1
The McDonald's C708 and C716 are similar to the standard Models C708 and C716. Follow the
instructions in the C708/C716 Operator's Manual and use this insert to substitute the following
information where applicable.
PARTS IDENTIFICATION/FUNCTIONS
2 140801
C708 Accessories
Figure 1
3 120621
C716 Accessories (See Figure 2.)
4 140801
C716 Accessories
Figure 2
5 120621
Add the following X53800-BRN/TAN Pump A.-Syrup Heated Parts Identification:
6 121204
X53800-BRN/TAN Pump A.-Syrup Heated
Figure 3
7 121204
Add the following 053794-BRN/RED/TAN Pump A.-Syrup Parts Identification:
8 121204
053794-BRN/RED/TAN Pump A.-Syrup
Figure 4
9 121204
DAILY OPENING PROCEDURES the way back to its locking position. Place
the cones in the drawer and release the
spring guide.
Replace the Daily Opening Procedures in
the C708/C716 Operator Manual with the 8. Prepare a small amount of KAY-5®
following information: Sanitizer (HCS) solution. Use one packet
in 2.5 gallons (9.5 liters) of water (100
Before performing the opening procedures, PPM).
check the display panel for any error
messages. Normally the display is blank 9. Return to the freezer with a small amount
unless an operational fault has occurred. If a of sanitizing solution. Dip the door spout
fault has been detected, investigate the cause brush into the sanitizing solution and
and follow the instructions on the display brush clean the door spouts and bottom
before proceeding with the opening of the draw valves.
procedures. (See “Failure Messages”, in the Note: To assure sanitary conditions are
C708/C716 Operator Manual.) maintained, brush clean each item for a total
of 60 seconds, repeatedly dipping the brush in
sanitizing solution.
Set-Up - Complete The Following
10. Using a clean, sanitized towel, wipe down
Make sure your hands are clean and the freezer door, front panel, the area
sanitized before performing these next around the bottom of the freezer door,
steps. and any other areas that demonstrate a
1. With the drain plugs closed, check the build-up of either moisture or food
water level in the two heated topping substance.
wells. Fill the wells with water to the 11. Install the front drip tray and splash shield.
indicating mark on the bottom of the well.
12. Install the design caps (C716, only).
2. Place the topping heaters in the ON
position by touching the topping heater 13. When ready to resume normal operation,
symbols . touch the AUTO symbol .
(See Figure 5.)
Caution: As soon as the heaters are turned on,
the topping wells will begin heating. This
heating process will take approximately 2-1/2
hours to reach temperature. The water level in
the wells should be checked daily.
10 121108
DAILY CLOSING PROCEDURES 6. Rinse these parts in cool, clean water.
Replace the Daily Closing Procedures in 7. Draw a small amount of SolidSense™ All
the C708/C716 Operator Manual with the Purpose Super Concentrate (APSC)
following information: (HCS) cleaning solution from the sink
proportioner and brush clean the parts.
THIS PROCEDURE MUST BE PERFORMED
ONCE DAILY! 8. Prepare a small amount of KAY-5®
Sanitizer (HCS) solution. Use one packet
The function of the Heat Treatment Cycle is to in 2.5 gallons (9.5 liters) of water (100
destroy bacteria by raising the temperature of PPM). Sanitize the agitator(s) and hopper
the mix in the freezing cylinder and the hopper cover(s).
to a specified temperature for a specified
period of time, and then bringing the
temperature back down low enough to retard 9. Install the agitators back onto the agitator
spoilage. drive shaft housings. Replace the hopper
covers.
The Heat Treatment Cycle will start at the time
designated in the Auto Heat Time.
IMPORTANT: If you do not install the
IMPORTANT: The level of mix in the mix agitators correctly, the machine will fail the
hoppers must be above the mix low heat cycle and lock out in the morning.
probe(s). (The mix low light must not be ON.)
Note: If the BRUSH CLEAN COUNTER
display has counted down to one day, do not 10. Return to the freezer with a small amount
add mix. The machine must be disassembled of cleaning solution. Dip the door spout
and brush cleaned within 24 hours. brush into the cleaning solution and brush
clean the door spouts and bottom of the
The freezer must be in the AUTO (AUTO draw valves.
symbol illuminated) or in the STANDBY
mode (STANDBY symbol illuminated) Note: To assure sanitary conditions are
before the HEAT cycle may be started. maintained, brush each item for a total of 60
seconds, repeatedly dipping the brush in
1. Place the topping heaters in the OFF cleaning solution.
position by touching the heater
symbols . The symbols will not be
11. Remove, clean and reinstall all drip pans.
illuminated when the heaters are off.
(See Figure 6.)
