Anda di halaman 1dari 3

KCJU.

R2556 - Glass Blocks Page 1 of 3

KCJU.R2556
Glass Blocks
Page Bottom

Glass Blocks

See General Information for Glass Blocks

PITTSBURGH CORNING CORP R2556


800 PRESQUE ISLE DR
PITTSBURGH, PA 15239 USA

Max Size Max Size


Nom In. In.
Block Size Masonry Drywall
Pattern (In.xin.xin.) Rating Hr Wall (Sq Ft) (Sq Ft)

*Vue® ***** 3/4 120** 94****

*Decora® ***** 3/4 120** 94****

*Argus® ***** 3/4 120** 94****

*Essex® ***** 3/4 120** 94****

*Essex AA® ***** 3/4 120** 94****

*Textra® ***** 3/4 120** 94****

*Cirrus® ***** 3/4 120** 94****

*Mistique® ***** 3/4 120** 94****

*Spyra® ***** 3/4 120** 94****

*IceScapes® ***** 3/4 120** 94****

*SeaScapes® ***** 3/4 120** 94****

*Focus® ***** 3/4 120** 94****

Vistabrik® 3x8x3 1-1/2 100*** —

Vistabrik® 4x8x3 1-1/2 100*** —

Vistabrik® 8x8x3 1-1/2 100*** —

Thickset®, 90 8x8x3-7/8 1-1/2 100*** —

Endura®

Thickset® 90 8x8x3-7/8 1-1/2 100*** —

Decora®

Thickset® 90 6x6x3-7/8 1-1/2 100*** —

Decora®

Thickset®, 90 8x8x3-7/8 1-1/2 100*** —

Vue®

Thickset®, 90 6x6x3-7/8 1-1/2 100*** —

Vue®

Vistabrik® 3x8x3 1 100*** 94****

Vistabrik® 4x8x3 1 100*** 94****

Vistabrik® 8x8x3 1 100*** 94****

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=KCJ... 2/2/12
KCJU.R2556 - Glass Blocks Page 2 of 3

Thickset®, 90 8x8x3-7/8 1 100*** 94****

Endura®

Thickset®, 90 8x8x3-7/8 1 100*** 94****

Vue®

Thickset®, 90 6x6x3-7/8 1 100*** 94****

Vue®

Thickset® 90 8x8x3-7/8 1 100*** 94****

Decora®

Thickset® 90 6x6x3-7/8 1 100*** 94****

Decora®

*Thickset® 60 8x8x3-7/8 1 100*** 94****

Decora®

*Thickset® 60 8x8x3-7/8 1 100*** 94****

Vue®

*Essex AA® 8x8x3-7/8 1 100*** 94****

*May have "LX" suffix.

**Max height and width 12 ft.

***Max height and width 10 ft.

****Max height and width 10 ft 9 in.

*****Block sizes: 8 in. x 8 in. x 3-7/8 in. or 3-1/8 in. or metric equivalent, 8 in. x 6 in. x 3-1/8 in. or 3-7/8 in., 6 in. x 6 in. x 3-1/8 in. or 3-7/8
in., 4 x 8 x 3-1/8 in. or 3-7/8 in., and 4 x 4 x 3-1/8 in. or 3-7/8 in., although all sizes may not be available in all patterns.

Vistabrik solid units may have "Stippled" pattern embossed on face of block. Hollow units may have a "Stipple" pattern, "Bevels" or Other design
embossed on the outer face of the block. Hollow units with a "Stipple", "Bevel" or other design may have the "Designer Select Bevel Series" name
associated with the pattern name.

Blocks are laid with 1/4 in. horizontal and vertical mortar joints; mortar consisting of one part portland cement, 1/2 part hydrated lime, and
screened sharp sand equal to 2-1/4 to 3 times the amount of cementitious material (cement plus lime), all measured by volume.

The horizontal rows of blocks shall be reinforced with Nos. 8 to 10 gauge galvanized wire mesh for the full length after the first and every other
row.

Glass or mineral wool or polyethylene shall be used to fill the remaining spaces in the lintel and jamb grooves to provide for expansion.

Exterior and interior jamb and lintel edges are to be caulked with a fire retardant type waterproofing mastic.

Sills for the blocks shall be coated with a water-based asphalt emulsion, to provide for waterproofing and movement.

Steel or masonry lintels/jambs for the blocks shall be provided with grooves/sufficiently deep to permit blocks to extend a min of 1 in. into the
groove and to permit a min of 3/8 in. thickness of expansion material to be inserted into the groove. Groove openings shall be oversized by 1/2 +
or - 1/8 in. to accommodate placement of packing material and fire retardant type sealant around lintels and jambs on both sides of the panel.

Steel lintels and jambs shall be secured to the structure of the building with 3/8 in. bolts provided with heavy galvanized washers in 2 in. slotted
holes space 12 in. OC.

Panel anchor framing construction may be used in lieu of steel angle/or masonry groove framing construction. Panel anchors shall be 20 gauge
perforated steel strips 24 in. long by 1-3/4 in. wide, galvanized after perforation. Panel anchors shall be used to secure the glass block panel at
both jambs and across the lintel. Panel anchors must be bent within the expansion joint, spaced apart vertically to coincide with the panel
reinforcing and 16 in. apart across the lintel. Panel anchors must be completely embedded in the mortar joints of the glass block panel, extending
a minimum of 12 in. into the joint. The panel anchors shall be attached to the inside of the masonry jambs with 2 steel expansion shell anchors,
1/4 in. to 3/8 in. in diameter, per anchor. Self-tapping screws may be used to attach panel anchors to steel lintels.

Both exterior and interior jambs and lintel edges are to be caulked with fire retardant type sealant as specified by the manufacturer's installation
instructions.

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=KCJ... 2/2/12
KCJU.R2556 - Glass Blocks Page 3 of 3

The blocks noted under 1-1/2 h "Rating" are classified for use in masonry walls only. Steel or masonry lintels/jambs shall only be used. Expansion
material in these locations shall be a minimum of 3/4 in. thickness .

The blocks noted under 1-1/2 h "Rating" and all other 8 in. x 8 in. x 3-7/8 in. sized glass blocks are classified for use in masonry walls as curved
window assemblies provided that the radius of the assembly is at least twice the opening width (ie. Chord Length).

Non-Masonry Application:The blocks noted under "Sizes" in drywall are Classified for use in non-masonry, metal or wood stud walls when
installed in accordance with the manufacturer's installation instructions.

Also Classified in accordance with the requirements of ANSI/NFPA 257, UBC 7-4, UL 9 and NFPA 80.

Last Updated on 2012-01-27

Questions? Print this page Notice of Disclaimer Page Top

© 2012 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the
data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the
extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2012 UL LLC".

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=KCJ... 2/2/12