior
Application versatility is available, making the 16LJ chiller
to shipment. Chiller monitoring and
Designed for a variety of applica- ideal for retrofit or replacement instal-
lations where equipment room access control is automatic and continuous,
tions — Specifically designed for use and the screen on the front panel dis-
with low temperature hot water, the may be limited. Re-assembly of the
plays chiller operational status and
16LJ chiller can be applied to a variety chiller at the jobsite, if required, is both
straightforward and simple due to fault indications in English or metric
of cooling needs. Waste heat from units.
industrial processes and/or cogenera- special provisions made to the
tion systems can be used to provide
chilled water for process cooling, as
well as comfort cooling, thus reducing
the need for additional energy and
Table of contents
contributing to greater overall energy Page
savings. Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Ideal for new or retrofit applica- Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
tions — From replacement or expan- Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
sion of existing chiller systems to new Machine Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
construction projects, the 16LJ chiller Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
is capable of meeting the needs of Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-16
almost any cooling application. Fifteen Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
model sizes, with a capacity range of Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-20
75 to 525 tons, make the 16LJ Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
single-effect absorption chiller the ulti- Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-24
mate choice for comfort cooling and/ Typical Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
or light industrial applications. Guide Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-30

2
The Carrier-Sanyo microprocessor Low maintenance Waterbox design simplifies main-
PID (proportional, integral, derivative) Durable machine construction — tenance procedures — Every 16LJ
control system surpasses proportional Each Carrier-Sanyo 16LJ chiller is chiller is provided with numerous
only control systems by maintaining pre- constructed to meet rigorous manufac- standard design features that permit
cise leaving chilled water temperature turing and design requirements in an convenient and simple maintenance
versus actual set point. The PID controls ISO-9002 and ISO-14001 certified to be carried out quickly. Hinged or
surpass proportional only controls in facility. Furthermore, every machine removable waterbox covers on the
their ability to control the machine and meets strict Underwriters’ Laboratories evaporator, absorber, and condenser
narrow temperature variations. The (UL) certification requirements and facilitate tube and waterbox inspection
16LJ chiller control system also incor- is UL listed. The 16LJ chiller offers and/or cleaning from either end of the
porates the ability to control the chilled numerous features as part of its machine. In addition, the absorber and
water and cooling water pumps auto- standard design to provide dependable condenser sections are furnished as
matically. During shutdown these operation. Corrosion-proof stainless standard with marine waterboxes for
pumps are sequenced to ensure a com- steel dispersion trays ensure continu- easy access without having to disas-
plete dilution cycle, thus providing pro- ous, reliable operation, free from semble water piping.
tection from solution crystallization. blockage often characteristic of Factory-trained service organiza-
Leaving chilled water temperature is alternative designs. The evaporator, tion — In addition to routine mainte-
measured every 5 seconds by the con- absorber and condenser tubesheets nance and repair services, Carrier also
trol system. Hot water input to the and waterboxes are epoxy painted to offers a wide array of preventative
generator is then adjusted according to resist rust and corrosion. Also, every maintenance, full maintenance, and/or
the degree of deviation of actual leav- machine is furnished with a rupture extended service contracts which can
ing chilled water temperature versus disk to protect against an overpressure be custom-tailored to fulfill any service
set point. System temperatures, set condition on the shellside. These requirements. Carrier’s extensive
points and operational records are dis- standard design and construction service organization offers trained and
played on the front of the panel along features mean that every 16LJ single- experienced service technicians in
with various indicator lights that repre- effect chiller is built to withstand the every major city.
sent chiller operational status. A purge most rigorous duty, whether applied Superior corrosion protection —
status light on the panel indicates when for comfort cooling service or light All absorption chillers must be protect-
noncondensables need to be exhausted process applications. ed from the corrosion that occurs on
from the external purge storage cham- Leakproof hermetic pumps with internal machine surfaces when in
ber via the purge pump. isolation valves cut maintenance contact with lithium bromide solution.
The Carrier-Sanyo 16LJ chiller’s costs — The 16LJ chiller’s absorbent The 16LJ absorption chiller includes
control system automatically performs and refrigerant pump/motor assem- an extremely effective corrosion
self-diagnostic checks by constantly blies have a leakproof, self-contained inhibitor to provide an extra margin of
monitoring the chiller’s operational and hermetically sealed design. The protection against internal corrosion.
status and will automatically shut down hermetic construction eliminates the Other inhibitors may need exotic tube
the machine if a fault occurs. The need for a separate, complicated, materials in certain heat exchangers as
cause of shut down will be retained in and possibly leakprone seal water they are less effective and require more
the controller’s memory and can be system and auxiliary water piping, frequent maintenance and analysis.
displayed for immediate operator while providing leak tightness and The superior corrosion protection of
review. The controller’s memory will longer machine life. Specially designed the Carrier-Sanyo inhibitor allows
also retain and display the cause of bearings absorb both radial and axial the use of standard copper tubes
the last three system fault conditions, thrusts to ensure correct fit at all times. throughout the machine, which results
which is extremely useful for maintain- Concerns about external contamination in long machine life and dependable
ing an accurate record of unit perfor- are eliminated since the fluid being operation.
mance and fault history. pumped lubricates and cools the pump
Local or remote operation of the and motor assemblies. In addition, both Automatic purge extends
16LJ chiller can be done by configura- the rotor and stator are separated by a machine life, ensures optimum
tion of the controls during initial setup. stainless steel liner that protects the efficiency and performance
windings from the fluid being handled. The purge system on an absorption
Single point electrical connection
— Installation costs are reduced by Thermal overload switches are embed- chiller is essential to ensuring long
eliminating the need for field wiring be- ded in the stator as an additional safety machine life and efficient operation.
feature. This feature protects against All absorption chillers operate in a
tween machine components. All elec-
trical items, including the unit-mounted high winding temperature. The pumps vacuum and generate hydrogen (and
purge pump, are factory-wired to the are field serviceable and inspection is other noncondensable gases) in small
recommended after 25,000 hours or quantities, even when they are vacuum
chiller control center and require a sin-
gle point electrical connection to the 3 years of continuous operation. Isola- tight and properly inhibited. If not
machine from the building’s electrical tion valves, a standard feature on the properly controlled, these gases can
suction and discharge of the absorbent interfere with machine operation,
service. A control power transformer
mounted in the chiller panel provides and refrigerant pumps, allow easy ac- therefore it is imperative that they be
secondary single-phase control power. cess for service and maintenance. removed to protect against internal