2. Remove the hopper cover(s).
Make sure your hands are clean and
sanitized before performing these next
steps.
Note: Pressing either one of the arrow
symbols will stop agitator movement. The
agitator will automatically restart after 10
seconds.
3. Remove the agitators from the mix
hoppers.
4. Remove the design caps (C716, only).
5. Take the agitators, hopper covers and
design caps to the sink for further
cleaning and sanitizing. Figure 6
11 100524
12. Using a clean, sanitized towel, wipe down WEEKLY CLEANING
the freezer door, front panel, the area
around the bottom of the freezer door,
and any other areas that demonstrate a Add the following Weekly Cleaning
build-up of either moisture or food information:
substance.
The topping containers, lids, topping pumps,
The heat cycle will start when the clock on the and water baths require weekly cleaning.
machine reaches the AUTO HEAT TIME set in
the Manager's Menu. For C708's equipped with optional shake
syrup containers and pumps: The shake
There are 3 phases of the heat cycle: Heating, syrup pumps and syrup containers require
Holding and Cooling. Each phase has a time weekly cleaning.
limit. If any one of the three phases fail to
reach the proper temperatures within the time
limit, the cycle will automatically abort and
Water Bath Cleaning
return to the STANDBY mode.
A failure message will appear on the 1. Place the topping heaters in the OFF
fluorescent display to inform the operator that position by touching the heater
the machine did not successfully complete the
symbols . The symbols will not be
heat treatment cycle. The product may not be
illuminated when the heaters are off.
safe to serve. The freezer will be locked out
(softlock) of the AUTO mode. The operator will 2. Remove the topping container assemblies
be given the option of selecting the HEAT and take them to the 3-compartment sink
symbol which will begin a new heat cycle, for cleaning and sanitizing.
or touching the WASH symbol which will
3. Allow the water in the water baths to cool
place the freezer into the OFF mode to allow a
for 10 minutes and then drain the water.
brush clean of the machine.
Note: Once the heating cycle has started, it 4. Fill the water bath with SolidSense™ All
cannot be interrupted. The heating cycle will Purpose Super Concentrate (APSC)
take a maximum of 3.5 hours to complete with (HCS) solution. Use a clean, sanitized
full hoppers. towel and thoroughly clean the inside of
the water bath. Drain the solution.
12 121204
Topping & Shake Syrup Container Cleaning 4. To remove the knob, compress the spring
by holding the nut and pressing on the
Note: The heated topping pump has been end of the plunger. Turn the knob
selected for illustration. The C708 optional counterclockwise. (See Figure 8.)
shake syrup pump looks slightly different, but
the procedures are essentially the same.
3. Remove the plunger assembly from the 6. Remove the spring and washer from the
plunger assembly. (See Figure 10.)
pump body by turning the plunger nut
counterclockwise. (See Figure 7.)
Figure 7 Figure 10
13 120228
7. Remove the seal assembly from the 10. Remove the lid by sliding it off the
plunger assembly. (See Figure 11.) discharge tube.
Figure 11
Figure 14
Figure 12
Figure 15
14
Topping & Shake Syrup Pump Cleaning 5. Insert the black shielded brush into the
1. Wash and scrub all parts in SolidSense™ top side of the outlet valve. Scrub this
All Purpose Super Concentrate (APSC) area, specifically around the steel ball.
(HCS). (See Figure 18.)
Figure 18
Figure 16
3. Advance the brush completely through 6. Insert the black shielded brush, by the
the discharge tube and pull the brush non-bristle end, into the passageway
from the bottom of the tube. between the inlet valve and the outlet
valve. (See Figure 19.)
4. Insert the black shielded brush into the
top side of the inlet valve. Scrub this area,
specifically around the steel ball.
(See Figure 17.)
Figure 17 Figure 19
15
7. Move the brush back and forth to scrub Topping & Shake Syrup Pump Assembly
this passageway. Advance the brush
After pump disassembly and cleaning is
completely, and pull the brush out of the
complete, assemble the pump.
valve body. (See Figure 20.)
1. Lubricate and install the seal o-ring into
the seal. (See Figure 22.)
Figure 22
Figure 20
2. Install the seal assembly onto the piston
end of the plunger assembly.
8. Insert the black shielded brush into the
bottom side of the inlet valve. Move the 3. Install the washer and spring onto the
brush back and forth to scrub this area, plunger assembly. (See Figure 23.)
specifically around the steel ball.
(See Figure 21.)
Figure 23
16
5. Install the plunger nut onto the plunger 8. Lubricate and install the 1” o-ring onto the
tube. (See Figure 25.) groove provided on the discharge tube.
(See Figure 28.)
