Anda di halaman 1dari 157

BTI BTI BTI

BAHRAIN TRAINING INSTITUTE

ELECTRICAL AND
ELECTRONICS DIVISION

HIGHER NATIONAL
DIPLOMA
YEAR 2

UTILIZATION OF
ELECTRICAL ENERGY
EET 442

SEMESTER 1
2012-2013
Outcomes
1. Operation Of Power Transformers (1
Elbaz Bader Ayad – 41 )
Construction: shell and core types Yosry Idrees
Operating principles: derive the equivalent circuit for an ideal transformer on load, phasor diagram for
an ideal transformer on load, identify the no-load losses, derive the equivalent circuit to represent no-
load losses, leakage reactance, winding impedance, derive the complete equivalent circuit,
components of the equivalent circuit referred to one winding, phasor diagram for the loaded
transformer, voltage regulation, approximate formula for voltage regulation, calculation of voltage
regulation, losses on load, efficiency of transformer, calculation of efficiency under load conditions,
effects of load changes on losses, load conditions for maximum efficiency, calculation of maximum
efficiency. Name: ____________________________________________________________
Connections: star-stare, delta-star, delta-zigzag
Number: _________________________________ Group No.: ___________
2. Circuit protection ( 42 - 68 )
Over-current protection devices: basic construction of oil, vacuum and airblast circuit breakers, high
rupture capacity fuse, overcurrent relay and miniature circuit breaker
Operating principles: characteristics and circuit positions of over-current relays, high rupture capacity
fuse, and miniature circuit breaker, calculations of ‘time to clear’ over-current faults, discriminations
Earth fault protection devices: basic construction of earth fault relay and residual current circuit
breaker, performance requirements of earth fault protection, principle of operation and characteristics
of earth fault relays and residual current circuit breaker, position in circuit, calculation of ‘time to clear’
earth faults, discrimination

3. Design of a simple lighting system ( 69 – 93 )


Common lamp types: low pressure mercury, high pressure mercury, low pressure sodium, high
pressure sodium, fluorescent and halogen
Lighting design: quality of light, control of glare, luminance distribution, consistency of lighting levels,
interior lighting design codes, lighting for visual tasks, emergency lighting
Light scheme: produce a scheme for one of the following developments or equivalent, given the
appropriate plans: small commercial development to involve roads, tunnel, pedestrian areas and car
parks; small supermarket; administration office of a college, including computer stations.

4. Operation of a polyphase induction motor ( 94 – 117 )


Type: single cage, double cage, wound rotor
Operating principles: production of a rotating magnetic field in the stator; synchronous speed; rotor
resistance, reactance, and induced voltage; standstill conditions; slip speed; the effect of rotor speed
on rotor resistance and reactance; torque equations; for a three-phase induction motor; torque/speed
characteristics, stator and rotor losses, efficiency calculations
Starting methods: direct on-line, stator voltage reduction, rotor resistance method
Speed control: change of stator voltage and frequency

5. Energy management and tariffs ( 118 –126 )


Tariff structures: domestic, Domestic Economy, Domestic Smart, business (eg Economy all-purpose,
Economy combined premises, evening and weekend), restricted hour, methods of controlling
maximum demand, metering arrangements
Energy consumption: load scheduling, power factor correction techniques, calculation of apparent
power rating of a capacitor to improve power factor of a load, location of power factor correction
capacitors, efficient control of heating and lighting systems, recycling heat from heating and lighting
systems
Cost of energy: cost of running a system using the different tariffs available, selection of appropriate
tariff for a given installation and set of circumstances.

BTI - Electrical & Electronics Division a Elbaz Bader Ayad


YOSRY IDREES
Outcomes and assessment criteria
Outcomes Assessment criteria
To achieve each outcome a student must
demonstrate the ability to:
1. Investigate the operation of  Describe the construction of different types of
power transformers power transformer
 Identify the operating principle of a power
transformer under no-load and load conditions
 Describe the modes of connection for polyphase
transformers.

2. Investigate circuit  Describe the construction of over-current


protection for distribution protection devices
and installation systems  Determine the operating principles of circuit
over-current protection devices
 Determine the operating principles of earth fault
protection devices

3. Investigate the design of a  Describe the construction and associated circuit


simple lighting system of common lamp type
 Determine the operation of common lamp types
 Determine the principles of good lighting design
 Plan a simple light scheme

4. Investigate the operation of  Describe the types and construction of induction


a polyphase induction motors
motor  Determine the operating principles and methods
of starting induction motor
 Determine the
methods of speed control of induction motors.

5. Investigate energy  Determine the factors governing tariff structures


management and tariffs  Analyse methods for reducing energy
consumption
 Determine cost of energy used in a system

Prepared By: Yosry Idrees

BTI - Electrical & Electronics Division b Elbaz Bader Ayad


YOSRY IDREES
BAHRAIN TRAINING INSTITUTE - 77585
Electrical and Electronics Division
BTEC Level 5 HND Diploma in Electrical and Electronics Engineering (XN040) – Year 2
Module Name: Utilization Of Electrical Energy
Module Code (BTEC/BTI): 21576D/HEE432

ASSESSMENT MAPPING SHEET 2012-2013(Semester1)

Learning Assessmen Assessment Criteria Wk Wk Wk Wk Wk


Outcome Ref. t Criteria
Ref. 8 (10-14) 15 16 18

1.1 Explain the construction of different types of power transformer Ph1 S/OP
LO1: Understand the operation of power 1.2 Identify the operating principles of a power transformer under no-load and load conditions Ph1 Exam
transformers
1.3 Discuss the modes of connection for polyphase transformers Ph1 S/OP
2.1** Explain the construction of over-current protection devices Ph1 S/OP
LO2: Understand the applications of
2.2 Explain the operating principles of circuit over current protection devices Ph1 Exam
circuit protection for distribution
and installation systems 2.3 Explain the operating principles of earth fault protection devices Ph1 S/OP
3.1 Explain the construction, operation and associated circuitry of common lamp types A Exam
LO3: Understand the design and
3.2 Explain the principles of good lighting design A S/OP
construction of lighting systems
3.3 Plan a light scheme A S/OP
4.1 Discuss the factors governing tariff structures Ph2 S/OP
LO4: Be able to determine the cost of
energy used in a system in order 4.2 Analyse methods for reducing energy consumption Ph2 S/OP
to be energy efficient
4.3 Determine the cost of energy used in a system Ph2 Exam
5.1 Describe the types and explain the construction of induction motors Ph2 S/OP
LO5: Understand the operation of a poly
phase induction motor 5.2 Explain the operating principles and methods of starting induction motors Ph2 Exam
5.3 Analyse the methods of speed control of induction motors. Ph2 S/OP

M1** Identify and apply strategies to find appropriate solutions (Assessment Criteria Ref. 4.3) Ph2
M2 Select/design and apply appropriate techniques (Assessment Criteria Ref. 2.2) Exam
M3 Present and communicate appropriate findings (Assessment Criteria Ref. 3.1) A
D1 Use critical reflection to evaluate own work and justify valid conclusions (Assessment Criteria Ref. 5.3) Ph2
D2 Take responsibility for the management and organisation of activities (Assessment Criteria Ref. 5.2) Exam
**
D3 Demonstrate convergent/lateral/creative thinking (Assessment Criteria Ref. 1.3) Ph1

** Assessed for U, S, G and E


A= Assignment; LB= Lab; PA= Practical Assignment; CS= Case Study; Ph= Phase Test; Pr= Project; Qz= Quiz; S/OP= Second Opportunity; Exam= End of Semester Exam
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

1. The Ideal Transformer

The transformer is one of the most useful electrical device.. It can raise or lower the voltage
or current in an ac circuit, it can isolate circuits from each other, and it can increase or
decrease the apparent value of a capacitor, an inductor, or a resistor. Furthermore, the
transformer enables us to transmit electrical energy over great distances and to distribute it
safely in factories and homes.

We will study some of the basic properties of transformers in this chapter. It will help us
understand not only the commercial transformers covered in later, but also the basic
operating principle of induction motors, alternators, and synchronous motors. All these
devices are based upon the laws of electromagnetic induction. Consequently, we encourage
the reader to pay particular attention to the subject matter covered here.

1.1 Voltage induced in a coil:


Consider the coil of Fig. 1.l-a, which surrounds (or links) a variable flux  . The flux
alternates sinusoidal at a frequency f; periodically reaching positive and negative peaks
 max . The alternating flux induces a sinusoidal ac voltage in the coil, whose effective value is
given by
E = 4.44 f N  max (1.1)

where: E = effective voltage induced [V]


f = frequency of the flux [Hz]
N = number of turns on the coil
max = peak value of the flux [Wb]
4.44 = a constant [exact value = 2 / 2]

I 
+max
N
turns
T/2

(a) (b)
time

-max

Fig. 1.1: (a) A voltage is induced in a coil when it links a variable flux.
(b) A sinusoidal flux induced a sinusoidal voltage.

It does not matter where the ac flux comes from: It may be created by a moving magnet, a
nearby a coil, or even by an ac current that flows in the coil itself.
Equation 1 is derived from Faraday's law equation e = N( / t) in which  / t is the rate of
change of flux and e is the instantaneous induced voltage. Thus, in Fig. 1-b when  / t is
positive, the flux is increasing with time and the voltage is positive. Then, when  / t is
negative, the induced voltage e is negative. Finally, when  / t is momentarily zero, the
voltage is zero.

BTI - Electrical & Electronics Division 1 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

Example 1.1:
The coil in Fig.1 possesses 4000 turns and links an ac flux having a peak value of 2 mWb. If
the frequency is 60Hz, calculate the effective value and frequency of the induced voltage E.

Solution:
E = 4.44 f N  max (1.1)
= 4.44  60  4000  0.002 = 2131 V

The induced voltage has an effective or RMS value of 2131 V and a frequency of 60 Hz. The
peak voltage is 2131 2 = 3013 V.

1.2 Applied voltage and induced voltage:

Fig. 1.2-a shows a coil of N turns connected to a sinusoidal ac source Eg. The coil has a
reactance Xm and draws a current Im . If the resistance of the coil is negligible, the current is
given by:

Im = Eg / Xm
Eg, E
Im 
+

Eg N Im
E
turns

(a) (b)

Fig. 1.2: (a) The voltage E induced in a coil is equal to the applied voltage Eg
(b) Phasor relationships between Eg, E, Im and 

As in any inductive circuit, Im lags 90° behind Eg and  is in phase with the current (Fig.
1.2-b).

The detailed behaviour of the circuit can be explained as follows:


The sinusoidal current Im produces a sinusoidal mmf (N Im) which in turn creates a sinusoidal
flux  . The peak value of this ac flux is  max. The flux induces an effective voltage E across
the terminals of the coil, whose value is given by Eq. 1.1.
On the other hand, the applied voltage Eg and the induced voltage E must be identical
because they appear between the same pair of conductors. Because Eg = E, we can write

Eg = 4.44 f N  max
so,
 max = Eg / 4.44 f N (1.2)

This equation shows that for a given frequency and a given number of turns,  max varies in
proportion to the applied voltage Eg . This means that if Eg is kept constant, the peak flux
must remain constant.
For example, suppose we gradually insert an iron core into the coil while keeping Eg fixed
(Fig. 1.3). The peak value of the ac flux will remain absolutely constant during this operation,
retaining its original value  max even when the core is completely inside the coil. In effect, if
the flux increased (as we would expect), the induced voltage E would also increase. But this
is impossible because E = Eg at every instant and, as we said, Eg is kept fixed.

BTI - Electrical & Electronics Division 2 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

For a given supply voltage Eg, the ac flux in Figs. 1.2 and 1.3 is therefore the same.
However, the magnetizing current Im is much smaller when the iron core is inside the coil. In
effect, to produce the same flux, a smaller magnetomotive force is needed with an iron core
than with an air core. Consequently, the magnetizing current in Fig. 1.3 is much smaller than
in Fig. 1.2

Im Eg, E
+ Im
N
Eg E turns

(a) (b)

Fig. 1.3: (a) The flux in the coil remain constant so long as Eg is constant.
(b) Phasor relationships.

Example 1.2:
A coil having 90 turns is connected to a 120 V, 60 Hz source. If the effective value of the
magnetizing current is 4 A, calculate the following:
a. The peak value of flux
b. The peak value of the mmf
c. The inductive reactance of the coil
d. The inductance of the coil

Solution:
a- max = Eg / (4.44 f N) = 120/(4.44  60  90) = 0.005 = 5 mWb
b- The peak current is: Im(peak) = 2 I = 1.41  4 = 5.64 A
The peak mmf (U) is: U = N Im = 90  5.64 = 507.6 AT
The flux is equal to 5 mWb at the instant when the coil mmf is 507.6 ampere-turns.
c- The inductive reactance is: Xm = Eg / Im = 120 / 4 = 30 
d- The inductance is: L = X m / 2  f = 30 / (2  x 60) = 0.0796 = 79.6 mH

1.3 Elementary transformer:

In Fig. 1.4, a coil having an air core is excited by an ac source Eg. The resulting current Im
produces a total flux  , which is dispersed in the space around the coil. If we bring a second
coil close to the first, it will surround a portion  m1 of the total flux. An ac voltage E2 is
therefore induced in the second coil and its value can be measured with a voltmeter. The
combination of the two coils is called a transformer.
Im  m1
3
1

Eg  f1 E2

2 4

Fig. 1.4: Voltage induced in a secondary winding.
Mutual flux is  m1 , leakage flux is  f1

The coil connected to the source is called the primary winding (or primary) and the other one
is called the secondary winding (or secondary).

BTI - Electrical & Electronics Division 3 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

A voltage exists only between primary terminals 1-2 and secondary terminals 3-4,
respectively. No voltage exists between primary terminal 1 and secondary terminal 3. The
secondary is therefore electrically isolated from the primary.

The flux  created by the primary can be broken up into two parts:
1- a mutual flux  m1, which links the turns of both coils; and
2- a leakage flux  f1, which links only the turns of the primary.

If the coils are far apart, the mutual flux is very small compared to the total flux  ; we then
say that the coupling between the two coils is weak. We can obtain a better coupling (and a
higher secondary voltage E2) by bringing the two coils closer together. However, even if we
bring the secondary right up to the primary so that the two coils touch, the mutual flux will still
be small compared to the total flux  . When the coupling is weak, voltage E2 is relatively
small and, worse still, it collapses almost completely when a load is connected across the
secondary terminals.

In most industrial transformers, the primary and secondary windings are wound on top of
each other to improve the coupling between them.

1.4 Polarity of a transformer:

In Fig. 1.4 fluxes  f1 and  m1 are both produced by magnetizing current Im. Consequently, the
fluxes are in phase, both reaching their peak values at the same instant. They also pass
through zero at the same instant. It follows that voltage E2 will reach its peak value at the
same instant as Eg does. Suppose, during one of these peak moments, that primary terminal
1 is positive with respect to primary terminal 2 and that secondary terminal 3 is positive with
respect to secondary terminal 4 (Fig. 1.5).

Terminals 1 and 3 are then said to possess the same polarity. This sameness can be shown
by placing a large dot beside primary terminal 1 and another large dot beside secondary
terminal 3. The dots are called polarity marks.
The polarity marks in Fig. 1.5 could equally well be placed beside terminals 2 and 4 because,
as the voltage alternates, they too, become simultaneously positive, every half-cycle.
Consequently, the polarity marks may be shown beside terminals 1 and 3 or beside terminals
2 and 4.
Polarity mark

Im  m1
3
1

Eg  f1 E2

2 4

Fig. 1.5: Terminals having the same instantaneous polarity are marked with a dot.

1.5 Properties of polarity marks:

A transformer is usually installed in a metal enclosure and so only the primary and secondary
terminals are accessible, together with their polarity marks. But although the transformer may
not be visible, the following rules always apply to polarity marks:

1. A current entering a polarity-marked terminal produces a mmf that acts in a "positive"


direction. As a result, it produces a flux in the "positive" direction (Fig. 1.6).
Conversely, a current flowing out of a polarity-marked terminal produces a mmf and
flux in the "negative" direction. Thus, currents that respectively flow into and out of
BTI - Electrical & Electronics Division 4 Elbaz Bader Ayad
YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

polarity-marked terminals of two coils produce magnetomotive forces that buck each
other.
2. If one polarity-marked terminal is momentarily positive, then the other polarity-marked
terminals is momentarily positive (each with respect to its other terminal). This rule
enables us to relate the phasor voltage on the secondary side with the phasor voltage
on the primary side. For example, in Fig. 1.7, phasor Edc is in phase with phasor Eab.

Polarity mark

Im
3
1 
+
Eg

2 4

Transformer

Fig. 1.6: A current entering a polarity-marked terminal produce


a flux in a “positive” direction

Im current
Increasing c
a + -
Edc Eab
Eg

b - + d

(a) (b)

Fig. 1.7: (a) Instantaneous polarities when the magnetizing current is increasing
(b) Phasor relationship.

1.6 Polarity tests:

To carry out he polarity test, we proceed as follows (Fig. 1.8):


1. Connect the high-voltage winding to an ac source Eg.
1. Connect a jumper J between any two adjacent HV and LV terminals.
2. Connect a voltmeter Ex between the other two adjacent HV and LV terminals.
4. Connect another voltmeter Ep across the HV winding. If Ex gives a higher reading than Ep,
the polarity is additive. On the other hand, if Ex gives a lower reading than Ep , the polarity
is subtractive.
J

H1 X1

Eg Ep V

H2 X2

V
EX

Fig. 1.8: Determining the polarity of a transformer using an ac source.

In this polarity test, jumper J effectively connects the secondary voltage Es in series with the
primary voltage Ep. Consequently, Es either adds to or subtracts from Ep. In other words,:
BTI - Electrical & Electronics Division 5 Elbaz Bader Ayad
YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

Ex = Ep + Es or Ex = Ep - Es, depending on the polarity.

In making the polarity test, an ordinary 120 V, 60 Hz source can be connected to the HV
winding, even though its nominal voltage may be several hundred kilovolts.

Example 1.3:
During a polarity test on a 500 kVA, 69 kV/600 V transformer (Fig. 1.8), the following
readings were obtained: Ep = 118 V, Ex = 119 V.
Determine the polarity markings of the terminals.

Solution:
The polarity is additive because Ex is greater than Ep. Consequently, the HV and LV
terminals connected by the jumper must respectively be labelled H1 and X2 (or H2 and X1).

Fig. 1.9 shows another circuit that may be used to determine the polarity of a transformer. A
dc source, in series with an open switch, is connected to the LV winding of the transformer.
The transformer terminal connected to the positive side of the source is marked Xl. A dc
voltmeter is connected across the HV terminals. When the switch is closed, a voltage is
momentarily induced in the HV winding. If, at this moment, the pointer of the voltmeter moves
upscale, the transformer terminal connected to the (+) terminal of the voltmeter is marked H1
and the other is marked H2.

X1 H1 +
+
V
- -
X2 H2

Fig. 1.9: Determining the polarity of a transformer using a dc source.

1.7 Ideal transformer at no-load; voltage ratio:

Before undertaking the study of practical, commercial transformers, we shall examine the
properties of the so-called ideal transformer. By definition, an ideal transformer has no losses
and its core is infinitely permeable. Furthermore, any flux produced by the primary is
completely linked by the secondary, and vice versa. Consequently, an ideal transformer has
no leakage flux of any kind.

Im m E2 Eg, E1
+
+

Eg E1 E2 Im
N1 N2

m
(a) (b)

Fig. 1.10: (a) The ideal transformer at no-load.


(b) Phasor relationship at no-load.

Figure 1.10-a shows an ideal transformer in which the primary and secondary respectively
possess N1 and N2 turns. The primary is connected to a sinusoidal source Eg and the

BTI - Electrical & Electronics Division 6 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

magnetizing current Im creates a flux  m. The flux is completely linked by the primary and
secondary windings and, consequently, it is a mutual flux. The flux varies sinusoidally, and
reaches a peak value  m .
According to Eq. 1.1, we can therefore write:
E1 = 4.44 f N1  m (1.3)
and
E2 = 4.44 f N2  m (1.4)
From these equations, we deduce the expression for the voltage ratio of an ideal
transformer:
E1 / E2 = N1 / N2 (1.5)
where:
E1 = voltage induced in the primary [V]
E2 = voltage induced in the secondary [V]
N1 = numbers of turns on the primary
N2 = numbers of turns on the secondary

This equation shows that the ratio of the primary and secondary voltages is equal to the ratio
of the number of turns. Furthermore, because the primary and secondary voltages are
induced by the same mutual  m, they are necessarily in phase.
The phasor diagram at no load is given in Fig. 1.10-b. Phasor E2 is in phase with phasor E1
(and not 180° out of phase) as indicated by the polarity marks. If the transformer has fewer
turns on the secondary than on the primary, phasor E2 is shorter than phasor E1. As in any
inductor, current Im lags 90° behind applied voltage Eg . The phasor representing flux  m is
obviously in phase with magnetizing current Im which produces it.

However, because this is an ideal transformer, the magnetic circuit is infinitely permeable and
so no magnetizing current is required to produce the flux  m. Thus, under no-load conditions,
the phasor diagram of such a transformer is identical to Fig. 1.10-b except that phasor Im is
infinitesimally small.

Example 1.4:
A not quite ideal transformer having 90 turns on the primary and 2250 turns on the
secondary, is connected to a 120 V, 60 Hz source. The coupling between the primary and
secondary is perfect, but the magnetizing current is 4 A.
Calculate:
a. The effective voltage across the secondary terminals
b. The peak voltage across the secondary terminals
c. The instantaneous voltage across the secondary when the instantaneous
voltage across the primary is 37 V
Solution:
a. The turns ratio is: N2 / N1 = 2250 / 90 = 25
The secondary voltage is therefore 25 times greater than the primary voltage
because the secondary has 25 times more turns. Consequently:

E2 = 25 x E1 = 25 x 120 = 3000 V
Instead of reasoning as above, we can apply Eq. 1.5:
E1 / E2 = N1 / N2 = 120 / E2 = 90 / 2250 V
which again yields E2 = 3000 V

b. The voltage varies sinusoidally; consequently, the peak secondary voltage is:
E2(peak) = 2 E = 1.414 x 3000 = 4242 V
c. The secondary voltage is 25 times greater than E1 at every instant.
Consequently, when e1 = 37 V e 2 =25 X 37 = 925 V

1.8 Ideal transformer under load; current ratio:

BTI - Electrical & Electronics Division 7 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

Pursuing our analysis, let us connect a load Z across the secondary of the ideal transformer
(Fig. 1.11). A secondary current I2 will immediately flow, given by: I2 = E2 / Z
Does E2 change when we connect the load?
To answer this question, we must recall two facts.
E2 Eg, E1

I1 m I2 
+ +
I1
Eg E1 E2 Z
N1 N2 I2
m

(a) (b)

Fig. 1.11: (a) Ideal transformer under load.


(b) Phasor relationships under load.

First, in an ideal transformer the primary and secondary windings are linked by a mutual flux
 m, and by no other flux. In other words, an ideal transformer, by definition, has no leakage
flux. Consequently, the voltage ratio under load is the same as at no-load, namely:

E1 / E2 = N1 / N2

Second, if the supply voltage Eg is kept fixed, then the primary induced voltage E1 remains
fixed. Consequently, mutual flux  m also remains fixed. It follows that E2 also remains fixed.
We conclude that E2 remains fixed whether a load is connected or not.

Let us now examine the magnetomotive forces created by the primary and secondary
windings. Current I2 produces a secondary mmf (N2 I2). If it acted alone, this mmf would
produce a profound change in the mutual flux  m. But we just saw that Him does not change
under load. We conclude that flux  m can only remain fixed if the primary develops a mmf
which exactly counterbalances (N2 I2 )at every instant. Thus, a primary current I1 must flow
so that:
N1 I1 = N2 I2 (1.6)

To obtain the required instant-to-instant bucking effect, currents I1 and I2 must increase and
decrease at the same time. Thus, when I2 goes through zero, I1 goes through zero, and when
I2 is maximum (+) I1 is maximum (+). In other words, the currents must be in phase.
Furthermore, in order to produce the bucking effect, when I1 flows into a polarity mark on the
primary side, I2 must flow out of the polarity mark on the secondary side (see Fig. 1.11-a).

Using these facts, we can now draw the phasor diagram of an ideal transformer under load
(Fig. 1.11-b). Assuming a resistive-inductive load, current I2 lags behind E2 by an angle ,
Flux  m lags 90° behind Eg, but no magnetizing current Im is needed to produce this flux
because this is an ideal transformer.
Finally, the primary and secondary currents are in phase. According to Eq. 1.6, they are
related by the equation:
I1 / I2 = N2 / N1 (1.7)
where:
I1 = primary current [A]
I2 = secondary current [A]
N1 = number of turns on the primary
N2 = number of turns on the secondary

Comparing Eq. 1.5 and Eq. 1.7, we see that the transformer current ratio is the inverse of the
voltage ratio. In effect, what we gain in voltage, we lose in current and vice versa. This is
consistent with the requirement that the instantaneous power input E1 I1 to the primary must

BTI - Electrical & Electronics Division 8 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

equal the instantaneous power output E2 I2 of the secondary. If the power inputs and outputs
were not identical, it would mean that the transformer itself absorbs power. By definition, this
is impossible in an ideal transformer.

Example 1.5:
An ideal transformer having 90 turns on the primary and 2250 turns on the secondary is
connected to a 200 V, 50 Hz source. The load across the secondary draws a current of 2 A at
a power factor of 80 percent lagging (Fig. 1.l2-a).

Calculate:
a) The effective value of the primary current
b) The instantaneous current in the primary when the instantaneous current in the
secondary is 100mA
c) The peak flux linked by the secondary winding
d) Draw the phasor diagram

Solution:
a- The turns ratio is: a = N1/ N2 = 90 / 2250 = 1 / 25
The current ratio is therefore 25 and because the primary has fewer turns, the primary
current is 25 times greater than the secondary current. Consequently:
I1 = 25 x 2 = 50A

Instead of reasoning as above, we can calculate the current by means of Eq. 1.6.
N1 I1 = N2 I2 = 90  I1 = 2250  2 I1 = 50 A

b- The instantaneous current in the primary is always 25 times greater than the
instantaneous current in the secondary. Therefore when I2 = 100 mA,I1 is:
I1 instantaneous = 25  I2 instantaneous = 25 x 0.1 = 2.5A
c- In an ideal transformer, the flux linking the secondary is the same as that linking the
primary. The peak flux in the secondary is:
 m = Eg / (4.44 f N1) = 200 / (4.44 x 50  90) = 0.01 = 10 mWb

I1 m I2 = 2A
+ Eg, =E1= 200V E2= 5000V
+
N1 N2 = 36.9
Z Cos 
200 V E E1 E2
g
60 HZ 90 2250 = 0.8
I2= 2A

m = I1= 50A
(a) 10 mWb (b)

Fig. 1.12: (a) See Example 4 (b) Phasor relationship.

d. To draw the phasor diagram, we reason as follows: Secondary voltage is:


E2 = 25 x E1 = 25 x 200 = 5000 V
E2 is in phase with E1 indicated by the polarity marks. For the same reason, I1
is in phase with I2. Phase angle between E2 and I2 is:
power factor = cos  = 0.8. The phase angle between E1 and I1 is also 36.9°.
The mutual flux lags 90° behind Eg (Fig. 1.12-b).

1.9 Circuit symbol for an ideal transformer:

BTI - Electrical & Electronics Division 9 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

We simply as shown in Fig. 1.13 by drawing the primary and secondary windings and the
mutual flux  m. Polarity marks are added, enabling us to indicate the direction of current flow
as well as the polarities of voltages E1 and E2 .
For example, a current I1 flowing into one polarity-marked terminal is always accompanied by
a current I2 flowing out of the other polarity-marked terminal. Consequently, I1 and I2 are
always in phase .
Ideal Ideal
I1 Trans. I2 a I1 Trans. I2
+ + c

E1 E2 E1 E2

N1 N2 b N1 N2
d
a = N1/N2 a = N1/N2
E2 E1 Ecd Eab

I1  Any angle  Any angle


I1

I2 (b)
I2 (a)
Fig. 1.13: (a) Symbol for an ideal trans. & phasor diagram using sign notation.
(b) Symbol for an ideal trans. & phasor diagram using double-subscript notation.

Furthermore, if we let the ratio of transformation N1 / N2 = a , we obtain E1 = a E2


and I1 = I2 / a

In an ideal transformer, and specifically referring to (Fig. 1.13-a), E1 and E2 are always in
phase, and so are I1 and I2

If the double-subscript notation is used (Fig. 1.13-b), Eab and Ecd are always in phase and so
are I1 and I2.

1.10 Impedance ratio:

Although a transformer is generally used to transform a voltage or current, it also has the
important ability to transform an impedance. Consider, for example, (Fig. 1.14-a) in which an
ideal transformer is connected between a source Eg and a load Z. The ratio of
transformation is a, and so we can write E1 / E2 = a and I1 / I2 = 1/a

As far as the source is concerned, it sees an impedance ZX between the primary terminals
given by: ZX = E1 / I1

On the other hand, the secondary sees an impedance Z given by: Z = E2 / I2

However, ZX can be expressed in another way:


E aE a2 E
ZX  1  2  2  a2 Z
I I2 / a I
1 2

Consequently, ZX = a2 Z (1.8)

This means that the impedance seen by the source is a2 times the real impedance (Fig.
1.14-b). Thus, an ideal transformer has the amazing ability to increase or decrease the value
of an impedance. In effect, the impedance seen across the primary terminals is identical to
the actual impedance across the secondary terminals multiplied by the square of the turns
ratio.
BTI - Electrical & Electronics Division 10 Elbaz Bader Ayad
YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

Ideal I1
I1 Trans. I2

Eg E1 E2 Eg E1 Zx = a 2 Z
Z

N1 N2
a = N1/N2

(a) (b)
Fig. 1.14: (a) Impedance transformation using a transformer.
(b) The impedance seen by the source differs from Z

The impedance transformation is real, and not illusory like the image produced by a
magnifying glass. An ideal transformer can modify the value of any component, be it a
resistor, capacitor, or inductor.

For example, if a 1000 resistor is placed across the secondary of a transformer having a
primary to secondary turns ratio of 1:5, it will appear across the primary as if it had a
resistance of 1000  (1/5)2 = 40.
Similarly, if a capacitor having a reactance of 1000 is connected to the secondary, it
appears as a 40 capacitive reactance across the primary. However, because the reactance
of a capacitor is inversely proportional to its capacitance (XC = 1 / 2  f C), the apparent
capacitance between the primary terminals is 25 times greater than its actual value. We can
therefore artificially increase (or decrease) the microfarad value of a capacitor by means of a
transformer.

1.11 Shifting impedances from secondary to primary and vice versa:

As a further illustration of the impedance-changing properties of an ideal transformer,


consider the circuits of Fig. 1.15. It is composed of a source Eg, a transformer T, and four
impedances Z 1 to Z4. The transformer has a turns ratio a. As the impedances are shifted, the
circuit configuration remains the same, but the shifted impedance values are multiplied by a2.
The reason is that the voltage E across each element in the secondary side becomes aE
when the element is shifted to the primary side. Similarly, the current I in each element in the
secondary side becomes I / a when the element is shifted to the primary side.
On account of this relationship, it is easy to solve a real circuit such as the one shown in Fig.
1.15-a. We simply reduce it to the equivalent form shown in Fig. 1.15-e and solve for all the
voltages and currents. These values are then respectively multiplied by 1/a and by a, which
yields the actual voltages and currents of each element in the secondary side.

E3
Ideal Z3
Z1
Trans.
I1  I3 
I2 I4
Eg Z2 E2 Z4 E4
 

a=1

(a)

Ideal E3
Z1
Trans. Z3

I1  I3

BTI - Electrical & Electronics Division
I2/a 11 I4 Elbaz Bader Ayad
Eg a2Z2 aE2 Z4 E4
 
 YOSRY IDREES

a=1
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

(b)

aE3
Z1 a2Z3 Ideal
Trans.
I1  I3/a 
I2/a I4
Eg  a Z2 aE2
2  Z4 E4
 

a=1

(c)

aE3
Z1 a2Z3 Ideal
Trans. I = 0

I1  I3/a 
I2/a I4/a

Eg a2Z2 aE2 a2Z4 aE4
 

a=1

(d)

Z1 a2Z3

I1 
I2/a I3/a
Eg a2Z2 a2Z4 aE4
 

(e)

Fig. 1.15:
a) The actual circuit showing the actual voltages and currents.
b) Impedance Z2 is shifted to the primary side.
c) Impedance Z3 is shifted to the primary side..
d) Impedance Z4 is shifted to the primary side.
e) All the impedances are now transferred to the primary side the transformer is no longer
needed.

To illustrate, suppose that the real voltage across Z4 in Fig. 1.16 is E4 volts and that the real
current through it is I4 amperes. Then, in the equivalent circuit, the voltage across the a2 Z4
impedance is equal to (E4  a ) volts. On the other hand, the current through the impedance
is equal to ( I4  a ) amperes (Fig. 1.17). In other words, whenever an impedance is
transferred to the primary side, the real voltage across the impedance multiplying by a factor
a, while the real current dividing by the factor a.
Ideal Z3
Z1
Trans.
A
I4 
BTI - Electrical & Electronics
E
Division 12 Elbaz Bader Ayad
Z2 Z4 V EYOSRY
g
4 IDREES

a=1
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

Fig. 1.16: Actual voltage & current in impedance Z4

Z1 a2Z3

I1 
I2/a I3/a
Eg a2Z2 a2Z4 aE4
 

Fig. 1.17: Equivalent voltage & current in Z4 referring to the primary side

In some cases it is useful to shift impedances in the opposite way, that is from the primary
side to the secondary side (Figs. 1.18). The procedure is the same, but all impedances so
transferred are now divided by a2 .