3
Features/Benefits (cont)
corrosion, lithium bromide solution bromide solution depends on the combi- temperature (approximately 40 F),
crystallization, and/or reduction of nation of temperature and concentra- thereby cooling the chilled water
chiller capacity. The Carrier-Sanyo tion. The Carrier-Sanyo concentration circulating through the tubes of the
purge system protects against these control system automatically monitors evaporator. A refrigerant pump is used
potential hazards by operating continu- solution concentration by continuously to circulate the refrigerant water over
ously during machine operation. sensing the temperature of the strong the evaporator tubes to enhance the
How the purge system operates — solution and the refrigerant condensa- heat transfer process. The refrigerant
During chiller operation, any noncon- tion temperature. From this data, the vapor is removed as it is produced in
densables that are present tend to microprocessor controls are able to order to make the cooling process
accumulate in the absorber section, determine the solution concentration continuous. A lithium bromide solution
which operates at the lowest pressure and automatically limit the heat input to (which has a high affinity for water)
internal to the machine. A slipstream the chiller, if necessary, to prevent an is used to absorb the water vapor. As
of lithium bromide solution flows overconcentration condition from this process continues, the lithium
through an eductor from the absorbent occurring. Constant monitoring of the bromide becomes diluted, which
pump discharge. This process creates cycle ensures continuous, reliable opera- reduces its absorption ability. An
suction, which draws the noncondens- tion even at cooling water temperatures absorbent pump then transfers this
ables from the absorber, entraining as low as 64 F. Upon shutdown, the weak (diluted) solution to the genera-
them with the solution flowing through chiller dilution cycle is automatically con- tor, where it is reconcentrated by the
the eductor. The eductor discharges the trolled to an optimized period ranging introduction of hot water in the tubes
solution and noncondensables into the from 6 to 15 minutes by the micropro- of the generator to boil off the previ-
purge tank, where the noncondens- cessor controls in conjunction with the ously absorbed water. The water vapor
ables are separated from the solution. generator solution temperature. This released on the shellside of the genera-
The noncondensables remain in the optimized dilution operation period en- tor enters the condenser to be cooled
purge tank while the lithium bromide ables energy savings of the onboard and returned to a liquid state. At this
solution returns to the absorber sump. chiller pumps as well as the chilled water point, the refrigerant water returns to
As noncondensables accumulate in the and cooling water pumps. The dilution the evaporator to begin a new cycle.
external purge tank, they are isolated cycle also minimizes the time required To remove heat from the machine, rel-
from the chiller and cannot re-enter the for chiller start-up by preventing overdil- atively cool water from a cooling tower
chiller even during shutdown. A heated ution of the solution. or other source is circulated through
palladium cell connected to the storage the tubes of the absorber to remove
16LJ single-effect absorption the heat of vaporization. This same
chamber aids in elimination of hydro- cooling cycle
gen from the purge tank at all times. A water is then circulated through the
unit-mounted purge pump further aids The 16LJ single-effect absorption chiller tubes of the condenser. The strong (re-
in removing noncondensables from the is comprised of an evaporator, absorber, concentrated) solution from the gener-
condenser, hot water generator, solution ator flows back to the absorber to be-
purge tank, when necessary.
heat exchanger, refrigerant/absorbent gin a new cycle. For efficiency, the
Anticrystallization controls main- pumps, purge, controls, and auxiliaries. strong solution from the generator is
tain proper solution concentration Water is used as the refrigerant in ves- passed through a solution heat ex-
— The 16LJ chiller automatically limits sels maintained under low absolute pres- changer to preheat the weak solution
solution concentration in several ways to sure (vacuum). while precooling the strong solution
avoid both crystallization and overdilu-
The chiller operates on the principle before returning to the absorber.
tion to provide dependable, trouble-free
operation. Crystallization of the lithium that under vacuum, water boils at a low

4
16LJ ABSORPTION CHILLER COOLING CYCLE

Hot Water

Condenser
Cooling Water

Generator

Evaporator

Chilled Water Absorber

Heat Exchanger
Cooling Water

5
Model number nomenclature
16 LJ 11
Unit Size – Nominal Tons
16 – Hermetic 11 – 75 31 – 270
Absorption 12 – 90 32 – 300
Chiller 13 – 110 41 – 335
14 – 135 42 – 375
LJ – Single Effect, Low Temperature 21 – 155 51 – 420
Hot Water (1-Stage) 22 – 180 52 – 470
23 – 210 53 – 525
24 – 240


Options and accessories
ITEM FACTORY-INSTALLED FIELD-INSTALLED
OPTION ACCESSORY
Cooling Water Flow Switch X
High-Pressure Waterboxes, 300 psig X
Hot Water Control Valve X
Isolation Package X
Marine Waterboxes X
Shipping Configuration (1-piece or 2-piece) X
Special Tubing X
Victaulic Nozzle Connections X
Thermometer Set X

6 609
Machine components
HOT WATER OUITLET
CONDENSER

GENERATOR

HOT WATER INLET

CHILLED WATER OUTLET

EVAPORATOR

CHILLED WATER INLET

COOLING WATER INLET

CONTROL PANEL

ABSORBER

HEAT EXCHANGER

7
Physical data
UNIT 16LJ 11 12 13 14 21
NOMINAL COOLING CAPACITY (ton) 75 90 110 135 155
RIGGING WEIGHT (lb) 7,800 8,000 10,000 10,400 12,600
OPERATING WEIGHT (lb) 8,900 9,300 11,500 12,200 14,800
LITHIUM BROMIDE SOLUTION CHARGE (lb) 950 950 1,240 1,370 1,660
REFRIGERANT (WATER) CHARGE (lb) 130 130 220 200 240
CHILLED WATER
Pipe Connection Size (in.) 3 3 4 4 5
No. of Passes 5 5 3 3 3
COOLING WATER
Pipe Connection Size (in.) 5 5 5 5 6
No. of Passes
Absorber 4 4 4 4 4
Condenser 2 2 2 2 2
HOT WATER
Pipe Connection Size (in.) 4 4 4 4 5
No. of Passes 6 4 4 4 4

UNIT 16LJ 22 23 24 31 32
NOMINAL COOLING CAPACITY (ton) 180 210 240 270 300
RIGGING WEIGHT (lb) 13,300 15,500 16,100 19,900 20,800
OPERATING WEIGHT (lb) 15,700 18,100 19,200 23,400 24,500
LITHIUM BROMIDE SOLUTION CHARGE (lb) 1,790 2,170 2,360 2,720 2,960
REFRIGERANT (WATER) CHARGE (lb) 260 330 310 420 370
CHILLED WATER
Pipe Connection Size (in.) 5 5 5 6 6
No. of Passes 3 3 3 3 3
COOLING WATER
Pipe Connection Size (in.) 6 8 8 8 8
No. of Passes
Absorber 4 2 2 2 2
Condenser 2 2 2 2 2
HOT WATER
Pipe Connection Size (in.) 5 6 6 6 6
No. of Passes 4 3 3 3 3

UNIT 16LJ 41 42 51 52 53
NOMINAL COOLING CAPACITY (ton) 335 375 420 470 525
RIGGING WEIGHT (lb) 23,900 24,700 33,300 36,200 38,900
OPERATING WEIGHT (lb) 28,500 29,600 40,200 43,500 46,600
LITHIUM BROMIDE SOLUTION CHARGE (lb) 3,440 3,710 4,300 4,790 5,340
REFRIGERANT (WATER) CHARGE (lb) 550 510 570 640 680
CHILLED WATER
Pipe Connection Size (in.) 8 8 8 8 8
No. of Passes 3 3 3 2 2
COOLING WATER
Pipe Connection Size (in.) 10 10 12 12 12
No. of Passes
Absorber 2 2 4 2 2
Condenser 2 2 2 2 2
HOT WATER
Pipe Connection Size (in.) 8 8 8 8 8
No. of Passes 3 3 3 3 3

8
16LJ11 AND 16LJ12
LEGEND
ANSI — American National Standards Institute
CHW — Chilled Water

7-1/4
29-3/8
74-5/8

0
COW — Cooling Water
HTW — Hot Water
3 1 - 1 /2 31

NOTES:
1. Dimensions are shown in inches.
Dimensions

2. Dimensions (L), (W), (H) are for standard machine.


3. indicates the position of anchor bolts.
6 - 3 /4
4. For routine maintenance allow 3 ft clearance on all sides and
8 in. above chiller. 0 0
5. For tube removal clearance, refer to drawing.
6. Standard water piping connections are ANSI 150 lb flanges. 1 0 - 3 /8
7. Pass quantity and nozzle locations are for standard machine;
other configurations are available.

8
95

-5/
T ub e r e m o v a l

23
UNIT 16LJ A (in.) Wire connection

R
11 41/4 1-3/8 in. hole
12 5

HTW inlet 5 1 (W ) 1 08 ( L )
4 in .
CO W o u t l e t 8 3 -5/ 8 82 1/8
R u p t u r e D i sk
5 in. 7 8- 1 / 2 86-3/8 2 in.
7 4 - 3 /4

H T W in le t
4 in. 63 - 3/ 8

C HW o u t l e t
3 in. 4 9- 3 / 4

88(H)
C H W i nl e t
3 in. 36- 3/ 8
30 7/8
COW inlet
5 in. 2 3 -3 / 8

1 1 -3 / 4

0 0 0
0

0
A
7-7/8
93 1/8

81-3/4
82-1/2
88-1/2

35-7/8
34-3/4
HT W o u t le t H T W o u tl e t
C H W o ut C O W i n / o ut
H T W i n l et
C H W in l e t

9
10
16LJ13 AND 16LJ14
LEGEND
ANSI — American National Standards Institute

0
29-3/8
114-3/4
122-1/8
CHW — Chilled Water
COW — Cooling Water
HTW — Hot Water
3 1 - 1/ 2 30 1/8
NOTES:
1. Dimensions are shown in inches.
2. Dimensions (L), (W), (H) are for standard machine.
3. indicates the position of anchor bolts. 6- 3 / 4
4. For routine maintenance allow 3 ft clearance on all sides and 0 0
8 in. above chiller.
5. For tube removal clearance, refer to drawing. 1 0- 3 / 8
6. Standard water piping connections are ANSI 150 lb flanges.