Figure 25
Figure 26
17 120228
12. Install the lid by inserting the discharge 15. Tighten the plunger nut by turning it
tube through the smaller hole in the lid. clockwise. (See Figure 31.)
Slide the lid until the larger hole fits
around the top of the cylinder. The
discharge tube lock nut will secure the lid
in position.
13. Install the discharge tube lock nut and
tighten, by turning it clockwise.
14. Lubricate the seal assembly and install
the plunger assembly into the cylinder
opening in the pump body.
(See Figure 30.)
Figure 31
Figure 30
Replace the Limited Warranty on Equipment information in the C708/C716 Operator Manual
with the following:
Taylor Company is pleased to provide this limited warranty on new Taylor-branded freezer equipment
available from Taylor (the “Product”) to the original McDonald’s purchaser only.
LIMITED WARRANTY
Taylor warrants the Product against failure due to defect in materials or workmanship under normal
use and service as follows. All warranty periods begin on the date of original Product installation. If a
part fails due to defect during the applicable warranty period Taylor, through an authorized Taylor
distributor or service agency, will provide a new or re-manufactured part, at Taylor’s option, to
replace the failed defective part at no charge for the part.
18 140102
In addition, during the one (1) year period commencing on the date of original installation of the Product,
Taylor will also provide, through an authorized Taylor distributor or service agency, all service needed to
replace the failed defective part at no charge for the service. This no-charge service shall not be available
for service performed by authorized McDonald’s service technicians. Local sales and use taxes may still
apply and will be charged accordingly.
Except as otherwise stated herein, these are Taylor’s exclusive obligations under this limited warranty for
a Product failure. This limited warranty is subject to all provisions, conditions, limitations and exclusions
listed below and on the reverse (if any) of this document.
LIMITED WARRANTY CONDITIONS
1. If the date of original installation of the Product cannot be verified, then the limited warranty period
begins ninety (90) days from the date of Product manufacture (as indicated by the Product serial
number). Proof of purchase may be required at time of service.
2. This limited warranty is valid only if the Product is installed and all required service work on the
Product is performed by an authorized Taylor distributor or service agency, and only if genuine,
new Taylor parts are used.
3. Installation, use, care, and maintenance must be normal and in accordance with all instructions
contained in the Equipment Manual.
4. Defective parts must be returned to the authorized Taylor distributor or service agency for credit.
5. The use of any refrigerant other than that specified on the Product’s data label will void this
limited warranty.
LIMITED WARRANTY EXCEPTIONS
This limited warranty does not cover:
1. Except as otherwise specifically set forth in this limited warranty, labor or other costs incurred for
diagnosing, repairing, removing, installing, shipping, servicing or handling of defective parts,
replacement parts, or new Products.
2. Normal maintenance, cleaning and lubrication as outlined in the Equipment Manual, including
cleaning of condensers.
3. Replacement of wear items designated as Class “000” parts in the Equipment Manual.
4. External hoses, electrical power supplies, and machine grounding.
5. Parts not supplied or designated by Taylor, or damages resulting from their use.
6. Return trips or waiting time required because a service technician is prevented from beginning
warranty service work promptly upon arrival.
7. Failure, damage or repairs due to faulty installation, misapplication, abuse, no or improper
servicing, unauthorized alteration or improper operation or use as indicated in the Equipment
Manual, including but not limited to the failure to use proper assembly and cleaning techniques,
tools, or approved cleaning supplies.
8. Failure, damage or repairs due to theft, vandalism, wind, rain, flood, high water, water, lightning,
earthquake or any other natural disaster, fire, corrosive environments, insect or rodent
infestation, or other casualty, accident or condition beyond the reasonable control of Taylor;
operation above or below the electrical or water supply specification of the Product; or
components repaired or altered in any way so as, in the judgment of the Manufacturer, to
adversely affect performance, or normal wear or deterioration.
9. Any Product purchased over the Internet.
10. Failure to start due to voltage conditions, blown fuses, open circuit breakers, or damages due to
the inadequacy or interruption of electrical service.
19
11. Electricity or fuel costs, or increases in electricity or fuel costs from any reason whatsoever.
12. Damages resulting from the use of any refrigerant other than that specified on the Product’s data
label will void this limited warranty.
13. ANY SPECIAL, INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL DAMAGE
OF ANY NATURE WHATSOEVER. Some jurisdictions do not allow the exclusion of incidental or
consequential damages, so this limitation may not apply to you.
This limited warranty gives you specific legal rights, and you may also have other rights which vary from
jurisdiction to jurisdiction.