E1 E1/a
Ideal Z3 Ideal Z3
Z1 Z1/a2
Trans. Trans.
I1  aI1
Eg  Z2 Z4 Eg  Z2 Z4

a=1 a=1

(a) (b)

E1/a
Ideal Z3
Z1/a2 Z3 Z1/a2
I=0 Trans. I = 0 
aI1

Eg/a  Z2 Z4 Eg/a Z2 Z4

a=1

(c) (d)

Fig. 1.18:
(a) The actual circuit, showing the real voltages and currents on the primary side.
(b) Impedance Z1 is transferred to the secondary side. Note the corresponding change
in E1 and I1.
(c) The source is transferred to the secondary side. Note the corresponding change in
Eg. Note also that the currents in T are zero.
(d) All the impedances and even the source are now on the secondary side. The
transformer is no longer needed because its currents are zero.

Example 1.6:
Calculate voltage E and current I in the circuit of Fig. 1.19, knowing that ideal transformer
has a primary to secondary turns ratio of 1:100.

BTI - Electrical & Electronics Division 13 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

Solution:
The easiest way to solve this problem is to shift all the impedances to the primary
side of the transformer. Because the primary has 100 times fewer turns than the
secondary, the impedance values are divided by 1002 , or 10 000.

Voltage E becomes E/100, but current I remains unchanged because it is already


on the primary side (Fig. 1.18).
The impedance of the circuit in Fig. 1.20 is:

Z =  R2 + (XL - XC )2 =  42 + (5 - 2)2 = 5

The current in the circuit is: I = E / Z = 10 / 5 = 2 A

The voltage across the resistor is: E /100 = IR = 2  4 = 8 V

The actual voltage E is, therefore, E = 8  100 = 800 V

Ideal 20K
5
Trans.
I1 
10 V Eg E
40K

a = 1/100

Fig. 1.19: See Example 5

5 2

I1 
10V
4 E/100

Fig. 1.20: Equivalent circuit of Fig. 17

BTI - Electrical & Electronics Division 14 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Ideal Transformer

1.12 Questions and Problems:

1. The coil in Fig. 1.2-a has 500 turns and a reactance of 60 but negligible resistance. If it
is connected to a 120 V, 60 Hz source Eg, calculate the following:
a. The effective value of the magnetizing current Im.
b. The peak value of Im.
c. The peak and mmf produced by the coil.
d. The peak flux  max.

2. In Problem 1, if the voltage Eg is reduced to 40 V, calculate the new mmf developed by


the coil and the peak flux  max.

3. What is meant by mutual flux? by leakage flux?

4. The ideal transformer in Fig. 1.11 has 500 turns on the primary and 300 turns on the
secondary. The source produces a voltage Eg of 600 V, and the load Z is a resistance of
12.
Calculate the following:
a. The voltage E2 b. The current I2
c. The current I1 d. The power delivered to the primary
e. The power output from the secondary

5. In Problem 4, what is the impedance seen by the source Eg?

6. In Fig. 1.19, calculate the voltage across the capacitor and the current flowing through it.

7. The nameplate on a 50 kVA transformer shows a primary voltage of 480 V and a sec-
ondary voltage of 120 V. We wish to determine the approximate number of turns on the
primary and secondary windings. Toward this end, three turns of wire are wound around
the external winding, and a voltmeter is connected across this 3-turn coil. A voltage of 76
V is then applied to the 120 V winding, and the voltage across the 3-turn winding is found
to be 0.93 V. How many turns are there on the 480 V and 120 V windings
(approximately)?

8. A coil with an air core has a resistance of 14.7. When it is connected to a 42 V, 60 Hz ac


source, it draws a current of 1.24 A. Calculate the following:
a) The impedance of the coil.
b) The reactance of the coil, and its inductance.
c) The phase angle between the applied voltage.

9. Two coils are set up as shown in Fig. 1.4. Their respective resistances are small and may
be neglected. The coil having terminals 1, 2 has 320 turns while the coil having terminals
3, 4 has 160 turns. It is found that when a 56 V, 60 Hz voltage is applied to terminals 1-2,
the voltage across terminals 3-4 is 22 V. Calculate the peak values of , f1 and m1.

10. A 40 F, 600 V paper capacitor is available, but we need one having a rating of about
300 F. It is proposed to use a transformer to modify the 40 F so that it appears as 300
F. The following transformer ratios are available: 120 V/330 V; 60 V/450V; 480 V/150 V.
Which transformer is the most appropriate and what is the reflected value of the 40 F
capacitance? To which side of the transformer should the 40 F capacitor be connected?

BTI - Electrical & Electronics Division 15 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer

2. Practical Transformers

We studied the ideal transformer and discovered its basic properties. However, in the real world
transformers are not ideal and so our simple analysis must be modified to take this into account.
Thus, the windings of practical transformers have resistance and the cores are not infinitely
permeable. Furthermore, the flux produced by the primary is not completely captured by the
secondary. Consequently the leakage flux must be taken into account. And finally, the iron cores
produce eddy-current and hysteresis losses, which contribute to the temperature rise of the
transformer.
The properties of a practical transformer can be described by an equivalent circuit comprising
an ideal transformer and resistances and reactances. The equivalent circuit is developed from
fundamental concepts. This enables us to calculate such characteristics as voltage regulation
and the of transformers that are connected in parallel. The per-unit method is also used to
illustrate its mode of application.

2.1. Ideal transformer with an iron core:

The ideal transformer studied before had an infinitely permeable core. We can replace the ideal
transformer core by an iron core having hysteresis and eddy-current losses and a circuit with
two elements Rm and Xm in parallel with the primary terminals of the ideal transformer (Fig. 2.l-
a). The primary is excited by a source Eg that develops a voltage E1 .

The resistance Rm the iron losses and the resulting heat they produce. To furnish these losses a
small current IF is drawn from the line. This current is in phase with E1 (Fig. 2.l-b).
The magnetizing reactance Xm is a measure of the permeability of the transformer core. Thus if
the permeability is low, Xm is relatively low. The current Im flowing through Xm represents the
magnetizing current needed to create the flux  m in the core. This current lags 90° behind E1.

Note:
In practice, the normal procedure ensure the ES is in phase with EP (secondary and primary
terminal voltages) also I2 and I1 (secondary and primary currents). However, if ES and EP were
drown in phase with one another Fig. 2.1-b, the diagram would become cluttered and therefore,
for convenience, it is usual to show EP and ES in phase opposition with one another and also E1
and E2. This should be remembered that the manner of drawing is for convenience only.

Io I1 = 0  E2 If Eg, E1
I2= 0 

Im
Im Io
Eg If E2
Xm Rm E
1

I
n
m
d
u
(a) (b)
s
t
Fig. 2.1: (a) An imperfect core represented by a reactance Xm and a resistance Rm.
(b) Phasorrdiagram of a practical transformer at no-load.
i
The values of the impedances a Rm and Xm can be found experimentally by connecting the trans-
former to an ac source and l measuring the active power and reactive power absorbed. The
following equations then apply:
Rm = E12 / Pma (2.1)
p
Xm = E12 /Qm p (2.2)
l
BTI - Electrical & Electronics Division 16 Elbaz Bader Ayad
i YOSRY IDREES
c
a
t
o
n
:
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer
34.
where: A
Rm= resistance representing the iron losses []
Xm t
= magnetizing reactance of the primary winding []
E1= primary induced r voltage [V]
Pm= iron losses [W]a
Qm= reactive powernneeded to set up the mutual flux  m [var]
s
The total current needed to fproduce the flux  m in an imperfect core is equal to the phasor sum
of If and Im. It is called othe exciting current lo. The phasor diagram at no-load for the
transformer is shown in Fig.r l-b. The peak value of the mutual flux  m is again given by :
m
e f N1 )
 m = E1 / (4.44 (1.3)
r
Example 2.1:
A large transformer operating h at no-load draws an exciting current Io of 5 A when the primary is
connected to a 120 V, 60 Hz a source (Fig. 2.2-a). From a wattmeter test it is known that the iron
losses are equal to 180 W. s

Calculate: a
a. The reactive power absorbed by the core
b. The value of Rr m and Xm
c. The value of Iaf and Im
t
5A  i
I = 0 If = 1.5A
n2 120 V
g I
120 V m= 4.8A
Eg E1 E2
60 HZ
2 Io= 5A
0
Pm = 180 W (a) 0 (b)
m
Fig. 2.2: (a) See Example 1.
k (b) Phasor diagram.
Solution: V
A
a. The apparent power supplied to the core is: Sm = E1  Io = 120  5 = 600 VA
,
The iron losses are: Pm = 180W
The reactive power absorbed by the core is:
1
Q =  (Sm 2 - Pm 2) =  600 2 - 1802 = 572 var
4 m
b. The impedance corresponding to the iron losses is:
4 2 2
0 Rm = E1 / Pm = 2120 / 180 =2 80
The magnetizing reactance
0 is: Xm = Em / Qm = 120 / 572 = 25.2

c. The current needed toV supply the iron losses is: If = E1 / Rm = 120 / 80 = 1.5A
The magnetizing current
/ is: Im = E1 / Xm = 120 / 25.2 = 4.8 A
The exciting current 2Io is: Io =  (If 2 + Im 2) =  1.52 + 4.82 = 5 A
The phasor diagram7is given in Fig. 2-b.
7

V
.

T
h
e loose coupling:
2.2 Ideal transformer with
h
i
BTI - Electrical & Electronics Division 17 Elbaz Bader Ayad
g YOSRY IDREES
h

v
l
t
a
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer
g
e
We have just seen how an ideal transformer behaves when it has an imperfect core. We now
assume a transformer having w a perfect core but rather loose coupling between its primary and
secondary windings. We also i assume that the primary and secondary windings have negligible
resistance and the turns arenN1, N2.
d
Let us now connect a load i Z across the secondary, keeping the source voltage EP fixed ( see
Fig. 2.3 ). The operation sets
n as the following list:
g
1. Currents I1 and I2 immediately begin to flow in the primary and secondary windings.
They are related by the ideal-transformer equation:
h
I1 /I2 = N2 / N1, hence N1 I1 = N2 I2
a
2. I2 produces an mmf s (N2 I2) while I1 produces an mmf (N1 I1) . These
magnetomotive forces are equal and in direct opposition because when I1 flows into
the polarity-marked terminal
a 1, I2 flows out of polarity-marked terminal 3.
3. The mmf N2 I2 produces r a total ac flux  2 . A portion of  2 ( m2) links with the
primary winding while eanother portion ( f2) does not. Flux  f2 is called the
secondary leakage flux. s
i
 m1
s 11

I
1 t1
m2 I2 3
2
a
Eg Ep n N  f1  f2

Z
N2 Es
1 
c
2 e 4

o
Fig. 2.3: Mutual fluxes and leakage fluxes produced by a transformer under load.
f fluxes are due to the imperfect coupling between the coils.
The leakage

4. Similarly, the mmf N1 I1 6produces a total ac flux  1 . A portion of  1 ( m1 ) links with


2
the secondary winding, while another portion ( f1)) does not. Flux  f1 is called the
primary leakage flux.

5. We combine  m1 and  m2 . into a single mutual flux  m (Fig. 2.4). This mutual flux is
created by the joint action of the primary and secondary mmfs.
W
h
m 
a I
1 1 I2 3
t
Eg Ep  f1  f2

Z
Es
i N1   N2
s
2 4
t
h
Fig. 2.4: A transformer possesses two leakage fluxes and a mutual flux.
e
6. We note that the primary leakage flux  f1 is created by N1 I1 , while the secondary leakage
a
 f2 created by N2 I2. Consequently, leakage flux  f1 is in phase with I1 and leakage flux  f2 is
in phase with I2. p
p
7. The voltage Es induced rin the secondary is actually composed of two parts:
a. A voltage Ef2 induced oby leakage flux  f2 and given by:
Ef2 = 4.44 f Nx2  f2 (2.3)
i
m mutual flux  and given by:
b. A voltage E2 induced by m
a
t
BTI - Electrical & Electronics Division 18 Elbaz Bader Ayad
e YOSRY IDREES

r
e
i
s
t
BTEC – HND Year 2 - Utilizationaof Electrical Energy Practical Transformer
n
E2 = 4.44 f Nc2  m (2.4)
e
In general, Ef2 and E2 are not in phase. Similarly, the voltage Ep induced in the primary is
composed of two parts: o
a. A voltage Efl induced by f leakage flux  f1 and given by
Ef1 = 4.44 f N1  f1 (2.5)
t
h mutual flux  and given by:
b. A voltage E1 induced by m
e
E1 = 4.44 f N1  m (2.6)
2
8. Induced voltage Ep = applied voltage Eg.
7
Using these eight basic facts, we now proceed to develop the equivalent circuit of the
7
transformer.
V
2.3 Primary and secondary leakage reactance:

We can better identify thew four induced voltages E1 , E2 , Ef1 and Ef2 by rearranging the
transformer circuit as shown i in Fig. 2.5. Thus, the secondary winding is drawn twice to show
n
even more clearly that the N2 turns are linked by two fluxes,  f2 and  m.
d
i
n
f1 g m  f2
I1 1 I2 3
 N1 ?  N2 
Eg Ep E35.
f1 E2 Ef2 Es Z
ET1
N1 N2
h
2 e 4

p Separating the various induced voltages due to


Fig. 2.5:
r the mutual flux and the leakage fluxes.
i
This rearrangement does not m change the value of the induced voltages, but it does make each
voltage stand out by itself. aThus, it becomes clear that Ef2 is really a voltage drop across a re-
r
actance. This secondary leakage reactance Xf2 is given by:
Xf2 = Ef2 / I2 y (2.7)

The primary winding is alsow shown twice, to separate E1 from Ef1. Again, it is clear that Ef1 is
simply a voltage drop across i a reactance. This primary leakage reactance Xf1 is given by:
Xf1 = Ef1 / I1 n (2.8)
d
The primary and secondaryi leakage reactances are shown in Fig. 2.6. We have also added the
primary and secondary winding n resistances R1 and R2, which, of course, act in series with the
respective windings. g

o Xf1

m Xf2 R2
R1
I1 1 f 3 I2

Eg Ep t E2 Es Z
E1
h
2 e N1 N2
4

t and leakage reactance of the primary and secondary windings.


Fig. 2.6: Resistance
2.4 Equivalent circuit of
r a practical transformer:
a
n
s
f
BTI - Electrical & Electronics Division 19 Elbaz Bader Ayad
o YOSRY IDREES
r
m
e
i
n
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer
P
The circuit of Fig. 2.6 is composedr of resistive and inductive elements (R1 , R2 , Xf1 , Xf2 , Z)
coupled together by a mutual o flux  m which links the primary and secondary windings. The
leakage-free magnetic coupling b enclosed in the dotted oval is actually an ideal transformer. It
possesses the same properties l and obeys the same rules as the ideal transformer discussed
before. For example, we can e shift impedances to the primary side by multiplying their values by
(NI / N2)2, as we did before. m
3
If we add circuit elements 4Xm and Rm to represent a practical core, we obtain the complete
equivalent circuit of a practical transformer (Fig. 2.7-a). In this circuit T is an ideal transformer,
but only the primary and secondary i terminals 1-2 and 3-4 are accessible; all other components
are "buried" inside the transformers itself. However, by appropriate tests we can find the values
of all the circuit elements that make up a practical transformer.
w
Fig. 2.7-b shows the phasor o diagram of a practical transformer. It is clear that the primary
current IP equal to the phasor u sum of I1 and Io .
where : n
Io = no-load dcurrent.
I1 = secondary current (I2) referred to the primary side.
[I1 = I2 / a = I2w(N2 / N1)]
i Xf2 R2
R1 Xf1
Ip 1 t I1 3 I2
 I
ho 
Eg Ep E1 E2 Es Z
Xm R
Im
NI m N1 N2
2 o f 4
. EP , E 1
(a)
P
1 IP
1 I1

o
g
a If Io
u
g circuit of a practical
Fig. 2.7: a) Complete equivalent
Im m
transformer. e
b) Phasor diagram of a practical S
transformer A
W
G I2

(b)
w ES , E2
Class work 2.2: i
The secondary winding of a r transformer possesses 180 turns. When the transformer is under
load, the secondary currentehas an effective value of 18 A, 60 Hz. Furthermore, the mutual  m
has a peak value of 20 mWb.. The secondary leakage flux f2 has a peak value of 3 mWb.
Calculate:
a) The voltage inducedCin the secondary winding by its leakage flux
b) The value of the secondary
a leakage reactance
c) The value of E2 induced
l by the mutual flux  m
c
u
l
a
t
2.5 Transformers and the e per-unit system:

t
h
BTI - Electrical & Electronics Division 20 Elbaz Bader Ayad
e YOSRY IDREES

a
p
r
o
BTEC – HND Year 2 - Utilizationxof Electrical Energy Practical Transformer
i
m
The per-unit system of measurement is particularly useful when dealing with transformer. The
a
nominal power rating SB of the transformer is selected as the base power, and the nominal
t
voltage EB is selected as the base voltage. It follows that the base current In is equal to SB / EB,
e
which is the same as the nominal current.
c
The base impedance ZB is therefore equal to EB / IB. Note that EB and IB are the nominal voltage
r
and nominal current on either the primary or secondary side. The base impedance may also be
o
calculated by the equation:
2 s
ZB = EB / SB (2.9)
s
where:
ZB = base impedances of the transformer []
SB = power rating of
e the transformer [VA]
EB = nominal voltage
c of the transformer on either the primary or secondary side [V]
t
Because the primary and secondary
i voltages are usually different, it follows that a transformer
has two base impedances, oone for the primary and one for the secondary. Depending upon the
respective voltages, the twonimpedances may be vastly different.

Example 2.3: (
Calculate the base impedance
i of a transformer rated 250 kVA, 4160 V / 480 V, 60 Hz, on the
a) primary and n
b) secondary side.
s
Solution: q
a. Base impedance onu the primary side is: ZBp = Ep2 / SB = 41602 / 250 000 = 69 
a
b. Base impedance onr the secondary side is: ZBs = Es2 / SB = 4802 / 250000 = 0.92 
e
2.6 Per-unit impedances:
m
We can get a better idea i of the relative magnitude of the winding resistance, leakage
reactance, etc., of a transformer
l by comparing these impedances with the base impedance of
the transformer. In makingl the comparison, circuit elements located on the primary side are
compared with the primary i base impedance. Similarly, circuit elements on the secondary side
are compared with the secondary
m base impedance. The comparison can be made either on a
percentage or on a per-unite basis; we shall use the latter. Typical per-unit values are listed in
Table 2-A, for transformers t ranging from 3 kVA to 100 MVA. For example, the per-unit
resistance of the primary winding
e of a transformer ranges from 0.009 to 0.002 for all power rat-
ings between 3 kVA and 100r MVA. Over this tremendous power range, the per-unit resistance of
the primary or secondary windings
s varies only from 0.009 to 0.002 of the base impedance of the
transformer. Knowing the base) impedance of either the primary or the secondary winding, we
can readily estimate the order of magnitude of the real values of the transformer impedances.
Table 2-A is, therefore, a useful
o source of information.
R1 f Xf1 Xf2 R2
Ip 1 I1 3 I2
 Io 
t Es Z
Eg Ep E1 E2
hXm Rm
N1 N2
eIm If
2 4
c
o
Fig. 2.8: Equivalent circuit of a transformer.
n
d
u
c Typical per-unit values
Circuit element t 3 KVA to 250 KVA 1 MVA to 100 MVA
o
BTI - Electrical & Electronics Division
r
21 Elbaz Bader Ayad
YOSRY IDREES
s

i
t
h
BTEC – HND Year 2 - Utilizationeof Electrical Energy Practical Transformer

R1 or R2 s 0.009 - 0.005 0.005 - 0.002


e
Xf1 or Xf2 0.008 - 0.025 0.03 - 0.06
c
Xm o 20 - 30 50 - 200
Rm n 20 - 50 100 - 500
Io d 0.05 - 0.03 0.02 - 0.005
a
Table 2-A: Typical per-unit valuesrof transformers
y
Example 2.4:
Using the information given w in Table 2-A, calculate the approximate real values of the
impedances of a 250 kVA, 4160 i V/480 V, 60 Hz distribution transformer.
n
Solution: d
We first determine the basei impedances on the primary and secondary side. From the results of
Example 3, we have: ZBp =n 69  ZBs = 0.92 
We now calculate the real impedance
g by multiplying ZBp and ZBs by the per-unit values given in
Table 2-A. Thus, referring to. Fig. 2-8 we find the following:
36.
R1 = 0.005  69 = 0.35  A R2 = 0.005  0.92 = 4.6 m
Xf1 = 0.025  69 = 1.7  n Xf2 = 0.025  0.92 = 23 m
Xm = 30  69 = 2 K Rm = 50  69 = 3.5 K
o
i Xf1 Xf2 R2
R1
l 4.6m
0.35
1.7 23
Eg 4160V f Xm
480V Z
Z 0.92
Rm
i 2K 3.5K N1 N2
l
l a = 4160/480
e = 8.87
d Fig. 2.9: See Example 2.4

This example shows the usefulness


d of the per-unit method of estimating impedances. The
equivalent circuit of the 250i kVA transformer is shown in Fig. 2.9. The true values may be 20 to
50 percent higher or lower than
s those shown in the figure. The reason is that the per-unit values
given in Table 2-A are broadt estimates covering a wide range of transformers.
r
2.7 Simplifying the equivalent
i circuit:
b
The equivalent circuit of a utransformer (Figs. 2.7 and 2.8) is relatively simple, but it gives far
more detail than is needed tin most practical problems. Consequently, we can simplify it to make
the calculations easier. Let us
i try to simplify the circuit when the transformer operates:
1. at no-load and o
2. at full-load. n

1. At no-load: (Fig. 2.10) It2 is zero and so is I1 because T is an ideal transformer.


Consequently, only the exciting
r current Io flows in Rl and Xfl. These impedances are so small
that the voltage drop across a them is negligible. Furthermore, the current in R2 and Xf2 is zero.
We can, therefore, neglectnthese four impedances, giving us the much simpler circuit of Fig.
2.11. s
f
o
r
Xf1 Xf2 R2
1 m
Ip R X1 I2
e  Io 
E E r Es
g p Xm Rm
BTI - Electrical & Electronics Division N1 22 N2 Elbaz Bader Ayad
r YOSRY IDREES
a
t
e
a
t
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer
1
0

k
Fig. 2.10: Complete equivalent circuit of a transformer at no-load.
V
A
Io
w
Eg eEp Rm E1 E2 Es
Xm
i N1 N2
g
h
Fig. 2.11: Simplified circuit at no-load
s
The turns ratio, a = N1 / N21, is obviously equal to the ratio of the primary to secondary voltages
Ep / Es measured across the1terminals.
8
2. At full-load: Ip is at least 20 times larger than Io. Consequently, we can neglect Io and the
corresponding magnetizingkbranch. The resulting circuit is shown in Fig. 2.12. This simplified
circuit may be used even wheng the load is only 10 percent of the rated capacity of the trans -
former. , Xf1 Xf2 R2
R1

w Ip

I2
Eg Ep h Es Z
e N1 N2
r
e
Fig. 2.12: Simplified equivalent circuit of a transformer at full-load.
a
s
R1 2
a R2 Xf1
2
a Xf2

a Ip

Fig. 2.13:Eg Equivalent


Ep circuit with impedances shifted
aEs to the aprimary
2
Z side.
1
We can further simplify the0circuit by shifting everything to the primary side, thus eliminating
transformer T (Fig. 2.13). Then,0 by summing the respective resistances and reactances, we
obtain the circuit of Fig. 2.14. In this circuit:
Rp = R1 + a2Rk2 (2.10)
V
Xp = Xfl + a2 XAf2 (2.11)
where:
t
Rp = total transformer resistance referred to the primary side
r
Xp = total transformer leakage reactance referred to the side
a
n Xp
Ip Rp
s
f
oEg Ep Zp aEs a2Z
r
m
Fig. 2.14: The einternal impedance of a large transformer is mainly reactive.
The combination of Rp and X r p constitutes the total transformer impedance Zp referred to the pri-
mary side. From the impedance triangle we have:
Zp =  (Rp2 + Xo p2 ) (2.12)
f
Impedance Zp is usually expressed as either a percent or per-unit of the base primary
impedance Zn, mentioned before. t The per-unit impedance is always given on the nameplate of
the transformer. h
e
BTI - Electrical & Electronics Division 23 Elbaz Bader Ayad
s YOSRY IDREES
a
m
e
k
i
n
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer
d

w
Transformers above 500 kVA possess a leakage reactance Xp at least five times greater than
e
Rp. In such transformers we can neglect Rp , as far as voltages and currents are concerned.
i
The equivalent circuit is thus reduced to a simple reactance Xp between the source and the
g
load (Fig. 2.15). It is quite remarkable that the relatively complex circuit of Fig. 2-8 can be
h
reduced to a simple reactance in series with the load.
s
Xp
4
4 Ip
Eg Ep aEs a2Z
5

k
g
Fig. 2.15: The internal impedance of a large transformer is mainly reactive.
.
2.8 Voltage Regulation of a Transformer:
C
The voltage regulation of aa transformer is defined as the variation of the secondary voltage
l
between no-load E2 and full-load VS , expressed as either a per-unit or a percentage of the no-
load voltage E2 , the primaryc voltage being assumed constant.
u
l Noload voltage  Full load voltage
PercentageaRegulation =  100
Noload voltage
t
e = (E2 - ES)  100 / E2
Per-unit Regulation = (E2 - ES) / E2 (2.13)
t
To calculate voltage regulation,
h the primary winding resistance and reactance are referred to the
secondary; the equivalent values
e are used to construct the secondary phasor diagram in which
the load current is with a lagging phase angle  S (See Fig. 2.16 & Fig. 2.17)
p
o RS XS Is
w
e
r
L
Ep = E1 o o
Es
u E2 a
N2 t
N1 d
p
u
t
Fig. 2.16: Equivalent Circuit Referred to Secondary Side

i
In a resistance, the voltage and current are in-phase therefore the (Is. Rs) is in-phase with IS.
n
This is added to Es as shown in Fig. 2.17.
w
The voltage developed across a pure inductance lead the current by 90 so that the voltage
a
(IsXs) leads Is by 90. t
t
Finally add (Is Rs) and (Is Xss) to give (Is Zs) and the later will add to Es to gives E2 . For the
E2 C
leading power factor, the load voltage Es is more than E2 .
p
s
e
r I 2 Zs
S
I 2 Xs
 ES
k M N
O
s i A s
BTI - Electrical & Electronics Division
l 24 Elbaz Bader Ayad
I 2 Rs YOSRY IDREES
o
g B
I r
2
m

i
BTEC – HND Year 2 - Utilizationnof Electrical Energy Practical Transformer

e
a
c
h

c
a
s
e
.
37.
T Fig. 2.17: Phasor diagram
h
e and losses are small. Thus, the impedance triangle will be small
Transformer are highly efficient
compared to the voltages (Es & E2 ).
t
r
The angle  will be so small a that it can be said that :
n
OC = ON s
E2 - Es = OC f- OA = ON - OA
o
= AN r = AM + MN
m
= Is Rs eCos  s  IS XS Sin  s
r
= I2 ( RS Cos  s + XS Sin  s ) at lagging power factor
= I2 ( RsS Cos  s - XS Sin  s ) at leading power factor
h
o
Therefore, the fractional regulation can be given by :
w
E2  E S nI (R Cos θ
 2 S S  X S Sin θ S )
(2.14)
E2 i E2
Example 2.5: n
A single-phase transformer that is rated 3000 kVA, 69 kV/4.16 kV,60 Hz has an impedance of 8
percent. F
i
g
Calculate:
.
a. The total impedance of the transformer referred to the primary side
b. The voltage regulation from no-load to full-load for a 2000 kW resistive load, knowing that the
1
primary supply voltage is fixed at 69 kV
3
c. The primary and secondary currents if the secondary is accidentally short-circuited.
h
Solution:
a
a. The base impedance on the primary side is:
s
ZBp = EB2 / SB = (69000)2 / 3 000 000 = 1587 
a
The transformer impedance referred to the primary side is:
r Zp = Z(pu)  ZBp = 0.08  1587 = 127 
a
Because the transformer exceeds
t 500 kVA, the windings have negligible resistance compared
to their leakage reactance; we
i can therefore write: Zp = Xp = 127 
n
g Xp= 127

o
BTI - Electrical & Electronics Division Ip 25 Elbaz Bader Ayad
69f KV Eg Ep aEs a2Z YOSRY IDREES
2380

4
0
k
V
A
BTEC – HND Year 2 - Utilization.of Electrical Energy Practical Transformer

I
f

8
0
Fig. 2.18: See Example 5.
V
b. Approximate impedance Z of the 2000 kW load:
i Z = Es / P = 4160 / 2 000 000 = 8.65 
2 2

s
Impedance referred to primary side: a2 Z = (69 / 4.16)2  8.65 = 2380 
a
Referring to Fig.p 2.18 we have:
p Ip = 69 000 / 1272 + 23802 = 28.95 A
l
ai Es = (a2 Z) Ip = 2380  28.95 = 68 902 V
e
d Es = 68 902  (4.16 / 69) = 4154 V

Secondary no-loadbvoltage = 4160 V


e percent is:
Voltage regulation in
t
w No load voltage  Full load voltage
Voltage Regulation   100
e No load voltage
e
n 4160 - 4154
=  100  0.14 %
4160
t
c. Referring again toe Fig. 2.18, if the secondary is accidentally short-circuited, we
find: r
m Ip = Ep / Xp = 69 000 / 127 = 543 A
i
The correspondingn current Is on the secondary side:
a Is = a Ip = (69 / 4.16)  543 = 9006 A
l
s
The short-circuit currents in the primary and secondary windings are 12.5 times greater than the
rated values. The I2R losses X are, therefore, 12.52 or 156 times greater than normal. The
circuit-breaker or fuse protecting
1 the transformer must open immediately to prevent overheating.
Very powerful electromagnetic forces are also set up. They, too, are 156 times greater than
normal and, unless the winding, are firmly braced and supported, they may be damaged or torn
apart.
a
n
d

X
2.9 Measuring transformer
2
impedances:
,
For a given transformer, we can determine the actual values of all the impedances shown in Fig.
2.8 by means of an open-circuit w test and a short-circuit test.
During the open-circuit test, h rated voltage is applied to the primary winding and current Io ,
voltage Ep, and active power a Pm are measured (Fig. 2.19). The secondary open-circuit voltage
Es is also measured. Thesettest results give us the following information:
active power absorbed by core = Pm
apparent power absorbed by v core = Sm = Ep Io
o
BTI - Electrical & Electronics Division 26 Elbaz Bader Ayad
l YOSRY IDREES
t
a
g
w
i
BTEC – HND Year 2 - Utilizationl of Electrical Energy Practical Transformer
l
reactive power absorbed by core = Qm
where : Qm = S m2 a Pm2
p
Resistance Rm corresponding to the core loss is: Rm = Ep2 / Pm (2.1)
p
Magnetizing reactance Xm is: Xm = Ep2 / Qm (2.2)
e
Turns ratio a is: a = N1 / N2 = Ep / Es
a
Io
r
W
Fig. 2.19: Open-circuit test and A
determination of Rm, Xm, and turns ratio.
b X1 H1
Pm
During the short-circuit test,e the secondary winding is short-circuited and a voltage Eg much
lower than normal (usually tless than 5 percent of rated voltage) is applied to the primary. The
primary
Eg current ISc shouldw be less than its Ep nominal
V value to prevent over-heating
Es V and,
e change in winding
particularly, to prevent a rapid resistance while the test is being made.
e
The voltage Esc, current Isc ,nand power Psc are measured on the primary side (Fig. 2.20) and the
following calculations made: X2 H
t 2

e
Total transformer impedance referred to the primary side is:
Zp = Esc / Isc r (2.15)
m
Total transformer resistance referred to the primary side is:
2i
Rp = Psc / Isc (2.16)
n
Total transformer leakage reactance referred to the primary side is:
Xp =  Z p - Ra2p
2
(2.12)
l Isc
s
W A
H1
Psc 3 X1

a
Eg n Esc V
d

4
? H X2
2

I
Fig. 2.20: Short-circuit test to determine leakage reactance and winding resistance.
f
Example 2.6:
a a transformer rated 500kVA, 69 kV/4.16 kV, 60 Hz, the
During a short-circuit test on
following voltage current, and power measurements were made.
s
Terminals X1 , X2 were in short-circuit (see Fig. 2.20):
Esc = 2600 V i Isc = 4 A Psc = 2400 W
Calculate: n
the value of the reactance gand resistance of the transformer, referred to the HV side, as
l
well as the percent impedances.
e
Solution :
Referring to the equivalent l circuit of the transformer under short-circuit conditions (Fig.
o
2.21), we find the following values:
 Transformer impedancea referred to the primary is: ZP = Esc / Isc = 2600 / 4 = 650 
 Resistance referred dto the primary is: Rp = Psc / Isc2 = 2400 /1 6 = l50 
 Leakage reactance referred to the primary is: Xp =  6502 - 1502 = 632 
i
 Nominal primary voltage is: Ep = 69 kV
s
 Nominal primary current is: Ip = 500 kVA / 69 kV = 7.25 A
 Base impedance referred
a to the primary is: ZBP = Ep / Ip = 69 000 / 7.25 = 9517 
p Xp
Rp
p
BTI - Electrical & Electronics Division 27 Elbaz Bader Ayad
l  Isc= 4 A
YOSRY IDREES
2600 Vi Esc
e
d
b
e
t
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer
w
e
e
n

t
e
r
Fig. 2.21 : See Example 2.6.
m
i
Per-unit impedance = Zp / ZBP = 650 / 9517 = 0.0682 (Percent impedance = 6.82%)
n
Per-unit reactance = Xp / ZBP = 632 / 9517 = 0.0664 (Percent reactance = 6.64%)
a
Per-unit resistance = Rp / ZBP = 150 / 9517 = 0.0158 (Percent resistance = 1.58%)
l
s
2.10 Efficiency of a Transformer:
3
The losses which occur in a transformer on load can divided into two groups:
a secondary windings, namely I 2 R + I 2 R ;
1. I2 R losses in primary and 1 1 2 2
n
2. Core losses due to hysteresis and eddy currents.
d
Since the maximum value of the flux in a normal transformer does not vary by more than about
2 per cent between no-load 4 and full-load, it is usual to assume the core loss constant at all
loads.
w total losses in transformer are:
Hence, if Pm = total core loss,
h Pm + I12 R1 + I22 R2
a
Efficiency = output power / input power = output power / (output power + losses)
t
I E  p.f.
i 2 S
= (2.17)
I E Ss p.f  Pm  I 12 R1  I 22 R2
2
Greater accuracy is tpossible by expressing the efficiency thus:
h
Efficiency = outputepower / input power = input power - losses / input power

= 1 - ( lossesm / input power) (2.18)


a
x
i
Example 2.7: m
An open-circuit test was conductedu on the transformer given in Example 2.6. The following
results were obtained whenmthe low-voltage winding was excited. (In some cases, such as in a
repair shop, a 69 kV voltage may not be available and the open-circuit test has to be done by
exciting the LV winding.) a
Es = 4160 V l Io = 2 A Pm = 5000 W
Using this information and the l transformer characteristics found in Example 2.6, calculate:
a) the efficiency and o
b) the voltage regulation
w of the transformer when it supplies a 250 kVA, 80
percent power factora (lagging) load.
b
l
Solution: e
The equivalent circuit of the transformer and its load is represented by Fig. 2.22. The values of
Rp end Xp are already known, c and so we only have to add the magnetizing branch. To simplify
the calculations, u
r
Rp Xp
1 r  3  5
150 e I1=3.62A I2=60A
632 250KVA
Xm Rm n 69KV 4160V cos  = 0.8
BTI - Electrical & Electronics Division
5000W t 28 N Elbaz Bader Ayad
N1 2 YOSRY IDREES
2 4 6
t
h
c
BTEC – HND Year 2 - Utilizationaof Electrical Energy Practical Transformer
n

b
e

d Fig. 2.22: See Example 2.7.


r
we shifted Xm and Rm fromaterminals 3, 4 to the input terminals 1, 2. This change is justified
because these impedancesware much greater than Xp and Rp. Let us assume that the voltage
across the load is 4160 V. We n now calculate the efficiency of the transformer.
?
a. The load current is: I2 = S / Es = 250 000 / 4160 = 60 A
The current in the primary is: I1 = I2 / a = 60  4.16 / 69= 3.62 A
The total copper loss (primary and secondary) is:
Pcopper = I12 Rp = 3.622  150 = 1966 W
The iron loss is the same as that measured on the LV side of the transformer.
Piron = 5000 W
Total losses are: Plosses = 5000 + 1966 = 6966 W = 7 kW
The active power delivered by the transformer to the load is:
Po/p = S cos  = 250  0.8 = 200 kW
The active power received by the transformer is:
Pi/p = Po + Plosses = 200 + 7 = 207 kW
The efficiency is:  = Po/p / Pi/p = 200 / 207 = 0.966 or 96.6%

Note that in making the above calculations, we only consider the active power. The reactive
power of the transformer and its load does not enter into efficiency calculation. Let us now
determine the voltage regulation.

b. In examining Fig. 2.22, it is obvious that the presence of the magnetizing branch does not
affect the voltage drop across RP and Xp. Consequently, the magnetizing branch does not
affect the voltage regulation.