8
Dimensions (cont)

7. Pass quantity and nozzle locations are for standard machine; 134

-5/
T ub e r e m o v a l

23
other configurations are available.
Wi r e c o n n e c t i o n

R
1- 3 / 8 i n . h o l e

H T W o u tl e t 5 1 (W ) 1 4 8 (L )
4 in.

C O W o utl et 8 3- 5 / 8 82 1/8
5 in . 7 8- 1 / 2 86 3/8 Rupture Disk
74-3/4 2 in.

HT W i n l e t
6 3- 3 /8
4 i n.

CHW outlet
4 i n. 49 -3 /4 PU R G E PURGE PUMP

C H W i n le t

88(H)
4 in . 3 6- 3 / 8
30 7/8
CO W i n le t
5 i n. 23 -3 /8

1 1 -3/4

0 0 0
0

0
5
7-7/8
7-1/8

18-3/8
13-7/8
122-5/8
128-5/8

35-7/8
34-3/4
CO W in / o u tl e t
H T W o u t l et C HW i n l e t
C H W o u tl e t
HTW inlet
H T W o utle t
16LJ21 AND 16LJ22

34-1/4
112-7/8
121-1/8

0
LEGEND
ANSI — American National Standards Institute
CHW — Chilled Water
COW — Cooling Water 39 -3 / 8
HTW — Hot Water 36 3/4

NOTES:
1. Dimensions are shown in inches.
2. Dimensions (L), (W), (H) are for standard machine.
0 7/8
3. indicates the position of anchor bolts. 0
4. For routine maintenance allow 3 ft clearance on all sides and 9- 5/8
8 in. above chiller.
5. For tube removal clearance, refer to drawing. /8 134
-5 T u b e r e m o va l
6. Standard water piping connections are ANSI 150 lb flanges. 23
W i r e c o n n ec t i o n R
7. Pass quantity and nozzle locations are for standard machine; 1-3/8 in. hole
other configurations are available.

5 8 ( W) 1 51( L)
HTW outlet
5 in.
90-1/4 88 3/4
CO W o u t le t Ru p t u re Dis k
6 in. 84 91-5/8 2 in.

7 4 -3 / 4
HT W i n l e t
5 in . 67-7/8

CH W o u t l e t
5 in. 53
PURGE PURGE PUMP

CHW inlet

93(H)
5 in. 39-5/8

C OW i n l e t 32 7/8
6 in .
23-7/8

1 1 -3 / 4

0 0 0
0

0
9-3/8
8-5/8

7-1/2
21-7/8
16-7/8

42-7/8
41-7/8
10-3/4
122-1/8

COW in/outlet
HTW outlet CH W i n l e t
HTW outlet C HW o u t l e t / H T W i n l e t

11
12
16LJ23 AND 16LJ24

LEGEND

0
46-1/8
153
161-1/4
ANSI — American National Standards Institute
CHW — Chilled Water
COW — Cooling Water
HTW — Hot Water
39 -3 /8
36 3/4

NOTES:
1. Dimensions are shown in inches.
2. Dimensions (L), (W), (H) are for standard machine.
3. indicates the position of anchor bolts. 7/8
0
0
4. For routine maintenance allow 3 ft clearance on all sides and
Dimensions (cont)

8 in. above chiller. 9-5/8


5. For tube removal clearance, refer to drawing.

8
178

-5 /
6. Standard water piping connections are ANSI 150 lb flanges.
T u be r em o v a l

23
7. Pass quantity and nozzle locations are for standard machine;

R
other configurations are available. Wire connection
1- 3/8 in . ho le

5 8 ( W)
19 2( L)
H T W o u tl e t
6 i n.
90-3/8 RuptureDisk 88 3/4
CO W o u t l e t 91-1/4 2 in.
8 in. 84
7 4-3/ 4
H T W in le t 67-7/8
6 i n.

CHW outlet 53
5 in .

93(H)
CH W i n l et 39-5 /8
5 in . 32 7/8
CO W i n le t 2 3- 7/8
8 in .
11-3/4

0 0 0
0

0
7-1/2
9-7/8
8-5/8

22-3/8

42-7/8
41-7/8
10-5/8
16-7/8
162-3/8

St e a m in le t COW inlet/outlet
C H W / HT W i n l e t
HT W o u tl e t CHW outlet
16LJ31 AND 16LJ32

18
10-1/4
0
45-1/8
151
LEGEND
ANSI — American National Standards Institute
CHW — Chilled Water 43 - 1/ 4
COW — Cooling Water 40 3/8
HTW — Hot Water

11
NOTES:
1. Dimensions are shown in inches. 2 1/2
0 0
2. Dimensions (L), (W), (H) are for standard machine.
8-7/8
3. indicates the position of anchor bolts. 17 8
4. For routine maintenance allow 3 ft clearance on all sides and Tub e r em o v al
8 in. above chiller.
5. For tube removal clearance, refer to drawing. W i r e c o n ne c ti o n
1 -3 / 8 i n . h o l e

/8
6. Standard water piping connections are ANSI 150 lb flanges.

-5
23
7. Pass quantity and nozzle locations are for standard machine;

R
other configurations are available.

6 0 (W)
1 9 7 ( L)
HTW outlet
6 in.
100-1/4 98 3/8
COW outlet Rupture Disk
8 in. 9 3 -1 / 8 1 0 2 -1 / 8 3 i n.

HTW inlet 7 5 -1 / 2 7 4 -3 / 4
6 in.

C HW o u t l e t 58-1/8
6 in.

104(H)
CHW inlet 42
6 in.
32 1/8
COW inlet 24
8 in.
1 1 -3 / 4

0 0 0

0
0

9-1/2

46-1/8
45-1/2
11-1/4
10-7/8
10-5/8
161-7/8
167-7/8
173-7/8

HTW outlet
CO W o u t l e t COW inlet
CHW inlet HT W o u t le t
CHW outlet
HTW inlet

13
14
16LJ41 AND 16LJ42

45-1/8
151
161-1/4
LEGEND

0
ANSI — American National Standards Institute
CHW — Chilled Water
COW — Cooling Water 4 5 - 1/ 4
HTW — Hot Water 43 3/4

NOTES:
1. Dimensions are shown in inches.
2. Dimensions (L), (W), (H) are for standard machine. 2
3. indicates the position of anchor bolts. 0 0
9 - 1/ 2
Dimensions (cont)

4. For routine maintenance allow 3 ft clearance on all sides and 178


8 in. above chiller.
5. For tube removal clearance, refer to drawing. T ub e re m o v a l
6. Standard water piping connections are ANSI 150 lb flanges. W i r e c on n e c ti o n

8
7. Pass quantity and nozzle locations are for standard machine; 1 - 3 / 8 i n . ho l e

- 5/
other configurations are available.

23
R
6 4 ( W) 198(L)
HTW outlet
8 in .
1 1 0 -3 / 8 R u p t u r e D i sk
COW outlet 111-7/8 3 109 1/2
10 i n. 1 0 2 -1 / 8 in .

