C0-16TB).
PLC Data Format 13-bit unsigned Integer, range is 0-8191
Sample Duration Time 5 ms
Wiring Diagram CHn All Channel Update Rate 20 ms (input plus output maximum time)
*0.032A fast-acting fuse Connect the unused input
(ADC p/n S500-32-R) channel to 0V terminal.
is recommended. 0V Open Circuit Detection Time Zero reading within 20 ms
C0-4AD2DA-1 All ‘0
‘0V’ Conversion Method Successive approximation
2-wire + 0-20mA In terminals are
ter Accuracy vs. Temperature ±75 PPM/°C maximum
4-20mA –
4-20mA Out connected
con
Transmitter
* CH1 internally.
intern Maximum Inaccuracy 0.5% of range (including temperature
changes)
0V
2-wire + ±3 count maximum,
N.C. Linearity Error (End to End)
INPUT
are powered through the CPU’s expansion CPU Current Consumption (mA) C0-08CDR 80 0
ports.
Basic CPU Modules C0-04RTD 25 0
system.
C0-08ND3 30 0 C-more Micro 90 0
Volume 13
2 Analog
D2-BAT-1).
AD1V
Communication
TX2 AD1 I Inputs
I/O Modules
A variety of discrete, combo, and analog
I/O modules are available for the CLICK
PLC system. Up to eight I/O modules can
be connected to a CLICK Discrete Input Modules
CPU module to expand the
system I/O count and meet
the needs of a specific
application. Complete I/O
module specifications and
wiring diagrams can be
found later in this section.
Systems
Overview
(continued)
Field I/O
Discrete Output Modules
Software
C-more &
other HMI
Drives
Soft
Starters
Motors &
Gearbox
Steppers/
Servos
Motor
Controls
Proximity
C0-08TD1 C0-08TD2 C0-16TD1 C0-16TD2 C0-08TA C0-04TRS C0-08TR
Sensors
Discrete Output Modules
Photo
I/O Type/ Sink or Voltage/Current Sensors
Part Number Number/ Commons Source Ratings
Limit
C0-08TD1 DC/8/2 Sink 3.3-27 VDC, 0.3 A Switches
C0-08TD2 DC/8/1 Source 12-24 VDC, 0.3 A
C0-16TD1 DC/16/2 Sink 5-27 VDC, 0.1 A Encoders
Current
C0-16TD2 DC/16/2 Source 12-24 VDC, 0.1 A
C0-08TA AC/8/2 N/A 17-240 VAC, 0.3 A Sensors
6-27 VDC, 7 A
Pressure
C0-04TRS Relay/4/4 N/A
Sensors
6-240 VAC, 7 A
6-27 VDC, 1 A
C0-08TR Relay/8/2 N/A
Temperature
6-240 VAC, 1 A
Sensors
Discrete Combo I/O Modules
Pushbuttons/
Lights
PWR C0-16CDD1
24V 4mA
PWR C0-16CDD2
24V 4mA
PWR C0-08CDR Process
12-24V 2.5-5mA
Relays/
C1 C1
Timers
1 1
2 2
INPUT
INPUT
INPUT
3 3
4 4
5 5 Comm.