LIMITATION OF WARRANTY
THIS LIMITED WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ALL OTHER WARRANTIES,
CONDITIONS AND/OR REMEDIES UNDER THE LAW, INCLUDING ANY IMPLIED WARRANTIES OR
CONDITIONS OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. THE
ORIGINAL OWNER'S SOLE REMEDY WITH RESPECT TO ANY PRODUCTS SHALL BE REPAIR OR
REPLACEMENT OF DEFECTIVE COMPONENTS UNDER THE TERMS OF THIS LIMITED
WARRANTY. ALL RIGHTS TO CONSEQUENTIAL OR INCIDENTAL DAMAGES (INCLUDING CLAIMS
FOR LOST SALES, LOST PROFITS, PRODUCT LOSS, PROPERTY DAMAGES OR SERVICE
EXPENSES) ARE EXPRESSLY EXCLUDED. THE EXPRESS WARRANTIES MADE IN THIS LIMITED
WARRANTY MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR,
DEALER, OR OTHER PERSON, WHATSOEVER.
LEGAL REMEDIES
The owner must notify Taylor in writing, by certified or registered letter to the following address, of any
defect or complaint with the Product, stating the defect or complaint and a specific request for repair,
replacement, or other correction of the Product under warranty, mailed at least thirty (30) days before
pursuing any legal rights or remedies.
Taylor Company
750 N. Blackhawk Blvd.
Rockton, IL 61072, U.S.A.
20 140311
OPERATOR'S
MANUAL
059061-M
January, 2005 (Original Publication)
(Updated 9/2/14)
Complete this page for quick reference when service is required:
Taylor Distributor:
Address:
Phone:
Service:
Parts:
Date of Installation:
Model Number:
Serial Number:
Phase
Taylor Company
750 N. Blackhawk Blvd.
Rockton, IL 61072
Table of Contents
Section 3 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rinsing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Hopper Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Brush Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Section 7 Important: Operator Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
During Cleaning and Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Troubleshooting Bacterial Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Regular Maintenance Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Winter Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Section 8 Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Note: Only instructions originating from the factory or its authorized translation
representative(s) are considered to be the original set of instructions.
Taylor Company
750 N. Blackhawk Blvd.
Rockton, IL 61072
Installer Safety
Site Preparation
In all areas of the world, equipment should
be installed in accordance with existing local codes.
Please contact your local authorities if you have any
questions. Review the area where the unit will be installed
before uncrating the unit. Make sure that all possible
Care should be taken to ensure that all basic safety hazards to the user and the equipment have been
practices are followed during the installation and addressed.
servicing activities related to the installation and
service of Taylor equipment.
For Indoor Use Only: This unit is designed to
S Only authorized Taylor service personnel operate indoors, under normal ambient
should perform installation and repairs on temperatures of 70_-75_F (21_-24_C). The freezer
the equipment. has successfully performed in high ambient
S Authorized service personnel should consult temperatures of 104_(40_C) at reduced capacities.
OSHA Standard 29CFRI910.147 or the
applicable code of the local area for the
industry standards on lockout/tagout
procedures before beginning any installation This unit must NOT be installed in an area
or repairs. where a water jet or hose can be used. NEVER use
S Authorized service personnel must ensure a water jet or hose to rinse or clean the unit. Failure
that the proper PPE is available and worn to follow this instruction may result in electrocution.
when required during installation and
service.
S Authorized service personnel must remove
all metal jewelry, rings, and watches before This unit must be installed on a level surface
working on electrical equipment. to avoid the hazard of tipping. Extreme care should
be taken in moving this equipment for any reason.
Two or more persons are required to safely move
this unit. Failure to comply may result in personal
The main power supply(s) to the freezer injury or equipment damage.
must be disconnected prior to performing any
repairs. Failure to follow this instruction may result in
Uncrate the unit and inspect it for damage. Report
personal injury or death from electrical shock or
any damage to your Taylor Distributor.
hazardous moving parts as well as poor
performance or damage to the equipment.
This piece of equipment is made in the USA and has
Note: All repairs must be performed by an USA sizes of hardware. All metric conversions are
authorized Taylor Service Technician. approximate and vary in size.
131121
Water Connections
(Water Cooled Units Only)
Each unit requires one power supply for each data
An adequate cold water supply must be provided label on the unit. Check the data label(s) on the
with a hand shut-off valve. On the underside of the freezer for branch circuit overcurrent protection or
base pan or on the right side, two 3/8” I.P.S. water fuse, circuit ampacity, and other electrical
connections for inlet and outlet are provided for easy specifications. Refer to the wiring diagram provided
hook-up. 1/2” inside diameter water lines should be inside of the electrical box for proper power
connected to the machine. (Flexible lines are connections.
recommended, if local codes permit.) Depending on
local water conditions, it may be advisable to install
a water strainer to prevent foreign substances from
clogging the automatic water valve. There will be
CAUTION: THIS EQUIPMENT MUST BE
only one water “in” and one water “out” connection.