HT W i n l e t
8 3 -3 / 8
8 in .
74-3/4
CH W o u t l e t
8 in. 6 3 -1 / 2

CHW inlet

113(H)
8 in. 45
CO W i n l e t
10 in. 32 1/4
22-3/4

1 1 -3 / 4

0 0 0

0
0

28-5/8
21-7/8
11-7/8
10-5/8

49-3/8
48-1/8
10-7/8
162-7/8

H T W o u t le t COW inlet/outlet
HTW outlet CHW outlet H T W i n le t
C H W i nl et
16LJ51-53

LEGEND
ANSI — American National Standards Institute

5-1/8
CHW — Chilled Water

40-1/2

0
AB C D
COW — Cooling Water
HTW — Hot Water
63
NOTES: 55 1/2
1. Dimensions are shown in inches.
2. Dimensions (L), (W), (H) are for standard machine.
3. indicates the position of anchor bolts.
4. For routine maintenance allow 3 ft clearance on all sides and 8 in. 17-3/4
above chiller.
5. For tube removal clearance, refer to drawing. 6 3/4
6. Standard water piping connections are ANSI 150 lb flanges. 0
5- 1/ 2 0
7. Pass quantity and nozzle locations are for standard machine; other
configurations are available.
K
UNIT Tube removal

8
A B C D E F K L Wire connection

-5/
16LJ 1 - 3/ 8 i n . h o l e

3
R2
51 1451/8 151 1583/4 1661/2 331/2 1605/8 182 205
52 1671/4 1723/8 180 1877/8 331/2 182 205 226
53 1867/8 192 1995/8 2071/2 331/2 2015/8 225 246
7 7 ( W) L
HT W out let
8 in.
1 24- 1/ 4
COW outlet 122 7/8
12 i n . 11 6 123-1/2 Rupture Disk
3 i n.

H T W i nl e t
8 i n. 91-3/4

C H W o u t le t
8 in . 74-3/ 4
6 9 - 1/ 4
C H W in le t

126(H)
8 in .
46 -1 /8
CO W i nl e t
12 in . 3 4 - 5/ 8
25-5/8

11 - 3 / 4
0 0 0

0
0

E F

9-7/8

66 7/8
15-1/8
26-3/4
14-5/8

HTW ou t le t HTW ou t l e t C H W o ut l e t CHW/HTW inlet


CO W i nl et / out l e t

15
16
FOUNDATION
A A

B B B B

F
AA AA
BB BB

G
K

G
K
Dimensions (cont)

C C J
J
D D

6
6

16LJ11-42 16LJ51-53

NOTES: WEIGHT (lb) DIMENSIONS (in.)


1. Dimensions are shown in inches. UNIT 16LJ
2. The base of the machine has AA BB A B C D E F G J K
2-in. diameter hole for anchor 11 4,450 4,450 745/8 71/4 37/8 141/8 311/2 57/8 431/4 61/4 353/8
bolt.
3. Anchor bolts should be fixed as 12 4,650 4,650 745/8 71/4 37/8 141/8 311/2 57/8 431/4 61/4 353/8
shown in detailed foundation 13 5,750 5,750 1143/4 71/4 37/8 141/8 311/2 57/8 431/4 61/4 353/8
drawings. Washer should be 1 1
welded to base. 14 6,100 6,100 1143/4 71/4 37/8 14 /8 31 /2 57/8 431/4 61/4 353/8
4. Drain ditch around the founda- 21 7,400 7,400 1127/8 77/8 37/8 153/4 393/8 57/8 511/8 77/8 431/4
tion is required. 22 7,850 7,850 1127/8 77/8 37/8 153/4 393/8 57/8 511/8 77/8 431/4
5. Surface of foundation should be
flat within ±1/4 in. per 20 ft. 23 9,050 9,050 153 77/8 37/8 153/4 393/8 57/8 511/8 77/8 431/4
6. Anchor bolts, washers and nuts 24 9,600 9,600 153 77/8 37/8 3
15 /4 3
39 /8 57/8 511/8 77/8 431/4
are supplied by customer.
31 11,700 11,700 151 87/8 37/8 173/4 431/4 57/8 551/8 97/8 471/4
32 12,250 12,250 151 87/8 37/8 173/4 431/4 57/8 551/8 97/8 471/4
41 14,250 14,250 151 87/8 37/8 173/4 451/4 57/8 571/8 97/8 491/4
42 14,800 14,800 151 87/8 37/8 3
17 /4 1
45 /4 57/8 571/8 97/8 491/4
51 20,100 20,100 1457/8 51/8 71/2 201/8 63 71/8 771/8 97/8 667/8
52 21,750 21,750 1671/4 51/8 71/2 201/8 63 71/8 771/8 97/8 667/8
53 23,300 23,300 1867/8 51/8 71/2 201/8 63 71/8 771/8 97/8 667/8
Performance data
UNIT 16LJ 11 12 13 14 21 22 23 24
COOLING CAPACITY (Ton) 75 90 110 135 155 180 210 240
CHILLED WATER
Flow Rate (gpm) 180 216 264 324 372 432 504 576
Pressure Drop (ft) 18.3 20.1 11.9 13.1 11.7 12.3 24.8 26.5
COOLING WATER
Flow Rate (gpm) 270 324 396 486 558 648 756 864
Pressure Drop (ft) 12.2 12.9 21.8 26.1 36.0 23.4 34.5 35.3
HOT WATER
Flow Rate (gpm) 164 197 241 296 339 394 460 526
Pressure Drop (ft) 10.3 4.0 9.9 10.8 10.1 10.1 9.9 10.1

UNIT 16LJ 31 32 41 42 51 52 53
COOLING CAPACITY (Ton) 270 300 335 375 420 470 525
CHILLED WATER
Flow Rate (gpm) 648 720 804 900 1008 1128 1260
Pressure Drop (ft) 25.4 26.9 25.1 25.0 20.6 10.8 14.1
COOLING WATER
Flow Rate (gpm) 972 1080 1206 1350 1512 1692 1890
Pressure Drop (ft) 32.4 32.9 33.0 34.3 31.3 29.4 39.1
HOT WATER
Flow Rate (gpm) 591 657 734 821 920 1029 1150
Pressure Drop (ft) 9.7 9.6 9.4 9.5 9.3 12.4 16.3
NOTE: Ratings are based on ARI 560-2000:
44 F chilled water, 2.4 gpm/ton, .0001 ft2-hr-F/Btu fouling factor
85 F cooling water, 3.6 gpm/ton, .00025 ft2-hr-F/Btu fouling factor
203 F hot water, 2.19 gpm/ton, .0001 ft2-hr-F/Btu fouling factor

Part-load performance
Part-load performance energy requirements for the 16LJ
chiller, ranging from 10% to 100% of full load, can be
obtained by contacting a local sales office.
All performance data is rated in accordance with ARI
560, latest edition, which defines Integrated Part Load
Value (IPLV) as a measure of part-load efficiency represent-
ing the weighted average of overall chiller performance
calculated by the following equation:
IPLV = .01A + .42B + .45C + .12D where
A = COP (Coefficient of Performance) at 100%
B = COP at 75%
C = COP at 50%
D = COP at 25% or minimum load