To determine the voltage regulation, we will use the per-unit method. All voltages, imped-
ances, and currents are referred to the HV (69 kV) side. We assume the voltage between
terminals 1, 2 is 69 kV, and that it remains fixed. The base power PB is 500 kVA The base
voltage EB is 69 kV. Consequently, the base current is:
IB = PB / EB = 500 000 / 69 000 = 7.25 A
and the base impedance is:
ZB = EB / IB = 69 000 / 7.25 = 9517 
The per-unit value of RP is: RP(PU) = 150 / 9517 = 0.0158
The per-unit value of Xp is: Xp(pu) = 632 / 9517 = 0.0664
The per-unit value of voltage El2 is: El2(pu) = 69 000 / 69 kV = 1.0
The per-unit value of the apparent power absorbed by the load is:
S(pu) = 250 kVA / 500 kVA = 0.5

The per-unit value of the active power absorbed by the load is:
P(pu)= S(pu) cos  = 0.5 X 0.8 = 0.4
The per-unit value of the reactive power absorbed by the load is:
Q(pu) =  S2(pu) - P2(pu) =  0.52 - 0.42 = 0.3
The per-unit load resistance RL corresponding to P is:
RL(PU) = E2(PU) / P(PU) = 12 / 0.4 = 2.50
The per-unit load reactance XL corresponding to Q is:
XL(PU) = E2(PU) / Q(PU) = 12 / 0.3 = 3.333

Rp(pu) Xp
1 3
0.058
I1 j0.066
E(pu) E 4 RL(pu) XL(pu)
g
BTI - Electrical & Electronics1.0
Division 29 2.5 j3.33 Elbaz Bader Ayad
YOSRY IDREES
2 4
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer

Fig. 2.23: Per-unit equivalent circuit of a 500 kVA transformer


feeding a 250 kVA load.

We now draw the equivalent per-unit circuit shown in Fig. 2.23. The magnetizing branch is not
shown because it does not enter into the calculations. Note that the load appears across the
primary terminals 3 ,4 of the circuit shown in Fig. 2.22.
The per-unit impedance between terminals 3, 4 is:
2.5  j3.33
Z  = 1.6 + j1.2  236.87
34(PU) 2.5  j3.33
1
The per-unit impedance between terminals 1, 2 is:
Z12(PU) = 0.0158 + 1.6 + j(1.2 + 0.0664) = 1.616 + j 1.266 = 2.053 38.07

The per-unit current I1 is:


I1(pu) = E12(PU) / Z12(PU) = 1.0 / 2.053 38.07 =0.4872 -38.07

The per-unit voltage E34 across the load is:


E34(pu) = Il(pu) x Z34(pU) = (0.4872  -38.07°)  (2  36.87°) = 0.9744  -1.20°

The per-unit voltage regulation is:


= ( E34(pu) at no-load - E34(pu) at full-load) / E34(pu) at no-load
= (1.0 - 0.9744 ) / 1 = 0.0256

If we wish, we can calculate the actual values of the voltage and current as follows:
a. Voltage across terminals 3, 4 is:
E34 = E34(pU)  EB == 0.9744 x 69 000 = 67.23 kV

b. Actual voltage across the load is: E56 = E34 x (4160 / 69 000) = 4053 V

c. Actual line current is: I1 = Il(pu) x IB = 0.4872  7.246 = 3.53 A

2.11 Condition for Maximum Efficiency of a Transformer:

If RS is the equivalent resistance of the transformer referred to the secondary circuit,

RS = R1(N2 / N1 )2 + R2 (2.10)

= a constant for a given transformer

Hence for any load current I2, total losses I2 R = I22 RS , and

I E  p.f.
2 S
Efficiency =
I E  p.f.  P  I2 R
2 S m 2 S

E Cos
s s
= E Cos  (P /I )  I R
s s m 2 2 s

For a normal transformer ES is approximately constant, hence for a load of given power factor
the efficiency is a maximum when the denominator of the last equation is minimum, i.e. when:

BTI - Electrical & Electronics Division 30 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer

d (E  p.f .  Pm  I 2 Rs )  0
dI 2 s I2

Pm
therefore  2
R 0
s
I2

or I22 RS = Pm (2.19)

Now it is clear that the efficiency is a maximum when the variable I 2R (copper losses) is equal
the constant core losses

BTI - Electrical & Electronics Division 31 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer

2.12 Questions and Problems:

Practical level:
1. Name the principal parts of a transformer.
2. Explain how a voltage is induced in the secondary winding of a transformer.
3. The secondary winding of a transformer has twice as many turns as the primary. Is the
secondary voltage higher or lower than the primary voltage?
4. Which winding is connected to the load: the primary or secondary?
5. State the voltage and current relationships between the primary and secondary windings of
a transformer under load. The primary and secondary windings have N 1 and N2 turns,
respectively.
6. Name the losses produced in a transformer.
7. What purpose does the no-load current of a transformer serve?
8. Name three conditions that must be met in order to connect two transformers in parallel.
9. What is the purpose of taps on a transformer?
10. Name three methods used to cool transformers.
11. The primary of a transformer is connected : to a 600 V, 60 Hz source. If the primary has
1200 turns and the secondary has 240, calculate the secondary voltage. [120V]
12 The windings of a transformer respectively have 300 and 7500 turns. If the low-voltage
winding is excited by a 2400 V source, calculate the voltage across the HV winding.
[60 KV]
13. A 6.9 kV transmission line is connected to a transformer having 1500 turns on the primary
and 24 turns on the secondary. If the load across the secondary has an impedance of 5 .
calculate the following: a. The secondary voltage b. The primary and secondary currents
[110.4V, 0.353A, 22.08A]
14. The primary of a transformer has twice as many turns as the secondary. The primary voltage
is 220 V and a 5  load is connected across the secondary. Calculate the power delivered
by the transformer, as well as the primary and secondary currents.
[2.42KW, 11A, 22A]
15. A 3000 kVA transformer has a ratio of 60 kV to 2.4 kV. Calculate the nominal current of each
winding. [50A, 1250A]

Intermediate level:
16. In Problem 11, calculate the peak value of the flux in the core.
17. Explain why the peak flux in a 60 Hz transformer remains fixed as long as the ac supply
voltage is fixed.
18. The transformer in Fig. 2.24 is excited by a 120 V, 60 Hz source and draws a no-load
current Io of 3 A. The primary and secondary respectively possess 200 and 600 turns. If 40
percent of the primary flux is linked by the secondary, calculate the following:
a. The voltage indicated by the voltmeter [144V]
b. The peak value of flux  [2.25mwb]
c. The peak value of m [0.9mwb]
d. Draw the phasor diagram showing El, E2,, Io , m and  f1

Fig. 2.24 See Problem 18.

BTI - Electrical & Electronics Division 32 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Practical Transformer

19. Explain why the secondary voltage of a practical transformer decreases with increasing
resistive load.

20. What is meant by the following terms:


a. Transformer impedance
b. Percent impedance of a transformer

21. The transformer in Problem 15 has an impedance of 6 percent. Calculate the impedance
referred to:
a. The 60 kV primary [72 ]
b. The 2.4 kV secondary [0.115 ]

22. A 66.7 MVA transformer has an efficiency of 99.3 percent when it delivers full power to a
load having a power factor of 100 percent.
a. Calculate the losses in the transformer under these conditions. [466.9 KW]
b. Calculate the losses and efficiency when the transformer delivers 66.7 MVA to a load
having a power factor of 80 percent. [466.9Kw, 99.1%]

Advanced level:
23. The impedance of a transformer increases as the coupling is reduced between the primary
and secondary windings. Explain.

24. The following information is given for the transformer circuit of Fig. 2.12.
Rl = 18  Ep = 14.4 kV (nominal)
R2 = 0.005  Es = 240 V (nominal)
Xfl = 40 Xf2 = 0.01
If the transformer has a nominal rating of 75kVA, calculate the following:
a. The transformer impedance [] referred to the primary side [84.1 ]
b. The percent impedance of the transformer [3.04%]
c. The impedance [] referred to the secondary side [23.36m]
d. The percent impedance referred to the secondary side [3.04%]
e. The total copper losses at full load [976 W]
f. The percent resistance and percent reactance of the transformer [1.3%, 2.75%]

25. During a short-circuit test on a 10 MVA, 66 kV/7.2 kV transformer, the following results were
obtained:
Eg = 2640 V ISc = 72 A Psc = 9.85 kW
Calculate the following:
a. The total resistance and the total leakage reactance referred to the 66 kV primary side
. [1.9 , 36.6 ]

b. The nominal impedance of the transformer referred to the primary side. [453.6 ]
c. The percent impedance of the transformer. [8.4%]

BTI - Electrical & Electronics Division 33 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Three Phase Transformer

3. Three Phase Transformers


In order to transmit and distribute an electrical power efficiently and economically, the voltages
must be at appropriate levels. These levels ((13.8 kV to 765 kV) depend upon the amount of
power that has to be transmitted and the distance it has to be carried. Another aspect is the
appropriate voltage levels used in factories and homes. These are fairly uniform, ranging from
120/240 V single-phase systems to 600 V 3-phase systems. Clearly, this required the use of
3-phase transformers to transform the voltages from one level to another.

The transformers may be inherently 3-phase, having three primary windings and three
secondary windings mounted on a 3-legged core. However, the same result can be achieved by
using three single-phase transformers connected together to form a 3-phase transformer bank.

3.1 Basic properties of 3-phase transformer banks:

When three single-phase transformers are used to transform a 3-phase voltage, the windings
can be connected in several ways. Thus, the primaries may be connected in delta and the
secondaries in star (wye), or vice versa. As a result, the ratio of the 3-phase input voltage to the
3-phase output voltage depends not only upon the turns ratio of the transformers, but also upon
how they are connected.
A 3-phase transformer bank can also produce a phase shift between the 3-phase input voltage
and the 3-phase output voltage. The amount of phase shift depends again upon the turns ratio
of the transformers, and on how the primaries and secondaries are connected.

Furthermore, the phase shift feature enable us to change the number of phases. Thus, a
3-phase system can be converted into a 2-phase, a 6-phase, or a 12-phase system. Indeed, if
there were a practical application for it, we could even convert a 3-phase system into a 5-phase
system by an appropriate choice of single-phase transformers and interconnections.

In making the various connections, it is important to observe transformer polarities. An error in


polarity may produce a short-circuit or unbalance the line voltages and currents.

The basic behavior of balanced 3-phase transformer banks can be understood by making the
following simplifying assumptions:

1. The exciting currents are negligible.


2. The transformer impedances, due to the resistance and leakage reactance of the
windings, are negligible.
3. The total apparent input power to the transformer bank is equal to the total apparent
output power.

Furthermore, when single-phase transformers are connected into a 3-phase system, they retain
all their basic single-phase properties, such as current ratio, voltage ratio, and flux in the core.
Given the polarity marks X1, X2 and H1, H2, the phase shift between primary and secondary is
zero, in the sense that EX1X2 is in phase with EH1H2

3.2 Delta-Delta Connection:

The three single-phase transformers P, Q, and R of Fig. 3.1 transform the voltage of the
incoming transmission line A, B, C to a level appropriate for the outgoing transmission line 1, 2,
3. The incoming line is connected to the source, and the outgoing line is connected to the load.

BTI - Electrical & Electronics Division 34 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Three Phase Transformer

The transformers are connected in delta-delta. Terminal H1 of each transformer is connected to


terminal H2 of the next transformer. Similarly, terminals X1 and X2 of successive transformers are
connected together. The actual physical layout of the transformers is shown in Fig. 3.1. The
corresponding schematic diagram is given in Fig. 3.2. The schematic diagram is drawn in such
a way to show not only the connections, but also the phasor relationship between the primary
and secondary voltages.

H1 X1 1
A

H2 X2 L

H1 2 O
B

H2 X2
A
H1 X1 3
C
D
H2 X2

Fig. 3.1: Delta-delta connection of three single-phase transformers. The incoming


lines (source) are A, B, C and the outgoing lines (load) are 1, 2, 3.

Fig. 3.2: Schematic diagram of a delta-delta connection and associated phasor diagram.

Thus, each secondary winding is drawn parallel to the corresponding primary winding to which it
is coupled. Furthermore, if source G produces voltages EAB, EBC, ECA according to the indicated
phasor diagram, the primary windings are oriented the same way, phase by phase.
For example, the primary of transformer P between lines A and B is oriented horizontally, in the
same direction as phasor EAB. Because the primary and secondary voltages EH1H2 and EX1X2 of a
given transformer must be in phase, it follows that E12 (secondary voltage of transformer P) must
be in phase with EAB (primary of the same transformer). Similarly, E23 is in phase with EBC and E31
with ECA.
In such a delta-delta connection, the voltages between the respective incoming and outgoing
transmission lines are in phase.

BTI - Electrical & Electronics Division 35 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Three Phase Transformer

If a balanced load is connected to lines 1-2-3, the resulting line currents are equal in magnitude.
This produces balanced line currents in the incoming lines A-B-C. As in any delta connection,
the line currents are ,3 times greater than the respective currents Ip and Is flowing in the
primary and secondary windings (Fig. 3.2). The power rating of the transformer bank is three
times the rating of a single transformer.

Example 3.1.
Three single-phase transformers are connected in delta-delta to step down a line voltage of 138
kV to 4160 V to supply power to a manufacturing plant. The plant draws 21 MW at a lagging
power factor of 86 percent.

Calculate:
a. The apparent power drawn by the plant
b. The apparent power furnished by the HV line
c. The current in the HV lines
d. The current in the LV lines
e. The currents in the primary and secondary windings of each transformer
f. The load carried by each transformer

Solution:
a. The apparent power drawn by the plant is:
S = P / cos  = 21 / 0.86 = 24.4 MVA

b. The transformer bank itself absorbs a negligible amount of active and reactive power
because the I2R losses and the reactive power associated with the mutual flux and
the leakage fluxes are small. It follows that the apparent power furnished by the HV
line is also 24.4 MVA.

c. The current in each HV line is:


I1 = S / ( 3 E) = (24.4  106) / (3  138 000) = 102 A

d. The current in the LV lines is:


I2 = S / (3 E) = (24.4  106) / (3  4160) = 3384 A

e. Referring to Fig. 3.2, the current in each primary winding is:


Ip = 102 / 3 = 58.9 A

The current in each secondary winding is:


Is = 3384 / 3 = 1954 A

f. Because the plant load is balanced, each transformer carries one-third of the total
load, or 24.4 / 3 = 8.13 MVA.

The individual transformer load can also be obtained by multiplying the primary voltage times
the primary current:
S = Ep Ip = 138 000  58.9 = 8.13 MVA

3.3 Delta-Star Connection:

When the transformers are connected in delta-star, the three primary windings are connected
the same way as in Fig. 3.1. However, the secondary windings are connected so that all the X2
terminals are joined together, creating a common neutral N (Fig. 3.3). In such a delta-star

BTI - Electrical & Electronics Division 36 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Three Phase Transformer

connection, the voltage across each primary winding is equal to the incoming line voltage.
However, the outgoing line voltage is 3 times the secondary voltage across each transformer.

Fig. 3.3: Delta-Star connection of three single-phase transform

The relative values of the currents in the transformers windings and transmission lines given in
Fig. 3.4. Thus, the line currents in phases A, B, and C are  3 times the currents in the primary
windings. The line currents in phases 1, 2, 3 are the same as the currents in the secondary
windings.

Fig. 3.4: Schematic diagram of a Delta-Star connection and associated phasor diagram.

A Delta-Star connection produces a 30° phase shift between the line voltages of the incoming
and outgoing transmission lines. Thus, outgoing line voltage E12 is 30° ahead of incoming line
voltage EAB as can be seen from the phasor diagram. If the outgoing line feeds an isolated group
of loads, the phase shift creates no problem. But, if the outgoing line has to be connected in
parallel with a line coming from another source, the 30° shift may make such a parallel
connection impossible, even if the line voltages are otherwise identical.

One of the important advantages of the Star connection is that it reduces the amount of
insulation needed inside the transformer. The HV winding has to be insulated for only 1/ 3 or
58 percent of the line voltage.

Example 3.2:
Three single-phase step-up transformers rated at 40 MVA,13.2 kV / 80 kV are connected in
Delta-Star on a 13.2 kV transmission line (Fig. 3.5). If they feed a 90 MVA load, calculate the
following:
a. The secondary line voltage
BTI - Electrical & Electronics Division 37 Elbaz Bader Ayad
YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Three Phase Transformer

b. The currents in the transformer windings


c. The incoming and outgoing transmission line currents

Fig. 3.5: See Example 2.

Solution:

The easiest Star to solve this problem is to consider the windings of only one
transformer, say, transformer P.

a. The voltage across the primary winding is obviously 13.2 kV.

The voltage across the secondary is, therefore, 80 kV. The voltage between the
outgoing lines 1, 2, and 3 is: ES = 803 = 138 kV

b. The load carried by each transformer is: S = 90 / 3 = 30 MVA

The phase current in the primary winding is: Ip = 30 MVA / 13.2 kV = 2272 A

The phase current in the secondary winding is: Is = 30 MVA / 80 kV = 375 A

c. The current in each incoming line A, B, C is: I = 22723 = 3932 A

The current in each outgoing line 1, 2, 3 is: I = 375 A

3.4 Star-Delta Connection:

The currents and voltages in a Star-Delta connection are identical to those in the Delta-Star
connection of Section 3.3. The primary and secondary connections are simply interchanged. In
other words, the H2 terminals are connected together to create a neutral, and the X1, X2 terminals
are connected in delta. Again, there results a 30° phase shift between the voltages of the
incoming and outgoing lines.

3.5 Star-Star Connection:

When transformers are connected in Star-Star, special precautions have to be taken to prevent
severe distortion of the line-to-neutral voltages. One way to prevent the distortion is to connect
the neutral of the primary to the neutral of the source, usually by way of the ground (Fig. 3.6).
Another way is to provide each transformer with a third winding, called tertiary winding. The
tertiary windings of the three transformers are connected in delta (Fig. 3.7). They often provide
the substation service voltage where the transformers are installed.
Note that there is no phase shift between the incoming and outgoing transmission line voltages
of a Star-Star connected transformer.

BTI - Electrical & Electronics Division 38 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Three Phase Transformer

Fig. 3.6: Star-Star connection with neutral of the primary to the neutral of the source.

Fig. 3.7: Star-Star connection using a tertiary winding.

3.6 Open-Delta Connection:

It is possible to transform the voltage of a 3-phase system by using only 2 transformers,


connected in open-delta. The Open-Delta arrangement is identical to a delta-delta connection,
except that one transformer is absent (Fig. 3.8). However, the Open-Delta connection is seldom
used because the load capacity of the transformer bank is only 86.6 percent of the installed
transformer capacity.

For example, if two 50 kVA transformers are connected in open-delta, the installed capacity of
the transformer bank is obviously 2 x 50 = 100 kVA. But, strange as it may seem, it can only
deliver 86.6 kVA before the transformers begin to overheat.

The Open-Delta connection is mainly used in emergency situations. Thus, if three transformers
are connected in delta-delta and one of them becomes defective and has to be removed, it is
possible to feed the load on a temporary basis with the two remaining transformers.

(a)

BTI - Electrical & Electronics Division 39 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Three Phase Transformer

(b)
Fig. 3.8 (a): Open-Delta connection.
(b): Associated schematic & phasor
Example 3.3:
Two single-phase 150 kVA, 7200 V/600 V transformers are connected in Open-Delta. Calculate
the maximum 3-phase load they can carry.

Solution:
Although each transformer has a rating of 150 kVA, the two together cannot carry a load
of 300 kVA.
The nominal secondary current of each transformer is:
Is = 150 kVA / 600 V = 250 A

The current Is in lines 1, 2, 3 cannot, therefore, exceed 250A (Fig. 3.8-b). Consequently,
the maximum load that the transformers can carry is:

S =  3 E I = 1.73  600  250 = 259 500 VA = 260 kVA

Thus, the ratio = maximum load / installed transformer rating = 260 kVA / 300 kVA
= 0.866, or 86.6%

BTI - Electrical & Electronics Division 40 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Three Phase Transformer

3.7 Questions and Problems

Practical level:
1. Assuming that the transformer terminals have polarity marks H1, H2, X1, X2, make schematic
drawings of the following connections:
a. Delta-Star
b. Open-delta

2. Three single-phase transformers rated at 250 kVA, 7200 V/600 V, 60 Hz, are connected in
Star-delta on a 12 470 V, 3-phase line. If the load is 450 kVA, calculate the following currents:
a. In the incoming and outgoing transmission lines [20.8A, 433A]
b. In the primary and secondary windings [20.8A, 250A]

3. A transformer has a rating of 36 MVA, 13.8 kV/320 V. Calculate the nominal currents in the
primary and secondary lines. [1506A, 65A]

Intermediate level:
4. The transformers in Problem 2 are used to raise the voltage of a 3-phase 600V line to 7.2kV.
a. How must they be connected?
a. Calculate the line currents for a 600 kVA load. [577A, 48.1A]
b. Calculate the corresponding primary and secondary currents. [333A, 27.8A]

5. In order to meet an emergency, three single-phase transformers rated 100 kVA, 13.2 kV/2.4
kV are connected in wye-delta on a 3-phase 18 kV line.
a. What is the maximum load that can be connected to the transformer bank? [236KVA]
b. What is the outgoing line voltage? [1.89KV]

6. transformers rated at 250 kVA, 2.4 kV/600 V are connected in open-delta to supply a load of
400 kVA.
a. Are the transformers overloaded?
b. What is the maximum load the bank can carry on a continuous basis? [433KVA]

7. Referring to Figs. 3.3 and 3.4, the line voltage between phases A-B-C is 6.9 kV and the
voltage between lines 1, 2, and 3 is balanced and equal to 600 V. Then, in a similar
installation the secondary of transformer P are by mistake connected inverse.
a. Determine the voltages measured between lines 1-2, 2-3, and 3-1. [347, 600,
347V]
b. Draw the new phasor diagram.

Industrial application:
8. Three 150 kVA, 480 V/4000 V, 60 Hz single-phase transformers are to be installed on a 4000
V, 3-phase line. The exciting current has a value of 0.02 put. Calculate the line current when
the transformers are operating at no-load. [1.3A]

9. Three single-phase transformers rated at 15 kVA, 480 V/120 V, 60 Hz are connected in delta
to function as auto-transformer on a 600 V 3-phase line. The H1, H2, X1, X2 polarity marks
appear on the metal housing.
a. Show how the transformers should be connected.
b. Determine the 3-phase voltage output of the transformer. [465V]
c. Determine the phase shift between the 3-phase voltage output and the 600 V, 3-phase
input. [12.9]

BTI - Electrical & Electronics Division 41 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Protective Relay

Protective Relays

1. Operating principles and Construction


Protective relays are classified into the following three categories, depending on the
technologies they use for their construction and operation.

1. Electromagnetic and electrothermal


2. Static; using semiconductor devices like ICs, transistor, diodes, logic gates, etc.
3. Microprocessor based

There are various types of protective relays in each category, depending on the operating
principle and application.

1. Electromagnetic Relays

The following are the important types of construction of electromagnetic Relays.


(i) Attracted armature
(ii) Induction disc
(iii) Printed disc dynamometer
(iv) Permanent magnet
(v) Moving-coil
(vi) Polarized moving-iron

1.1 Attracted Armature Relay:

Hinged armature and plunger type construction comes under this group of relays. Fig. (1.1-a)
shows a hinged armature type construction. The coil is energised by an operating quantity
proportional to the system current or voltage. The operating quantity produces a magnetic flux
which in turn produces an electromagnetic force. The electromagnetic force is proportional to
the square of the flux in the air gap or the square of the current. The attractive force increases
as the armature approaches the pole of the electromagnet. This type of a relay is used for the
protection of small machines, equipment, etc. It is also used for auxiliary relays, such as
indicating flags, slave relays, alarm relays, annunciators, semaphores, etc.

The actuating quantity of the relay may be either ac or dc in dc relays, the electromagnetic
force of attraction is constant. In the case of ac relays, sinusoidal current flows through the coil
and hence the force of attraction is given by:

F = KI2
= K( Imax sin  t)2
= ½ KI2max ( 1 - cos 2  t)
= ½ K(I2max - I2max cos 2  t )

From the above expression, it is evident that the electromagnetic force consists of two
components. One component is constant and is equal to ½KI2max . The other component is time
dependent and pulsates at double the frequency of the applied ac quantity. Its magnitude is ½
KI2max cos 2  t. The total force is a double frequency pulsating force. This may cause the
armature to vibrate at double the frequency. Consequently, the relay produces a humming
sound and becomes noisy. This difficulty can be overcome by making the pole of the
electromagnet of shaded construction. Alternatively, the electromagnet may be provided with
two coils. One coil is energised with the actuating quantity. The other coil gets its supply through
a phase shifting circuit.

BTI - Electrical & Electronics Division 42 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Protective Relay

The restraining force is provided by a spring. The reset to pick-up ratio for attracted armature
type relays is 0.5 to 0.9. For this type of a relay, the ratio for ac relays is higher as compared to
dc relays. The VA burden is low, which is 0.08 W at pick-up for the relay with one contact, 0.2 W
for the relay with four contacts. The relay is an instantaneous relay. The operating speed is very
high. For a modern relay, the operating time is about 5 ms. It is faster than the induction disc
and cup type relays.

Attracted armature relays are compact, robust and reliable. They are affected by transients as
they are fast and operate on both dc and ac The fault current contains a dc component in the
beginning for a few cycles. Due to the presence of dc transient, the relay may operate though
the steady state value of the fault current may be less than its pick-up. A modified constructions
as shown in Fig. (1.1-b) reduces the effect of dc transients.

(a) Hinged armature type relay (b) Modified hinged armature type relay

Fig. 1.1

1.2 Induction Disc Relay:

There are two types of construction of induction disc relays, namely the shaded pole type, as
shown in Fig. 1.2; and watt hour meter type, as shown in Fig. 1.3.

Fig. (1.2-a) shows a simple theoretical figure, whereas Fig. (1.2-b) shows the construction which
is actually used in practice. The rotating disc is made of aluminium. In the shaded pole type
construction, a C-shaped electromagnet is used. One half of each pole of the electromagnet is
surrounded by a copper band known as the shading ring. The shaded portion of the pole
produces a flux which is displaced in space and time with respect to the flux produced by the
unshaded portion of the pole. Thus two alternating fluxes displaced in space and time cut the
disc and produce eddy currents in it. Torques are produced by the interaction of each flux with
the eddy current produced by the other flux. The resultant torque causes the disc to rotate.
In wattmetric type of construction, two electromagnets are used: upper and lower one. Each
magnet produces an alternating flux which cuts the disc. To obtain a phase displacement
between two fluxes produced by upper and lower electromagnets, their coils may be energised
by two different sources. If they are energised by the same source, the resistances and
BTI - Electrical & Electronics Division 43 Elbaz Bader Ayad
YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Protective Relay

reactances of the two circuits are made different so that there will be sufficient phase difference
between the two fluxes.
Induction disc type construction is robust and reliable. It is used for over-current protection. Disc
type units give an inverse time current characteristic and are slow compared to the induction
cup and attracted armature type relays. The induction disc type is used for slow-speed relays.
Its operating time is adjustable and is employed where a time-delay is required. Its reset/pick-up
ratio is high, above 95% because its operation does not involve any change in the air gap. The
VA burden depends on its application, and is generally of the order of 2.5 VA. The torque is
proportional to the square of the actuating current if single actuating quantity is used.

A spring is used to supply the resetting torque. A permanent magnet is employed to produce
eddy current braking to the disc. The magnets should remain stable with age so that its
accuracy will not be affected. Magnets of high coercive force are used for the purpose. The
braking torque is proportional to the speed of the disc. When the operating current exceeds
pick-up value, driving torque is produced and the disc accelerates to a speed where the braking
torque balances the driving torque. The disc rotates at a speed proportional to the driving
torque.

Fig. 1.2: Shaded pole type induction disc relay

It rotates at a constant speed for a given current. The disc inertia should be as small as
possible, so that it should stop rotating as soon as the fault current disappears when circuit
breaker operates at any other location or fault current is for a short moment (i.e.. transient in
nature). After the cessation of the fault current, the disc will travel to some distance due to
inertia. This distance should be minimum. It is called the over-run of the disc. A brake magnet is
used to minimise over-run. The over-run is usually not more than 2 cycles on the interruption of
a current which is 20 times the current setting.

BTI - Electrical & Electronics Division 44 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Protective Relay

At a current below pick-up value, the disc remains stationary by the tension of the control spring
acting against the normal direction of disc rotation. The disc rests against a backstop. The
position of the backstop is adjustable and therefore, the distance by which the moving contact of
the relay travels before it closes contacts, can be varied. The distance of travel is adjusted for
the time setting of the relay.

The rotor disc carries an arm which is attached to its spindle. The spindle is supported by
jewelled bearings. The arm bridges the relay contacts. In earlier constructions, there were two
contacts which were bridged when the relay operated. In modern units however, there is a
single contact with a flexible lead-in.

Current setting:
In disc type units, there are a number of tappings provided on coil to select the desired pick-up
value of the current. These tappings are shown in Fig. 1.3. This will be discussed in more detail
in the next chapter.

Fig. 1.3: Wattmetric type induction-disc relay

Time setting:
The distance which the disc travels before it closes the relay contact can be adjusted by
adjusting the position of the backstop. If the backstop is advanced in the normal direction of
rotation, the distance of travel is reduced, resulting in a shorter operating time of the relay. More
details on time-setting will be discussed in the next chapter.

1.3. Reverse Power or Directional Relay

Fig. (1.4-a) shows an electromagnetic directional relay. A directional relay is energised by two
quantities, namely voltage and current. Fluxes  1 and  2 are set up by voltage and current,
respectively. Eddy currents induced in the disc by  1 interact with  2 and produce a torque.

BTI - Electrical & Electronics Division 45 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Protective Relay

Similarly,  2 also induces eddy currents in the disc, which interact with  1 and produce a
torque. The resultant torque rotates the disc. The torque is proportional to VI cos where  is
the phase angle between V and I. The torque is maximum when voltage and current are in
phase. To produce maximum torque during the fault condition, when the power factor is very
poor, a compensating winding and shading are provided, as shown in Fig. (1.4-a).

Earlier it has been mentioned that the torque produced by an induction relay is given by:

T =  1  2 sin 
 I1 I2 sin 

where  1 and  2 are fluxes produced by I1 and I2 respectively. The angle between  1 and  2 or
I1 and I2 is  . If one of the actuating quantities is voltage, the current flowing in the voltage coil
lags behind voltage by approximately 90. Assume this current to be I2. The load current I (say
I1) lags V by  . Then the angle  between I1 and I2 is equal to (90-  ), as shown in Fig. (1.4-
b).