6 6
Terminal
7 7
Blocks &
8 8 C1
C2 1
Wiring
+V
1 1 2
OUTPUT
2 2 3
OUTPUT
OUTPUT
3 3 4
Power
4 4 C2
+V C2 1
5 5 2
Circuit
6 6 3
Protection
7 7 4
8 8 30V 1A
5-27V 0.1A 12-24V 0.1A 250V∼ 1A 50-60Hz
Tools
Discrete Combo I/O Modules
Pneumatics
Part Output Voltage /
Appendix
Input Type Input Voltage Output Type
Number Current Ratings
5-27 VDC / Product
Index
C0-16CDD1 8 DC (source/sink) 24 VDC 8 DC (sink) 0.1 A
12-24 VDC /
Part #
C0-16CDD2 8 DC (source/sink) 24 VDC 8 DC (source) 0.1 A
6.25-24 VDC, 1 A Index
C0-08CDR 4 DC (source/sink) 12-24 VDC 4 (relay) 6-240 VAC, 1 A
Volume 13
w w w. a u to m a t i o n d i re c t . c o m / c l i c k- p l c Programmable Controllers e1-33
Choosing the I/O Type
Analog I/O Modules
COM
R1+
R1–
INPUT
INPUT
INPUT
INPUT
R1C
COM
COM
R2+
R2–
R2C
CH1 CH1 COM COM
CH2 CH2 COM TC1+
CH3 CH3 R3+ TC1–
CH4 CH4 R3– TC2+
0V 0V R3C TC2–
0V 0V COM COM
0V 0V COM TC3+
0V 0V R4+ TC3–
0V 0V R4– TC4+
24V 24V R4C TC4–
0V 0V COM COM
C0-04DA-1 C0-04DA-2
4-20mA 0-10V
OUTPUT
OUTPUT
CH1 CH1
CH2 CH2
CH3 CH3
CH4 CH4
0V 0V
0V 0V
0V 0V
0V 0V
0V 0V
24V 24V
0V 0V
C0-04DA-1 C0-04DA-2
Volume 13
Systems
Overview
(continued)
Analog Combo I/O Modules Field I/O
Software
C-more &
C0-4AD2DA-1 C0-4AD2DA-2
0-20mA In 0-10V
other HMI
4-20mA Out
CH1 CH1
0V 0V
INPUT
Drives
INPUT
CH2 CH2
0V 0V
Soft
CH3 CH3
Starters
0V 0V
CH4 CH4
0V 0V
Motors &
Gearbox
CH1 CH1
0V 0V
OUTPUT
OUTPUT
Steppers/
CH2 CH2
Servos
0V 0V
24V 24V
0V 0V
Motor
Controls
C0-4AD2DA-1 C0-4AD2DA-2
Proximity
Sensors
Analog Combo I/O Modules
External Power Photo
Part Number Analog Input Type Analog Output Type Required Sensors
Limit
4 channel, current (0-20 mA), 2 channel, current sourcing
Switches
C0-4AD2DA-1 13 bit (4-20 mA), 12 bit 24 VDC
4 channel, voltage (0-10 V), 4 channel, voltage
Encoders
C0-4AD2DA-2 13 bit (0-10 V), 12 bit 24 VDC
Current
Sensors
Pressure
Sensors
Products
Power Input Voltage Range 20-28 VDC
Maximum Power Consumption 5 W (No 5 V use from communication port) Pushbuttons/
Lights
Maximum Inrush Current 30 A (less than 1ms)
application. Power
MIL STD 810C, Method 514.2, EC60068-2-6
Vibration JIS C60068-2-6 (Sine wave vibration test)
Shock
Circuit
MIL STD 810C, Method 516.2, IEC60068-2-27, JIS C60068-2-27
Comply with NEMA ICS3-304, Impulse noise 1µs, 1000V Protection
EN61000-4-2 (ESD), EN61000-4-3 (RFI), EN61000-4-4 (FTB)
Enclosures
Noise Immunity EN61000-4-5 (Surge), EN61000-4-6 (Conducted)
EN61000-4-8 (Power frequency magnetic field immunity)
RFI: No interference measured at 150 and 450 MHz (5w/15cm)
Emissions EN55011:1998 Class A Tools
Pneumatics
Agency Approvals UL508 (File No. E157382, E316037); CE (EN61131-2)
Other RoHS
Appendix
Product
Index
Part #
Index
Volume 13
w w w. a u to m a t i o n d i re c t . c o m / c l i c k- p l c Programmable Controllers e1-35
Wiring System for CLICK PLCs
Devices
When wanting to connect I/O to another device within close proximity of Using the I/O Modules to 3rd Party Devices selector tables
the I/O modules, no extra terminal blocks are necessary when using the located in the ZIPLink section,
ZIPLink Pigtail Cables. ZIPLink Pigtail Cables are prewired to an I/O
terminal block with color-coded pigtail with soldered-tip wires on the other
1. Locate your CPU or I/O module.
end.