17
Application data
Range of application DESIGN AND TEST PRESSURES
The 16LJ single-effect hot water absorption chiller is de- RUPTURE DISK PIPING CONNECTION
UNIT 16LJ
signed for standard water chilling applications of 75 to SIZE SIZE
525 tons at standard ARI rating conditions. In most appli- 11-24 2 in. 2 in. 150 psig RF flange
cations, the minimum leaving chilled water temperature is 31-53 3 in. 3 in. 150 psig RF flange
limited to 41 F. The minimum continuous inlet water LEGEND
temperature to the absorber-condenser circuit is 64 F, RF — Raised Face
although lower temperatures are permitted during machine
start-up. Use of a cooling tower bypass is required if water
temperatures are anticipated to be less than this value.
Service access
To perform routine service or maintenance, allow 3 ft
UL certification clearance on all sides of the machine and 8 in. above the
All 16LJ chillers have met the necessary design and con- chiller. Tube removal space equal to the overall length of
struction qualifications for certification per Underwriters’ the unit should be provided on at least one end of the 16LJ
Laboratories. Each machine carries a UL listing and is chiller. The absorber and condenser waterbox covers are
labeled accordingly. hinged to permit easy opening and access for routine tube
cleaning.
Vent and drain connections
Vent and drain connections are found on each waterbox. Thermal insulation
Provide a vent on the high points of all water piping and a Thermal insulation of cold and hot machine surfaces
drain on all low points. If shutoff valves are provided in the should be done after final installation at jobsite. Refer to
main water piping close to the chiller, some system water thermal insulation drawings for details on application tech-
will be lost when the heat exchangers are drained. nique and specific areas of the machine to be insulated.
It is recommended that pressure gages be provided at Insulation material should be Armaflex or equal for cold
the entering and leaving water connections to measure surfaces and fiberglass or equal for hot surfaces. Surface
pressure drop through the heat exchanger. Gages may be area requirements are per table below.
installed as shown in the table below. Pressure gages in- THERMAL INSULATION SURFACE AREA
stalled at the vent and drain connections do not include REQUIREMENTS (sq ft)
nozzle pressure losses.
INSULATION THICKNESS
Use a reliable manometer to measure pressure differen-
UNIT 16LJ Hot Surface Cold Surface
tial when determining water flow. Regular gages are insen-
3 in. 11/8 in. 2 in. 11/8 in.
sitive and do not provide an accurate measurement of flow
11 30.1 17.3 43.0 3.3
conditions.
12 30.1 19.4 43.0 3.3
PRESSURE GAGE LOCATION 13 40.9 20.5 59.3 3.3
14 40.9 23.7 59.3 3.3
NUMBER GAGE LOCATION
OF PASSES (Cooler or Condenser) 21 43.0 26.9 65.7 4.3
Even Two gages in waterbox with nozzles 22 43.0 26.9 65.7 4.3
Odd One gage in each waterbox 23 56.0 33.4 81.8 5.4
24 56.0 35.5 81.8 5.4
Rupture disk piping 31 64.6 37.6 91.5 5.4
32 64.6 38.8 91.5 5.4
All 16LJ chillers are equipped with a rupture disk. It is
41 71.0 39.9 106.7 5.4
recommended that piping from the rupture disk be routed
42 71.0 42.0 106.7 5.4
to appropriate areas away from the machine in accordance
51 81.8 51.7 148.5 7.5
with Carrier-Sanyo’s written installation instructions, the
52 90.4 54.9 161.5 7.5
latest version of ANSI/ASHRAE-15 (American National
53 99.0 57.0 173.3 7.5
Standards Institute/American Society of Heating, Refriger-
ation, and Air Conditioning Engineers), and any local
jurisdictional requirements that may apply. Piping should
be adequately supported and the proper fittings should be
provided to allow periodic inspection of the disk. Refer to
the machine dimensional drawing for the exact location of
the rupture disk on the chiller.

18
→ Hot water control valve A 4 to 20 mA signal from the chiller control panel
The hot water control valve for the 16LJ chiller is not part operates the valve through either an electric or pneumatic
of the standard scope of supply of the unit. It is available as actuator. The control signal allows the valve to modulate the
a field-installed accessory and is intended for installation at flow of hot water to meet the required cooling load. An elec-
the jobsite. The valve should be installed in the hot water tric actuator requires 120-1-60 vac power, supplied from a
return line leaving the generator section of the chiller. The separate source, to operate the motor. If the valve is of the
accessory valve is a three-way globe mixing type with linear pneumatic type, an I/P (current-to-pressure) transducer is
V-port trim. The valve has a carbon steel body with ANSI provided to convert the 4 to 20 mA control signal into a 3 to
150 psig flanged end connections. Valve sizes are normally 15 psig input signal to the pneumatic actuator.
2½ to 6 in., depending on specific job requirements.

ACCESSORY HOT WATER CONTROL VALVE


(Pneumatic Actuator Shown)

NOTE: All dimensions are in inches.

DIMENSIONS — FLANGED ENDS (150 psig Carbon Steel)


VALVE SIZE (in.) A B C D E
2.5 10.88 23.75 12.81 7.25 6.25
3 11.75 28.25 15.0 7.56 8.13
4 13.88 29.25 15.0 9.38 9.13
6 17.75 38.25 17.5 11.56 12.88

609 19
Application data (cont)
HEAT EXCHANGER STANDARD PASS AND NOZZLE LOCATION
EVAPORATOR ABSORBER CONDENSER GENERATOR
UNIT 16LJ
Pass Qty Inlet Location Pass Qty Inlet Location Pass Qty Outlet Location Pass Qty Inlet Location
11 5 R 4 R 2 R 6 R
12 5 R 4 R 2 R 4 R
13-22 3 R 4 L 2 L 4 L
23-51 3 R 2 L 2 L 3 R
52-53 2 L 2 L 2 L 3 R
LEGEND
L — Left End (when facing control panel)
R — Right End (when facing control panel)

HEAT EXCHANGER STANDARD WATERBOX AND CROSSOVER PIPE CONFIGURATION

EVAPORATOR ABSORBER CONDENSER CROSSOVER PIPE


UNIT 16LJ INCLUDED
Inlet Outlet Inlet Outlet Inlet Outlet
11-53 N N M M M M Yes Yes
LEGEND
M — Marine Type Waterbox
N — Nozzle-In-Head Waterbox

AVAILABLE NOZZLE ARRANGEMENTS


CHILLED WATER COOLING WATER HOT WATER
UNIT 6 pass 5 pass 4 pass 3 pass 2 pass 4+2 3+2 3+1 2+2 2+1 6 pass 4 pass 3 pass 2 pass 1 pass
16LJ pass pass pass pass pass
I O I O I O I O I O I O I O I O I O I O I O I O I O I O I O
11 L L R L L L R L L L R R L R L L — — R L R R R R L R R R — —
12 L L R L L L R L L L R R L R — — R R R L — — R R L R R R — —
13 — — R L L L R L L L L L R L R R — — L R L L L L R L L L — —
14 L L R L L L R L L L L L R L — — L L L R — — L L R L L L — —
21 L L R L L L R L L L L L R L — — L L L R L L L L R L L L — —
22 — — R L L L R L L L L L R L — — L L L R — — L L R L L L — —
23 L L R L L L R L L L L L R L R R L L L R L L L L R L L L R L
24 — — R L L L R L L L L L R L R R L L L R — — L L R L L L R L
31 — — — — L L R L L L L L R L R R L L L R — — R R L R R R L R
32 — — — — L L R L L L — — R L R R L L L R — — R R L R R R L R
41 — — — — L L R L L L — — R L R R L L L R — — L L R L L L R L
42 — — — — L L R L L L — — R L R R L L L R — — L L R L L L R L
51 — — — — L L R L L L L L R L R R L L L R — — L L R L L L R L
52 — — — — L L R L L L — — R L R R L L L R — — L L R L L L R L
53 — — — — L L R L L L — — R L R R L L L R — — L L R L L L R L
LEGEND
I — In
O — Out
L — Nozzle location on LEFT end (when facing control panel)
R — Nozzle location on RIGHT end (when facing control panel)
Standard nozzle arrangement

20
Electrical data
UNIT VOLTAGE
460-3-60

UNIT PUMP/MOTOR (kW) RLA TOTAL MCA MFA kW


16LJ AP RP PP AP RP PP AMPS
11 1.1 0.2 0.75 2.7 1.2 1.45 6.2 7.5 10 4.3
12 1.1 0.2 0.75 2.7 1.2 1.45 6.2 7.5 10 4.3
13 1.1 0.2 0.75 2.7 1.2 1.45 6.2 7.5 10 4.3
14 1.1 0.2 0.75 2.7 1.2 1.45 6.2 7.5 10 4.3
21 2.2 0.2 0.75 5.1 1.2 1.45 8.6 10.4 15 5.9
22 2.2 0.2 0.75 5.1 1.2 1.45 8.6 10.4 15 5.9
23 2.2 0.3 0.75 5.1 1.3 1.45 8.7 10.4 15 5.9
24 2.2 0.3 0.75 5.1 1.3 1.45 8.7 10.4 15 5.9
31 3.0 0.3 0.75 6.7 1.3 1.45 10.3 12.9 20 7.2
32 3.0 0.3 0.75 6.7 1.3 1.45 10.3 12.9 20 7.2
41 3.0 0.3 0.75 6.7 1.3 1.45 10.3 12.9 20 7.2
42 3.0 0.3 0.75 6.7 1.3 1.45 10.3 12.9 20 7.2
51 3.0 0.3 0.75 6.7 1.3 1.45 10.3 12.9 20 7.2
52 3.0 0.3 0.75 6.7 1.3 1.45 10.3 12.9 20 7.2
53 3.0 0.3 0.75 6.7 1.3 1.45 10.3 12.9 20 7.2