(a) Construction (b) Phasor diagram

Fig. 1.4: Induction disc type directional relay

T = I1 I2 sin (9O -  )
 I1 I2 cos 
 VI cos 

Torque produced is positive when cos  is positive, i.e.  is less than 90 . When  is more than
90 (between 90 and 180 ), the torque is negative. At a particular relay location, when power
flows in the normal direction, the relay is connected to producing negative torque. The angle
between the actuating quantities supplied to the relays is kept (180 -  ) to produce negative
torque. If due to any reason, the power flows in the reverse direction, the relay produces a
positive torque and it operates.

In this condition, the angle between the actuating quantities  is kept less than 90 to produce
a positive torque. This is shown in Fig. (1.5-a). For normal flow of power, the relay is supplied
with V and (-I). For reverse flow, the actuating quantities become V and I. Torque becomes VI
cos  , i.e. positive. This can be achieved easily by reversing the current coil, as shown in Fig.
(1.5-b).

BTI - Electrical & Electronics Division 46 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Protective Relay

Relaying units supplied with single actuating quantity discussed earlier are non-directional over-
current relays. Non-directional relays are simple and less expensive than directional relays.

(a) (b)

Fig. 1.5 (a): Phasor diagram for directional relay


(b): Connection of current coil for reverse power relay

2. Static Relays

The expansion and growing complexity of power systems have brought a need for protective
relays with a higher performance and more sophisticated characteristics. These have been
made possible by the development of semiconductors and other associated components, and
many types of static relay are commercially available. All duties performed by electromagnetic
relays can now be undertaken by static devices, in most cases with performance and economic
advantages.

The emergence of the static relay has posed a new set of problems for the relay designer. The
requirement of a d.c. supply for measurement purposes and the necessity to protect static
devices from high voltage surge are two which have been thrown up in the development of this
kind of equipment.

As the development of static relays has progressed, certain basic circuits have emerged which
go to make up the required relaying characteristic. The use of semiconductors has allowed
greater flexibility in the design process and has presented an opportunity to optimise the
parameters of each particular element.

2.1 Over-current definite time relay:

BTI - Electrical & Electronics Division 47 Elbaz Bader Ayad


YOSRY IDREES
BTEC – HND Year 2 - Utilization of Electrical Energy Protective Relay

As an example, Fig. (1.6-a) shows the elements used in a single-phase definite time over-
current relay. Alternating current is converted to a proportional direct voltage and compared with
a fixed d.c. level. When it exceeds the reference level a timer is initiated. After the set time delay
the second level detector operates to activate the output element.

The input circuit consists of a current transformer, the secondary current of which is rectified and
fed into a resistive shunt. The current setting of the relay can be changed by means of primary
taps on the CT or by varying the value of the secondary shunt. A time delay setting can be
obtained by varying the resistance value of RC delay circuit with a calibrated potentiometer.
Instantaneous operation above a set level is achieved by by-passing the time delay element to a
further level detector.

Fig. 1.6: Definite time over-current static relay.

Fig. (1.6-b) shows the circuit of a simplified level detector which also includes an output stage
driving the coil of an attracted armature relay. In this circuit all transistors are biased off until the
input voltage exceeds that at the emitter of TR1, set by potentiometer chain R1 and R2. When
this voltage is exceeds both transistors turn on and the output relay is energized. The circuit has
the advantages of drawing no current when in the non-operated state and giving a drop-out
level of almost 100% of the pick-up level.

Timing can be performed by connecting an RC time delay network, shown dashed in Fig.
(1.6-b), at the input to the second level detector monitoring the voltage across the capacitor.

2.2 Advantages of Static Relays:

The main advantages of static relays over electromagnetic relays are:


1- C.T. burden is about one tenth, thereby a smaller C.T. can be employed.
2- The space required for a single-phase relay is half and that for a three-phase relay is
about one third. Consequently, the panel space and overall cost of installation are
reduced. This helps in miniaturization of control equipment.
3- Instantaneous reset can easily be achieved. This allows the application of automatic
reclosing of circuit breaker.
4- Accuracy in time-current characteristics.
5- Fast operation, absence of mechanical inertia and bouncing of contacts.
6- Long life and less maintenance, immunity to vibration, dust and polluted atmosphere.

BTI - Electrical & Electronics Division 48 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

2. Over Current Protection

A protective relay which operates when the load current exceeds a preset value, is called an
over-current relay. The value of the preset current above which the relay operates is known
as its pick-up value. An over-current relay is used for the protection of distribution lines, large
motors, power equipment, etc. A scheme which incorporates over-current relays for the
protection of an element of a power system, is known as an over-current scheme or over-
current protection. An over-current scheme may include one or more over-current relays.
At present electromagnetic relays are widely used for over-current protection. The induction
disc type construction, as shown in Fig. (1.2-b) is commonly used.

1 Time-current Characteristics

A wide variety of time-current characteristics is available for over-current relays. The name
assigned to an over-current relay indicates its time-current characteristic as described below.

1.1 Definite-time Over-current Relay

A definite-time over-current relay operates after a predetermined time when the current
exceeds its pick-up value. Curve (a) of Fig. 2.1 shows the time-current characteristic for this
type of relay. The operating time is constant, irrespective of the magnitude of the current
above the pick-up value. The desired definite operating time can be set with the help of an
intentional time-delay mechanism provided in the relaying unit.

1.2 Instantaneous Over-current Relay

An instantaneous relay operates in a definite time when the current exceeds its pick-up
value. The operating time is constant, irrespective of the magnitude of the current, as shown
by the curve (a) of Fig. 2.1. There is no intentional time delay. It operates in 0.1 s or less.
Sometimes the term like “high set” or “high speed” is used for very fast relays having
operating times less than 0.1 s.

Fig. 2.1: Definite-time and inverse-time characteristics of over-current relays

BTI - Electrical & Electronics Division 49 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

1.3 Inverse-time Over-current Relay

An inverse-time over-current relay operates when the current exceeds its pickup value. The
operating time depends on the magnitude of the operating current. The operating time
decreases as the current increases. Curve (b) of Fig. 2.1 shows the inverse time-current
characteristic of this type of relays.

1.4 Inverse Definite Minimum Time Over-current (I.D.M. T.) Relay

This type of a relay gives an inverse-time current characteristic at lower values of the fault
current and definite-time characteristic at higher values of the fault current. Generally, an
inverse-time characteristic is obtained if the value of the plug setting multiplier is below 10.
For values of plug setting multiplier between 10 and 20, the characteristic tends to become a
straight line, i.e. towards the definite time characteristic. Fig. 2.2 shows the characteristic of
an I.D.M.T. relay along with other characteristics. I.D.M.T. relays are widely used for the
protection of distribution lines. Such relays have a provision for current and time settings
which will be discussed later on.

1.5 Very Inverse-time Over-current Relay

A very inverse-time over-current relay gives more inverse characteristic than that of the
I.D.M.T. relay. Its time-current characteristic lies between an I.D.M.T. characteristic and
extremely inverse characteristic, as shown in Fig. 2.2. The very inverse characteristic gives
better selectivity than the I.D.MT characteristic. Hence, it can be used where an I.D.M.T.
relay fails to achieve good selectivity.
Very inverse time-current relays are recommended for the cases where there is a substantial
reduction of fault current as the distance from the power source increases. They are
particularly effective with ground faults because of their steep characteristic.

Fig. 2.2: IDMT, very inverse-time and extremely inverse-time characteristics

BTI - Electrical & Electronics Division 50 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

1.6 Extremely Inverse-time Over-current Relay

An extremely inverse time over-current relay gives a time-current characteristic more inverse
than that of the very inverse and I.D.M.T. relays, as shown in Fig. 2.2. When I.D.M.T. and
very inverse relays fall in selectivity, extremely inverse relays are employed. I.D.M.T. relays
are not suitable to be graded with fuses.

The electromagnetic relay which gives the steepest time-current characteristic is an


extremely inverse relay. The time-current characteristic of an extremely inverse relay is not
good enough to be graded with fuses.

An extremely inverse relay is very suitable for the protection of machines against
overheating. Hence, this type of relays are used for the protection of alternators, power
transformers, earthing transformers, expensive cables, railways trolley wires, etc.

The rotors of large alternators may be overheated if an unbalanced load or fault remains for
a longer period on the system. In such a case, an extremely inverse relay, in conjunction with
a negative sequence network is used. By adjusting the time and current settings, a suitable
characteristic of the relay is obtained for a particular machine to be protected.

A relay should not operate on momentary overloads. But it must operate on sustained short
circuit current. For such a situation, it is difficult to set I.D.M.T. relays. An extremely inverse
relay is quite suitable for such a situation. This relay is used for the protection of alternators
against overloads and internal faults. It is also used for reclosing distribution circuits after a
long outage. After long outages, when the circuit breaker is reclosed there is a heavy inrush
current which is comparable to a fault current.

An I.D.M.T. relay is not able to distinguish between the rapidly decaying inrush current of the
load and the persistent high current of a fault. Hence, an I.D.M.T. relay trips again after
reclosing. But an extremely inverse relay is able to distinguish between a fault current and
inrush current due to its steep time-current characteristic. Therefore an extremely inverse
relay is quite suitable for the load restoration purpose.

2. Current Setting

The current above which an over-current relay should operate can be set. Suppose that a
relay is set at 5A. It will then operate if the current exceeds 5A. Below 5A, the relay will not
operate. There are a number of tappings on the current coil, available for current setting, as
shown in Fig. 1.2 and Fig. 1.3. An over-current relay which is used for phase to phase fault
protection, can be set at 50% to 200% of the rated current in steps of 25%.

The usual current rating of this relay is 5A. So it can be set. at 2.5 A, 3.75 A, 5 A,..., 10 A.
When a relay is set at 2.5 A, it will operate when current exceeds 2.5 A. When the relay is
set at 10 A, it will operate when current exceeds 10 A. The relay which is used for protection
against ground faults (earth-fault relay) has settings 20% to 80% of the rated current in steps
of 10%. The current rating of an earth-fault relay is usually 1 A.

If time-current curves are drawn, taking current in amperes on the X - axis, there will be one
graph for each setting of the relay. To avoid this complex situation, the plug setting multipliers
are taken on the X - axis. The actual r.m.s. current flowing in the relay expressed as a
multiple of the setting current (pickup current) is known as the plug setting multiplier
(PSM).

BTI - Electrical & Electronics Division 51 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

Suppose, the rating of a relay is 5A and it is set at 200%, i.e. at 10 A. If the current flowing
through the relay is 100 A, then the plug setting multiplier will be 10. The PSM = 4 means 40
A of current is flowing, PSM = 6 means 60 A of current is flowing and so on.

Fig 2.3: Standard I.D.M.T. characteristic

If the same relay is set at 50%, i.e. at 2.5 A, the PSM = 4 means 10 A; PSM = 6 means
l5A;PSM= l0 means 25A and so on. Hence, PSM can be expressed as:

PSM = Secondary current / Relay current setting


= Primary current during fault / (Relay current setting  CT. Ratio)

While plotting the time-current characteristic, if PSM is taken on the X-axis, there will be only
one curve for all the settings of the relay. Fig. 2.3 shows a time-current characteristic with
PSM on the X-axis. The curve is generally plotted on log/log graph. Only this curve will give
the operating time for different settings of the relay. Suppose the relay is set at 5 A. The
operating times for different currents are shown in Table 2.1.

If the same relay is set at 10 A, the corresponding operating times for different currents are
shown in Table 3.2, using the same curve of Fig. 2.3.

Table 2.1
Current in 5 10 20 50

Amperes
PSM 1 2 4 10
Operating time in Sec No 10 5 3
operation

Table 2.2
Current in Amperes 5 10 20 40 100
PSM less than 1 1 2 4 10
Operating time in Relay will No
seconds not operation 10 5 3
operate

BTI - Electrical & Electronics Division 52 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

3. Time Setting

The operating time of the relay can be set at a desired value. In induction disc type relay, the
angular distance by which the moving part of the relay travels for closing the contacts can be
adjusted to get different operating time. There are 10 steps in which time can be set. The
term time setting multiplier (TSM) is used for these steps of time settings. The values of TSM
are 0.1,0.2,..., 0.9, 1. Suppose that at a particular value of the current or plug setting
multiplier (PSM), the operating time is 4 s with TSM = 1. The operating time for the same
current with TSM = 0.5 will be 4  0.5 = 2 s. The operating time with TSM=0.2 will be 4 
0.2=0.8 s.

Fig. (2.4-a) shows time-current characteristics for different values of TSM. The characteristic
at TSM = 1 can also be presented in the form shown in Fig. (2.4-b)

Fig. (2.4-a): Time-current characteristics for different values of T SM

Plug Setting Multiplier

1 1.3 2 2.5 3 4 6 10 14 20

30 15 10 8 6 5 4 3.5 3 2.2
Time in Seconds

Fig. (2.4-b): Logarithmic scale for IDMT relay at TSM = 1

BTI - Electrical & Electronics Division 53 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

Example:
The current rating of a relay is 5 A. Rating current setting = 1.5, TSM = 0.4,
C.T. ratio = 400/5, fault current = 6000A. Determine the operating time of the relay.
At TSM = 1, operating time at various PSM are indicated in the table below.

PSM 2 4 5 8 10 20
Operating time in
second 10 5 4 3 2.8 2.4

Solution:
C.T. ratio = 400 / 5 = 80
Relay current setting =5  1.5 = 7.5 A

PSM = Secondary current / Relay current setting


= Primary current (fault current) / (Relay current setting  CT. Ratio)
= 6000 / (7.5  80) = 10

Operating time from the given table at PSM = 10 is 2.8 Sec. This time is for TSM = 1.
The operating time for TSM = 0.4 will be equal to 2.8 x 0.4 = 1.12 Sec..

4. Over-current Protective Schemes

Over-current protective schemes are widely used for the protection of distribution lines.
Protection against excess current was naturally the earliest protective system to evolve.
From this basic principle has been evolved the graded over-current system, a discriminative
fault protection. This should not be confused with ‘overload’ protection, which normally
makes use of relays that operate in a time related in some degree to the thermal capability of
the plant to be protected.

Over-current protection, on the other hand, is directed entirely to the clearance of faults,
although with the settings usually adopted some measure of overload protection is obtained.

4.1 CO-Ordination Procedure

Correct current relay application requires a knowledge of the fault current that can flow in
each part of the network. Since large scale tests are normally impracticable, system analysis
must be used. It is generally sufficient to use machine transient reactance X and to work on
the instantaneous symmetrical currents. The data required for a relay setting study are:

a. A one-line diagram of the power system involved, showing the type and rating of the
protective devices and their associated current transformers.

b. The impedances in ohms, per cent or per unit, of all power transformers, rotating
machines and feeder circuits.

c. The maximum and minimum values of short circuit currents that are expected to flow
through each protective device.

d. The starting current requirements of motors and the starting and stalling times of
induction motors.

e. The maximum peak load current through protective devices.

f. Decrement curves showing the rate of decay of the fault current supplied by the
generators.

g. Performance curves of the current transformers.

The relay settings are first determined so as to give the shortest operating times at maximum
fault levels and then checked to see if operation will also be satisfactory at the minimum fault

BTI - Electrical & Electronics Division 54 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

current expected. It is always advisable to plot the curves of relays and other protective
devices, such as fuses, that are to operate in series, on a common scale. It is usually more
convenient to use a scale corresponding to the current expected at the lowest voltage base
or to use the predominant voltage base.

The alternatives are a common MVA base or a separate current scale for each system
voltage. The basic rules for correct relay co-ordination can generally be stated as follows:

i. Whenever possible, use relays with the same operating characteristic in series with each
other.
ii. Make sure that the relay farthest from the source has current settings equal to or less
than the relays behind it, that is, that the primary current required to operate the relay in
front is always equal to or less than the primary current required to operate the relay
behind it.

4.2 Principles of Time/Current Grading

Among the various possible methods used to achieve correct relay co-ordination are those
using either time or over-current or a combination of both time and over-current. The
common aim of all three methods is to give correct discrimination. That is to say, each one
must select and isolate only the faulty section of the power system network, leaving the rest
of the system undisturbed.

4.3 Discrimination by time

In this method an appropriate time interval is given by each of the relays controlling the
circuit breakers in a power system to ensure that the breaker nearest to the fault opens first.
A simple radial distribution system is shown in Fig. 2.5, to illustrate the principles.

Fig. 2.5: Radial


system with time
discrimination.

Circuit breaker protection is provided at B, C, D and E, that is, at the infeed end of each
section of the power system. Each protection unit comprises a definite time delay over-
current relay in which the operation of the current sensitive element simply initiates the time
delay element. Provided the setting of the current element is below the fault current value
this element plays no part in the achievement of discrimination. For this reason, the relay is
sometimes described as an ‘independent definite time delay relay’ since its operating time is
for practical purposes independent of the level of over-current.

It is the time delay element, therefore, which provides the means of discrimination. The relay
at B is set at the shortest time delay permissible to allow a fuse to blow for a fault on the
secondary side of transformer A. Typically, a time delay of 0.25s is adequate.

If a fault occurs at F, the relay at B will operate in 0.25s and the subsequent operation of the
circuit breaker at B will clear the fault before the relays at C, D and E have time to operate.
The main disadvantage of this method of discrimination is that the longest fault clearance
time occurs for faults in the section closest to the power source, where the fault level (MVA)
is highest.

4.4 Discrimination by current

Discrimination by current relies on the fact that the fault current varies with the position of the
fault, because of the difference in impedance values between the source and the fault.
Hence, typically, the relays controlling the various circuit breakers are set to operate at
suitably tapered values such that only the relay nearest to the fault trips its breaker. Fig. 2.6
illustrates the method.

BTI - Electrical & Electronics Division 55 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

Fig. 2.6: Radial system with current discrimination

For a fault at F1, the system short-circuit current is given by:

I = 6350 / (ZS + ZL1)


Where: ZS = source impedance = 112 / 250 = 0.485 ohms
ZL1 = cable impedance between C and B = 0.24 ohms
Hence I = 6350 / 0.725 = 8800 A
So a relay controlling the circuit breaker at C and set to operate at a fault current of 8800 A
would in simple theory protect the whole of the cable section between C and B.

Assuming a fault at F4, the short-circuit current is given by:

I = 6350 / (ZS + ZL1 + ZL2 + ZT)

Where: ZS = source impedance = 112 / 250 = 0.485 ohms


ZL1 = cable impedance between C and B = 0.24 ohms
ZL2 = cable impedance between B and 4 MVA transformer = 0.04 ohms
ZT = transformer impedance = 0.07 (112 / 4) = 2.12 ohms

Hence I = 6350 / 2.885 = 2200 A

For this reason, a relay controlling the circuit breaker at B and set to operate at a current of
2200A plus a safety margin would not operate for a fault at F4 and would thus discriminate
with the relay at A. Assuming a safety margin of 20% to allow for relay errors and a further
10% for variations in the system impedance values, it is reasonable to choose a relay setting
of 1.3 x 2200, that is, 2860 A for the relay at B. Now, assuming a fault at F3, that is, at the end
of the 11 kV cable feeding the 4 MVA transformer, the short-circuit current is given by:
I = 6350 / (ZS + ZL1 + ZL2)

Thus, assuming a 250 MVA source fault level:


I = 6350 / (0.485 + 0.24 + 0.04) = 8300 A

Alternatively, assuming a source fault level of 130 MVA:


I = 6350 / (0.93 + 0.24 + 0.04) = 5250 A

In other words, for either value of source level, the relay at B would operate correctly for
faults anywhere on the 11 kV cable feeding the transformer.

4.5 Discrimination by both time and current

Each of the two methods described so far has a fundamental disadvantage. In the case of
discrimination by time alone, the disadvantage is due to the fact that the more severe faults
are cleared in the longest operating time. Discrimination by current can only be applied
where there is an appreciable impedance between the two circuit breakers concerned.

It is because of the limitations imposed by the independent use of either time or current co-
ordination that the inverse time over-current relay characteristic has evolved. With this
characteristic, the time of operation is inversely proportional to the fault current level and the
actual characteristic is a function of both ‘time’ and ‘current’ settings. The advantage of this
method of relay co-ordination may be best illustrated by the system shown in Fig. 2.7, which
is identical to that shown in Fig. 2.5 except that typical system parameters have been added.

BTI - Electrical & Electronics Division 56 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

Fig. 2.7 : Time and Current Grading

In order to carry out a system analysis, before a relay co-ordination study of the system
shown in Fig. 2.7, it is necessary to refer all the system impedances to a common base and
thus, using 10 MVA as the reference base, we have:

4 MVA transformer percentage impedance on 10 MVA base = 7  (10 / 4) = 17.5%


11 kV cable between B and A percentage impedance on 10 MVA base:
= 0.04  100  10 / 112 = 0.33 %
11 kV cable between C and B Percentage impedance on 10MVA base:
= 0.24  100  10 / 112 =1.98 %
30 MVA transformer percentage impedance on10 MVA base:
= 22.5  10 / 30 = 7.5%
132 kV overhead line percentage impedance on 10MVA base:
= )6.2  100  10( / (132)2 = 0.36 %
132 kV source percentage impedance on 10 MVA base:
= (100  10) / 3500 = 0.29 %

BTI - Electrical & Electronics Division 57 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

The graph in Fig. 2.7 illustrates the use of ‘discrimination curves’, which are an important aid
to satisfactory protection co-ordination. In this example, a voltage base of 3.3 kV has been
chosen and the first curve plotted is that of the 200A fuse, which is assumed to protect the
largest outgoing 3.3 kV circuit. Once the operating characteristic of the highest rated 3.3 kV
fuse has been plotted, the grading of the over-current relays at the various substations of the
radial system is carried out as follows:

Substation B:
CT ratio 250/5A
Relay over-current characteristic assumed to be extremely inverse relay. This relay must
discriminate with the 200A fuse at fault levels up to:
(10 x 100) / (17.5 + 0.33 + 1.98 + 7.5 + 0.36 + 0.29) = 35.7 MVA

that is, 6260A at 3.3 kV or 1880A at 11 kV. The operating characteristics of the relay show that at a plug setting of
100%, that is, 250 A and 4.76 MVA at 11 kV, and at a time multiplier setting of 0.2, suitable discrimination with the
200 A fuse is achieved.

Substation C:
CT ratio 500/5A
Relay over-current characteristic assumed to be extremely inverse relay. This relay must
discriminate with the relay in substation B at fault levels up to:
(10 x 100) / (1.98 + 7.5 + 0.36 + 0.29) = 98.7 MVA

that is, 17,280A at 3.3kV or 5180A at 11 kV. The operating characteristics of the relay show
that at a plug setting of 100%, that is, 500 A and 9.52 MVA at 11 kV, and at a time multiplier
setting of 0.7, suitable discrimination with the relay at substation B is achieved.

Substation D:
CT ratio 150/1 A
Relay over-current characteristic assumed to be extremely inverse relay. This relay must
discriminate with the relay in substation C at fault levels up to:
(10 x 100) / (7.5 + 0.36 + 0.29) = 123 MVA

that is, 21,500 A at 3.3 kV or 538 A at 132 kV. The operating characteristics of the relay show
that at a plug setting of 100%, that is, 150 A and 34.2 MVA at 132 kV and at a time multiplier
setting of 0.25, suitable discrimination with the relay at substation C is achieved.

Substation E:
CT ratio 500/1 A
Relay over-current characteristic assumed to be extremely inverse relay. This relay must
discriminate with the relay in substation D at fault levels up to:
(10 x 100) / ( 0.36 + 0.29) = 1540 MVA

that is, 270,000 A at 3.3 kV or 6750 A at 132 kV. The operating characteristics of the relay
show that at a plug setting of 100%, that is, 500A and 114 MVA at 1 32 kV, and at a time
multiplier setting of 0.9, suitable discrimination with the relay at substation D is achieved.

4.6. Protection of Parallel Feeders

Fig. 2.8 shows an over-current protective scheme for parallel feeders. At the sending end of
the feeders (at A and B), non-directional relays are required. The symbol ( ↔ ) indicates a
non-directional relay. At the other end of feeders (at C and D), directional over-current relays
are required. The arrow mark (  ) for directional relays placed at C and D indicate that the
relay will operate if current flows in the direction shown by the arrow. If a fault occurs at F, the
directional relay at D trips, as the direction of the current is reversed. The relay at C does not
trip, as the current flows in the normal direction. The relay at B trips for a fault at F after relay
D. Thus, the faulty feeder is isolated and the supply of the healthy feeder is maintained.

BTI - Electrical & Electronics Division 58 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

Fig. 2.8: Protective scheme for parallel feeder

It is not desired to place non-directional relays at C and D to clear a fault at F. Due to this
very reason relays at C and D are directional over-current relays. For faults at feeders, the
direction of current at A and B does not change and hence relays used at A and B are non-
directional.

4.7. Protection of Ring Mains

Fig. (2.9-a) shows an over-current scheme for the protection of a ring feeder. Fig. (2.9-b) is
another way of drawing the same scheme. Compared with radial feeders, the protection of
ring feeders is costly and complex. Each feeder requires two relays.
A non-directional relay is required at one end and a directional relay at the other end. The
operating times for relays are determined by considering the grading, first in one direction
and then in the other direction, as shown in Fig. 2.9. If a fault occurs at F1 as shown in Fig.
(2.9-a) , the relays at C’ and D’ will trip to isolate the faulty feeder. The relay at C will not trip
as the fault current is not flowing in its tripping direction though its operating time is the same
as that of C’. Similarly, the relays at B and D will not trip as the fault currents are not in their
tripping direction, though their operating time is less than the operating time of B’ and D’
respectively.

Fig. 2.9: Protection of Ring Feeder.

Fig. (2.9-c) shows a scheme involving an even greater number of feeders.

BTI - Electrical & Electronics Division 59 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

3. Earth Protection

1. Earth Fault and Phase Fault Protection

A fault which involves ground is called an earth fault. Examples are:


i) Single line to ground (L-G) fault and
ii) Double line to ground (2L-G) fault.

Faults which do not involve ground are called phase faults. The protective scheme used for
the protection of an element of a power system against earth faults is known as earth fault
protection. Similarly, the scheme used for the protection against phase faults is known as
phase fault protection.

1.1 Earth Fault Relay and Over-current Relay

Relays which are used for the protection of a section (or an element) of the power system
against earth faults are called earth fault relays. Similarly, relays used for the protection of a
section of the power system against phase faults are called phase fault relays or over-current
relays.
The operating principles and constructional features of earth fault relays and phase fault
relays are the same. They differ only in the current levels of their operation.

The plug setting for earth fault relays varies from 20% to 80% of the C.T. secondary rating in
steps of 10%. Earth fault relays are more sensitive than the relays used for phase faults. The
plug setting for phase fault relays varies from 50% to 200% of the C.T. secondary rating in
steps of 25%. The name phase fault relay or phase relays is not common.
The common name for such relays is over-current relay. One should not confuse this term
with the general meaning of over-current relay.

In a general sense, a relay which operates when the current exceeds its pick-up value is
called an over-current relay. But in the context under consideration, i.e. phase fault protection
and earth fault protection, the relays which are used for the protection of the system against
phase faults are called over-current relays.

1.2 Earth Fault Protective Schemes

An earth fault relay may be energised by a residual current as shown in Fig. (3.1-a) ia ,ib and
ic are currents in the secondary of C.T.s of different phases. The sum (ia + ib + ic) is called
residual current. Under normal conditions the residual current is zero .

When an earth fault occurs, the residual current is non-zero. When it exceeds pick-up value,
the earth fault relay operates. In this scheme, the relay operates only for earth faults. During
balanced load conditions, the earth fault relay carries no current hence theoretically its
current setting may be any value greater than zero. But in practice, it is not true as ideal
conditions do not exist in the system. Usually, the minimum plug setting is made at 20% or
30%.

The manufacturer provides a range of plug settings for earth fault relay from 20% to 80% of
the C.T. secondary rating in steps of 10%.

BTI - Electrical & Electronics Division 60 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

BTI - Electrical & Electronics Division 61 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

Fig. 3.1: Various earth fault protection schemes

The magnitude of the earth current depends on the fault impedance. In case of an earth fault,
the fault impedance depends on the system parameter and also on the type of neutral
earthing. The neutral may be solidly grounded, through resistance or reactance. The fault
impedance for earth faults is much higher than that for phase faults. Hence, the earth fault
current is low compared to the phase fault currents. An earth fault relay is set independent of
load current. Its setting is below normal load current. When an earth fault relay is set at lower
values, its ohmic impedance is high, resulting in a high C.T. burden.

Fig. (3.1-b) and 3.1 (c) show an earth fault relay used for the protection of transformer and
an alternator, respectively. When an earth fault occurs, zero sequence current flows through
the neutral. It actuates earth fault relay. Fig. (3.1-d) shows the connection of an earth fault
relay using a special type of C.T. known as a core-balance C.T., which encircles the three-
phase conductors.

BTI - Electrical & Electronics Division 62 Elbaz Bader Ayad


YOSRY IDREES
BTI – HND Year 2 – Utilization of Electrical Energy Protective Relay

2. Combined Earth Fault and Phase Fault Protective Scheme

Fig. 3.2 shows two over-current relays (phase to phase fault relays) and one earth fault relay.
When an earth fault occurs, the burden on the active C.T. is that of an over-current relay
(phase fault relay) and the earth fault relay in series. Thus, the C.T. burden becomes high
and may cause saturation.

Fig. 3.2: Two over-current and one earth fault relays

3. Phase Fault Protective Scheme

Fig. 3.3 shows three over-current relays for the protection of a three-phase system. This
scheme is mainly for the protection of the system against phase faults. If there is no separate
scheme for earth fault protection, the over-current relays used in this scheme will also sense
earth faults but they will be less sensitive.

Fig. 3.3: Three over-current relays

BTI - Electrical & Electronics Division 63 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Circuit Breakers

4. Circuit Breakers Operation and Construction

1. Principles of Operation

In interrupting a circuit, the circuit breaker actually makes a physical separation in the
current-carrying or conducting element by inserting an insulating medium sufficient to prevent
current from continuing to flow.

The circuit is usually opened by drawing out an arc between contacts until the arc can no
longer support itself. The arc is formed when the contacts of a circuit breaker move apart to
interrupt a circuit. The arc is a conductor made up of ionized particles of the insulating
material. With the advent of higher voltage power systems, the length of arc that would
extinguish itself in air requires breakers of such physical size as to be impractical. Hence,
whenever voltages and currents are going to be large, other forms of insulation are used in
place of air to extinguish the arc as quickly as possible. The magnetic fields set up and the
heat generated will persist as long as current continues to flow through the contacts and the
arc. Should this current be “fault current,” the enormous magnetic fields and the great
amount of heat will tend to cause damage in terms of their own duration.

The most commonly used insulation is oil. For higher voltages and larger capacities, the
insulating medium may be a vacuum or an inert gas, such as Sulphur hexafluoride (SF6).
Other means are also employed to limit and extinguish the arc as quickly as possible as well
as to reduce the magnitude and duration of the fault current, both of which are factors in the
size, reliability, and cost of circuit breakers.

2. Types of Breakers Categorized by Insulation Medium

The classification of circuit breakers has been made on the basis of insulation medium
employed in the circuit breaker to extinguish the arc. Depending on the arc quenching
medium employed, the following are important types of circuit breakers:
1. Air circuit Breakers
2. Oil Circuit Breakers
3. Vacuum Circuit Breakers.
4. Sulphur Hexafluoride (SF6) Circuit Breakers.

2.1 Air Circuit Breaker:

An air circuit breaker employs air as the interrupting insulation medium. Of all the insulating
media mentioned, air is the most easily ionized and, hence, arcs formed in air tend to be
severe and persistent.

The switching elements, for an air current breaker, therefore, may often consist of main and
auxiliary contacts. The auxiliary contacts open before the main contacts do, and the arc is
drawn on them, thereby avoiding severe pitting of the main contacts (see Fig. 4.1). As the
contacts separate, a puff of air is sometimes used to blow the arc into “arc chutes.”
Moreover, the current itself is made to flow through coils that set up magnetic fields that force
the arc into these arc chutes. An electric arc is essentially an electric conductor with a
surrounding magnetic field; hence it can be attracted or repulsed by another magnetic field.

The arc chutes are usually made of corrugated insulating material (such as porcelain or
slate). Their function is to stretch out the arc until it can no longer sustain itself. In simple
form, it is an enclosed channel in which the arc is dissipated and kept from striking
surrounding objects.

BTI - Electrical & Electronics Division 64 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Circuit Breakers

Beakers of this type are usually employed in electric systems where fault currents are
relatively small. Their advantages are simplicity of construction, low cost, and relatively low
maintenance requirements.
As a means of extending the short-circuit duty of this type of breaker, a blast of air trained on
the arc from a reservoir of compressed air enables a heavier arc to be extinguished.

(a) (b)
Fig. 4.1: (a) Air circuit breaker, and
(b) schematic showing main and auxiliary contacts and arcing
arrangement

2.2 Oil Circuit Breaker:

Oil circuit breakers have their contacts immersed in insulating oil. They are used to open and
close high-voltage circuits carrying relatively large currents in situations where air circuit
breakers would be impractical because of the danger of the exposed arcs that might be
formed (see Fig. 4.2).

When the contacts are drawn apart, the oil covering them tends to quench the arc by its
cooling effect and by the gases thereby generated, which tend to “blow out” the arc. At the
instant the contacts part, the arc formed at each contact not only displaces the oil but
decomposes it, creating gas and a carbon residue. If these carbon particles were to remain
in place, as a conductor they would tend to sustain the arc formed. However, the violence of
the gas and the resulting turbulence of the oil disperse these particles, and they eventually
settle to the bottom of the tank. The rate of expansion and the volume of gas generated
depend to a great extent on the energy to be interrupted, the speed of the separation of the
contacts, the cooling effect, and the quantity of oil used as the insulating medium.

The use of oil as insulation also permits smaller distances between live parts and between
live parts and ground (the structural and mechanical support parts of the circuit breaker)
because of its better insulating qualities (higher dielectric strength) in comparison to air.

The insulating oil normally used has a dielectric strength of around 30 kV per one-tenth of an
inch (compared to a similar value of 1 kV for air). Oil is also an effective cooling medium.