PROPERLY GROUNDED! FAILURE TO DO SO
DO NOT install a hand shut-off valve on the water
CAN RESULT IN SEVERE PERSONAL INJURY
“out” line! Water should always flow in this order:
FROM ELECTRICAL SHOCK!
first, through the automatic water valve; second,
through the condenser; and third, through the outlet
fitting to an open trap drain.
This unit is provided with an equipotential
grounding lug that is to be properly attached to the
A back flow prevention device is rear of the frame by the authorized installer. The
required on the incoming water connection side. installation location is marked by the equipotential
Please refer to the applicable National, State, and bonding symbol (5021 of IEC 60417-1) on both the
local codes for determining the proper configuration. removable panel and the equipment's frame.
101027
130809
131121
130225
Access to the service area of the unit is DO NOT run the machine without product. Failure to
restricted to persons having knowledge and practical follow this instruction can result in damage to the
experience with the appliance, in particular as far as machine.
safety and hygiene are concerned.
130304
Figure 1
110506
Figure 2
130129
120409
Figure 3
Figure 4
140121
Figure 5
ITEM DESCRIPTION PART NO. ITEM DESCRIPTION PART NO.
1- 7 PUMP ASSEMBLY - MIX X57029-XX* 10a CRANK-DRIVE 039235
SIMPLIFIED SOFT SERVE
10b SHAFT-DRIVE 041948
1 CYLINDER-PUMP-HOPPER-SS 057943
10c O-RING 1-3/4 OD X .139W 008904
2 PIN-RETAINING X55450
10d O-RING 1/2 ID X .139W 048632
3 PISTON-PUMP-SIMPLIFIED 053526
11 TUBE A.-FEED HOPPER (C708) X56521
4 O-RING 2-1/8” OD - RED 020051
12 TUBE A.-FEED RIGHT (C716) X59809
5 CAP-VALVE BODY SS 056874-XX
13 TUBE A.-FEED LEFT (C716) X59808
6 GASKET-SIMPLIFIED PUMP 053527
VALVE 14 RING-CHECK .120 OD 056524
15 CLIP-MIX PUMP RETAINER 044641
7 ADAPTOR - MIX INLET SS RED 054825
16 SLEEVE A.- MIX PUMP *HT X44761
8 O-RING - 11/16 OD - RED 016132
*NOTE: THE STANDARD PUMP X57029-XX IS -14.
9 PIN - COTTER 044731
OVERRUN CAN BE CHANGED HIGHER OR LOWER
10 SHAFT A.-DRIVE-MIX PUMP- X41947 BY SUBSTITUTING THE CAP (056874-XX) WITH
HOPPER CAPS AVAILABLE -1 THROUGH -20. THE HIGHER
THE DASH (-) NUMBER, THE HIGHER THE
OVERRUN.
140312
Figure 6
140718
Figure 7
100507
C708 C716
Figure 8
ITEM DESCRIPTION
1 POWER SWITCH
2 LIQUID CRYSTAL DISPLAY
3 KEYPADS
4 MIX OUT INDICATOR
5 STANDBY INDICATOR
6 MIX LOW INDICATOR
7 SELECT KEY
8 SERVICE MENU KEY
9 BRUSH CLEAN COUNTER
10 ARROW KEY(S)
11 TOPPING HEATER KEY
Power Switch
The following chart identifies the symbol definitions.
When placed in the ON position, the power switch
allows control panel operation.
= SELECT
Fluorescent Display
100507
Figure 9
If the beater motor is turning properly, touch the The fluorescent display located in the center of the
control panel is normally blank during the daily
WASH symbol to cancel the cycle. Touch the operation of the machine. The display is activated
AUTO symbol to resume normal operation. If the when the SEL symbol or the Manager's Menu is
freezer shuts down again, contact your authorized selected. The display screen will also alert the
service technician. operator of specific faults detected by the control.
Note: The displays illustrated in this section are
those seen on the Models C708. The Model C716
Air/Mix Pump Reset Mechanism displays may vary slightly.
110817
System Data
System data is protected separately from the rest of If Lockout Data is corrupted, all lockout history data
the data in memory. System data includes variables is cleared. A “LOCKOUT CRC ERR” fault is
that change frequently such as the mode the displayed.
machine is in, lockout status, serving counters, fault
codes, and others. While System Data is being After the memory integrity has been tested, the
checked the following screen is displayed. Safety Timeout screen will be displayed.
SAFETY TIMEOUT
If Configuration data is corrupted, all user and ANY KEY ABORTS
service settings are set to defaults. A “CONFIG
CRC ERR” fault is set and displayed on the VFD.