208-3-60

UNIT PUMP/MOTOR (kW) RLA TOTAL MCA MFA kW


16LJ AP RP PP AP RP PP AMPS
11 1.1 0.2 0.75 5.4 2.2 3.2 12.7 15.6 20 4.0
12 1.1 0.2 0.75 5.4 2.2 3.2 12.7 15.6 20 4.0
13 1.1 0.2 0.75 5.4 2.2 3.2 12.7 15.6 20 4.0
14 1.1 0.2 0.75 5.4 2.2 3.2 12.7 15.6 20 4.0
21 2.2 0.2 0.75 10.2 2.2 3.2 17.5 21.7 30 5.5
22 2.2 0.2 0.75 10.2 2.2 3.2 17.5 21.7 30 5.5
23 2.2 0.3 0.75 10.2 2.4 3.2 17.7 21.9 30 5.6
24 2.2 0.3 0.75 10.2 2.4 3.2 17.7 21.9 30 5.6
31 3.0 0.3 0.75 13.8 2.4 3.2 21.3 27.5 40 7.0
32 3.0 0.3 0.75 13.8 2.4 3.2 21.3 27.5 40 7.0
41 3.0 0.3 0.75 13.8 2.4 3.2 21.3 27.5 40 7.0
42 3.0 0.3 0.75 13.8 2.4 3.2 21.3 27.5 40 7.0
51 3.0 0.3 0.75 13.8 2.4 3.2 21.3 27.5 40 7.0
52 3.0 0.3 0.75 13.8 2.4 3.2 21.3 27.5 40 7.0
53 3.0 0.3 0.75 13.8 2.4 3.2 21.3 27.5 40 7.0
LEGEND NOTES:
AP — Absorbent Pump 1. MCA and MFA include absorbent pump, refrigerant pump, purge
MCA — Minimum Circuit Ampacity pumps, palladium cell heater and control circuit.
MFA — Maximum Fuse Amps 2. kW includes refrigerant pump, absorbent pump, purge pump, pal-
PP — Purge Pump ladium cell heater and control circuit.
RLA — Rated Load Amps 3. Control circuit voltage = 24-1-60.
RP — Refrigerant Pump 4. Palladium cell voltage = 230-1-60 (460-3-60 power supply) and
208-1-60 (208-3-60 power supply).

STANDARD VOLTAGE FOR USE ON


(3-Ph, 60 Hz) SUPPLY VOLTAGES
208 200 to 208-volt systems
460 440 to 480-volt systems

21
Controls
Microprocessor controls • Low cooling water temperature
Microprocessor controls provide the safety, interlock, • Generator high temperature
capacity control, and indications necessary to operate the • Generator high pressure
chiller in a safe and efficient manner. • Chilled water flow
• Optional cooling water flow
Control system • Chilled water pump interlock
The microprocessor control on each 16LJ chiller is • Cooling water pump interlock
factory-mounted, factory-wired, and factory-tested to • High solution concentration
ensure chiller protection and efficient capacity control. In Overrides
addition, the program logic ensures proper starting, stop- • Solution concentration control
ping, and cycling of the chiller. • Desolidification mode
Features Capacity control
Control system • Leaving chilled water control
• Diagnostic check • Chilled water reset
• Keypad interface for display, set point control and Indications
system configuration • Chiller operating status
• Local and remote operation modes • Dilution cycle
• Recall of alarm/alert messages
• Power-on
• Extensive diagnostic and service capabilities • Pre-alarm alert
• Advanced crystallization protection • Alarm
Safety cutouts • Safety shutdown messages
• Absorbent pump motor overload • Elapsed time (hours of operation)
• Refrigerant pump motor overload • Remote/local
• Purge pump motor overload • Standby mode
• Low chilled water temperature

22
TYPICAL 16LJ ABSORPTION CHILLER CONTROL PANEL
FRONT AND LEFT SIDE VIEW

FAN

CONTROL DISPLAY
(SEE DETAIL BELOW)

TERMINAL BLOCK
STOP RUN
CHILLER / HEATER
#1ABS PUMP
#2ABS PUMP
REF PUMP
SET BACK
PURGE PUMP

REMOTE

STAND BY
DILUTION
BUZZER STOP LOCAL
SAFETY CIRCUIT

CHILLER ALARM OPERATION


STOP RUN

POWER

PURGE INDICATION
LAMP
TERMINAL BLOCK

PURGE PUMP
ON-OFF SWITCH

EMERGENCY STOP
BUTTON

TERMINAL BLOCK
FOR POWER SUPPLY

GROUND TERMINAL

CONTROL DISPLAY

1 NUMBER DESCRIPTION
1 Data display
2 Remote/local select button with lamp
3 Operation select button with lamp
10
4 Alarm indication lamp
9 5 Power indication lamp
STOP RUN
CHILLER / HEATER
6 Safety circuit indication lamp
#1ABS PUMP
#2ABS PUMP
7 Dilution indication lamp
REF PUMP
SET BACK 8 Stand by indication lamp
8 PURGE PUMP

2 9 Stop indication lamp


7 REMOTE

STAND BY
10 Operation indication lamp
6 DILUTION
BUZZER STOP LOCAL
SAFETY CIRCUIT

5 CHILLER ALARM
STOP
OPERATION
RUN

POWER
3

23
Controls (cont)
TYPICAL 16LJ ABSORPTION CHILLER CONTROL PANEL (cont)
INSIDE AND RIGHT SIDE VIEW

CONTROL RELAY

CIRCUIT PROTECTOR

TRANSFORMER

TERMINAL BLOCK

TRANSFORMER

I/O BOARD

TERMINAL BLOCK

FUSE

MAIN CIRCUIT
BREAKER

TRANSFORMER

ELECTROMAGNETIC
CONTACTOR

FUSE

24
Hot water Cooling
3 way valve tower

Hot water
Pump

Air
Conditioner P T Make up
water
P T
Typical piping

C C
P T
Primary
F Chilled water pump P T

P T
Secondary
Chilled Air vent
Bypass valve
Water pump
P T

Supply Return
Header Header

Cooling water pump


To drain To drain

LEGEND NOTES:
1. All items external to the dotted line in the above diagram are to be field-supplied.
Flow Meter 2. Piping and components shown are typical to indicate general point-of-connection only and are not intended to show details for
a specific installation. Installation and piping should be done in accordance with 16LJ Installation Instructions.
Pressure Gage 3. Refer to 16LJ chiller dimensional, foundation and field wiring drawings for details of a specific model size.
4. Install thermometers and pressure gages at locations convenient for servicing in the inlet and outlet water lines to the chiller.
Pump 5. Location of the chilled water, cooling water and hot water pumps as well as the expansion tank must take into account the
Stop Valve hydrostatic head to ensure that the waterbox design pressure is not exceeded.
6. Provide vent and drain valves in each waterbox.
Stop Valve for Cleaning Liquid 7. Provide a tower bypass valve if the temperature of the cooling water returning from the tower can fall below 64 F.
Strainer
Thermometer
Thermostat