2. Select a ZIPLink Pigtail Cable that is compatible
with your 3rd party device.
Volume 13
Systems
Overview
Programmable
Controllers
CLICK PLC CPU Module ZIPLink Selector CLICK PLC Combo I/O Module ZIPLink Selector
Field I/O
PLC ZIPLink I/O Module ZIPLink
CPU Module Part Cable Part Combo Module Part Cable Part Software
# of Terms Component # of Terms Component
Module No. No. Module No. No.
C-more &
other HMI
C0-00DD1-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20* C0-16CDD1 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*
C0-00DD2-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20* C0-16CDD2 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*
C0-00DR-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20* C0-08CDR 11 Feedthrough ZL-RTB20 ZL-C0-CBL11* Drives
Soft
C0-00AR-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*
C0-01DD1-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20* Starters
C0-01DD2-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20* CLICK PLC Analog I/O Module ZIPLink Selector
Motors &
Gearbox
C0-01DR-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20* I/O Module ZIPLink
C0-01AR-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20* Analog # of Module Part Cable Part
Steppers/
Component No.
Servos
C0-02DD1-D 20 Module Terms No.
C0-02DD2-D 20 No ZIPLinks are available for analog CPU modules. C0-04AD-1 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
C0-02DR-D 20 Motor
Controls
C0-04AD-2 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
C0-04RTD 20 No ZIPLinks are available for RTD and thermocouple
Proximity
C0-04THM 11 modules.
CLICK PLC Discrete Input Module ZIPLink Selector C0-04DA-1 11 Feedthrough ZL-RTB20 ZL-C0-CBL11* Sensors
I/O Module ZIPLink
Photo
C0-04DA-2 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
Input # of C0-4AD2DA-1 20 Feedthrough ZL-RTB20 ZL-C0-CBL20* Sensors
Component Module Part Cable Part
Module Terms No. No.
Limit
C0-4AD2DA-2 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*
C0-08ND3 11 Feedthrough ZL-RTB20 ZL-C0-CBL11* * Select the cable length by replacing the * with: Blank = 0.5m, -1 = 1.0m, Switches
C0-08ND3-1 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
Encoders
or -2 = 2.0m.
C0-08NE3 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
Current
C0-08NA 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
Feedthrough ZL-RTB20 ZL-C0-CBL20* Sensors
C0-16ND3 20
Pressure
Sensor ZL-LTB16-24 ZL-C0-CBL20*
Feedthrough ZL-RTB20 ZL-C0-CBL20* Sensors
C0-16NE3 20
Sensor ZL-LTB16-24 ZL-C0-CBL20*
Temperature
Sensors
Comm.
C0-08TD2 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
C0-08TR 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
C0-08TA 11 Feedthrough ZL-RTB20 ZL-C0-CBL11* Terminal
Blocks &
Wiring
Feedthrough ZL-RTB20 ZL-C0-CBL20*
C0-16TD1 20 Fuse ZL-RFU202 ZL-C0-CBL20*
Relay (sinking) ZL-RRL16-24-1 ZL-C0-CBL20* Power
Circuit
Feedthrough ZL-RTB20 ZL-C0-CBL20*
C0-16TD2 20 Fuse ZL-RFU202 ZL-C0-CBL20* Protection
Relay (sourcing) ZL-RRL16-24-2 ZL-C0-CBL20*
C0-04TRS1 20 Feedthrough ZL-RTB20 ZL-C0-CBL20* Enclosures
1 Note: The C0-04TRS relay output is derated not to exceed 2A per point maximum Tools
Pneumatics
when used with the ZIPLink wiring system.
2 Note: Fuses (5 x 20 mm) are not included. See Edison Electronic Fuse section for
(5 x 20 mm) fuse. S500 and GMA electronic circuit protection for fast-acting maxi- Appendix
mum protection. S506 and GMC electronic circuit protection for time-delay perfor-
mance. Ideal for inductive circuits. Product
To ensure proper operation, do not exceed the voltage and current rating of Index
ZIPLink module. ZL-RFU20 = 2A per circuit.
Part #
Index
Volume 13