050628
HOT PRODUCT
050628
Freezer Locks
HOPPER THERM BAD
There are two types of freezer lock conditions that FREEZER LOCKED
can occur: Hard Lock or Soft Lock. A Hard Lock
requires the machine be disassembled and brush
cleaned. A Soft Lock can be corrected by either
disassembling and brush cleaning the machine, or If the machine has hard locked and an attempt is
by starting another heat treatment cycle. made to enter AUTO, the machine will enter the
STANDBY mode and display the following message.
Hardlock
There are two causes of a hard lock failure. The
freezer will hardlock if either the Brush Clean Timer
FREEZER LOCKED
has elapsed or if a Thermistor Failure (Freezing
Cylinder or Hopper) occurred during a Heat cycle.
1. The following screen will be displayed if a Brush To restore the message that identified the reason for
Clean Cycle Time has occurred. the hard lock, turn the power switch OFF for five
seconds and then return the power switch to the ON
position. The original message with the reason for
BRUSH CLEAN TIMEOUT the Hard Lock will be displayed.
FREEZER LOCKED
CLEANING REQ'D The FREEZER LOCKED message will remain on
> WASH TO BRUSH CLEAN the display until the brush clean requirements are
fulfilled. The freezer must be disassembled in order
to activate the five minute timer on the display
Touching the SEL symbol will display the following screen. Once the timer counts down to zero, the
screen. lockout is cleared.
121008
Following are the variable messages for soft lock Once the freezer is unlocked by starting a heat
failures that appear on the second line of the screen. treatment cycle the HEAT symbol will illuminate and
the following message will be displayed on the
POWER SWITCH OFF Power switch was in the screen.
OFF position.
MIX OUT PRESENT There was a mix out
condition present.
AUTO OR STANDBY The machine was not in DO NOT DRAW
OFF the AUTO or STANDBY
mode.
NO HEAT CYCLE A heat treatment cycle
TRIED was not attempted in
the last 24 hours.
If BRUSH CLEAN is selected to clear the lockout by
(AUTO HEAT TIME
brush cleaning the machine, the FREEZER
was advanced or a
LOCKED message will remain on the display until
power loss was experi-
enced at the time the the brush clean requirements are fulfilled. The
cycle was to occur.) freezer must be disassembled in order to activate
the five minute timer on the display screen. Once
the timer counts down to zero, the lockout is
If the following screen appears, a soft lock has cleared.
occurred during the heat treatment cycle.
050628
HEAT TREAT FAILURE Note: The machine will continue operation in the
REASON mode it was in when the Menu was selected. However,
> HEAT FOR HEAT CYCLE the control keys will not be lit and are non- functional
WASH TO BRUSH CLEAN when the Manager’s Menu is displayed. The control
keys are functional in the Manager’s Menu when the
CURRENT CONDITIONS screen is displayed. (See
Note: A record of Heat Cycle Data and Lock Out CURRENT CONDITIONS on page 31.)
History can be found in the Manager's Menu.
Figure 10
050628
SERVINGS COUNTER
SET CLOCK
AUTO HEAT TIME Set Clock
AUTO START TIME The SET CLOCK option allows the Manager to
STANDBY MODE adjust the control clock date and time. The date and
time may only be changed after the freezer has
MIX LEVEL AUDIBLE been manually cleaned but before it has been
FAULT DESCRIPTION placed in the AUTO or STANDBY mode. The
following message will be displayed if the SET
FAULT HISTORY
CLOCK option is selected when the machine is not
LOCKOUT HISTORY in a brush clean state.
HEAT CYCLE SUMMARY
HEAT CYCLE DATA SET CLOCK
SYSTEM INFORMATION 12:01 6/10/2010
NO CHANGES ALLOWED
CURRENT CONDITIONS Press Any Key
NET SERVICE PIN
To change the date or time, select the SET CLOCK
option in the menu. Touch the UP arrow symbol to
Exit From Menu advance the arrow from Exit to Change, then touch
the SEL symbol to select the Change option.
Selecting “EXIT FROM MENU” will exit the
Manager's Menu and the return the control panel
symbols to normal operation. SET CLOCK
12:01 6/10/2010
Change
> Exit
Servings Counter
The SERVINGS COUNTER screen is used to check Change the time by touching the UP arrow with the
or reset the number of servings dispensed from the cursor under the hour position. Move the cursor to
machine. The SERVINGS COUNTER will the minutes position by touching the SEL symbol.
automatically reset to zero when the machine is Once the correct minutes are entered, touch the
brush cleaned. SEL symbol to advance the cursor to the month.