BTI - Electrical & Electronics Division 65 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Circuit Breakers

Fig. 4.2: Oil circuit breaker

2.3 Vacuum Circuit Breaker:

In this type of breaker, the contacts are drawn apart in a chamber from which air has been
evacuated. (see Fig. 4.3). The electric arc is essentially an electric conductor made up of
ionized air. Thus, if there is no air, theoretically the arc cannot form. In practice, however, a
perfect vacuum is not likely to be obtained. The small residual amount of air that may exist
permits only a small arc to be formed and one of only a very short duration. The same
vacuum, however, will not dissipate the heat generated as readily as other insulating media.
Although this type of breaker has certain advantages in terms of its size and simplicity, its
interrupting ratings are not comparable to those of oil circuit breakers. Furthermore,
maintenance procedures are more complex and hence more costly.

Fig. 4.3: Vacuum circuit breaker

BTI - Electrical & Electronics Division 66 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Circuit Breakers

2.4 Sulphur Hexafluoride (SF6) Breaker:

This type of breaker (see Fig. 4.4) is similar to the vacuum type of breaker except that the
vacuum is replaced by an inert, non-toxic, odourless gas Sulphur Hexafluoride (SF6). This
gas, under pressures that may vary from 45 to 240 lb/sq in., extinguishes the arc so rapidly
as almost to prevent its formation. It also has excellent heat-dissipating characteristics, and
its dielectric strength is very much greater than that of oil.

Fig. 4.4: Sulphur Hexafluoride Circuit Breaker, 34.5 to 69 KV

The breakers are constructed in modules capable of operation at voltages from 34.5 kV at
gas pressures of 45 psi to 362 kV at 240 psi. (see Fig. 4.5). By connecting two or three
such modules in series, breakers capable of operating at 800 kV at 240 psi can be
constructed, with two- to three-cycle interrupting time. Installation and maintenance
requirements of these breakers are less costly than for other types.

Fig. 4.5: Features of Sulphur Hexafluoride Interrupting Module

2.5 Types of SF5 Circuit Breakers:

BTI - Electrical & Electronics Division 67 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Circuit Breakers

2.5.1 Double-pressure SF6 circuit breakers:

This is the early design of SF6 circuit breakers. Its operating principle is similar to that of air-
blast circuit breakers. In this type of a circuit breaker, the gas from a high-pressure
compartment is released to the low pressure compartment to extinguish the arc. Because of
its complicated design and construction, and its need for various auxiliaries such as gas
compressors, filters and control devices, this type of circuit breakers have become obsolete.

2.5.2 Puffer-type SF6 circuit breakers:

This type of circuit breakers are also sometimes called single-pressure or impulse type SF 6
circuit breakers. In this type of breakers, gas is compressed by a moving cylinder system and
is released through a nozzle to quench the arc. This type is available in the voltage range
3.6kV to 765 kV.

Fig. (4.6-a) shows a puffer-type breaker in closed position. The moving cylinder and the
moving contact are coupled together. When the contacts separate and the moving cylinder
moves, the trapped gas is compressed. The trapped gas is released through a nozzle and
flows axially to quench the arc as shown in Fig. (4.6-b). There are two types of tank designs.
Live tank design and dead tank design. In live tank design, interrupters are supported on
porcelain insulators. In the dead tank design, interrupters are placed in SF 6 filled-tank which
is at earth potential. Live tank design is preferred for outdoor substations.

A number of interrupters (connected in series) on insulating supports are employed for EHV
systems up to 765 kV. Two interrupters are used in a 420 kV system. Breaking time of 2 to 3
cycles can be achieved. In the circuit breaker the steady pressure of the gas is kept at
5kg/cm2. The gas pressure in the interrupter compartment increases rapidly to a level much
above its steady value to quench the arc.

Fig. 4.6: Puffer-Type SF6 Circuit Breaker

BTI - Electrical & Electronics Division 68 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Circuit Breakers

3. Selection of Circuit Breakers

Table 4.1 shows the summary of various types of circuit breakers, their voltage ranges and
arc quenching medium they employ.

Table 4.1 Types Of


Type
Circuit Breaker Arc Quenching Medium Voltage Range &
Breaking Capacity

Miniature C.B. Air at atmospheric pressure 400V; for small current rating

Air-Break C.B. Air at atmospheric pressure 400V-11KV; 5-750MVA

Minimum Oil C.B. Transformer Oil 3.3KV-220KV;150-25000MVA

Vacuum C.B. Vacuum 3.3KV-33KV; 250-2000MVA

SF6 C.B. SF6 at 5Kg/cm2 pressure 3.3-765KV;1000-50,000MVA

Air Blast C.B. Comp. Air at high presser 66-1100KV; 2500-60,000MVA


(20-30Kg/cm2)

Table 4.2 shows the choice of circuit breakers for various voltage ranges.

Table 4.2: Selection of Circuit Breakers

Rated Voltage Choice of C.B. Remark

Below 1KV Air-Break C.B.

3.3KV-33KV Vacuum; SF6; Minimum Oil C.B.`s Vacuum Preferred

SF6 Preferred
132KV-220KV SF6; Air Blast; Minimum Oil C.B.`s

400KV-760KV SF6; Air Blast C.B.`s SF6 is Preferred

Earlier oil circuit breakers were preferred in the voltage range of 3.3 kV-66kV. Between
132kV and 220 kV, either oil circuit breakers or air blast circuit breakers were recommended.
For voltages 400 kV and above, air blast circuit breakers were preferred. The present trend
BTI - Electrical & Electronics Division 69 Elbaz Bader Ayad
YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Circuit Breakers

is to recommend vacuum or SF6 circuit breakers in the voltage range 3.3 kV-33 kV. For
132kV and above, SF6 circuit breakers are preferred. Up to 1 kV, air break circuit breakers
are used. Air blast circuit breakers are becoming obsolete and oil circuit breakers are being
superseded by SF6 and vacuum circuit breakers.

BTI - Electrical & Electronics Division 70 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Lighting System
1 Types of Lamps

The whole of interior lighting design revolves around the lamp, and development and
competition within the industry has resulted in an enormous range of lamps now being
available to the lighting designers.
The proliferation of lamp types is a mixed blessing because lamp development can often
make an existing installation obsolete both in appearance and efficiency before its time.
However, a surfeit of choice is not to be scorned. It means that the lighting designer must
appreciate the range of lamps at his disposal and keep himself well informed on new
developments.

1. Filament lamps

In a tungsten filament lamp the passage of electricity through the filament raises the
temperature of the molecules within the filament to the point where they begin to give off
light, or they incandesce.

1.1 The general lighting service lamp (GLS):

A lamp designed for general lighting service (GLS) is illustrated in Fig. 1.

Fig. 1: General lighting service - Filament Lamp (GLS)

Filaments: These are constructed of drawn tungsten wire which is then coiled, and in the
lower-wattage gas-filled lamps the coils can be coiled again to reduce convection losses
(coiled-coil).

Gas filling: The rate of filament evaporation can be reduced by raising the vapour pressure
in the lamp. This can only be done by introducing gases which are chemically inactive with
hot tungsten. The most common gas filling is a mixture of argon and nitrogen, and this can
only be used with coiled filaments where the heat losses are much less than for a
straight-wire filament.

Lamp caps: The British GLS lamps normally have Bayonet Caps (BC) up to 150 W. Edison
Screw (ES) caps are used for 200 W lamps and Goliath Edison Screw (GES) caps are used
for 300-1500 W lamps.

BTI - Electrical & Electronics Division 91 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

1.2 Tungsten-halogen lamps:

The most important factor deciding the light output of a lamp is the filament temperature, and
this determines the life of the lamp.
The addition of a halogen vapour to the gas filling effectively reduces the evaporation rate of
the filament. This allows the use of a higher filament temperature and, hence, promotes
greater efficacy without the detriment of short lamp life.

Fig. 2: Tungsten-halogen linear lamp

Construction: The bulb must be capable of operating continuously above 250 °C and a form
of fused silica called quartz is used. These lamps operate with higher filament temperatures,
resulting in increased efficacy and an increased lamp life, generally 2000 h. A typical linear
lamp is illustrated in Fig. 2.

Operation: There are several operating conditions which must be observed for satisfactory
performance.
1. The quartz bulb wall must be maintained above the condensation temperature of the
halide (approx. 250 °C).

2. Linear lamps must be operated within 4° of horizontal. Outside this range, the halogen
vapour will migrate to the lower end of the lamp, resulting in early lamp failure of the
upper part of the filament.

3. Contamination of the outside surface of the lamp wall must be avoided. For example, a
deposit of grease by handling will cause the quartz envelope to fail at high temperatures as
the grease will cause the surface to develop fine cracks. Before use, any such
contamination should be cleaned off with a suitable solvent such as methylated spirit.

BTI - Electrical & Electronics Division 92 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

2. Discharge lamps:

The method of light production previously discussed is concerned with the passage of
electricity through a solid. Lamps which produce light due to the passage of electricity
through a gas are termed discharge lamps.

Ionisation: Initially when a voltage is applied to a discharge lamp the gas inside the lamp is
in an insulating state and will not conduct electricity. Ionisation can occur within the lamp in
two ways. Initially the application of a high voltage pulse to the lamp will pull many electrons
from their orbits. However, once the lamp is running, charged particles moving along the
lamp will collide with gas atoms dislodging electrons in the process.

High- and low-pressure discharges: In the low-pressure discharge the charged particles
move along the lamp a relatively long distance between collisions and will easily build up
sufficient speed to cause excitation to the first possible orbit. As the gas pressure is
increased the distance between collisions decreases and so the energy gained by the
particle during its acceleration time is proportionally lower.

Fluorescence: The low-pressure mercury discharge produces radiant energy within the
ultra-violet part of the spectrum. By coating the inside of the arc-tube with a fluorescent
coating or phosphor, this UV radiation is converted to visible radiation.

Gas fillings in discharge lamps: The discharge envelope is filled with a mixture of gases
and vapours. The main gas or vapour is the one responsible for the emission of light. This
may be in solid state at room temperature, so a further gas is needed to initiate the
discharge. When the lamp is running there may be loss of energy due to the current
electrons not colliding with the main gas or vapour, and even passing out of the envelope. To
increase the probability of collision a buffer gas or vapour is included. Examples of these
three elements are given in Table 1.1.

Table 1.1 Typical gas and vapour fillings

Lamp type Main filling Starting Buffer


Fluorescent tube Mercury Argon Argon
Low-pressure sodium Sodium Neon
High-pressure sodium Sodium Xenon Mercury
High-pressure mercury Mercury Argon and Nitrogen

3. Types of discharge lamps and typical control circuits

There are two kinds of discharge lamp, one is called the cold-cathode type and the other hot-
cathode type. The former is normally referred to as a neon lamp, which required a very high
voltage to initiate the discharge.

Five of these will now be discussed.

1. Low-pressure mercury vapour lamps (MCF).


2. High-pressure mercury vapour lamps (MBF)
3. Metal halide lamps (HBI)
4. Low-pressure sodium vapour lamps (SOX).
5. High-pressure sodium vapour lamps (SON)

3.1 Low-pressure Mercury Vapour Lamps (MCF):


BTI - Electrical & Electronics Division 93 Elbaz Bader Ayad
YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

The low-pressure mercury vapour lamp (it is coded MCF) can have a relatively high light
output and efficacy provided the ultra-violet radiation generated in the lamp is converted into
light by means of the fluorescent coating. This type of lamp is one of the most common
lamps manufactured today. It is used extensively in industrial and commercial premises and
is beginning to be used in the home. Its general construction is shown in Fig. 3

Fig. 3: Tubular fluorescent lamp (MCF)

Electrodes: The electrodes, which are at the ends of the tube, act as both anode and
cathode alternately when connected to alternating current but are normally called cathodes.

Electrons are emitted at the cathode and collected at the anode. For an electron to leave the
cathode, it has to be given sufficient energy to overcome the forces holding it to the atoms of
the cathode material.
Heating the electrodes by passing a current through them before the arc is struck makes
sure that a large number of free electrons exist around the electrodes, making the striking of
the lamp easier. During operation the electrodes are kept hot by the passage of the
discharge current.
Control gear: In fluorescent lamp circuits operated on a.c. supplies, the ballast is usually a
choke and is connected in series with the lamp, as shown in Fig. 4. There are many more
complex circuits used to control the lamp current and to assist in striking the lamp, and the
term ballast is used to cover all forms of control gear.

Fig.4: Switch-start circuit

Fig. 5: Glow type starter switch

BTI - Electrical & Electronics Division 94 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Switch-start circuits: Glow type starter switch This switch, shown in Fig. 5, has two switch
contacts, one of which is bimetal strip in a small envelope containing argon.

Starter capacitor: The small capacitor which is connected across the starter terminals (i.e.
in parallel with the switch contacts) reduces emission by the lamp at radio frequencies and
also improves the waveform of the starting voltage pulse.

Circuit Operation: Circuit operation on starting having considered the sequence of events
that takes place in the starter switch, this must be related to the lamp and choke during this
time. First there is a current flowing through the choke, cathodes, and starter switch. This
current is about 1.5 times the running current; it heats the cathodes and causes free
electrons to be emitted and ionisation to take place near the electrodes.

When the starter switch opens, the choke opposes the change by producing a voltage which
is in the same direction as the supply voltage and therefore adds to it. A high-voltage surge
across the lamp is enough to cause an arc between the electrodes of the lamp.

Electronic starter switch: A switch is available, at extra cost, which uses a thyristor trigger.
This sets up a pre-heat circuit and a high voltage is generated. Starting is near instant and, in
the event of lamp failure, the electrode current ceases. This overcomes damage to the
starter and ballast.

Starterless circuits: Although the switch-start circuit is reliable and is more suitable for
low-temperature applications, the starter switch is the one item in the circuit with moving
parts liable to fail. Also, in some applications its operation can be a nuisance due to flicker
until the lamp has struck - especially with old lamps.
Starterless circuits operate without a starter switch and so reduce the maintenance required.
They have disadvantages, however: they are more complex and expensive; ballast losses
are higher than those of the simple choke; and they are more susceptible to difficulties in
starting at temperatures below 5°C. The circuit is shown in Fin 6.

Fig. 6: Starterless transformer circuit

The major change from the switch-start circuit is that a transformer is used to provide a low
voltage across each electrode, which is contained within the ballast canister together with the
choke.

When the circuit is first switched on, nearly all the supply voltage appears across the lamp
and the transformer. Current flows through the electrodes from the two transformer windings,
one heating each electrode and producing emission of electrons, until there are enough free
electrons to enable the lamp to strike with only the supply voltage across the lamp. Once the
arc has struck the current through the choke increases and therefore the voltage drop

BTI - Electrical & Electronics Division 95 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

previously across the transformer now appears across the choke, reducing the lamp and
transformer voltage so that the lamp current is limited to its correct value. The voltage across
the electrodes falls to about half.

This circuit is more complex and expensive than the switch start but is the only circuit
suitable for use with dimming control. To dim fluorescent tubes the lamp voltage and filament
temperatures must be maintained while the lamp current is reduced. A typical circuit is shown
in Fig. 7.

Fig. 7: Circuit for dimming a fluorescent tube

Semi-resonant start circuit: This comes within the category of starterless circuits, but is
simpler and has lower gear losses than the transformer type. It comprises a double wound
choke with two equal coils wound in opposition and a series capacitor. The term resonant is
used since the sub-circuit of the lamp, coil B. and the capacitor (Fig. 8) produces a high lamp
voltage and filament current for starting (the capacitor and coil combination have minimum
impedance). When the lamp is running, the coil B becomes ineffective and the circuit is coil
A, lamp, and capacitor. This circuit will operate at low temperatures.

Fig. 8: Semi-resonant start circuit

Electronic control circuits: Raising the electrical frequency to the lamp from 50 Hz to a
high frequency of around 30 kHz brings a number of significant improvements to
performance. These include:

1. reduction in ballast losses, and weight;


2. elimination of flicker and noise;
3. improved lamp efficacy and life;
4. instant lamp start.

The electronic element of the circuit is the frequency conversion. Figure 9 shows an example
of this type of circuit.

BTI - Electrical & Electronics Division 96 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Fig. 9: Typical circuit for a high frequency electronic ballast

The HF system offers particular advantages in twin-lamp luminaires, because a single ballast
drives two lamps instead of the two separate ballasts in conventional luminaires.
3.2. High-pressure mercury lamp (MBF):

Increasing the vapour pressure of a discharge has the effect of changing the spectral power
distribution by increasing the width of the spectral lines (bands) produced, and by changing
the relative intensities. Absorption of the resonance radiation also takes place.

Lamp construction: The basic high-pressure mercury vapour lamp shown in Fig. 10
consists of a glass outer envelope containing the quartz arc tube, its supports, and the
lead-in wires. This outer envelope contains nitrogen to dissipate the heat produced and
maintain the arc tube at the correct temperature.
Inside the arc tube; there are small quantity of mercury, argon (which acts as a starting gas),
and the tungsten electrodes. There are usually three or four electrodes - two of which are
main electrodes and a smaller auxiliary electrode (or electrodes) used to initiate the arc.
The auxiliary electrode is very close to a main electrode and is connected through a resistor
to the electrode at the other end of the lamp.

Lamp operation: When the lamp is connected to the supply, there will initially be no current
flow and mains voltage will exist between the two main electrodes and between a main
electrode and its auxiliary electrode via the internal resistor.

This voltage will produce a local arc in the argon gas with the current limited to a safe value
by a high resistance of a few thousand ohms connected in series with the auxiliary electrode
as shown on Fig. 10. The initial arc produces ionization, and an argon arc is soon struck
between the two main electrodes.

This produces further ionisation until sufficient mercury ions exist for the mercury arc to be
formed. At first a low-pressure arc exists and very little light is produced; but gradually, as the
lamp heats up, the mercury vapour pressure rises and a high pressure arc is formed and
more light is emitted. Once the main arc is established, its resistance is lower than in the
auxiliary electrode circuit and this auxiliary electrode ceases to function. The time taken for
the lamp to completely 'run up' - that is, to reach full light output - is approximately 5 min.
This type of lamp is also widely used for street lighting in residential areas where its colour
rendering may be preferred to low-pressure sodium.

BTI - Electrical & Electronics Division 97 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Fig. 10: High-pressure mercury fluorescent lamp (MBF)

Lamp circuits: The circuit is relatively simple as


the lamp incorporates its own starter. The circuit is
shown in Fig. 11 and consists of a choke and power
factor capacitor. A series resistance in the form of a
tungsten filament can be used instead of the choke.
These are called MBT-type lamps; they have
improved colour rendering but only about half the
luminous efficacy.

Fig. 11: Control circuit for an MBF lamp


3.3. Metal halide lamps (MBI):

This lamp, known as the mercury halide or metal halide lamp, is similar in construction to the
MB lamp but has a much shorter arc tube. Strictly speaking, they are not mercury lamps but
are a series of lamps combined within a single arc tube with output characteristics of different
mixtures of elements.

One disadvantage of these lamps is that a high starting voltage is necessary. This is usually
provided by an electronic igniter which generates very short duration high-voltage pulses is
connected across the lamp terminals. This type of starter enables the lamp to be restruck
within one minute of being switched off.

Due to its high efficacy and good colour rendering properties, the MBI lamp is suited to both
high bay interior and high mast exterior installations, and is often used in sports stadiums,
especially where colour television transmission is expected. A typical lamp is shown in
Fig. 12.

Fig. 12: 365 W metal halide lamp (MBI)

Lamp circuits: The lamp requires an igniter, choke, and power factor capacitor. A typical
circuit is shown in Fig. 13.

BTI - Electrical & Electronics Division 98 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Fig. 13: Control circuit with ignitor for an MBI lamp


3.4 Low-pressure sodium vapour lamp (SOX):

Light is produced by the action of the excited electrons returning to lower energy levels. The
sodium vapour arc produces a number of spectral lines but most of the visible radiation
(95 %) is concentrated in a very narrow region of the spectrum at 589.0 and 589.6 nm
(known as the sodium 'D' lines). The light output is therefore monochromatic (single
coloured) and the lamp is easily recognised by its yellow appearance.

Although this yellow light has the disadvantage that colours are greatly distorted, it has the
advantage that, as the relative response of the eye, it has a potential for a high lumen output,
depending upon how much energy is actually put into the lamp.

Lamp construction and performance: There are a number of different types of lamp. The
two main types are SOX and SL1. SOX is a single-ended lamp with an integral outer jacket
coated with a heated reflector (see Fig. 14). The inner discharge tube is made of 2-layer
glass, the outer being soft glass and the inner a thin film of sodium-resistant class.

Fig. 14: Single-ended low-pressure sodium lamp (SOX)

SL1 is a double-ended single-line discharge tube. This lamp is of particular value in


floodlights which require a narrow linear source.

The electrical characteristics are similar to those of the fluorescent tube. The lamps are not
temperature sensitive as they operate within a vacuum jacket.

Lamp circuits: At room temperature the metallic sodium solid, and in order to vaporise the
sodium, neon and argon are added. Initially a neon-argon arc is formed and the heat
produced gradually vaporises the sodium. The lamp has a run-up period of about 10 min
before maximum light output is reached.

A transformer is used in the sodium lamp circuit because of the 'higher-than-mains' ignition
voltage required, i.e. approximately 470 to 490 V. If a normal transformer is used, a choke
would also be needed to limit the current after the discharge has struck because of the
negative resistance characteristic of the arc. Such a circuit is, however, expensive in material
BTI - Electrical & Electronics Division 99 Elbaz Bader Ayad
YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

usage, when one considers that the transformer output voltage is about 500 V while the
normal operating lamp voltage required is 100 V.A lot of material can be saved by, first of all,
using an auto-transformer and, secondly, by making it an auto-leak-transformer which
removes the need for a separate choke (see Fig. 15).

This leak transformer type of circuit has a low power factor (0.3) and a capacitor is connected
across the supply to increase the power factor to an acceptable value.
The linear lamp can be operated on circuits similar to fluorescent lamps.

Fig. 15: 'Leakage-flux' transformer circuit

3.5 High-pressure sodium lamp (SON, SON-L, SON-R):

The low-pressure sodium arc emits all of its radiation in the two yellow. The colour rendering
is, as stated earlier, very unsuitable for most applications other than road lighting and
security lighting.

Lamp construction and performance: The high temperature (1300 °C) necessary to
produce the very high vapour pressure required in this lamp would melt any glass arc tube,
and at this temperature quartz also is readily attacked by hot sodium vapour. A 400 W
high-pressure SON sodium lamp is shown in Fig. 16.

The lamp consists of an evacuated outer envelope containing the arc tube and its
support-similar to the MB lamp except that the arc tube is longer and narrower than the arc
tube of the MB lamp and no auxiliary electrode is possible. The arc tube contains an
amalgam of mercury and sodium together with a small quantity of argon or xenon to assist in
striking the arc. The mercury is used to reduce the lamp current for a given wattage.

A high voltage is required across the lamp in order to strike the arc. This high voltage may be
provided, as in the MBI circuit, by an electronic igniter which generates pulses of a few
thousand volts for a few microseconds duration and is connected across the lamp terminals.
The igniter continues to pulse until the lamp is struck.

BTI - Electrical & Electronics Division 100 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Fig. 16: High-pressure sodium lamp

Some manufacturers include in the outer envelope of the lamp a bimetal starting switch and
small heating element. The switch and element are in series and are connected across the
electrodes. This type of lamp is manufactured in many sizes from 125 W (76 lm/W) to 1 kW
(130 lm/W) and the outer envelope may be either elliptical with a diffusing coating on the
inside, or tubular clear glass.

BTI - Electrical & Electronics Division 101 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

2. Design of lighting

This should be the culmination of all the knowledge gained from the previous chapters. Unfortunately, this is
where many people responsible for the design of lighting start and finish. Good design is the application of the
best or most appropriate equipment in an economical but effective manner.
This chapter covers the normal design processes for establishing a satisfactory illuminance
on the working plane, provided in a glare controlled manner.

1. Amount of light Required

Standard values of illuminance (lux) are specified in the CIBSE 1984 Lighting Code for all the
usual locations and occupations. These values are necessary to achieve:

(1) satisfactory illuminance of the task;


(2) an agreeable general appearance of the interior.

They are quoted as 'standard service illuminances', normally on a horizontal working plane. A
'service' illuminance is the mean illuminance throughout the life of the lighting system and
averaged over the relevant area. 'Standard' implies a value suitable for many locations,
unless there are special requirements.

Table 3.1 shows the illuminances relevant to a range of different visual tasks. This table is
expanded in the Guide to quote recommended standard service illuminance values covering
nearly 150 activities or types of interiors.
The illuminance values serve as a guide to good practice. They are not mandatory although
some authorities may adopt them as part of their standard requirements.

It is also recognised that there can be circumstances for a given situation where the standard
service value should be modified to give a design service value, i.e. one applicable to the
specific circumstances.

2. Designing a general layout

The first stage is to decide on the type of luminaire to be used. This decision may seem
premature, but, unless using computer programs, it is difficult to achieve anything without
immediate access to specific photometric data. Alternative approaches can be used where all
the design requirements are established, and luminaires are then found to fit these
requirements. However, it is easier to explain the design process by the first method.

Next, the total number of lamp lumens is calculated to achieve the recommended
illuminance, and finally the layout is planned.

2.1 Determination of lumens required:


A commonly accepted method involves the use of the 'lumen formula' which is:

Lamp lumens required = E  A / UF  LLF


where: E = standard service illuminance (Ix)
A = area of working plane (m2)
UF = utilization factor
LLF = light loss factor

BTI - Electrical & Electronics Division 102 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Table 2.1 Examples of activities/interiors appropriate for each standard service illuminance
(reproduced by permission of the Chartered Institution of Building Services Engineers.
CIBSE 1984 Interior Lighting Code).

Standard Characteristics of the activity/interior Representative activities/interiors


Illumin.
(lx)
Interiors visited rarely with visual tasks Cable tunnels, indoor storage tanks,
50 confined to movement and casual walkways
seeing without perception of detail.
Interiors visited occasionally with Corridors, changing rooms, bulk
100 visual tasks confined to movement
and casual seeing calling for only
limited perception of detail.
Interiors visited occasionally with visual Loading bays, medical stores, switch-
tasks requiring some perception of detail rooms.
150 or involving some risk to people, plant or
product.
Continuously occupied interiors, visual Monitoring automatic processes in
200 tasks not requiring any perception or manufacture, casting concrete,
detail. turbine halls.
Continuously occupied interiors, visual Packing goods, rough core making in
300 tasks moderately easy, i.e. large details foundries, rough sawing.
> 10 min arc and/or high contrast.
Visual tasks moderately difficult, i.e. General of fires, engine assembly,
details to be seen are of moderate painting and spraying.
500 Size (5-10 min arc) and may be of low
contrast. Also colour judgement
may be required.
Visual tasks difficult, i.e. details to be Drawing of rice’s, ceramic decoration,
seen are small (3-5 min arc) and of low meat inspection.
750 contrast, also good colour judgements
may be required.

Visual tasks very difficult, i.e. details Electronic component assembly,


to be seen are very small (2-3 min arc) gauge and tool rooms, retouching
1000 and can be of very low contrast. paintwork.
Also accurate colour judgements may
be required.
Visual tasks extremely difficult, i.e. Inspection of graphic reproduction,
1500 details to be seen extremely small hand tailoring, fine die sinking.
(1-2 min arc) and of low contrast. Visual
aids may be of advantage.
Visual tasks exceptionally difficult, i.e. Assembly of minute mechanisms,
details to be seen exceptionally small ( < finished fabric inspection.
2000 I min arc) with very low contrasts. Visual
aids will be of advantage.

BTI - Electrical & Electronics Division 103 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

2.2 Utilization factor:


This is a measure of the efficiency of the lighting scheme and is the proportion of lamp flux
that reaches the working plane. Some will come direct and some will come after reflection
from other room surfaces.
Table 2.2 shows a typical set of data, and to determine the precise value involves details of
the room dimensions and surface reflectance.

The room dimensions are required in terms of the room index, where

Room index= (L  W) / [(L + W)  H]


where: L = Room Length
W = Room Width
H = Height of lamp above working plane

Table 2.2: A typical set of data, and to determine the precise value involves details of the room
dimensions and surface reflectance.

Room reflectance Room Index


C W F 0.75 1.0 1.25 1.50 2.00 2.50 3.00 4.00 5.00

0.50 0.20 0.41 0.47 0.52 0.55 0.60 0.63 0.66 0.69 0.71
0.7 0.30 0.36 0.42 0.47 0.50 0.56 0.59 0.62 0.66 0.68
0.10 0.32 0.38 0.43 0.47 0.52 0.56 0.59 0.63 0.66

0.50 0.20 0.37 0.42 0.46 0.49 0.53 0.55 0.57 0.60 0.61
0.5 0.30 0.33 0.38 0.42 0.45 0.49 0.52 0.55 0.57 0.59
0.10 0.29 0.34 0.39 0.42 0.47 0.50 0.52 0.56 0.58

0.50 0.20 0.33 0.37 0.40 0.43 0.46 0.48 0.49 0.51 0.53
0.3 0.30 0.29 0.34 0.37 0.40 0.43 0.46 0.48 0.50 0.51
0.10 0.27 0.31 0.35 0.38 0.41 0.42 0.46 0.48 0.50

0.00 0.00 0.00 0.23 0.26 0.28 0.30 0.33 0.35 0.36 0.38 0.39

2.3 Light loss factor and maintenance factor

In previous lighting codes the effect of hours of operation on the lumen output from lamps
has been allowed for by using lighting design lumens rather than initial lumens, and the effect
of dirt depreciation has been allowed for by using a maintenance factor.

The maintenance factor is the ratio of the illuminance provided when the installation is in an
average condition of dirtiness to the illuminance provided when it is clean.

This system has been abandoned because with the range of light sources now available it
has become unrealistic to consider the illuminance provided at 2000 h as an accurate
description of the average through-life illuminance provided by the installation. Dealing with
maintenance by means of the light loss factor allows for a more comprehensive examination
of the effect of the operating conditions and maintenance procedures on the illuminance
provided.

2.4 Determination of light loss factor:


BTI - Electrical & Electronics Division 104 Elbaz Bader Ayad
YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Light loss factor is the product of three other factors:


Light loss factor = Lamp lumen maintenance factor
 Luminaire maintenance factor
 Room surface maintenance factor

Lamp lumen maintenance factor estimates the decline in light output of the light source over
a specified time. Luminaire maintenance factor estimates the effect of dirt deposited on or in
the luminaire over a set time on the light output of the luminaire. Room surface maintenance
factor estimates the effect of dirt deposited on the room surfaces over a set time on the
illuminance produced by the installation.

By calculating the light loss factor for different times, and taking into account the proposed
maintenance schedule, it is possible to predict the pattern of illuminance produced by the
installation over time. This pattern can be used to assess the suitability of any proposed
maintenance schedule. It can also be used to estimate the average illuminance provided by
the installation over time, and hence to determine whether the installation is likely to meet the
appropriate design service illuminance criterion recommended.

As a guide, the lumen output of discharge lamps after 2000 h of use is about 0.92 of their
initial lumens. Typical depreciation curves for luminaires are shown in Fig. 1. This also
includes data on light loss due to dirt on the room surfaces.

% 100 a
Light b
output
8 c
0 d
60
a. Ventilated reflector
b. Open base reflector
4
c. Non-ventilated
0 reflector
20 d. Indirect cornice

0 2 4 6 8 10 12 14 Elapsed time months


Fig. 1: Loss of light due to dirt on luminaires and room surfaces

Example:
What is the light loss factor due to open base fluorescent reflector luminaires assuming a 6
month cleaning interval based on lamp lumen output after 2000 h?

Solution:
Lamp lumen maintenance factor = 0.92 (from lamp data)

Average 3 month depreciation = 0.90 (from Fig. 1)

 Light loss factor = 0.92  0.90 = 0.83

It must be stressed that this is an over simplification, and that to obtain an accurate factor the
Guide must be used.

3. Lighting Fittings Layout

BTI - Electrical & Electronics Division 105 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

The previous section has shown how to calculate the number of lumens necessary for
efficient lighting. This section will consider how the fittings chosen should be disposed to give
the best results. It should first be appreciated that the type of fitting to be used must be
chosen before the lumen calculation is completed, since this effect the coefficient of
utilization. The choice may be altered in the light of figures obtained.
In most applications the type of fitting used will often be dictated by architectural or financial
considerations. In many cases, the pattern used will be dictated because the ceiling is
divided into bays or panels. The example which follow shows the methods to be adopted, but
the following points should always be in mind.

1) Always arrange the fittings symmetrically in straight or staggered rows, unless there is something (such as a special architectural feature
in the ceiling) to prevent it .

2) If the calculated number of fittings will not give a suitable pattern, increase the number to
be used. A decrease will result in a lower level of illumination than that planed.
3) Allow even spaces between fittings, and “half-spaces” between fittings and walls.
The fittings may need to be nearer the wall if they are in line with work-benches.
4) Make sure that the space / height ratio is reasonable. The correct ratio depends on the
type of fitting used, but as a rough guide, the distance between the fittings should not
exceed 1.5  the mounting height.
5) Glare must be prevented by shielding lamps where necessary. This is of particular
importance where lamps become visible by only a slight elevation of the angle of vision,
as in low-ceiling or very large rooms.

The required uniformity should be achieved if the layout conforms to the manufacturers
quoted maximum spacing to height ratio (S / hm). The values of S and hm are illustrated in
Fig. 2. Where manufacturers' data are not available, the BZ classification gives a guide to the
ratio.

S/2 S
S/2

hm

Working plane S/2 S

(a) (b)

Fig. 2: Space to mounting height ratio

If linear luminaires are used in continues rows, then the manufacturer may quote a maximum
transverse spacing to height ratio. This indicates the maximum spacing between parallel
rows of luminaires (Normally from 1 to 1.5).

Example:
A lighting scheme is required for a small drawing office, 6  6 m , with a 3 m ceiling height.
BTI - Electrical & Electronics Division 106 Elbaz Bader Ayad
YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

The office is air conditioned (LLF = 0.85) and the room reflectance are 0.7 ceiling, 0.3 walls,
and 0.2 floor and the disk height is 0.8m.

