Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
Instrument Transformers
� CT – Current Transformer
� Current Scaling
� Isolation
� VT – Voltage Transformer
� Voltage Scaling
� Isolation
1.Current Transformers
Current and voltage transformers are responsible for
scaling primary system signals.
Typical nominal secondary values are 5 A and 1 A for
current transformers and 110 V for voltage transformers.
Conventional magnetic current and voltage transformers
are still in wide use in power systems. For voltage levels
greater than 230 kV, we substitute capacitive-coupled
voltage transformers (CCVT) for VTs.CT saturation and
bad transient response of CCVTs create protection
problems.
New trends in current and voltage transducers are low-
power-output current and voltage transformers (recently
included in an IEC Standard) and magneto-optic current
and voltage transducers (MOCT and MOVT). MOCTs use
the Faraday Effect, and MOVTs can use either the Faraday
or the Pockels effect.
26
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
The initial problem was how to connect a low-voltage device to the high-voltage
system and have the ability to handle large fault currents (kilo-Amps). How can we
make the relay measure the currents flowing in the high-voltage system in order to
detect these faults?
The solution consists of using a special type of transformer, called a current
transformer.
The main parts of a current transformer are:
• Iron core
• Secondary winding
• Primary conductor
• External insulation
Some current transformers do not have a primary conductor. In those cases the
primary is the line or bus itself. Sometimes the core and its secondary winding are
directly installed in the bushing of the circuit breakers or transformers. These CTs are
called “bushing CTs”.
Some current transformers may have a primary that consists of several turns.
Typically there are no more turns than the natural, which is equivalent to say that the
primary number of turns is 1.
The total load connected to the CT terminal (g and h in this case) is called “burden”.
Ideally, the secondary current of a CT is perfectly proportional to the primary current.
It will be shown later that in reality this is sometimes not true.
26
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
High-Voltage CT Example
26
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
VDE: K, L, k, l
22
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
CT Common Connections
At the left, the “Y” connection provides the line currents at the
secondary.
At the right, the “∆” connection provides the difference currents
(delta currents) to the secondary loads.
26
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
� Typically: 1 A or 5 A
26
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
26
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
CT Performance Calculations
The performance of a C.T may be found from two approaches :
1. The formula method.
2. The saturation curve method.
The relation between Es and Ie is not linear like the relation shown in the Fig.1
due to the saturation of C.T core. Therefore the C.T. has ratio error.
67
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
The deviation of Is’ from Is is called the C.T error, and can be expressed
as a percentage.
I s I s' I
C.Terror x100% e x100%
Is Is
Where:
Is –Is’ = Ie
Example:
Assume that a C.T has rated current ratio of 500/5 A. The impedance of
the secondary winding Z2 = 0.242 Ω, and the burden impedance ZB =
0.351 Ω .The core area A = 0.00193 m2. The C.T must operate at
máximum primary current of 10 kA.If the frequency is 60 Hz and the
core is built from silicon steel:
(a) Determine whether or not the C.T will saturate.
(b) Determine the C.T error.
Solution
67
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
'
I 0.1
C.T error % = e x100% x100% 0.1%
Is 100
66
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
Accuracy Class
Class % error Applications
0.1 ± 0.1
0.2 ± 0.2 Metering
0.5 ± 0.5
1.0 ± 1.0
5P ±1 Protection
10P ±3
C.T specifications:
A rated burden at rated current or (VA).
An accuracy clases
(ALF) accuracy limit factor an upper limit beyond which the accuracy is
not guaranteed.
Example:
1. 15 VA clases 0.5→mettering C.T
2. 15 5p 20 →protection C.T
66
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
2.Voltage Transformers
Voltage transformers are connected across the points at which the voltage
to be measured.
Types of voltage Transformers:
There are three main types of voltage transformers:
Magnetic voltage transformers (ordinary two winding type – used
for L.V. and M.V).
Capacitive Voltage Transformers (CVT), used for high and extra
high voltages.
Magneto—optic voltage transformers (new ).
Line
Vs = 110 or 120
66
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
VT Equivalent Circuit
Referred to the Secondary Side
66
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
62
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
Vn =Nominal voltage
66
Power System Protection Part – 3 Dr.Prof .Mohammed Tawfeeq
VT connections
66