120321
If the correct Sunday for the time change is not The AUTO HEAT TIME screen allows the Manager
displayed, then “Change” should be selected. to set the time of day in which the heat treatment
Pressing the SEL symbol with the arrow next to cycle will start.
“Change” displays the third screen. Press the UP or
DOWN symbol to move the arrow to the appropriate
AUTO HEAT TIME
month for the start of DST.
00:00
Change
DST START MONTH > Exit
> MAR
APR
MAY To set the AUTO HEAT TIME, touch the UP arrow
symbol to move the arrow to “Change”. Then touch
the SEL symbol. The screen will display the time
Pressing the SEL symbol with the arrow next to the with the cursor under the hour position.
appropriate month will display the following screen.
AUTO HEAT TIME
DST START WEEK 00:00
> Second Sunday
Third Sunday
Fourth Sunday
STANDBY MODE
AUTO START TIME Yes
DISABLED No
Enable > Exit
> Disable
Enable the AUTO START TIME by touching the UP Mix Level Audible
arrow symbol to move the arrow up to “Enable”. The MIX LEVEL AUDIBLE option, when enabled,
Touch the SEL symbol to advance to the next will alert the operator with an audible tone when
screen. there is Mix Low or Mix Out condition. The following
screen is displayed upon selecting this option.
Program the AUTO START TIME by touching the Disable the audible tone feature by touching the
UP arrow symbol to move the arrow to “Change”. DOWN arrow symbol to move the arrow to
Touch the SEL symbol to advance to the next “Disable”. Touch the SEL symbol to save the new
screen. setting and return to the Menu. The control panel
icons for Mix Low and Mix Out will illuminate as the
mix level drops in the hopper, but the audible tone
will be disabled.
140303
(L/R) BRL>41F (5C) AFTER 4 HR - The mix Each heat cycle record has three screens. The first
temperature in the freezing cylinder (barrel) was screen displays the month and day of the heat cycle,
above 41°F (5°C) more than four hours. the start time and end time, and the fault description.
(L/R) HPR>41F (5C) AFTER PF - The mix The bottom line displays the record number and
temperature in the hopper was above 41°F (5°C) indicates if a power failure occurred during the heat
more than four hours following a power failure. cycle (POWER FAILURE IN HC).
051025
The top line of these screens shows the hopper (H) HT HEAT TIME FAILURE
and barrel (B) temperatures recorded at the end of Mix temperature did not rise above 151_F
the Heat Treat Cycle and indicates the side (L or R) (66.1_C) in less than 90 minutes.
of the freezer. CL COOL MODE FAILURE
Mix temperature in the hopper and freezing
The remaining lines indicate the following: cylinder did not fall below 41_F (5_C) in less
than 90 minutes for UVC3 units or 120
HEAT = Total time for the hopper (h) and barrel (b) minutes for UVC4 units.
to reach 150.9°F (66.1°C). TT TOTAL TIME FAILURE
The heat treatment cycle must be completed
OVER = Total time the hopper (h) and barrel (b) in no more than 4 hours.
temperature was above 150°F (65.6°C). ML MIX LOW FAILURE
The Heat Phase or Cool Phase time was
COOL = Total time the hopper (h) and barrel (b) exceeded and a mix low condition was
temperature was above 41°F (5°C) during the COOL present.
phase. MO MIX OUT FAILURE
A mix out condition was detected at the start
PEAK = Highest temperature reading for the hopper or during the heat cycle.
(h) and barrel (b) during the Heat Treatment Cycle.
BO BEATER OLVD IN HC
A beater overload occurred during the heat
cycle.
H: 40.9 B:26.3 L
HO HPCO IN HEAT CYCLE
HEAT OVER COOL PEAK
A high pressure cut-out condition occurred
1:12 0:49 h 1:19 161.0
during the heat cycle.
0:46 1:11 b 0:15 169.7
PF POWER FAILURE IN HC
A power failure caused the Heat Phase,
Cool Phase, or Total Cycle Time to exceed
the maximum allowed time. If a power failure
H: 38.0 B:23.7 R occurs, but the heat treatment cycle does
HEAT OVER COOL PEAK not fail, an asterisk(*) will appear on the third
1:09 0:52 h 1:11 161.2 line of the display.
0:66 1:00 b 0:11 169.9
OP OPERATOR INTERRUPT
Indicates the heat cycle was aborted in the
OPERATOR INTERRUPT option in the
The HEAT time indicates the amount of time taken Service Menu.
in each zone to reach 150.9°F (66.1°C). Each zone PS POWER SWITCH OFF
must remain above 150°F (65.6°C) for a minimum of The power switch was placed into the OFF
35 minutes. position during the heat cycle.