25
Guide specifications
Single-Effect, Low Temperature Hermetic 6. Final inspection shall be performed on each
Absorption Liquid Chillers unit to check that the nameplate data is correct
and that all accessories are furnished as
Size Range: 75 to 525 Tons required.
Carrier-Sanyo Model Number: 16LJ 1.03 DELIVERY, STORAGE, AND HANDLING
Part 1 — General A. Unit shall be stored and handled in accordance with
1.01 SYSTEM DESCRIPTION the manufacturer's recommendations.
Electronically controlled, single effect (one-stage) absorp- B. Unit shall be factory-charged with lithium bromide
tion liquid chiller utilizing hermetic refrigerant and absor- solution if the machine is configured to ship in one
bent pumps, lithium bromide solution as the absorbent, piece. For shipments of multiple pieces, charging of
and water as the refrigerant. Low temperature hot water lithium bromide solution shall be performed at the
shall be supplied to the generator as the heat source. jobsite in accordance with the manufacturer’s writ-
1.02 QUALITY ASSURANCE ten instructions.
A. Chiller performance shall be rated in accordance C. All units shall be shipped with 3 psig nitrogen
with ARI Standard 560-2000. pressure.
B. Chiller shall be manufactured in accordance with D. Chiller shall be shipped with nameplates indicating
ANSI/ASHRAE 15 (latest edition) Safety Code for name of manufacturer, model size, serial number
Mechanical Refrigeration. and all other pertinent machine data.
C. Chiller shall be designed and constructed to meet 1.04 WARRANTY
applicable UL requirements and shall bear the UL Manufacturer shall guarantee the chiller against defects in
label. materials or workmanship for a period of one year from
D. Each chiller shall undergo a series of standard fac- date of initial operation or 18 months from date of ship-
tory tests to ensure that the unit is leak tight, that all ment, whichever occurs first. Manufacturer shall provide
electrical components operate as intended, and that the labor to repair or replace any part found to be defective
every aspect of unit fabrication meets stringent qual- in material or workmanship within the warranty period.
ity standards in accordance with good practice and Part 2 — Products
the manufacturer’s quality assurance requirements. 2.01 EQUIPMENT
1. The shellside of each chiller shall be leak tested A. General:
by pressurizing to 7 psig with nitrogen and then
Absorption liquid chiller shall include evaporator,
checked by spraying a soap and water mixture
absorber, condenser, generator, solution heat
on all welds, tube joints and/or gasketed joints
exchanger, refrigerant/absorbent pumps, purge
to identify any major leaks. Afterward, a mass
system, piping, wiring, controls and auxiliaries.
spectrometer test shall be performed by evacu-
Standard shipment of the machine shall be in one
ating the unit to 0.01 mm Hg absolute, cover-
piece. Initial charge of lithium bromide shall be
ing the machine with a vinyl tent and
shipped inside the machine for all single-piece ship-
introducing helium gas under the tent. Any
ments. For multiple-piece shipments, initial charge
remaining leaks will allow the helium to be
of lithium bromide shall be shipped separately for
drawn into the shellside of the machine. The
charging at the jobsite. Generator shall be designed
acceptable total leak rate as measured by the
for operation on low temperature hot water as spec-
mass spectrometer test shall not exceed
ified on the equipment schedule. A rupture disk shall
.000002 cc/sec standard air.
be provided as standard on all machines.
2. The tubeside of the evaporator, absorber, con-
B. Operating Characteristics:
denser and generator shall be hydrostatically
tested at 1.5 times rated design pressure and 1. Chiller operation shall be characteristic of a
held for 1 hour. single-effect absorption cycle. The weak
solution pumped from the absorber to the
3. All machine wiring shall undergo an insulation
generator shall initially pass through a solution
resistance test. The machine control panel and
all electrical components shall also be function- heat exchanger to improve operating efficiency
ally tested to verify continuity and proper by preheating the weak solution on the tube
side with the strong solution returning from the
electrical operation.
generator on the shellside.
4. Final assembly inspection shall consist of verify-
ing that all valves, controls, instrumentation, 2. Unit shall be capable of continuous operation
from 100 to 10% capacity, with entering
pumps, purge components and all other
machine components have been properly condenser water temperatures as low as 64 F
installed on the machine. without the need for a cooling tower bypass
valve. Thermostat on/off control of the cooling
5. Each unit shall be checked for overall appear- tower fan is recommended when cooling water
ance and dimensional accuracy. temperature falls below 64 F.

26
C. Heat Exchangers: which shall use flow from the absorbent pump to
1. All heat exchangers shall be of shell and tube create a suction. Noncondensables shall be stored
construction with shells, tube sheets, tube external to the unit and shall be prevented from dif-
support sheets and waterboxes fabricated of fusing back into the machine when the unit is not
carbon steel. All heat exchangers shall incorpo- operating. A palladium cell shall be provided to
rate straight tubes. Tube material shall be automatically vent hydrogen gas from the purge
copper for all heat exchangers. The evaporator, chamber to the atmosphere. It shall be continuously
absorber, condenser and generator tubes shall energized, even during machine shutdown. Further
be rolled into grooved tubesheets and expanded evacuation of the external storage chamber shall be
into tube support sheets, and shall be individu- accomplished with a factory-mounted purge pump,
ally replaceable. piped and wired to the machine. The need to oper-
ate the purge pump shall be indicated on the front
2. The evaporator, absorber and condenser water- of the control panel.
boxes shall be designed for 150 psig working
pressure. The absorber and condenser water- F. Controls, Safeties and Diagnostics:
boxes shall be hinged to permit access to 1. Controls:
all tubes from either end. Nozzle-in-head a. The chiller shall be provided with a factory-
(NIH) type waterboxes shall be supplied on the installed and factory-wired microprocessor
evaporator while the absorber-condenser water- control system with modular component
boxes shall be marine type. Waterboxes shall be construction. The controls shall be of the
provided with vent and drain connections. PID type and shall continuously monitor
Epoxy painting of the waterboxes and tube the operation of the chiller and perform
sheets shall be provided for corrosion protec- self-diagnostic checks to ensure that all
tion. ANSI 150 psig R.F. (raised face) flanges control limits are satisfied and maintained.
shall be furnished on all waterbox nozzle The system shall include a control center,
connections. power supply, temperature sensors, pres-
3. The generator tube side shall be designed for sure sensors and all necessary auxiliary
150 psig working pressure for use with low devices required for safe and proper chiller
temperature hot water. operation housed in a NEMA-1 enclosure
4. A solution heat exchanger shall be an integral with a hinged, lockable door. Control power
part of the machine to increase cycle efficiency shall be 24-1-60.
by preheating the weak solution on its way to The chiller control system shall have the abil-
the generator while pre-cooling the strong solu- ity to interface and communicate with a
tion returning from the generator. building management system with additional
5. Dispersion trays shall evenly distribute refriger- hardware.
ant over the evaporator tubes and lithium bro- The control system shall include a 7-segment
mide over the absorber tubes. These trays shall light-emitting diode (LED) display screen
be fabricated of stainless steel to ensure contin- with function keys, emergency stop button
uous, corrosion-free, high-efficiency operation. and indication lamps. The microprocessor
D. Pump/Motors: shall be configurable to display either English
or metric units.
Refrigerant and absorbent pump/motor assemblies
shall be of the self contained, leakproof, hermetic b. The control panel display screen shall allow
type, without an external seal water system to an operator to easily set and display the
minimize air leakage into the machine. Lubrication operating mode and configurable settings of
and cooling shall be accomplished by the fluid being the machine. The display shall indicate
pumped; auxiliary water piping for cooling and power on, chiller run status, safety circuit
lubrication shall not be acceptable. Each pump and alarm status, remote/local operation,
casing shall be welded into the piping at the factory standby mode and dilution cycle operation.
and shall be furnished with isolation valves on the Data input and machine settings shall be
suction and discharge side. Each pump shall include done via a data select key and shall allow
spring-loaded, wear-compensating tapered carbon scrolling through the individual chiller
bearings to ensure long life and reliability. Pump/ parameter settings.
motor assemblies shall be designed for 25,000 hours
of normal operation between inspections.
E. Purge System:
An automatic purge system shall be furnished to
provide a continuous purging action whenever the
chiller is in operation to assure long machine life and
efficient performance. Noncondensables shall be
removed from the absorber by a liquid eductor,