Solution:
Step 1.
Select the mounting height. In this case the ceiling is relatively low and the luminaires would
be mounted direct to the ceiling and the height is 0.8 m.
Mounting height hm = Ceiling height - Desk height = 3.0 - 0.8 = 2.2 m

Step 2.
Determine the illuminance and, hence, the lumens required. The illuminance would normally
be selected from the Table 3.1. However, a drawing office is an example given in that table
and the value is 750 Ix. Values of UF and LLF must be determined. The room index is given
by: RI = (6  6) / 12  2.2 = 1.4
From Table 2.2 UF = 0.49 and as the office is air conditioned, an LLF value of 0.85 will
be assumed. Lamp lumens =(750  6  6) / (0.49  0.85) = 64 826 Im

Step 3.
Determine the minimum number of lighting points. This may not produce a satisfactory layout
but the golden rule is that this number can be increased but not reduced.

The luminaire has a quoted maximum S / hm ratio of 1.4. If hm = 2.2 m, then


S = 2.2  1.4 = 3 m So the minimum number of points is 2  2, i.e. 4.

Step 4.
Can this number achieve 750 Ix with a sensible lamping?
The available lamp sizes are shown in Table 2.3 and range from a 40 W to a 125 W
fluorescent lamp. For a layout of four points:
Lumens per point = 64 826 / 4 = 16206 lm

No single lamp approaches this initial lumen value. The nearest is the 125 W white tube with
9500 Im or triple tube of 75 W with 6050 lm . A possible solution is to use twin or triple lamp
luminaires, but a new set of calculations is required. As it is a drawing office it would be more
advantageous to increase the number of points to eight or nine to reduce the risk of shadow
( try to do it). A suggested layout is shown in Fig. 3.
1.5 3.0 1.5
m m m

1.5
m

3.0
m

1.5
m

Fig. 3: Suggest layout for the above example.

Table 2.3 : Range of typical lamps and their lumen outputs

BTI - Electrical & Electronics Division 107 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Lamp type Wattage Average initial Lighting design


Lumens (100 h) Lumens (2000 h)

Tungsten filament
GLS 60 610 -
150 2 060 -
500 8 200 -
Tungsten Halogen K 750 15 000 -
1 500 32 000 -
Fluorescent tubes
White 125 9 500 8 500
75 6 050 5 750
65 5 100 4 750
40 3 050 2 800
Normal 75 4 400 4 000
65 3 700 3 400
40 2 300 2 100
Krypton filled 26 mm
Triphosphor 70 6 550 6 300
58 5 400 5 100
36 3 450 3 200
Compact lamps 16 1 050 1 800
24 1 800 1 690
Low-pressure sodium
SOX 35 4 600 4 500
180 32 000 31 500
SLI 60 6 000 5 700
200 20 500 20 000
High-pressure sodium
SON 70 6 000 5 500
400 47 000 45 000
SON Deluxe 150 12 500 11 500
400 38 5000 35 500
High-pressure mercury
MBF 50 1 900 1 750
125 6 200 5 700
1 000 58 000 54 000
MBIF 250 19 000 16 000
1 000 92 000 85 000

Example :

BTI - Electrical & Electronics Division 108 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

A workshop has a floor area of 10m  15m and is to be illuminated at 100 (lux) by using
single-tube 4-ft, 40 W fluorescent fittings. The tube output through life averages 2150 (lm)
and the estimated values for the coefficient of utilization factor is 0.4 and the light
loss/maintenance factor is 0.75. Find the number of fittings required and show on a drawing
how they could be arranged.
E A
Solution:   lm
UF  MF
100  (1015 )
Lumens required   50000 lm
0.4  0.75
50000
Number of fittings required = = 23.26  24 fittings
2150

Since it is impossible to have a part of a fitting, at least twenty four will be needed. In a
rectangular space 10m  15m it is easy to arrange 24-fittings symmetrically, so 4-rows of 6-
fittings is suggested arrangement.

To space 4-fittings over 10m with a half-space at the wall on Y axis, spacing will be:
10  4 = 2.5 m.
To space 6-fittings over 15m with a half-space at the wall on X axis, spacing will be:
15  6 = 2.5 m.

The proposed layout is shown in Fig. 4.

It is important to appreciate that this solution is one of many. Particularly in workshops, where
appearance may not be too important, a symmetrical pattern must be sacrificed to provide
even illumination for benches and machinery.

1.25 2.5 2.5 2.5 2.5 2.5 1.25


m m m m m m m

1.25m

2.5m

2.5m

2.5m

1.25m

Fig. 4: Layout of the example above

Class work :

A heavy engineering assemble bay 120m  40m is to be illuminated by twin mercury-


vapour/tungsten fittings mounted 15m above floor level, at which the illumination must be
250 lux. Each fitting comprises 1-250W h.p.m.v. lamp emitting 9250 lm, and 1-800W
tungsten filament lamp emitting 4650 lm. If the coefficient of utilization is 0.25 and the
maintenance factor is 0.6, find the number of fittings required and suggest a suitable layout.

BTI - Electrical & Electronics Division 109 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

4. Calculation of glare

In both daylight and electric light there is always a need to restrict the luminance within the
normal field of view, otherwise an unacceptable degree of glare will be experienced.

4.1 Disability glare

This can be defined as: Glare which impairs the ability to see detail without necessarily
causing visual discomfort. As it is a definite reduction in the ability to see, it can be measured
in terms of visual performance, and its effect can be expressed as a shift in the adaptation
level of the eye. If the adaptation level is raised by a light source, such as an unshaded lamp
or window, then the eye becomes less sensitive to small differences in brightness.

4.2 Discomfort glare

This can be defined as: Glare which causes visual discomfort without necessarily impairing
the vision. The degree of discomfort will depend on the type of location and angle of view; for
instance, people will tolerate a much brighter installation in a supermarket, where they are
continually on the move and looking in all directions, than in a classroom, where the direction
of view is fixed, the visual task more exacting, and the occupants have more time to become
aware of the lighting. This is very much a subjective assessment; it cannot be measured in
terms of performance, but only in relative degrees of discomfort.

To calculate the glare from each light point for a range of room positions would be too
time-consuming. The method can be simplified by considering a number of standard
conditions and making adjustments as necessary. The standard conditions and assumptions
are:

1. Glare is additive; therefore, for a complete installation, the glare from all the luminaires
would be the same as for a single luminaire of the same luminance.
2. The direction of view is horizontal, straight across the room, and 1.2 m above floor level.
3. The room is rectangular and has a regular array of luminaires.
The calculations and corrections depend on the tabular data being used. A list of typical
limiting glare indices is given in Table 2.4.
Table 2.4 CIBSE recommended limiting glare indices for different classes of visual task

Class of visual task Examples Limiting glare index

Critical, often with a fixed Drawing offices; very fine 16


direction of view inspection
Critical, but general Offices, libraries; computer 19
direction of view buildings
Ordinary task with general Kitchens; reception areas; 22
direction of view fine assembly work
Large task or limited Stock rooms; medium 25
viewing time assembly work
No specific visual task or Rough industrial work; 28
direction of view indoor parking areas

BTI - Electrical & Electronics Division 110 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Table 2.5 shows a typical glare data sheet for prismatic enclosure type luminaire.

Glare indices
Ceiling reflectance 0.7 0.7 0.5 0.5 0.3 0.7 0.7 0.5 0.5 0.3
Wall reflectance 0.5 0.3 0.5 0.3 0.3 0.5 0.3 0.5 0.3 0.3
0.14
Floor reflectance
0.14 0.14 0.14 0.14 0.14 0.14 0.14 0.14 0.14
Room dimension Viewed crosswise Viewed endwise
X Y
2H 7.3 8.5 8.4 9.7 11.1 6.7 8.0 7.8 9.1 10.6
3H 9.4 10.5 10.5 11.6 13.1 8.4 9.5 9.5 10.7 12.2
4H 10.4 11.4 11.5 12.6 14.1 9.1 10.2 10.3 11.4 12.9
6H 11.5 12.5 12.6 13.6 15.2 9.8 10.7 10.9 11.9 13.5
8H 12.1 13.0 13.3 14.2 15.8 10.0 10.9 11.1 12.1 13.7
2H 12H 12.8 13.7 13.9 14.9 16.4 10.1 11.0 11.2 12.2 13.7

2H 8.1 9.1 9.2 15.3 11.8 7.6 8.7 8.8 9.8 11.4
3H 10.5 11.4 11.6 12.6 14.1 9.6 10.5 10.8 11.7 13.2
4H 11.7 12.5 12.8 13.7 15.3 10.5 11.3 11.7 12.5 14.1
6H 13.0 13.8 14.2 15.0 16.6 11.4 12.1 12.6 13.3 14.9
8H 13.8 14.5 15.0 15.7 17.3 11.7 12.4 12.9 13.6 15.2
4H 12H 14.6 15.2 15.8 16.4 18.1 11.9 12.5 13.1 13.8 15.4

4H 12.3 13.0 13.5 14.2 15.8 11.3 12.0 12.5 13.2 14.8
6H 13.9 14.5 15.2 15.7 17.4 12.5 13.1 13.7 14.3 15.9
8H 14.9 15.4 16.1 16.6 18.2 13.0 13.5 14.2 14.7 16.4
8H 12H 15.9 16.4 17.2 17.6 19.3 13.4 13.8 14.6 15.1 16.7

4H 12.4 13.0 13.6 14.2 15.8 11.6 12.2 12.8 13.4 15.0
6H 14.1 14.7 15.4 15.9 17.5 12.9 13.4 14.1 14.6 16.2
8H 15.2 15.7 16.5 16.9 18.6 13.5 14.0 14.7 15.2 16.9
12H 12H 16.1 16.5 17.4 17.8 19.4 13.7 14.1 15.0 15.4 17.0

Glare index conversion:


Luminaire length (mm) 600 1200 1500 1800 2400
Conversion +3.82 +1.41 +0.63 0 -1.0

The glare data sheet is based on a number of assumptions:

1. the luminaire is 2 m above eye level;


2. the lamp emits 1000 lumens;
3. the spacing to height ratio is 1 : 1.

Table 3.6 gives corrections for factors (1) and (2) . No corrections are available for (3).

Initial glare indices are tabulated according to room dimensions and reflectances. Fig..5
shows the method of specifying the room dimensions. The Y dimension is always parallel to
the line of sight and the X dimension is perpendicular to the line of sight. They are both
expressed as multiples of the mounting height above eye level.

BTI - Electrical & Electronics Division 111 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

One view of the room will show the ends of the luminaires (endwise view) and the other view
will show the sides (crosswise view).

Direction of view
Plan of room X

Eye level
Elevation
1.2 m

Fig. 5 : Room dimensions for glare calculation

Table 2.6: Glare Correction data

Initial lamp Correction Height H above Correction


Lumens term 1.2 m eye level tem
100 -6.0 1 -1.2
150 -4.9 1.5 -0.5
20 -4.2
300 -3.1 2 0.0
500 -1.8
700 -0.9 2.5 +0.4
1 000 0.0 3 +0.7
1 500 +1.1 3.5 +1.0
2 000 +1.8
3 000 +2.9 4 +1.2
5 000 +4.2 5 +1.6
7 000 +5.1 6 +1.9
10 000 +6.0
15 000 +7.1 8 +2.4
20 000 +7.8 10 +2.8
30 000 +8.9 12 +3.1
50 000 +10.2

When the initial glare index has found it must be corrected for:
1. mounting height above 1.2 m eye level if this differs from 3 m. (table 2.6)
2. total downward luminous flux if this differs from 1000 lm. (table 2.6)
3. extra correction sizes or lamp types. (table 2.5)

BTI - Electrical & Electronics Division 112 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

These correction terms are added to (or subtract from) the initial glare index to give the final
glare index of the installation.

Example:
Referring to the scheme designed earlier in Fig 3, what is the glare index?

Solution:
The room is square, so X = Y = 6m. The ceiling height is 3m and the height of eye level for a
seated man is 1.2m above the floor.

H = 3 - 1.2 = 1.8 m X = 6 m = 6 H / 1.8 = 3.3 H = Y

The reflectances are 0.7 ceiling, 0.3 wall and 0.2 floor. In this case the worst glare situation
is when the luminaires are viewed crosswise. From Table 2.5, the initial glare index is found
by interpolation:

X Y Y = 3.3H X = 3.3 H
2H 3H 10.5
10.8
4H 11.4
11.4
4H 3H 11.4
11.73
4H 12.5

Applying correction from Table 2.6 :

Initial lamp lumens = 6050 lm Correction = + 4.8

Height above eye level is 1.8 m Correction = - 0.2

There is a further glare index conversion of + 0.63 (see Table 2.5) for 1.5 m lamp.

 Final glare index = 11.4 + 4.8 - 0.2 + 0.63 = 16.23

As the limiting glare index for a drawing office is 16, this installation barely meets the glare
limit requirements. It does suggest that glare could be a problem, and another type of
luminaire should be selected.

BTI - Electrical & Electronics Division 113 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

3. Emergency lighting

It is an increasing requirement that commercial, industrial, and public buildings are provided
with some form of emergency lighting. Requirements vary for different types of buildings and
even their geographical location. General guidance is given in BS 5266: 1975 The
emergency lighting of premises.

The following is a summary of the design requirements. The main classifications are:

1. Emergency lighting: lighting provided for use when the normal lighting fails.

2. Escape lighting: that part of emergency lighting which is provided to ensure that the
means of escape can be safely and effectively used at all material times.

3. Standby lighting: that part of emergency lighting which may be provided to enable
normal activities to continue.

The basic recommendations are that, during the period of use, the horizontal illuminance
measured on the centre line of any escape route should never fall below 0.2 /x and in halls
and corridors it should be measured at floor level. The emergency system should be in
operation within 5 seconds of the failure of the normal lighting installation.

The ratio of the minimum illuminance to the maximum illuminance along the escape route
should not exceed 1: 40 and care should be taken to avoid abrupt alternations of excessive
dark and light areas on the floor.

There are points in these recommendations that require some elaboration.

1. The illumination level quoted, of 0.2 lx, is roughly equivalent to a moonlit night. It is the
intention of the BS that this should be an absolute minimum, i.e. with an aged lamp and
battery, soiled luminaire and at the end of the period of duration. Such a situation would
suggest a desirable illumination level of between one-tenth and one-fiftieth of the normal
lighting level with a minimum value of 1.0 Ix.

2. The BS allowance of 5 sec. before the emergency lighting must be in operation (it can be
15 sec. for some areas at the local authority's discretion) is based upon practical tests
that indicated that after 15 sec. of darkness people began to move irrationally. Fortunately
many of the specialist emergency luminaires are capable of virtually instantaneous
operation and the 5 sec. requirement will be redundant in such cases.

The BS goes on to deal with the problems of specific areas and provides useful comment on the factors that
should be considered in the design of an emergency lighting installation. In particular, the merits of the various
possible systems are dealt with.

1. Planning the Layouts:

Positioning of luminaires: The correct positioning of emergency luminaires is essential in


order to provide a system that not only complies with the various legislative requirements but
provides a safe and effective way of evacuating a building in the event of a mains failure.
Therefore, apart from achieving the minimum light levels, various obstructions, hazards and
routes must be covered.

BTI - Electrical & Electronics Division 114 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

Luminaires and signs should be positioned:

(a) To show exit routes and final exits from premises clearly. Signs should be illuminated;

(b) To ensure exterior areas of final exits are lit to at least the same level as the
area immediately inside the exit to enable people to move away from the exit to
areas of safety;

(c) Near each intersection of corridors (less than 2 m horizontally);

(d) Near each change of direction (less than 2 m horizontally);

(e) Near each staircase so that each flight of stairs receives direct light (less than 2 m
horizontally);

(f) Near any other change of floor level which may constitute a hazard (less than 2 m
horizontally);

(g) To illuminate fire alarm call points and fire fighting equipment at all material times;

(h) To ensure normal pedestrian escape routes from covered car parks are
illuminated to the same standard as escape routes within buildings;

(i) In plant, switch and control rooms;

(I) Within passenger lift cars, (only self-contained emergency luminaires are suitable for
this application);

(k) In toilets exceeding 8 m2.

In order to meet the illuminance levels manufacturers should provide a table of


recommended spacing. A typical example is shown in Table 3.1.

Table 3.1 Spacing for a 4W fluorescent surface mounted luminaire

Ceiling Lighting Transverse Transverse Axial Axial


mounting level to wall spacing spacing to wall
height directly
(m) under (m) (m) (m) (m)
luminaires

2.5 1.8 lux 3.8 10.2 9.2 3.4


4.0 0.8 lux 4.0 11.2 10.2 3.6
6.0 0.4 1ux 3.2 11.2 10.2 3.0

Spacing Chart for Briklite Luminaire (dimensions in metros).

2 Undefined Escape Routes:

In an open area, such as a hall or shop, it is not possible to define a precise escape route. In
this case an average illuminance of 1 Ix is required, again with a uniformity of 40: 1. This

BTI - Electrical & Electronics Division 115 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Lighting System

may be achieved with separate luminaires or emergency packs in some of the normal
luminaires. The lumen method is used to calculate the lamps required for 1 Ix and a spacing
to height ratio of 2.5: 1 can give a guide to the minimum number of points.

Calculation:

N = (E  L  W) / (UFO  SF  ELDL  K)

where:
N = number of luminaires
UFO= utilization factor at zero reflectance. This is provided by the luminaire manufacturer for a given room index. When using
conversion sets in standard mains luminaires the UFO is taken for the mains luminaire

L = room length (in metros)


W = room width (in metros)
E = average illuminance required, i.e. 1.0 lx
SF = service correction factor to cover effects of lamp ageing, dust build up, etc,
assumed to be 0.8 for normal environments.
ELDL= emergency lighting design lumens at nominal volts. For self-contained
luminaires the ELDL is given in the specification for each luminaire. For
conversion units, multiply the design lumen output of the lamp by the ballast
lumen factor.
K = a factor to cover the reduction in light output at end of discharge, or 5 seconds
after mains failure, whichever is the lowest.

Values of ELDL and K depend on the type of lamp, system and luminaire. It would be
misleading to include typical tables in the text. The values should be provided by the supplier
of the luminaire. These factors can in some cases effectively reduce the lighting design
lumens to less than 10% of the initial lamp lumens.

BTI - Electrical & Electronics Division 116 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

Three-Phase Induction Motors

Three-phase induction motors are the motors most frequently encountered in industry. They are
simple, rugged, low-priced, and easy to maintain. They run at essentially constant speed from zero to
full-load. The speed is frequency-dependent and, consequently, these motors are not easily adapted to
speed control. However, variable frequency electronic drives are being used more and more to control
the speed of commercial induction motors.

In this chapter we cover the basic principles of the 3-phase induction motor and develop the
fundamental equations describing its behavior. We then discuss its general construction and the way
the windings are made.

Squirrel-cage, wound-rotor, and linear induction motors ranging from a few horsepower to several
thousand horsepower permit the reader to see that they all operate on the same basic principles.

1. Principal components

A 3-phase induction motor (Fig.1) has two main parts: a stationary stator and a revolving rotor. The
rotor is separated from the stator by a small air gap that ranges from 0.4 mm to 4 mm, depending on
the power of the motor.

The stator consists of a steel frame that supports a hollow, cylindrical core made up of stacked
laminations. A number of evenly spaced slots, punched out of the internal circumference of the
laminations, provide the space for the stator winding.

The rotor is also composed of punched laminations. These are carefully stacked to create a series of
rotor slots to provide space for the rotor winding. We use two- types of rotor windings:
a) conventional 3-phase windings made of insulated wire, called wound-rotor induction
motors, and
b) squirrel-cage windings, called cage-rotor induction motors.

Fig. 1: Exploded view of the cage motor

a) A squirrel-cage rotor is composed of bare copper bars, slightly longer than the rotor, which are
pushed into the slots. The opposite ends are welded to two copper end-rings, so that all the bars are
short-circuited together. The entire construction (bars and end-rings) resembles a squirrel cage, from
which the name is derived. In small and medium-size motors, the bars and end-rings are made of
die-cast aluminum, molded to form an integral block Fig. 2.

BTI - Electrical & Electronics Division 117 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

Fig. 2: Squirrel-cage rotor with integral cooling fan

b) A wound rotor has a 3-phase winding, similar to the one on the stator. The winding is uniformly
distributed in the slots and is usually connected in wye. The terminals are connected to three slip-rings,
which turn with the rotor (Fig. 3). The revolving slip-rings and associated stationary brushes enable us
to connect external resistors in series with the rotor winding. The external resistors are mainly used
during the start-up period; under normal running conditions, the three brushes are short-circuited.

Fig. 3: Exploded view of wound-rotor induction motor

BTI - Electrical & Electronics Division 118 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

2. Principle of operation

The operation of a 3-phase induction motor is based upon the application of Faraday's Law and the
Lorentz force on a conductor early studied. To understand the principle of operation, the rotating
magnetic field and it's direction of rotation should be in consideration.

2.1 The rotating field:


Consider a simple stator having 6 salient poles, each of which carries a coil having 2 turns (Fig. 4).
Coils that are diametrically opposite are connected in series by means of three jumpers that
respectively connect terminals a-a, b-b, and c-c. This creates three identical sets of windings AN, BN,
CN, that are mechanically spaced at 120° to each other. The two coils in each winding produce
magnetomotive forces that act in the same direction.
The three sets of windings are connected in wye (Star), thus forming a common neutral N. Owing to
the perfectly symmetrical arrangement, the line to neutral impedances are identical. In other words, as
regards terminals A, B. C, the windings constitute a balanced 3-phase system.
If we connect a 3-phase source to terminals A, B. C, alternating currents la, Ib , and Ic will flow in the
windings. The currents will have the same value but will be displaced in time by an angle of 120°.
These currents produce magnetomotive forces which, in turn, create a magnetic flux. It is this flux we
are interested in.

Fig. 4: Elementary stator having terminals A, B, C


connected to a 3-phase source

As time goes by, we can determine the instantaneous value and direction of the current in each winding and
thereby establish the successive flux patterns. Thus, referring to Fig. 5 for each of the successive instants 1. 2, 3,
4, 5, 6, and 7, separated by intervals of 1/6 cycle, we find that the magnetic field makes one complete turn during
one cycle.

BTI - Electrical & Electronics Division 119 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

Fig. 5: Instantaneous value of current and position of the rotating flux

The rotational speed of the field depends, therefore, upon the duration of one cycle, which in turn
depends on the frequency of the source. If the frequency is 60 Hz, the resulting field makes one turn in
1/60 s, that is, 3600 revolutions per minute. On the other hand, if the frequency were 5 Hz, the field
would make one turn in 1/5 s, giving a speed of only 300 r/min. Because the speed of the rotating field
is necessarily synchronized with the frequency of the source, it is called synchronous speed.

2.2 Direction of rotation


The positive crests of the currents in (Fig. 5), follow each other in the order A-B-C. This phase
sequence produces a field that rotates clockwise. If we interchange any two of the lines connected to
the stator, the new phase sequence will be A-C-B. By following the same line of reasoning explained
before, we find that the field now revolves at synchronous speed in the opposite, or counterclockwise
direction. Interchanging any two lines of a 3-phase motor will, therefore, reverse its direction of
rotation.

3. Synchronous speed

Soon after the invention of the induction motor, it was found that the speed of the revolving flux could
be reduced by increasing the number of poles.

The speed of a rotating field depends therefore upon the frequency of the source and the number of
poles on the stator. Using the same reasoning as above, we can prove that the synchronous speed is
always given by:

Ns = (120 f) / p
where:
Ns = synchronous speed (r/min)
f = frequency of the source (HZ)
p = number of poles per phase.

BTI - Electrical & Electronics Division 120 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

4. Starting characteristics of a squirrel-cage motor

Let us connect the stator of an induction motor to a 3-phase source, with the rotor locked. The
revolving field created by the stator cuts a the rotor bars and induces an a.c. voltage in all of them.

The frequency of the voltage depends upon the number of N and S poles that sweep across a conductor
per second; when the rotor is at rest, it is always equal to the frequency of the source. Since the rotor
bars are short-circuited by the end-rings, the induced voltage causes a large current to flow usually
several hundred amperes per bar in machines of medium power. The current-carrying conductors are
in the path of the flux created by the stator, consequently, they all experience a strong mechanical
force. These forces tend to drag the rotor along with the revolving field. In summary:

1. A revolving magnetic field is set up when a 3-phase voltage is applied to the stator of an
induction motor.
2. The revolving field induces a voltage in the rotor bars.
3. The induced voltage creates large circulating current which flow in the rotor bars and end-rings.
4. The current-carrying rotor bars are immersed in the magnetic field created by the stator; they are
therefore subjected to a strong mechanical force.
5. The sum of the mechanical forces on all the rotor bars produces a torque which tends to drag the
rotor along in the same direction as revolving field.

5. Motor under load

Suppose the motor is initially running at no-load. If we apply a mechanical load to the shaft, the motor
will begin to slow down and the revolving field will cut the rotor bars at a higher and higher rate. The
induced voltage and the resulting current in the bars will increase progressively, producing a greater
and greater motor torque.
The motor and the mechanical load will reach a state of equilibrium when the motor torque is exactly
equal to the load torque. When this state is reached, the speed will cease to drop and the motor will
turn at a constant rate. It is very important to understand that a motor only turns at constant speed
when its torque is exactly equal to the torque exerted by the mechanical load. The moment this state of
equilibrium is upset, the motor speed will start to change.

Under normal loads, induction motors run very close to synchronous speed. Thus, at full-load, the slip
for large motors (1000 kW and more) rarely exceeds 0.5% of synchronous speed, and for small
machines (10 kW and less), it seldom exceeds 3%. That is why induction motors are considered to be
constant speed machines. However, because they never actually turn at synchronous speed, they are
sometimes called asynchronous machines.

6. Slip

The slip s of an induction motor is the difference between the synchronous speed and the rotor speed,
expressed as a percent (or per-unit) of synchronous speed. The per-unit slip is given by the equation
S = (Ns - N) / Ns
where:
S = Slip
Ns = Synchronous speed (r/min)
N = Rotor speed (r/min)

The slip is practically zero at no-load and is equal to 1 (or 100%) when the rotor is locked.

BTI - Electrical & Electronics Division 121 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

7. Voltage and frequency induced in the rotor

The voltage and frequency induced in the rotor both depend upon the slip. They are given by the
following equations:
fr = s f
Er = s EO (approx.)
where:
fr = frequency of the voltage and current in the rotor [Hz]
f = frequency of the source connected to the stator [Hz]
s = slip
Er = voltage induced in the rotor at slip s
Eo = open-circuit voltage induced in the rotor when at rest [V]

In a cage motor, the open-circuit voltage Eo is the voltage that would be induced in the rotor bars if the
bars were disconnected from the end-rings. In the case of a wound-rotor motor the open-circuit voltage
is 1/3 times the voltage between the open circuit slip-rings. It should be noted that fr (in the Equ.
Above) always holds true, but Er (in the Equ. above) is valid only if the revolving flux (expressed in
webers) remains absolutely constant. However, between zero and full-load the actual value of Er is
only slightly less than the value given by the equation.

Classwork:
A 6-pole wound-rotor induction motor is excited by a 3-phase 60 Hz source. If the full-load speed is
1140 r/min calculate the frequency of the rotor current under the following conditions:
a. At standstill
b. Motor turning at 500 r/min in the same direction as the revolving field.
c. Motor turning at 500 r/min in the opposite direction to the revolving field
d. Motor turning at 2000 r/min in the same direction as the revolving field

8. Characteristics of Squirrel cage Induction Motors

Table 1 lists the typical properties of squirrel-cage induction motors in the power range between 1 kW
and 20 000 kW. Note that the current and torque are expressed in per-unit values.

Table 1 Typical Characteristics of cage-rotor induction motors

Loading I (per unit) T (per unit) S (per unit)  P.F.

Motor Size Small Big Small Big Small Big Small Big Small Big
Fuul-load 1 1 1 1 0.03 0.004 0.7 0.96 0.8 0.87
to to to to
0.9 0.98 0.85 0.9

No-load 0.5 0.3 0 0 ≈0 ≈0 0 0 0.2 0.05

Locked rotor 5 4 1.5 0.5


to to to to 1 1 0 0 0.4 0.1
6 6 3 1
Small means under 11 KW (15 hp); Big means over 1000 KW (~ 1350 hp)

The following explanations will clarify the meaning of the values given in the table.

8.1 Motor at no-load.

BTI - Electrical & Electronics Division 122 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

When the motor runs at no load, the stator current lies between 0.5 and 0.3 pu (of full-load current).
The no-load current is similar to the exciting current in a transformer. Thus, it is composed of a
magnetizing component that creates the revolving flux  m and a small active component that supplies
the windage and friction losses in the rotor plus the iron losses in the stator. The flux  m links both the
stator and the rotor; consequently it is similar to the mutual flux in a transformer (Fig. 6).

Considerable reactive power is needed to create the revolving field and, in order to keep it within
acceptable limits, the air gap is made as short as mechanical tolerances will permit. The power factor
at no-load is therefore low; it ranges from 0.2 (or 20%) for small machines to 0.05 for large machines.
The efficiency is zero because the output power is zero.

Fig. 6: Flux  m at No-load

8.2 Motor under load.


When the motor is under load, the current in the rotor produces a mmf which tends to change the
mutual flux  m.. This sets up an opposing current flow in the stator. The opposing mmfs of the rotor
and stator are very similar to the opposing mmfs of the secondary and primary in a transformer. As a
result, leakage fluxes  f1 , and  f2 are created, in addition to the mutual flux  m (Fig. 7).

The total reactive power needed to produce these three fluxes is slightly greater than when the motor is
operating at no-load. However, the active power (kW) absorbed by the motor increases in almost
direct proportion to the mechanical load. It follows that the power factor of the motor improves
dramatically as the mechanical load increases. At full-load it ranges from 0.80 for small machines to
0.90 for large machines. The efficiency at full-load is particularly high; it can attain 98% for very large
machines.

Fig. 7: Fluxes at full-load


8.3 Locked-rotor characteristics.
The locked-rotor current is 5 to 6 times the full-load current, making the I2R losses 25 to 36 times
higher than normal. The rotor must therefore never remain locked for more than a few seconds.

BTI - Electrical & Electronics Division 123 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

Although the mechanical power at standstill is zero, the motor develops a strong torque. The power
factor is low because considerable reactive power is needed to produce the leakage flux in the rotor
and stator windings. These leakage fluxes are much larger than in a transformer because the stator and
the rotor windings are not as tightly coupled.

9. Active power flow

Voltages, currents, and phasor diagrams enable us to understand the detailed behavior of an induction
motor. However, it is easier to see how electrical energy is converted into mechanical energy by
following the active power as it flows through the machine. Thus, referring to Fig. 8, active power Pe
flows from the line into the 3-phase stator. Due to the stator copper losses, a portion Pjs is dissipated as
heat in the windings. Another portion Pf is dissipated as heat in the stator core, owing to the iron
losses. The remaining active power Pr is carried across the air gap and transferred to the rotor by
electromagnetic induction.

Due to the I2R losses in the rotor, a third portion Pjr is dissipated as heat, and the remainder is finally
available in the form of mechanical power Pm. By subtracting a small fourth portion Pv, representing
windage and bearing-friction losses, we finally obtain PL, the mechanical power available at the shaft
to drive the load.

Fig. 8: Active power flow in a 3-phase induction motor.

The power flow diagram of Fig. 8 enables us to identify and to calculate three important properties of
the induction motor: (1) its efficiency, (2) its rotor copper losses, (3) its power, and (4) its torque.

9.1 Efficiency.
By definition, the efficiency of a motor is the ratio of the output power to the input power:

Efficiency ( ) = PL / Pe
9.2 I2 R losses in the rotor.
It can be shown that the rotor I2 R losses Pjr are related to the rotor input power Pr by the equation
Pjr = s Pr
where:
Pjr = rotor I2 R losses [W]
s = slip
Pr = power transmitted to the rotor [W]

The equation above shows that as the slip increases, the rotor I2 R losses consume a larger and larger
proportion of the power Pr transmitted across the air gap to the rotor. A rotor turning at half
synchronous speed (s = 0.5) dissipates in the form of heat 50 percent of the active power it receives.
When the rotor is locked (s = I ), all the power transmitted to the rotor is dissipated as heat.

9.3 Mechanical power.

BTI - Electrical & Electronics Division 124 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

The mechanical power Pm developed by the motor is equal to the power transmitted to the rotor minus
its I2 R losses.
Thus, Pm = Pr - Pjr
= P r - s Pr
whence Pm = (1 - s) Pr
The actual mechanical power available to drive the load is slightly less than Pm, due to the power
needed to overcome the windage and friction losses. In most calculations we can neglect this small
loss.

9.4 Motor torque.


The torque Tm developed by the motor at any speed is given by

Tm = 9.55 Pm / N
= [9.55(1 - s)Pr] / Ns(1 - s)
= 9.55 Pr / Ns
therefore,
Tm = 9.55 Pr / Ns
where:
Tm = torque developed by the motor at any speed [N.m]
Pr = power transmitted to the rotor [W]
Ns = synchronous speed [r/min]
9.55 = multiplier to take care of units [exact value: 60/2]

The actual torque TL available at the shaft is slightly less than Tm, due to the torque required to
overcome the windage and friction losses. However, in most calculations we can neglect this small
difference.
The torque equations show that the torque is directly proportional to the active power transmitted to
the rotor. Thus, to develop a high locked-rotor torque, the rotor must absorb a large amount of active
power. The latter is dissipated in the form of heat, consequently, the temperature of the rotor rises very
rapidly.

Classwork: 1
A 3-phase induction motor having a synchronous speed of 1200 r/min draws 80 kW from a 3-phase
feeder. The copper losses and iron losses in the stator amount to 5 kW. If the motor runs at 1152 r/min,
calculate the following:

a. The active power transmitted to the rotor


b. The rotor I2R losses
c. The mechanical power developed
d. The mechanical power delivered to the load, knowing that the windage and friction losses are
equal to 2 kW
e. The efficiency of the motor.