27
Guide specifications (cont)
c. Monitoring the operation of the chiller shall → h. The rate at which the accessory hot water
be done on a continuous basis. The display control valve is opened shall be precisely
shall indicate all pertinent system operating controlled.
parameters and alarms, as necessary, includ- i. The control system shall automatically cycle
ing the following: the refrigerant pump whenever the leaving
1) Chiller operating hours. chilled water temperature falls below the
2) Chilled water inlet temperature. desired set point. The chilled water pump
3) Chilled water outlet temperature. shall remain on and when the leaving chilled
4) Chilled water temperature set point. water temperature rises above the set point,
5) Cooling water inlet temperature. the refrigerant pump shall automatically
6) Condenser temperature. restart.
7) Generator temperature. j. The control center shall allow reset of the
8) Hot water inlet temperature. chiller water temperature set point based
9) Hot water outlet temperature. upon any one of the following criteria:
10) Absorbent pump start counter and oper-
1) Chilled water reset based on an external
ating hours.
4 to 20 mA signal.
11) Refrigerant pump start counter and
2) Chilled water reset based on cooling
operating hours.
water inlet temperature.
12) Purge pump start counter and operating
hours. k. When the stop button is pressed or remote
13) Chiller start counter. contacts open the control center shall imme-
14) Purge tank pressure. diately drive the hot water control valve to
→ the closed position and initiate the normal
d. Capacity control shall be by means of elec-
shutdown sequence including dilution cycle.
tronically modulating the accessory hot
The display shall indicate that the machine is
water control valve to maintain the tempera-
in the dilution cycle.
ture of the chilled water. Load modulation
shall be from 100% to 10% of machine full 2. Safeties:
load under normal ARI conditions. The hot a. Unit shall automatically shut down when any
water control valve shall be positioned by a of the following conditions occur. In addi-
PID control algorithm to ensure precise con- tion, the chiller goes into alarm mode and
trol of desired chilled water temperature indicates the reason for the shutdown on the
without hunting or overshooting the set chiller data display.
point. 1) Absorbent pump motor overload.
e. The microprocessor control system shall 2) Refrigerant pump motor overload.
include a programmed sequence to ensure 3) Purge pump motor overload.
machine readiness prior to machine start-up. 4) Low chilled water temperature.
The microprocessor shall automatically 5) Low cooling water temperature.
enable and interlock the chilled water pump, 6) Generator high temperature.
cooling water pump and cooling tower fans 7) Generator high pressure.
upon chiller activation. 8) Loss of chilled water flow.
f. Upon request to start the chiller, the control 9) (Optional) loss of cooling water flow.
system shall start the chilled water pump and 10) Loss of chilled water pump interlock.
verify chilled water flow. The controller shall 11) Loss of cooling water pump interlock.
then start the cooling water pump and verify 12) High solution concentration.
interlock signal, before starting tower fan(s), b. The control system shall detect conditions
absorbent pump and refrigerant pump. that approach protective limits and take self-
g. The control system shall automatically sense corrective action prior to an alarm occur-
impending abnormalities in the absorption ring. The system shall automatically reduce
operating cycle and take the following chiller capacity when any of the following
actions to either self-correct and/or limit the parameters are outside their normal operat-
machine from approaching cycle crystalliza- ing range:
tion line: 1) Low cooling water inlet temperature.
1) Close hot water control valve for a set 2) High cooling water inlet temperature.
period. 3) High solution concentration.
2) Stop the operation of the machine after 3. Diagnostics and Service:
performing a dilution cycle if the solu- a. The chiller control system shall execute a
tion concentration is still over the pre-set series of self-diagnostic checks whenever
level. power is first turned on to determine if tem-
peratures are within pre-start limits, thereby
allowing start-up to proceed. If any of the

28 609
limits are exceeded, an alert message will be 3. Cooling water flow switch shall be supplied
displayed, informing the operator of the by either the chiller manufacturer or the
cause of the pre-start alert. contractor/owner.
b. The control system shall provide an alarm 4. Piping from the rupture disk shall be provided
display on the front of the panel for any sen- and installed by the contractor/owner and piped
sor that has failed. These sensors include: in accordance with the chiller manufacturer’s
1) Chilled water inlet temperature. written instructions and any local jurisdictional
2) Chilled water outlet temperature. requirements.
3) Cooling water inlet temperature. I. Thermal Insulation:
4) Cooling water outlet temperature. Insulation of the evaporator, refrigerant pump,
5) Cooling water intermediate temperature. sump, piping and chilled water headers, in addition
6) Hot water inlet temperature. to any hot surfaces shall be field supplied and
7) Hot water outlet temperature. installed on the machine. Chiller manufacturer shall
8) Condenser temperature. recommend the material and specify surface area to
9) Refrigerant temperature. be insulated.
10) Diluted solution temperature.
J. Sound Level:
11) Generator temperature.
12) Purge tank pressure. The overall sound pressure level of the chiller shall
13) Steam condensate temperature. not exceed 80 dbA when measured per ARI
Standard 575-1994.
c. The chiller controls shall display mainte-
nance messages and alarms when efficient K. Start-up:
operation of the chiller is in jeopardy or 1. Unit manufacturer shall provide a factory-
when immediate attention is necessary. trained service representative, employed by the
When operating conditions are predicted to chiller manufacturer, to perform and/or super-
be problematic, the following messages shall vise chiller pressure test (when required), charge
be displayed on the panel: chiller with refrigerant (water) and lithium
1) Purge tank high pressure. bromide solution, place unit into operation, and
2) Cooling water tubes excessive fouling. calibrate all controls in accordance with the
3) Cooling water high temperature. manufacturer’s written start-up, operating and
4) Power failure. maintenance instructions.
4. Building Control System Interface: 2. After unit start-up has been performed, the same
factory representative shall be available for a
The chiller control system shall have the ability
period of instruction not to exceed 4 hours to
to interface and communicate directly to the
instruct the owner's personnel in the proper
building control system with additional field-
start-up, operating and maintenance procedures.
installed hardware and software.
3. Manufacturer shall provide the following docu-
G. Electrical Requirements:
mentation and literature:
1. Power supply to the unit shall be 3 ph, 60 Hz
a. Installation Instructions.
with voltages of 208 or 460 as specified on the
equipment schedule. A control transformer b. Start-Up, Operating and Maintenance
shall provide 24-volt single-phase secondary Instructions.
power for the control panel. c. Dimensional Drawing.
2. Contractor/owner shall supply and install d. Foundation Drawing.
the electrical power line and all auxiliary electri- e. Field Wiring Diagram.
cal protection devices per local code require-
ments and as indicated necessary by the chiller L. Options and Accessories:
manufacturer. 1. Marine Waterboxes:
3. Contractor/owner shall supply and install elec- Marine waterboxes with removable covers to
trical wiring and devices required to interface facilitate tube cleaning and maintenance shall
the chiller controls with the building controls be furnished when specified on the equipment
system if applicable. schedule.
H. Piping Requirements: 2. High-Pressure Waterboxes:
1. Piping and instrumentation for the chilled Waterboxes rated for 300 psig working pres-
water, cooling water and hot water shall be sup- sure with removable covers shall be furnished
plied and installed by the contractor/owner. when specified on the equipment schedule.
2. Absorber-condenser crossover piping shall be 3. Special Tubing:
furnished by the chiller manufacturer. Tubing of non-standard materials, geometry or
wall thickness shall be provided when specified
on the equipment schedule.

29
Guide specifications (cont)
4. Shipping Configuration: 8. Thermometer Set:
Chiller shall ship either fully assembled or in A package of 5 adjustable angle thermometers
multiple pieces as specified on the equipment shall be factory-supplied for field installation
schedule. when specified on the equipment schedule.
5. Victaulic Nozzle Connections: Each shall have a 9 in. scale with a working
range of 0° F to 120 F and shall be equipped
Victaulic grooves shall be provided on all water- with a ¾-in. NPT brass well.
box nozzle connections when specified on the
equipment schedule. → 9. Hot Water Control Valve:
6. Cooling Water Flow Switch: An accessory hot water control valve shall be
provided when specified on the equipment
Cooling water flow switch, rated for either schedule.
150 psig or 300 psig, shall be factory supplied
when specified on the equipment schedule.
7. Isolation Package:
A vibration isolation package consisting of neo-
prene isolation pads shall be furnished when
specified on the equipment schedule.

30 609
Carrier Corporation • Syracuse, New York 13221 609 8-05
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 New Book 3 Pg 32 Catalog No. 04-52160003-01 Printed in U.S.A. PC 211 Form 16LJ-1PD
Tab 5b Tab 3AC1 Replaces: New

Anda mungkin juga menyukai