Classwork:2
BTI - Electrical & Electronics Division 125 Elbaz Bader Ayad
YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

A 3-phase induction motor having a nominal rating of 100 hp (~75 kW) and a synchronous speed of
1800 r/min is connected to a 600 V source

The two-wattmeter method shows a total power consumption of 70 kW, and an ammeter indicates a
line current of 78 A. Precise measurements give a rotor speed of 1763 r/min. In addition, the following
characteristics are known about the motor:
stator iron losses Pf = 2 kW windage and friction losses Pv = 1.2 kW resistance between two stator
terminals = 0.34 
Calculate:
a. Power supplied to the rotor
b. Rotor I2R losses
c. Mechanical power supplied to the load, in horsepower
d. Efficiency
e. Torque developed at 1763 r/min

10. Torque versus speed curve

The torque developed by a motor depends upon its speed, but the relationship between the two cannot
be expressed by a simple equation. Consequently, we prefer to show the relationship in the form of a
curve. Fig. 9 shows the torque-speed curve of a conventional 3-phase induction motor whose nominal
full-load torque is T. The starting torque is 1.5 T and the maximum torque (called breakdown torque)
is 2.5 T.

At full-load the motor runs at a speed n. If the mechanical load increases slightly, the speed will drop
until the motor torque is again equal to the load torque. As soon as the two torques are in balance, the
motor will turn at a constant but slightly lower speed. However, if the load torque exceeds 2.5 T (the
breakdown torque), the motor will quickly stop.
Small motors (10 kW and less) develop Their breakdown torque at a speed rid of about 80% of
synchronous speed. Big motors (1000 kW and more) attain their breakdown torque at about 98% of
synchronous speed.
The rotor resistance of a squirrel-cage rotor is essentially constant, except chat it increases with
temperature. Thus, the resistance increases with increasing load because the temperature rises.
In designing a squirrel-cage motor, the rotor resistance can be set over a wide range by using copper,
aluminum, or ocher metals in the rotor bars and end-rings. The torque-speed curve is greatly affected
by such a change in resistance. The only characteristic that remains unchanged is the breakdown
torque. The following example illustrates the changes chat occur.

Fig. 9: Typical torque-speed curve of a 3-phase cage-rotor motor

11. Wound-rotor motor

BTI - Electrical & Electronics Division 126 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

We explained the basic difference between a squirrel-cage motor and a wound-rotor motor previously. Although a
wound-rotor motor costs more than a squirrel-cage motor, it offers the following advantages:
1. The locked-rotor current can be drastically reduced by inserting three external resistors in series
with the rotor. Nevertheless, the locked -rotor torque will still be as high as of a squirrel-cage
motor.
2. The speed can be varied by varying the external rotor resistors.
3. The motor is ideally suited to accelerate high-inertia loads, which require a long time to bring up to
speed.

Fig. 10 is a diagram of the circuit used to start a wound-rotor motor. The rotor windings are connected to three
Y-connected external resistors by means of a set of slip-rings and brushes. Under locked-rotor (LR) conditions,
The variable resistors are set to Their highest value. As the motor speeds up, the resistance is gradually reduced
until full-load speed is reached, whereupon the brushes are short-circuited. By properly selecting the resistance
values, we can produce a high accelerating torque with a stator current chat never exceeds twice full-load current.

Fig. 10: External resistors connected to the three slip-rings


of a wound-rotor induction motor.

We can also regulate the speed of a wound-rotor motor by varying the resistance of the rheostat. As we
increase the resistance, the speed will drop. This method of speed control has the disadvantage that a
lot of heat is dissipated in the resistors; the efficiency is therefore low. Furthermore, for a given
rheostat setting, the speed varies considerably if the mechanical load varies.

12. Equivalent Circuit of the Induction Motor

Studying of the principle of operation and characteristics of the three-phase have shown that we can
describe the important properties of squirrel-cage and wound-rotor induction motors without using a
circuit diagram. However, if we want to gain even a better understanding of the properties of the
motor, an equivalent circuit diagram is absolutely essentially. In this part we develop the equivalent
circuit from basic principles. We then analyze the characteristics of a low-power and high-power
motor and observe their basic differences.
Finally, we develop the equivalent circuit of an asynchronous generator and determine its properties
under load.

12.1 The wound-rotor Induction Motor

BTI - Electrical & Electronics Division 127 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

A 3-phase wound-rotor induction motor is very similar in construction to a 3-phase transformer. Thus,
the motor has 3 identical primary windings and 3 identical secondary windings one set for each phase.
On account of the perfect symmetry, we can consider a single primary winding and a single secondary
winding in analyzing the behavior of the motor.

When the motor is at standstill, it acts exactly like a conventional transformer, and so its equivalent
circuit (Fig. 14) is the same as a transformer equivalent circuit.

We assume a wye connection for the stator and the rotor, and a turns ratio of 1:1. The circuit para-
meters, per phase, are identified as follows:

Eg = source voltage, line to neutral


r1 = stator winding resistance
r2 = rotor winding resistance
x1 = stator leakage reactance
x2 = rotor leakage reactance
Rx = external resistance, effectively connected between one slip-ring and the neutral of the
rotor
Xm = magnetizing reactance
Rm = resistance corresponding to the iron losses and windage and friction losses
T = ideal transformer having a turns ratio of 1:1

Fig.
r1 jX1 jX2 r2 I 2
I1 1 3 14:

Ip Io
T
Eg RX
jX Rm 1:1
m

2 4

Equivalent circuit of a wound-rotor induction motor at standstill

In the case of a conventional 3-phase transformer, we would be justified in removing the magnetizing
branch composed of jXm and Rm because the exciting current Io is negligible compared to the load
current Ip. However, in a motor this is no longer true: Io may be as high as 40 percent of Ip because of
the air gap. Consequently, we cannot eliminate the magnetizing branch. However, for motors
exceeding 2 hp. we can shift it to the input terminals, as shown in Fig. 15.

Ip r1 jX1 I1 jX2 r2 I 2


1 3

T
Eg E1 E2=E1 RX
jX Rm 1:1
m

2 4

Fig. 15: Approximation of the equivalent circuit is acceptable for motors above 5 hp.

BTI - Electrical & Electronics Division 128 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

Suppose the motor runs at a slip s, meaning that the rotor speed is NS (1 - s), where NS is the syn-
chronous speed. This will modify the values of E1, I1 and E2, I2 on the primary and secondary side of
the ideal transformer T. Furthermore, the frequency in the secondary winding will become sf where f
is the frequency of the source Eg. Fig. 16 shows these new operating conditions.

Directing our attention to the secondary side, the amplitude of the induced voltage E2 would be equal
to E1 (the turns ratio is 1:1) if the motor were stationary. But because the slip is s, the actual voltage
induced is
E 2 = s E1

The frequency is sf and this changes the impedance of the secondary leakage reactance from jx2 to
jsX2. Because resistors are not frequency-sensitive, the values of r2 and Rx remain the same. Let us
lump the two together to form a single secondary resistance R2, given by;

R2 = r2 + Rx

r1 jX1 jsX2 r2 I2


Ip I1 1 3

Stator T Rotor
Eg resistance E1 E2=E1 RX
resistance External
jX Rm N1=N2
m
resistance

2 4

Frequency = sf

F
Fig.
16:

re
q
u
BTI - Electrical & Electronics Division 129 Elbaz Bader Ayad
YOSRY IDREES
e
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

Equivalent circuit of a wound-rotor motor when it is running at a slip s. The frequency of the voltages
and currents in the stator is f . But the frequency of the voltages and current in the rotor is sf
The details of the secondary circuit are shown in Fig. 4-a, and the resulting current I2 is:

n
I2 = sE1 / (R2 + jsx2 ) = sE1 - / [ (R2 )2 + (sX2)2]
where:
 = arctan sX2 / R2

The corresponding phasor diagram is shown in Fig. 17-b.

c
sE1
jsX2
3

I2

E2=sE1 R2 Total resistance

of rotor circuit
frequency = sf

4 Frequency = sf I2

y
(a) (b)

Fig. 17- a) Equivalent circuit of the rotor; E2 and I2 have a frequency sf


b) Phasor diagram showing the current lagging behind the voltage by angle .
It is important to realize that this phasor diagram relates to the frequency sf. Consequently, it cannot be
integrated into the phasor diagram on the primary side, where the frequency is f. Nevertheless, there is
a direct relationship between I2 (frequency sf) in the rotor and I1 (frequency f) in the stator. In effect,
the absolute value of I1 is exactly the same as that of I2 . Furthermore, the phase angle ,  between E1

=
and I1 is exactly the same as that between E2 and I2. This enables us to draw the phasor diagram for E1
and I1 as shown in Fig. 18.
E1

frequency = f

f
I1 absolute = sE1/ (R2)2 + (sx2)2
I1
 = arctan sx2/R2

Fig. 18: The voltage and current in the stator are separated by the same phase angle 
even though the frequency different.

To summarize:
1. The effective value of I1 is equal to the effective value of I2, even though their frequencies are
different.

2. The effective value of E1 is equal to the effective value of E2 divided by the slip s.

3. The phase angle between E1 and I1 is the same as that between E2 and I2.

Thus, on the primary side we can write:

BTI - Electrical & Electronics Division 130 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

I1 = I2 = sE1 / (R2 + jsx2 ) = E1 / [(R2 /s) + jx2] = E1 / Z2

The impedance Z2 seen between the primary terminals 1, 2 of the ideal transformer is, therefore,
Z2 = E1 / I1 = (R2 / s) + jx2
As a result, we can simplify the circuit of Fig. 16 to that shown in Fig. 19. The leakage reactances jx1,
jx2 can now be lumped together to create a single total leakage reactance jx. It is equal to the total
leakage reactance of the motor referred to the stator side.
r1 jX1 jX2
Ip 1

Io I1
Eg R2/s
jX Rm
m

Fig. 19: Equivalent circuit of a wound-rotor motor referred


to the primary (stator) side.

The final equivalent circuit of the wound-rotor induction motor is shown in Fig. 20. In this diagram,
the circuit elements are fixed, except for the resistance R2 /s. Its value depends upon the slip and hence
upon the speed of the motor. Thus, the value of R2 /s will vary from R2 to infinity as the motor goes
from start-up (s = 1) to synchronous speed (s = 0).

This equivalent circuit of a wound-rotor induction motor is so similar to that of a transformer that it is
not surprising that the wound-rotor induction motor is sometimes called a rotary transformer.
The equivalent circuit of a squirrel-cage induction motor is the same, except that R2 is then equal to
the equivalent resistance r2 of the rotor alone referred to the stator, there being no external resistor.

r1 jX
Ip Pr
Io I1
Eg R2/s
jX Rm
m

Im 
If

Fig. 20: The primary and secondary leakage reactances x1 and x2 are combined
to form an equivalent total leakage reactance x.

12.2 Power relationships


The equivalent circuit enables us to arrive at some basic electromechanical power relationships for the
3-phase induction motor. The following equations can be deduced by visual inspection of the equiva-
lent circuit of the wound-rotor motor (Fig. 20):

1. Active power absorbed by the motor is: P = [(E g) 2 / Rm ] + [(I1)2 r1 ] + [(I1)2 (R2 /s)]
2. Reactive power absorbed by the motor is: Q = [(Eg)2 / xm ] + [(I1)2 x]
3. Apparent power absorbed by the motor is: S =  P2 + Q2
4. Power factor of the motor is: cos  = P / S
5. Line current is: Ip = S / Eg
6. Active power supplied to the rotor is: Pr = (I1)2 (R2 / s)
7. Power dissipated as I2 R losses in the rotor circuit is: Pjr = (I1)2 R2 = sPr

BTI - Electrical & Electronics Division 131 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

8. Mechanical power developed by the motor is: Pm = Pr - Pjr = Pr (1 - s)


9. Torque developed by the motor is:
T = 9.55 Pm / N = [9.55 Pr (1 -s)] / Ns ( 1 - s) = 9.55 Pr / Ns
10. Efficiency of the motor is:  = Pm / P

13. Starting Method For Cage-Rotor Machines :

13.1 Direct On-line Starting :


Induction motors when direct-switched by this method of starting, the three-phase supply is supplied
at full voltage to the stator windings employing a circuit breaker or contactor.

The motors starting current is large being typically between five and seven times the normal full load
value. Such large currents can cause problems of volt drop in supply lines and affect other electrical
equipment connected to the same areas of the system .

Direct on-line starting method is acceptable for example a small motor of rating to 20 KW in a factory
which is fed from its own, probably large, supply transformer.

When the motor is direct-switched onto normal voltage, then the slip is 100%, the rotor induced
voltage is maximum voltage, the starting current is the short-circuit current I sc and the starting torque
Tst is about 1.5 to 2.5 times their full-load torque Tf.
Therefore:
Tst / Tf = (Ist / If)2  S = a2  S
Where:
S = Full-load motor slip

a = (Ist/If)
Suppose in a case, Ist = 6.If , S = 5% then:
Tst / Tf = 62  0.05 = 1.8

Therefore Starting torque Tst = 1.8  full-load current


Hence, we find that with a current as great as six times the full current, the motor develops a staring
torque which in only 1.8 times the full-load value.

13.2 Star- Delta Starting :

The motor windings must be such that all six coil ends are available for connection.
The motor is started with the windings in a star connection effectively connecting two coils in series
between the supply line voltages. This results in a reduced voltage across each winding of V L/3.
Since the torque proportional to the square of the voltage, the torque developed becomes 1/3 of that
which would have been developed if motor were directly connected in delta and consequently a
reduced current to 1/3 .

Tst / Tf = (Ist/ If)2  S = (Ist/  3)2  S = 1/3 (Ist/If)  S = 1/3 a2  S

This method is cheap and effective provided the starting torque is required not to be more than 1.5
times the full-load torque.

Fig. 27 shows, at the beginning the main contactor and the star contactor are closed which provides a
star point.
When the rotor speed is approximately full speed, star contactor will open and delta contactor will
close which joins stator windings, so creating the delta connection.

BTI - Electrical & Electronics Division 132 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

L1
L2
L3

Fuses

Contactors

Main Delta Star

Overload Relay

U V W

3-
Motor

Z X Y

Fig. 27: Power Circuit Diagram

Class work:

A 3-phase,6-pole,50HZ induction motor takes 60A at full-load speed of 960 rpm, and develops a
torque of 15 N.m. The staring current at rated voltage is 300A. What is the starting torque?. If a
star/delta starter is used, determine the starting torque and starting current.

13.3 Auto-transformer Starting :

The supply to the motor is applied via a star-connected auto-transformer which a voltage tapping.

BTI - Electrical & Electronics Division 133 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

On starting, the supply is taken from the tap connecting 50, 65 or 80 percent of the supply voltage to
the motor windings thus reducing the staring current.
When the rotor speed approaches to full speed, the full supply voltage is connected to the motor (See
Fig. 28 )

With this method of starting, the motor remains connected delta at all times while the reduction in
voltage is achieved by the use of the transformer. The power input to the motor is reduced in the same
proportion as is the starting torque.

This method is therefore only suitable for off load starting of induction motors

Ist = 5If

Stator

(a)
I1


Ist = 5If


V
V

Stator
Auto-Transformer

(b)

Fig. 28: a) the case when the motor is DOL


b) the case when the motor is connected to auto-transformer

13.4 static voltage controller


The speed of a 3-phase squirrel-cage induction motor can be varied by simply varying the
stator voltage. This method of speed control is particularly useful for a motor driving a blower
BTI - Electrical & Electronics Division 134 Elbaz Bader Ayad
YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

or centrifugal pump.
At rated voltage, the torque-speed characteristic of the motor is given by curve 1 of Fig.
29. If we apply half the rated voltage, we obtain curve 2. Because torque is proportional to
the square of the applied voltage, the torques in curve 2 are only 1/4 of the corresponding
torques in curve 1. For example, the breakdown torque drops from 184% to 46%. Similarly,
the torque at 60 percent speed drops from 175% to 43.75%.

Fig. 29: Torque speed carve


1) at rated voltage
2) at 50 % of rated voltage

The load torque varies nearly as the square of the speed. This typical characteristic, shown
by curve 3, is superimposed on the motor torque-speed curves. Thus, at rated voltage, the
intersection of curves 1 and 3 shows that the motor runs at 90 percent of synchronous
speed. On the other hand, at half rated voltage, the blower rotates at only 60 percent of
synchronous speed. By varying the voltage this way, we can control the speed.
The variable-voltage autotransformer shown in Fig. 28 can be replaced by three sets of
thyristors connected back-to-back, as shown in Fig. 30. The sets are called valves. To
produce rated voltage across the motor, the respective thyristors are fired with a delay 
equal to the phase angle lag that would exist if the motor were directly connected to the line.

Fig. 30: Variable-voltage speed control of cage-rotor


Induction motor
Fig. 31 shows the resulting current and line-to-neutral voltage for phase A. The valves in
phases B and C are triggered the same way, except for an additional delay of 120 and 240,
respectively.

BTI - Electrical & Electronics Division 135 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

Fig. 31:Wave shapes at rated voltage. Fig. 32:Wave shapes at 50% rated voltage

To reduce the voltage across the motor, the firing angle  is delayed still more. For example,
to obtain 50 percent rated voltage, all the pulses are delayed by about 100. The resulting
distorted voltage and current wave shape for phase A are pictured very approximately in
Fig. 32.

The distortion increases the losses in the motor compared to the autotransformer method.
Furthermore, the power factor is considerably lower because of the large phase angle lag .
Nevertheless, to a first approximation, the torque-speed characteristics shown in Fig. 29
still apply.

Due to the considerable I2R losses and lower power factor, this type of electronic speed
control is only feasible for motors rated below 20 hp. Small hoists are also suited to this type
of control, because they operate intermittently. Consequently, they can cool off during the idle
and light-load periods.

13.5 Self-commutated inverters for cage motors

The cage-rotor induction motor can be driven using a self-commutated inverter (also called
force commutated inverter). It operates quite differently from a line-commutated inverter.

First, it can generate its own frequency, determined by the frequency of the pulses applied to
the gates.

Second, it can either absorb or deliver reactive power. The reactive power generated or
absorbed depends upon the nature of the load and the switching action of the power
semiconductors. They may be IGBTs, power MOSFETs, GTOs, or ordinary thyristors.

In the latter case, the thyristors are arranged in a conventional 3-phase bridge circuit.
However, each thyristor is surrounded by an array of capacitors, inductors, diodes, and
auxiliary thyristors. The purpose of these auxiliary components is to force some power
thyristors to conduct when normally they would not, and to force other thyristors to stop con-
ducting before their “natural” time. It is precisely this forced switching action that enables
these converters to generate and absorb reactive power.

Because of the variety of the switching circuits used, we show the self-commutated inverter
as a simple 5-terminal device having two dc input terminals and three ac output terminals to
provide 3-phase power to the motor. The basic type of inverters: current-source inverters is
shown in Fig. 33.

BTI - Electrical & Electronics Division 136 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

Fig. 33: Current-fed frequency converter.

BTI - Electrical & Electronics Division 137 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

14. Tutorial Questions and Problems

14.1 Practical level:


1. Name the principal components of an induction motor.

2. Explain how a revolving field is set up in a 3-phase induction motor.

3. If we double the number of poles on the stator of an induction motor, will its synchronous speed
also double?

4. The rotor of an induction should never be locked while full voltage is being applied to the stator.
Explain.

5. Why does the rotor of an induction motor turn slower than the revolving field?

6. What happens to the rotor speed and rotor current when the mechanical load on an induction
motor increases?

7. Would you recommend using a 50 hp induction motor to drive a 10 hp load? Explain.

8. Give two advantages of a wound-rotor motor over a squirrel-cage motor.

9. Both the voltage and frequency induced in the rotor of an induction motor decrease as the rotor
speeds up. Explain.

10. A 3-phase, 20-pole induction motor is connected to a 600 V, 60 Hz source.


a. What is the synchronous speed? [360 rpm]
h If the voltage is reduced to 300 V, will the synchronous speed change?
c. How many groups are there, per phase? [20]

11. Make a drawing of the magnetic field created by a 3-phase, 12-pole induction motor.

12. How can we change the direction of rotation of a 3-phase induction motor?

14.2 Intermediate level:


13-a. Calculate the synchronous speed of a 3-phase, 12-pole induction motor that is excited by a 60 Hz
source. [600 rpm]
b. What is the nominal speed if the slip at full load is 6 percent? [564 rpm]

14. A 3-phase 6-pole induction motor is connected to a 60 Hz supply. The voltage induced in the
rotor bars is 4 V when the rotor is locked. If the motor turns in the same direction as the flux,
calculate the approximate voltage induced and its frequency:
a. At 300 r/min [3V, 45 Hz]
b. At 1000 r/min [0.67V, 10 Hz]
c. At 1500 r/min [1V, 15 Hz]

15. A 3-phase, 75 hp. 440 V induction motor has a full-load efficiency of 91 percent and a power
factor of 83 percent. Calculate the nominal current per phase. [97.2A]

16. An open-circuit voltage of 240 V appears across the slip-rings of a wound-rotor induction
motor when the rotor is locked. The stator has 6 poles and is excited by a 60 Hz source. If
the rotor is driven by a variable-speed dc motor, calculate the open-circuit voltage and
frequency across the slip-rings if the dc motor turns

BTI - Electrical & Electronics Division 138 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

a. At 600 r/min, in the same direction as the rotating field [120V,30Hz]


b. At 900 r/min, in the same direction as the rotating field [60V,15Hz]
c. At 3600 r/min, opposite to the rotating field [960V, 240Hz]

17. A large 3-phase, 4000 V, 60 Hz squirrel-cage induction motor draws a current of 385 A and a total
active power of 2344 kW when operating at full-load. The corresponding speed is accurately
measured and is found to be 709.2 r/min. The stator is connected in wye and the resistance
between two stator terminals is 0.10 . The total iron losses are 23.4 kW and the windage and
friction losses are 12 kW.
Calculate the following:
a. The power factor at full-load [0.879]
b. The active power supplied to the rotor [2298Kw]
e. The total I2R losses in the rotor [24.5Kw]
d. The load mechanical power [kW], torque [kN m], and efficiency [%]
[2251Kw, 30.3KNm, 96%]

18. If we slightly increase the rotor resistance of an induction motor, what effect does this have
(increase or decrease) upon
a. Starting torque
b. Starting current
c. Full- load speed
d. Efficiency
e. Power factor
f. Temperature rise of the motor at its rated power output

14.3 Advanced level:


19. A 3-phase, 5000 hp. 6000 V, 60 Hz 12 poles wound-rotor induction motor turns at 594 r/min.
The motor has the following characteristics:
a) dc resistance between stator terminals = 0.112  at 17°C
2. dc resistance between rotor slip-rings = 0.0073 
3. open-circuit voltage induced between slip rings with rotor locked = 1600 V
4. Iine – to- line stator voltage = 6000 V
5. no-load stator current, per phase = 100 A
6. active power supplied to motor at no-load = 91 kW
7. windage and friction losses = 51 kW
8. iron losses in the stator = 39 kW
9. Locked-rotor current at 6000 V = 1800 A
10. active power to stator with rotor locked = 2207 kW

Calculate:
a) Rotor and stator resistance per phase at 75°C (assume a wye connection)
[4.49m, 66.9m]
b) Voltage and frequency induced in the rotor when it turns at 200 r/min and at
594 r/min [1067V, 40Hz, 16V, 0.6Hz]
c. Reactive power absorbed by the motor to create the revolving field, at no-load
[1035 KVAr]
d. I2R losses in the stator when the motor runs at no-load (winding temperature 75°C)
[2.07 Kw]
e. Active power supplied to the rotor at no-load [50Kw]
20. Referring to the motor described in Problem (19) above, calculate under full voltage LR
(locked-rotor) conditions:
a. Reactive power absorbed by the motor [18.6 MVAr]
b. I2R losses in the stator [670 Kw]
c. Active power supplied to the rotor [1498 Kw]

BTI - Electrical & Electronics Division 139 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Three Phase Induction Motors

d. Mechanical power output [ zero ]


e. Torque developed by the rotor [23.8 KNm]

21. We wish to control the speed of the motor given in Problem (19) by inserting resistance in
series with the rotor (see Fig. 10). If the motor has to develop a torque of 20 kN.m at a speed
of 450 r/min, calculate the following:
a. Voltage between the slip rings [400 V]
b. Rotor resistance (per phase) and the total power dissipated [508 m, 314 Kw]
c. Approximate rotor current, per phase [455 A]

23. A 3-phase, 300 kW, 2300 V, 60 Hz,1780 r/min induction motor is used to drive a compressor.
The motor has a full-load efficiency and power factor of 92% and 86%, respectively. If the
terminal voltage rises to 2760 V while the motor operates at full-load, determine the effect
(increase or decrease) upon
a. Mechanical power delivered by the motor
b. Motor torque
c. Rotational speed
d. Full-load current
e. Power factor and efficiency
f. Starting torque
g. Starting current
h. Breakdown torque
i. Motor temperature rise
j. Flux per pole
k. Exciting current
l. Iron losses

BTI - Electrical & Electronics Division 140 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Energy Management and tariffs

BTI - Electrical & Electronics Division 141 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Experiment 1
Transformer Polarity

OBJECTIVES
• To determine the polarity of transformer windings.

• To learn how to connect transformer windings in series aiding.

• To learn how to connect transformer windings in series opposing.

DISCUSSION

When the primary winding of a transformer is energized by an ac source, an alternating magnetic flux is
established in the transformer core. This alternating flux links the turn of each winding on the transformer,
thereby inducing ac voltages in them. Consider the circuit shown in Figure 1.

Figure 1

By definition an ac voltage is continually changing its magnitude and its polarity, therefore, the voltage across
the primary winding (terminals 1 and 2) keeps changing the polarity of terminal 1 with respect to terminal 2.
Terminals 1 and 2 can never have the same polarity. Terminal 1 must always be positive or negative with respect
to terminal 2. Thus, the alternating magnetic flux induces voltages in all of the other windings causing an ac
voltage to be produced across each pair of terminals. The terminals of each winding also change polarity with
respect to each other.

When we speak of "the polarity" of transformer windings we are identifying all of the terminals that are the same
polarity (positive or negative) at any instant of time. Polarity marks are employed to identify these terminals.
These marks may be black dots, crosses, numerals, letters or any other convenient means of showing which
terminals are of the same polarity. For example, in Figure 1, we have used black dots. These black dots, "polarity
marks", indicate that for a given instant in time,

1 is positive with respect to 2,


3 is positive with respect to 4,
6 is positive with respect to 5,
7 is positive with respect to 8,
10 is positive with respect to 9.
It should be noted that a terminal cannot be positive by itself. It can only be positive with respect to some other
terminal. Therefore, at any given instant of time, terminals 1, 3, 6, 7 and 10 are all positive with respect to
terminals 2, 4, 5, 8 and 9.

When batteries (or cells) are connected in series, to obtain a higher output voltage, the positive terminal of one
battery must be connected to the negative terminal of the other battery. Connected in this manner, their
individual voltages will add. Similarly, if transformer windings are to be connected in series, so that their

BTI - Electrical & Electronics Division 142 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

individual voltages add, the "polarity mark" terminal of one winding must connect to the "unmarked" terminal of
the other winding.

INSTRUMENTS AND COMPONENTS

DESCRIPTION MODEL

Single-Phase Transformer 8341


DC Voltmeter/Ammeter 8412
AC Voltmeter 8426
Power Supply 8821
Connection Leads 8941

PROCEDURE
Warning: High voltages are present in this Laboratory Experiment! Do not
make any connections with the power on! The power should be turned off
after completing each individual measurement!

1. a) Connect the 0-40 V meter of the DC Voltmeter/Ammeter across the variable dc output of your Power
Supply, terminals 7 and N.

b) Turn on the Power Supply and slowly adjust the voltage to 20 V dc.

c) Without touching the voltage control knob, turn off the Power Supply and disconnect your DC
Voltmeter/Ammeter.

d) Using the Single-Phase Transformer, Power Supply and DC Voltmeter/Ammeter, connect the circuit shown
in Figure 2. Note that the 40 V dc meter is connected across terminals 3 and 4.

Figure 2

e) Note the deflection of the DC Voltmeter/Ammeter upon turning on the Power Supply switch. If the
Voltmeter pointer momentarily deflects to the right, then terminals 1 and 3 have the same polarity mark.
(Terminal 1 is connected to the positive side of the dc supply and terminal 3 is connected to the positive
side of the Voltmeter).

f) Which two terminals are positive in windings 1 , 2 and 3 , 4?

________________________________________________________________________

g) Disconnect the DC Voltmeter from winding 3 , 4 and connect it across winding 5 , 6. Repeat (e).

h) Which two terminals are positive in windings 1 , 2 or 5 , 6?

________________________________________________________________________

BTI - Electrical & Electronics Division 143 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

i) Return the voltage to zero and turn off the Power Supply.

2. In this Procedure step you will see the effect of connecting two windings of a transformer in series and the
importance of polarity.

a) Using your AC Voltmeter, connect the circuit shown in Figure 3. Note that terminals 1 , 5 are connected
together.

b) Turn on the Power Supply and adjust for exactly 208 V ac (one-half of the rated voltage of winding 3 , 4).

Figure 3

c) Measure and record the voltages across the following terminals:

E1 to 2 = ____________ Vac

E5 to 6 = ____________ Vac

E2 to 6 = ____________ Vac

d) Return the voltage to zero and turn off the Power Supply,

e) Remove the connection between terminals 1 and 5. Connect terminals 1 and 6 together and connect the
Voltmeter across terminals 2 and 5 as shown in Figure 4.

BTI - Electrical & Electronics Division 144 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Figure 4
f) Turn on the Power Supply and adjust for exactly 208 V ac

g) Measure and record the voltages across the following terminals:

E1 , 2 = ____________ Vac

E5 , 6 = ____________ Vac

E2 , 6 = ____________ Vac

h) Return the voltage to zero and turn off the Power Supply.

i) Explain why the voltage with the two windings in series is approximately zero in one case and nearly 240
V ac in the other.
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
___________________________

j) Which terminals have the same polarity?

________________________________________________________________________

3. a) Consider the circuit shown in Figure 5. Note that winding 3 , 4 is connected to a 208 V ac power source.
Do not connect the circuit at this time!

b) What would be the induced voltage


across winding 1to 2?
E12 = _____________ V ac

Figure 5

c) If winding 1 , 2 is connected in series with winding 3 , 4 what three possible output voltages can be
obtained?

E = ______________ Vac E = ____________ Vac E = _____________ Vac

d) Connect the circuit shown in Figure 5 and place the windings in series, joining terminals 1 and 3.

e) Turn on the Power Supply and adjust for 208 V ac. Measure and record the voltage between terminals 2
and 4.

E2 4 = —————— V ac

f) Return the voltage to zero and turn off the Power Supply.

g) Remove the connection between terminals 1 and 3 and join terminals 1 and 4.

h) Turn on the Power Supply and adjust for 208 V ac. Measure and record the voltage between terminals 2 to
3 and 1 to 2.

BTI - Electrical & Electronics Division 145 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

E23 = —————— V ac E12 = —————— V ac

i) Return the voltage to zero and turn off the Power Supply.

j) Do the results of (e) and (h) meet with your prediction in (c)?

Yes No

Explain
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
______________

k) Which terminals have the same polarity?

_____________________________________________________________________________________
_____________________________________________________________________________________
___________________________________________

TEST YOUR KNOWLEDGE

1. Assuming you have a 240 V ac power source and that all of the windings on your transformer module develop
their rated voltage, show in the spaces provided, how you would connect the windings to obtain the following
voltages.

a) 480V:

b) 176V:

c) 360V:

d) 186V:

BTI - Electrical & Electronics Division 146 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Experiment 2
Transformer Regulation

OBJECTIVES

• To study the voltage regulation of the transformer with varying loads.

• To study transformer regulation with inductive and capacitive loading.

DISCUSSION

The load on a large power transformer in a sub-station will vary from a very small value in the early hours of the
morning to a very high value during the heavy peaks of maximum industrial and commercial activity. The
transformer secondary voltage will vary somewhat with the load, and because motors and incandescent lamps
and heating devices are all quite sensitive to voltage changes, transformer regulation is of considerable
importance. The secondary voltage is also dependent upon whether the power factor of the load is leading,
lagging, or unity. Therefore, it should be known how the transformer will behave when it is loaded with a
capacitive, an
inductive, or a resistive load.
If a transformer were perfect (ideal) its windings would have no resistance. Furthermore, it would require no
reactive power (vars) to set up the magnetic field within it. Such a transformer would have perfect regulation
under all load conditions and the secondary voltage would remain absolutely constant. But, practical
transformers do have winding resistance and they do require reactive power to produce their magnetic fields. The
primary and secondary windings possess, therefore, an overall resistance R and an overall reactance X. The
equivalent circuit of a power
transformer having a turns ratio of 1 to 1, can be approximated by the circuit shown in Figure 1. The actual
transformer terminals are P1P2 on the primary side and S1S2 on the secondary.

Figure 1

In between these terminals we have shown the transformer as being composed of a perfect (ideal) transformer in
series with an impedance consisting of R and X, which represents its imperfections. It is clear that if the primary
voltage is held constant, then the secondary voltage will vary with loading because of R and X.
An interesting phenomenon occurs with a capacitive load. Partial resonance is set up between the capacitance
and the reactance X. Secondary voltage E; may actually tend to rise as the capacitive load value increases.

INSTRUMENTS AND COMPONENTS

DESCRIPTION MODEL

Variable Resistance 8311


Variable Inductance 8321
Variable Capacitance 8331
Single-Phase Transformer 8341

BTI - Electrical & Electronics Division 147 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

AC Ammeter 8425
AC Voltmeter 8426
Power Supply 8821
Connection Leads 8941

PROCEDURE

Warning: High voltages are present in this Laboratory Experiment! Do not make any connections with
the power on! The power should be turned off after completing each individual measurement!

Figure 2

1. Using your Single-Phase Transformer, Power Supply, Variable Resistance and AC Voltmeter and AC
Ammeter, connect the circuit shown in Figure 2

2. a) Place all of the Variable Resistance module switches in their open position for zero load current.

b) Turn on the Power Supply and adjust for exactly 240 V ac as indicated by Voltmeter E1.

c) Measure and record in Table 1 the input current l1, the output current I2, and the output voltage E2 .

d) Adjust the load resistance ZL to 4800 Ω. Make sure that the input voltage remains at exactly 240 V ac.
Measure and record I1 I2 and E2 .

e) Repeat (d) for each of the listed values in Table 1.

f) Return the voltage to zero and turn off the Power Supply.

ZL I2 E2 I1
Ω mA Vac mA

4800
2400
1600
1200
960
Table 1

3. a) Calculate the transformer regulation using the no-load and full-load output voltages from Table 1.

BTI - Electrical & Electronics Division 148 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

____________________________________________________________________

____________________________________________________________________

____________________________________________________________________

___________________________________________Regulation_______________%

b) Does the primary winding VA equal the secondary winding VA for every
value of load resistance in the Table?

Yes No
Explain ____________________________________________________________

____________________________________________________________________

____________________________________________________________________

4. a) Repeat Procedure step 2 using the Variable Inductance in place of the resistance load.

b) Record your measurements in Table 2.

ZL I2 E2 I1
Ω mA Vac mA

4800
2400
1600
1200
960
Table 2

5. a) Repeat Procedure step 2 using the Variable Capacitance in place of the resistance load.

b) Record your measurements in Table 3.

ZL I2 E2 I1
Ω mA Vac mA

4800
2400
1600
1200
960
Table 3

BTI - Electrical & Electronics Division 149 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

6. You will now plot a regulation curve of the output voltage E2 vs output current I2 regulation curve for each
type of transformer load.

a) Plot your recorded values of E2 (at each value of I2 listed in Table 3-1) on the graph of Figure 3.

b) Draw a smooth curve through your plotted points. Label this curve "resistive load".

c) Repeat (a) for the inductive (Table 2) and capacitive (Table 3) loads. Label these curves "inductive load"
and "capacitive load".

E2
240
230
220
210
200
190
50 100 150 200 I2 mA
Figure 3
TEST YOUR KNOWLEDGE

1.Explain why the output voltage increases when capacitance loading is used.
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________

2.A transformer has a very low impedance (small R and X)

a) What effect does this have on the regulation?


______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________

b) What effect does this have on short-circuit current?


______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________

3.Very large transformers are sometimes designed not to have optimum regulation properties in order for the
associated circuit breakers to be within reasonable size. Explain,
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________

4.Will transformer heating be approximately the same for resistive, inductive or capacitive loads of the same VA
rating?

Yes No
Explain _______________________________________________________________________
______________________________________________________________________________

BTI - Electrical & Electronics Division 150 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________

BTI - Electrical & Electronics Division 151 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Experiment 3
Transformers in Parallel

OBJECTIVES

• To learn how to connect transformers in parallel.

• To determine the efficiency of parallel-connected transformers.

DISCUSSION

Transformers may be connected in parallel to furnish load currents greater than the
rated current of each transformer. There are two precautions to be observed when
connecting transformers in parallel.

1 The windings to be paralleled must have identical output voltage ratings.

2 The windings to be paralleled must have identical polarities.

Very large short-circuit currents can be developed if these rules are not followed. In
fact, transformers, circuit breakers and associated circuitry can be severely dam-
aged, or may even explode, if these short-circuit currents are large enough.

The efficiency of any machine or electrical device is given by the ratio of output
power to input power. (Apparent power and reactive power are not used in calcula-
ting transformer efficiency). The equation for percent efficiency is:

efficiency = [ active power out / active power in ] x 100%

INSTRUMENTS AND COMPONENTS

DESCRIPTION MODEL

Variable Resistance 8311


Single-Phase Transformer 8341
AC Ammeter 8425
AC Voltmeter 8426
Single-Phase Wattmeter 8431
Power Supply 8821
Connection Leads 8941

PROCEDURE

Warning: High voltages are present in this Laboratory Experiment! Do not make any connections with the power
on! The power should be turned off after completing each individual measurement!

1. Using your Single-Phase Transformer, Power Supply, Variable Resistance, AC Voltmeter and AC
Ammeter, connect the circuit shown in Figure5-1. Note that the two transformers are connected in
parallel. The primary windings (1 to 2) are connected together to the 240 V ac power source. The
wattmeter will indicate the input power. Each secondary winding (3 to 4) is connected in parallel to the
load RL. Ammeters are inserted to measure load current IL and transformer secondary currents I1 and I2

BTI - Electrical & Electronics Division 152 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Figure 1

2. Place all the resistance switches in their open positions for zero load current. Note that the windings are
connected for voltage step-up operation (240 V primary to 415 V secondary).

3. Have your circuit wiring approved by the instructor before proceeding.

4. a) Turn on the Power Supply and slowly turn the voltage output control knob while observing the transformer
secondary current meters l1 and I2 and the load current meter IL. If the windings are properly phased, no
load or secondary currents should be flowing.

b) Adjust the Power Supply voltage to 240 V ac as indicated by the voltmeter connected across the wattmeter.

5. a) Gradually increase the load RL until the load current IL equals approximately 250 mA. Check to see that the
input voltage is exactly 240 V ac.

b) Measure and record the load voltage, load current, transformer secondary currents and the input power.

EL = ___________ V ac

IL = ____________ A ac

li = ____________ A ac

Iz = ____________ A ac

Pin = ____________ W

c) Return the voltage to zero and turn off the Power Supply.

6. a) Calculate the load power.

EL_________________ x IL_________________ = _________W

b) Calculate the circuit efficiency.

Pout____________ / Pin____________ X 100 = _________ %

c) Calculate the transformer losses.

Pin ____________ _ Pout _______________ = _________ w

BTI - Electrical & Electronics Division 153 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

d) Calculate the power delivered by transformer 1.

I1________________ x EL ________________ = ___________ W

e) Calculate the power delivered by transformer 2.


I2 ________________ x EL ________________ = ___________ W

7. Is the load reasonably distributed between the two transformers?

Yes No

Explain

TEST YOUR KNOWLEDGE

1 . Show how you would parallel connect the transformers to the source and the load in Figure 5-2. Windings 1
to 2 and 3 to 4 are rated for 1,1 kV ac and windings 5 to 6 and 7 to 8 are rated for 415 V ac.

Figure 5-2

2. The efficiency of a transformer which supplies a pure capacitive load is zero.


Explain.

3. Name the losses which cause a transformer to heat up.

4. How does the efficiency of your Single-Phase Transformer compare to the efficiency of your DC Motor?
Explain

BTI - Electrical & Electronics Division 154 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Experiment 4
Distribution Transformer

OBJECTIVE
• To understand the standard distribution transformer with a 240/415 V secondary winding.

DISCUSSION
Some distribution transformers which supply homes and stores with power have one primary high voltage
winding. The secondary winding furnishes 240 V for lighting and the operation of small appliances and also 415
V for electric stoves, water heaters, clothes dryers, etc. The secondary may be a centre tapped single-winding or
two separate windings connected in series.

This Laboratory Experiment will show how such a transformer reacts under various load conditions.

INSTRUMENTS AND COMPONENTS

DESCRIPTION MODEL

Variable Resistance 8311


Variable Inductance 8321
Single-Phase Transformer 8341
AC Amrneter 8425
AC Voltmeter 8426
Power Supply 8821
Connection Leads 8941

PROCEDURE
Warning: High voltages are present in this Laboratory Experiment! Do not make any connections with
the power on! The power should be turned off after completing each individual measurement!

1. Using your Single-Phase Transformer, Variable Resistance, Power Supply, AC Voltmeter, and AC Ammeter,
connect the circuit shown in Figure 1. Note that the primary winding (3 , 4) is connected to the 0-415 V ac
output of the Power Supply, terminals 4 and 5. The transformer secondary windings 1 , 2 and 5 , 6 are
connected in series to obtain 480 V ac between points A and B. R1 and R2 are two Variable Resistance
modules.

2. a) Place all of the Variable Resistance module switches in their open positions.

b) Turn on the Power Supply and adjust for 415 V ac as indicated by the Power Supply voltmeter.

c) Measure and record in Table 1 the transformer total output voltage ET, the voltages across each of the loads
E1 and E2, the line currents l1 and I2, and the current in the neutral line IN.

BTI - Electrical & Electronics Division 155 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Figure 1
3. a) Place 1200 Ω in each load circuit by closing the appropriate switches.

b) Measure and record all quantities in Table 1.

c) Why is the neutral line current zero?

PROCEDURE
STEP R1 R2 I1 I2 IN E1 E2 ET
Ω Ω
2c ∞ ∞
3b 1200 1200
4b 1200 4800
5c 1200 4800
6c 1600 1600
Table 1
4. a) Place 4800 Ω in the R2 load while leaving 1200 Ω in load R1.

b) Measure and record all quantities.

c) Return the voltage to zero and turn off the Power Supply.

d) Is the neutral line current equal to the difference of the line currents?
Yes No

5. a) Disconnect the neutral line from the transformer by removing the connection between the transformer and
the neutral current meter IN.

b) Turn on the Power Supply and adjust for 415 V ac as indicated by the Power Supply voltmeter.

c) Measure and record all quantities.

d) Return the voltage to zero and turn off the Power Supply.

e) If the load R1 and R2 were incandescent lamps in a home, what would be noticeable?
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________

6. a) Reconnect the neutral line from the transformer to the neutral current meter IN.

b) Replace the load R2 with the Variable Inductance.

c) Adjust R1 for a resistance of 1600 Ω.

d) Adjust R2 for an inductive reactance Xi. of 1600 Ω.

e) Turn on the Power Supply and adjust for 415 V ac.

f) Measure and record all quantities.

g) Return the voltage to zero and turn off the Power Supply.

h) Is the current in the neutral line equal to the arithmetic difference of the line currents?

Yes No

Explain ____________________________________________________________________________

BTI - Electrical & Electronics Division 156 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

_______________________________________________________________________________
_______________________________________________________________________________
TEST YOUR KNOWLEDGE

1. A home is equipped with a 240/415 V ac power system and the following electri-
cal loads are in operation:

Line 1 to Neutral

7 ea lamps 60 W
1 ea lamp 100W
1 ea motor (2,5 A ac)

Line 2 to Neutral

1 ea television 200 W
1 ea toaster 1200 W
4 ea lamps 40 W

Line 1 to Line 2

1 ea dryer 2 kW
1 ea stove 1 kW

a) Calculate the currents in Line 1, Line 2 and the Neutral (assume a 100 %
power factor for all appliances).
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________

Line 1 = _____ A ac
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________

Line 2 = ______ A ac
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________

Neutral = ______ A ac

b) If the neutral wire opened, which lamps would get brighter and which ones
would get dimmer?

2. A 2400 V to 240/415 V distribution transformer has a capacity of 60 kVA.


a) What is the rated secondary (415 V) line current?

_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________

b) If the load is all placed on one side (line to neutral, 240 V) what is the maxi-
mum load that the transformer will carry without overheating?

BTI - Electrical & Electronics Division 157 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________

BTI - Electrical & Electronics Division 158 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Experiment 5
Prime Mover and Torque Measurement

OBJECTIVES

• To learn how to connect a split-phase induction motor.

• To learn how to connect the Electrodynamometer.

• To learn how to use the Prony Brake.

DISCUSSION

The split-phase induction motor is the simplest alternating current single-phase motor. It is the least expensive
type, and for that reason, the most frequently used. Its speed varies very little from no load to full load.

Even though the study of the split-phase motor is not the main object of this Laboratory Experiment, you will
learn how to connect this motor as a driver for the Electrodynamometer and the Prony Brake. The complete
study of its characteristics will be taken up in later Laboratory Experiments.

You will note that the motor is started with two windings and that one of them, the auxiliary (starting) winding,
is disconnected from the supply by a centrifugal switch when the motor has reached approximately 75% of its
normal running speed. You will also note that when a split-phase induction motor is severely overloaded, its
speed decreases rapidly until the centrifugal switch closes again and reenergizes the auxiliary winding. When
such a condition occurs, the motor should be disconnected immediately from the power source in order to
prevent it from burning.

The load imposed on a motor can be measured by two different means; these two torque measuring devices are
the Prony Brake and the Electrodynamometer. The Prony Brake is an entirely passive device (no electrical power
is required) while the Electrodynamometer requires external power.

The Prony Brake is a friction brake which is used to act as a load for any type of motor and to measure the
torque developed by these motors. This brake is entirely mechanical, and consist of a spring balance mounted in
a standard full size module. It is built to accurately measure the torque developed by any rotating machine placed
on its left-hand side.

A self-cooling friction wheel is slipped over the shaft of the machine under test, and attached to its output pulley
by means of two screws. The friction belt of the Prony Brake is then removed from inside the module and
slipped over the friction wheel. The braking torque applied to the machine can be varied by turning the knurled
wheel (LOAD) in the upper left corner of the module. A second knurled wheel (TORQUE PRESET) in the upper
centre allows to bring the spring balance back into equilibrium by aligning the red line in the right-hand window
(ZERO) with the black
line; the torque can then be read directly on the 0-3,3 N-m, 360° circular scale, in steps of 0,1 N-m.
The accuracy is better than 2% and the torque is continuously adjustable over the full range from no load to
locked rotor. When one wants to apply a known torque to the machine, the TORQUE PRESET wheel must first
be set so that the calibrated circular scale reads exactly the desired torque value and the LOAD wheel must then
be turned in such a way that the red line in the ZERO window is aligned with the black line.

The Electrodynamometer is a device used to accurately measure the torque developed by motors of all kinds. It
is actually an electrical brake in which the braking force can be varied electrically rather than by mechanical
friction. The Electrodynamometer is a more stable, easier to adjust, device than the mechanical friction brakes.

The Electrodynamometer consists of a stator and a squirrel-cage rotor. The stator, unlike other electromechanical
devices, is free to turn, but its motion is restricted by a helical spring.

In normal operation, dc current is applied to the stator winding. This sets up a magnetic field which passes
through both the stator and the rotor. As the rotor turns (being belt-coupled to the driving motor), a voltage is
induced in the rotor bars, and the resulting eddy currents react with the magnetic field causing the stator to turn
in the same direction as the rotor.

BTI - Electrical & Electronics Division 159 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

The stator rotation is limited by the helical spring and the amount that it turns is marked off on a scale attached
to the external stator housing.

The Electrodynamometer is calibrated from -0,3 to 3 N-m which is more than adequate for the testing of 0,2 kW
motors even when they are tested at overload conditions.

The power output of a motor depends on its speed and the torque it develops, This relationship is given by the
following equation:

P = [ 2 π x N x T ] / 60
where

P = power output (W)


N = speed (r/min)
T = torque (N.m)

INSTRUMENTS AND COMPONENTS

DESCRIPTION MODEL

Capacitor-Start Motor 8251


AC Ammeter 8425
Power Supply 8821
Electrodynamometer 8911
or Prony Brake 8913
Hand Tachometer 8920
Connection Leads 8941
Timing Belt 8942

PROCEDURE

Warning: High voltages are present in this Laboratory Experiment! Do not


make any connections with the power on! The power should be turned off
after completing each individual measurement!

The Split-Phase Induction Motor

1. Examine the front panel of the Capacitor-Start Motor. (The entire Capacitor-Start Motor will be fully
described in a later Laboratory Experiment).

a) Note the two separate windings. The main winding is rated 2,5 A while the auxiliary winding is marked
"intermittent". A circuit breaker protecting the auxiliary winding will trip if the winding is left
connected to the input line (240 V) for longer than a few seconds.

b) Identify the centrifugal switch connected between terminals 6 and 7. The centrifugal switch should
always be connected in series with the auxiliary winding.

c) Note also the capacitor connected between terminals 4 and 5. The capacitor is not used in the split-phase
induction motor wiring; it will be used in the capacitor-start motor wiring.

2. Using the Power Supply, Capacitor-Start Motor and AC Ammeter, connect the circuit shown in Figure 1.

Terminals 1 and N on the Power Supply provide fixed single-phase 240 V power to the main winding in parallel
with the series connection of the centrifugal switch and the auxiliary winding. The capacitor connected between
terminals 4 and 5 is not used when this module is operated as a split-phase motor.

BTI - Electrical & Electronics Division 160 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Figure 1

a) Have your instructor check your completed circuit.

b) Turn on the Power Supply, The motor should start running immediately and you should hear the click of
the centrifugal switch as it opens.

c) c) Note the indication of the current meter.


I = _____________ A ac

d) d) Note whether the direction of rotation is clockwise or counter clockwise.


Rotation = ____________

e) e) Measure with your Hand Tachometer the speed of the motor without load.

Speed without load = __________ r/min

f) Turn off the Power Supply. You should hear the closing of the centrifugal switch as the motor slows
down and comes to a rest.

g) Disconnect the motor.

Note: If you are not using the Electrodynamometer in this experiment, proceed to Procedure 12.

3. a) Examine the construction of the Electrodynamometer.

b) Note the cradle construction for the Electrodynamometer housing. (This is also called turning mounting).

c) Note the helical spring at the rear of the machine. This spring has been accurately calibrated against the
graduations marked on the front of the housing.

d) Note the mechanical stops that limit the rotational travel of the stator housing.

e) Identify the stator winding attached to the inside of the housing. (This winding carries dc current).

f) Identify the two wire leads that carry dc current to the stator winding. (They enter the housing through
the centre of the helical spring).

g) Identify the bridge rectifier located at the rear of the module. (This bridge furnishes dc power for the
stator magnetic field).

BTI - Electrical & Electronics Division 161 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

h) Identify the variable autotransformer mounted on the front panel of the module. The braking effect of the
Electrodynamometer is controlled by the strength of the stator magnetic field, which is proportional to
the dc output of the bridge rectifier. The dc output is varied by the variable autotransformer.

i) Identify the two ac connections terminals mounted on the front panel of the module.

4. a) Connect the Electrodynamometer to the fixed ac output of the power source by connecting the two input
terminals of the Electrodynamometer to terminals 1 and N of the Power Supply.

DO NOT APPLY POWER AT THIS TIME!

b) Set the Electrodynamometer variable transformer control knob to its mid-position.

c) Lower the front panel of the module so that you may turn the pulley by hand.

5. a) Turn on the Power Supply.

b) Keeping one hand in your pocket, for safety reasons, carefully reach in and try to turn the pulley.

Warning: Caution is advised because there are several live terminals exposed
when the front panel is dropped.

Do you feel a drag when you turn the pulley?

Yes No
Does the stator housing tend to turn in the same direction as the pulley?

Yes No

6. a) Remove your hand from inside the module and advance the control knob, thereby increasing the magnetic
stator field.

b) Carefully reach in and turn the pulley. Did the drag increase?
Yes No

c) Repeat (a) but this time reduce the stator magnetic field.

d) Carefully reach in and turn the pulley. Did the drag increase?
Yes No

e) Turn off the Power Supply.

7. a) Couple the Capacitor-Start Motor to the Electrodynamometer with the Timing Belt.

b) Connect the motor as shown in Figure 7-1.

c) Connect the Electrodynamometer to terminals 1 and N of the Power Supply. (There should now be two
connection leads at these terminals of one to the Electrodynamometer).

d) Set the Electrodynamometer control knob at its full ccw position (to provide minimum starting load for
the motor).

8. Apply power and note if the motor revolves in a cw direction. If not, reverse its rotation by interchanging the
connections to one of the motor windings. (The Electrodynamometer torque can only be measured for cw
rotation).

9. Increase the load on the motor (the Electrodynamometer braking action) by varying the control knob on the
Electrodynamometer until the scale marked on the stator housing indicates 1 N-m. (The numeral 1 should be
directly beneath the red vertical line on the window beneath the pulley).

10. a) Measure and record the motor current with a 1 N-m load on the motor.

BTI - Electrical & Electronics Division 162 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

I = __________ A ac

b) Measure and record the motor speed with a 1 N-m load.


Speed with load = ______________ r/min

11. Gradually increase the load on the motor, by advancing the variable auto-transformer control knob on the
Electrodynamometer, until the motor stalls. Quickly note the maximum value measured by the
Electrodynamometer and immediately turn off the Power Supply.

"Break-down" torque = ____________ N-m

Prony Brake

Note: If you are not using a Prony Brake in this experiment, proceed to the TEST YOUR
KNOWLEDGE

12, a) Examine the construction of the Prony Brake.

b) Remove the friction wheel from inside the module and note the holes in the web of the pulley; they are
for cooling purposes. Slip the friction wheel over the shaft of the motor and secure it firmly to the motor
pulley by tightening the two screws in the grooves of the motor pulley.

c) Note the floating plate inside the module. In operation, this plate is pulled in one direction by the friction
belt and in the other direction by a spring which is connected to the fixed frame by means of a rack
gear. A pinion gear, driven by the rack, turns the front plastic disc which has a red line to read the
torque. The TORQUE PRESET wheel effectively increases the spring tension and so, the force which
tends to turn the floating plate.

d) The LOAD wheel effectively increases the tension on the friction belt,
and tends to turn the floating plate in the opposite direction.

e) Note the friction belt attached at one end to the floating plate and at the other end to the LOAD wheel
screw.

f) The complete system constitutes a spring balance.

13. a) Turn the LOAD wheel downwards to release the tension on the friction belt, and slip the belt over the
friction pulley mounted on the motor. Leave the belt loose.

b) Connect the motor as shown in Figure 7-1.

c) Turn on the Power Supply and note if the motor revolves in a cw direction. If not, reverse its rotation by
interchanging the connections to one of the motor windings. (The Prony Brake can only measure torque
for cw rotation).

d) Measure the motor current.

I = __________ A ac

e) Vary the TORQUE PRESET wheel until the circular scale indicates 1 N-m. This does not impose any
torque on the motor and the current should not change. You have just preset the balance to the indicated
torque.

f) Turn slowly the LOAD wheel upwards to tighten the belt over the friction pulley. Note the gradual
increase in the motor current. Keep turning the LOAD wheel until the hairlines in the right-hand
window are aligned. The balance is now in equilibrium and is imposing a torque of 1 N-m on the motor.

g) Measure and record the motor current with a 1 N-m load.

I = _______________ A ac

BTI - Electrical & Electronics Division 163 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

h) Measure and record the motor speed with a 1 N-m load.


Speed with load = ____________ r/min

14. a) Gradually increase the load on the motor by turning the LOAD wheel Then bring the balance into
equilibrium. Repeat successively these last two steps until the motor stalls. Immediately turn off the
Power Supply.

b) Record the value of the "break-down" torque as indicated by the calibrated dial.

"Break-down" torque = ____________ N-m

TEST YOUR KNOWLEDGE

1 How can your reverse the direction of rotation of a split-phase induction motor?
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
__________________________________________

2. Calculate the developed motor power P in Procedure 10 or 13 (h).


______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
__________________________________________

P = ____________W

3. Which torque measuring device is easier to use, the Electrodynamometer or the


Prony Brake?

______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
__________________________________________

4. Where is the power (heat) dissipated in the Electrodynamometer?

______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
__________________________________________

5. Where is the power (heat) dissipated in the Prony Brake?

______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
__________________________________________

BTI - Electrical & Electronics Division 164 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Experiment No. 6 The Wound-Rotor Induction Motor-part I

Objectives:

 To examine the construction of the three-phase wound-rotor induction


motor.
 To understand synchronous speed and slip in a three-phase induction
motor.
 To observe the effect of the revolving field and rotor speed on the voltage
induced in the rotor.

Discussing :

The wound rotor consists of a rotor core with three windings instead of
conducting bars of the squirrel cage rotor. In this case, currents are induced in
the windings just as they would be in short-circuited turns. However. the
advantage of using windings is that the wires can be brought out through slip
rings so that resistance, and therefore the current through the rotor windings,
can be controlled

The rotating stator field induces an alternating voltage in each winding of the
rotor. When the rotor is at a standstill, the frequency of the induced rotor
voltage is equal to that of the power source. If the rotor is now rotated by some
external means, in the same direction as the rotating stator field, the rate at
which the magnetic flux cuts the rotor windings will diminish. The induced
voltage and its frequency will drop.

When the rotor revolves at the same speed and in the same direction as the
rotating stator field, the induced voltage, as well as its frequency, will drop to
zero. (The rotor is now at synchronous speed).

Conversely, if the rotor is driven at synchronous speed, but in the opposite direction to the
rotating stator field, the induced voltage, as well as its frequency, will be twice what they
were when the rotor was at a standstill (although the rotor will be driven by an external
motor in this case), it should be noted that for a given rotor speed the induced voltage value
and its frequency will be the same even if the rotor were turning by itself.

Instruments And Components:

 DC Motor/Generator
 Three-phase Wound Rotor-Induction Motor
 AC Ammeter
 AC Voltmeter
 Three-Phase Wattmeter
 Power Supply
 Hand Tachometer
 Connection Leads
 Timing Belt
Procedure:
BTI - Electrical & Electronics Division 165 Elbaz Bader Ayad
YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Warning
High voltages are present in this laboratory Experiment! Do not make
any connections with power on! The power should be turned off after
completing each individual measurement!

1. Using your Power Supply Module, Three-Phase Wound-Rotor Induction


Motor, DC Motor/Generator, AC Voltmeter and Three-Phase Wattmeter,
connect the circuit in Fig. 1. The field rheostat should be turned to its full cw
position for minimum resistance.

Fig. 1
2. a) Couple the DC Motor/Generator and the Three-Phase Wound-Rotor
Induction Motor using the Timing Belt.

b) Make sure the variable output control knob is at zero. Turn on the
Power supply. The dc motor should not be turning.

c) Measure and record the following:

E1 = ------- Vac E2 = --------- V ac P = --------- W

I1 = -------- A ac I2 = ---------- Aac I3 = --------- Aac

d) Turn off the Power Supply.


3. a) Turn on the Power Supply and gradually adjust the variable dc output
voltage for a motor speed of 750 r/min.

BTI - Electrical & Electronics Division 166 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

If the value of E2 gets higher than in Procedure step 4, turn off the Power Supply
and interchange any two of the three stator leads.

b) Measure and record the following:

E1 = --------- V E2 = ----------- V P = ------------ W

I1 = --------- A I2 = ----------- A I3 = ---------- A

4. a) Increase the variable dc output voltage to 240 V and adjust the field
rheostat for a motor speed of exactly 1500 r/min.
b) Measure and record the following:

E1 = ------------ V E2 = --------- V P = -------- W

I1 = ----------- A I2 = ---------- A I3 = -------- A.

c) Return the voltage to zero and turn off the Power Supply.

5. a) Interchange your dc armature connections in order to reverse the motor


direction. Turn the field rheostat to its full cw position.

b) Turn on the Power Supply and adjust the dc output voltage for a motor
speed of 750 r/min.
c) Measure and record the following:

E1 = ------------ V E2 = ---------------- V

I1 = ------- A I2 = -------A and I3 = --------- A.

W1 = ---------------- W W2 = ------------- W

6. a) Increase the variable dc output voltage to 240 V dc and adjust the field
rheostat for a motor speed of 1500 r/min.
b) Measure and record the following:

E1 = --------- V E2 = --------------- V

I1 = --------- A I2 = -------- A and I3 = -------- A .

W1 = ------------ W W2 = ------------- W

c) Return the voltage to zero and turn off the Power Supply.

BTI - Electrical & Electronics Division 167 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

HND2 – Utilization of Electrical Energy


The Wound-Rotor Induction Motor Experiment 1
Testing Knowledge

Name: _______________________ No.: __________ Date: / /


Group:

1. Refer to procedure 2-c Calculate the following: [15-marks]

a) Apparent power S = ----------------------------------------- = -------- VA

b) Power factor Cos  = ---------------------------------------- = ---------

c) Reactive power Q = ------------------------------------ = --------- VA r

2. In Procedure steps 3 and 4, is the rotor being driven with or against the
rotating field? Explain? [10-marks]

------------------------------------------------------------------------------------------------------
-

3. In Procedures 5 and 6 is the rotor being turned with or against the


rotating stator field? Explain? [10-marks]

----------------------------------------------------------------------------------------------------

4. Knowing that the voltage induced in the rotor winding is zero when it is
turning at synchronous speed, what is the synchronous speed of your
motor? [5-marks]
----------------------------------------------------------------------------------------------------

-----------------------------------------------------------------------------------------------------

5. Determine the number of poles in your motor. [5-marks]

----------------------------------------------------------------------------------------------------
-

6. Calculate the rotor slip in Procedure steps 2, 3, 4, 5 and 6. [30-marks]

Step 2: -----------------------------------------------------------------------------------------

Step 3: ------------------------------------------------------------------------------------------

Step 4: ------------------------------------------------------------------------------------------

BTI - Electrical & Electronics Division 168 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

Step 5: ------------------------------------------------------------------------------------------

Step 6: ------------------------------------------------------------------------------------------

7. How much reactive power (Q) is needed to produce the magnetic field in your
motor? [5-marks]

----------------------------------------------------------------------------------------------------

8. How much active power (P) is needed to supply the losses associated with
the production of the magnetic field? [5-marks]

9. Plot the rotor speed against the rotor voltage on the graph paper below and
write your conclusion. [15-marks]

Conclusion:
--------------------------------------------------------------------------------

----------------------------------------------------------------------------------------------------
-

BTI - Electrical & Electronics Division 169 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

----------------------------------------------------------------------------------------------------

Experiment No. 8

The Wound-Rotor Induction Motor-part II

Objectives
• To observe the rotor and stator currents and the torque values at
different motor speeds.
• To determine the starting characteristics of the wound-rotor
induction motor.

Discussion

In the previous Laboratory Experiment we saw that a considerable voltage


appears across the rotor windings on open circuit, and that this voltage
varies linearly with rotor slip in r/min, becoming zero at synchronous
speed.
If the rotor windings are short-circuited, the induced voltage will cause large
circulating currents in the windings. To supply this rotor current, the stator
current must increase in value above its ordinary exciting current level.
The power consumed (VA) in the rotor windings (and associated circuitry)
must be supplied by the stator windings. Therefore, we should expect the
following:
a) At standstill, or at low speed, the rotor currents, stator currents,
and torque will be high.
b) At synchronous speed, the rotor current and torque will be zero,
and the stator will only carry the exciting current.
c) At any other motor speed, the currents will be between the above
extremes.

INSTRUMENTS AND COMPONENTS


Descriptions Model

 Three-Phase Wound-Rotor Induction Motor 8231


 AC Ammeter 8425
 AC Voltmeter 8426
 Electrodynamometer 8911
 Power Supply 8821
 Connection Leads 8941
 Timing Belt 8942

BTI - Electrical & Electronics Division 170 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

PROCEDURE

Caution:

High voltages are present in this Laboratory Experiment! Do not


make any connections with the power on! The power should be
turned off after completing each individual measurement

Fig. 1

1. Using your Power Supply, AC Ammeter, AC Voltmeter, and Electrody-


namometer, connect the circuit shown in Fig. 1. Note that the three stator
windings are connected to the variable 3-phase output of the Power
Supply (terminals 4, 5 and 6).

2. a) Couple the Electrodynamometer to the motor with the Timing Belt.

b) Connect the input terminals of the Electrodynamometer to


the fixed 240 V ac output of the Power Supply, terminals 1
and N.
c) Set the Electrodynamometer control knob at its full cw
position (to provide a maximum starting load for the motor).
3. a) Turn on the Power Supply and adjust E 1 at 208 V ac (50% of the rated

voltage). The motor should be turning slowly.

b) Measure and record the three rotor currents and the developed
torque.

I1 = -------- A ac I2 = ------A ac

BTI - Electrical & Electronics Division 171 Elbaz Bader Ayad


YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

I3 = -------- A ac Torque = -------- Nm


4. a) Gradually reduce the load on the motor by slowly adjusting
the Electrodynamometer control knob. As the load is
reduced the motor speed will increase.
b) Do the three rotor currents remain approximately equal?

Yes ------- OR No ------------

c) Do the three rotor currents decrease as the motor speeds up?

Yes -------- OR No --------

d) Measure and record the rotor currents at a torque of 0,2 Nm.


I 1 = _______ A ac I2 = _______ A ac, I3 = _______ A ac
e) Return the voltage to zero and turn off the Power Supply.

5. a) Connect the circuit shown in Fig. 2. Note that the fixed 3-


phase output of the Power Supply, terminals 1, 2 and 3
are now being used.

Fig. 2

b) Set the Electrodynamometer control knob at its full cw


position (to provide a maximum starting load for the
motor).

6. Turn on the Power Supply and quickly measure E 1 , I1, I2 and the
developed starting torque. Turn off the Power Supply.

I1= --------- Aac I2 = ---------- Aac

E1= -------- Vac Torque = --------- Nm


BTI - Electrical & Electronics Division 172 Elbaz Bader Ayad
YOSRY IDREES
BTEC - HND Year 2 - Utilization of Electrical Energy Experiments

HND2 – Utilization of Electrical Energy


The Wound-Rotor Induction Motor Experiment 2
Testing Knowledge

Name: _______________________ No.: __________ Date: / /


Group:

TEST YOUR KNOWLEDGE

1. Assuming the full load (175 W) motor speed is 1315 r/min,


calculate the value of the full load torque using the formula for
output power:

P = 2NT / 60 = ----------------------------------------------------------------------------
[8 marks]
2. Calculate the ratio of starting torque to full load torque:

--------------------------------------------------------------------------------------
[7 marks]

3. Assuming that the full load stator current is 0,48 A per phase,
calculate the ratio of starting current to full load operating current.
---------------------------------------------------------------------------------------
[7 marks]
4. In Procedure step 6 Calculate the apparent power (S) to the

motor at starting torque.


Apparent power (S) = -------------------------------------- = -------------- VA
[7 marks]

5. If the stator voltage of a wound rotor motor is reduced by


approximately 50% of the rated value:

a) By how much is the starting current reduced?

----------------------------------------------------------------------------------
[7 marks]

b) By how much is the apparent power reduced?

-----------------------------------------------------------------------------------
[7 marks]
c) By how much is the starting torque reduced?
-----------------------------------------------------------------------------------
[7 marks]

BTI - Electrical & Electronics Division 173 Elbaz Bader Ayad


YOSRY IDREES

Anda mungkin juga menyukai