TH THERMISTOR FAILURE
Touch the UP arrow symbol to advance to the next A thermistor probe has failed.
page or the DOWN arrow symbol to view the
previous page. A Heat Cycle Failure message will PD PRODUCT DOOR OFF
display on the first screen if a failure occurred. A product door is not in place or is loose.
140303
VISC 0.0
SOFTWARE VERSION HOPPER 41.0
C708 CONTROL UVC BARREL 41.0
VERSION X.XX
> Next
B.O.M. C70827C000
S/N M0000000 Pressing the UP or DOWN key will move the arrow
to “Yes” or “No”. Pressing the SEL key with the
> Next arrow next to either option selects that option and
returns to the Menu screen.
120227
Step 5
Note: When lubricating parts, use an approved food Insert the beater drive shaft through the rear shell
grade lubricant (example: Taylor Lube). bearing in the freezing cylinder and engage the hex
end firmly into the drive coupling. (See Figure 13.)
Step 1
Before installing the beater drive shaft, lubricate the
groove on the beater drive shaft.
Step 2
Slide the beater drive shaft boot seal over the small
end of the beater drive shaft and engage into the
groove on the shaft. Figure 13
Figure 16
Step 9
Slide the beater assembly the rest of the way into
the freezing cylinder.
Figure 17
Figure 20
Step 4
Insert the draw valve from the top, with the draw
handle slot facing forward. (See Figure 21.)
Figure 18
Step 2
Slide the three o-rings into the grooves on the draw
valve and lubricate. (See Figure 19.)
Figure 19 Figure 21
Figure 22
Step 6
Slide the fork of the draw handle into the slot of the
draw valve. Secure with pivot pin. (See Figure 23.) Figure 24
Step 8
Install the front drip tray and splash shield under the
door spout. (See Figure 34.)
Figure 23
Note: The C708 features an adjustable draw handle
to provide portion control, giving a better consistent
quality to your product and controlling costs. Figure 25
Step 1
Place the door gaskets into the grooves on the back
of the freezer door.
Figure 28
Step 4
Slide the three o-rings into the grooves of each
standard draw valve. Slide the H-ring and o-ring into
the grooves of the center draw valve. Lubricate the
H-ring and o-rings.
Figure 26
Step 2
Slide the front bearings over the baffle rods. The
flanged edges should be against the door. DO NOT
lubricate the gaskets or bearings.
Figure 29
Step 5
Lubricate the inside of the freezer door spouts, top
and bottom.
Figure 27
Step 3
Insert the baffle rods through the beaters in the
freezing cylinders. With the door seated on the
freezer studs, install the handscrews, with the longer
ones on top. Tighten equally in a criss-cross pattern
to insure the door is snug. Figure 30
140121
Step 9
Snap the design caps over the bottom of the door
spouts.
Step 10
Slide the two short drip pans into the holes in the
back panel. Slide the two long drip pans into the
holes in the side panels. (See Figure 33.)
Figure 31
Step 7
Position each draw handle with the adjustment
screw facing down. Slide the fork of each draw
handle into the slot of each draw valve, starting from
the right.
Step 8
Slide the pivot pin through the draw handles as the
handles are inserted into the draw valves.
Figure 33
Step 11
Install the front drip tray and splash shield under the
door spouts. (See Figure 34.)
Figure 32
Note: This freezer features adjustable draw handles
to provide portion control, giving a better consistent
quality to your product and controlling costs. The
draw handles should be adjusted to provide a flow
rate of 5 to 7-1/2 oz. (142 g. to 213 g.) of product by
weight per 10 seconds. Figure 34
140121
Step 2
Assemble the piston. Slide the red o-ring into the
groove of the piston. DO NOT lubricate the o-ring.
(See Figure 35.) Figure 37
Step 5
Assemble the valve cap. Slide the o-ring into the
groove of the valve cap. DO NOT lubricate the
o-ring. (See Figure 38.)
Figure 35
Step 3
Apply a thin layer of lubricant to the inside of the Figure 38
pump cylinder at the retaining pin hole end.
(See Figure 36.) Step 6
Slide the pump valve gasket into the holes on the
cap. DO NOT lubricate the gasket. (See Figure 39.)
Figure 36 Figure 39
Figure 40 Figure 42
Step 8 Note: The head of the retaining pin should located
Insert the mix inlet assembly into the pump cylinder. at the top of the pump when installed.
(See Figure 41.)
Step 10
Assemble the feed tube assembly. Slide the check
ring into the groove of the feed tube.
(See Figure 43.)
Figure 41
Figure 46
Figure 44 Step 14
Install the hex end of the drive shaft into the drive
Step 12 hub at the rear wall of the mix hopper.
Lay the pump assembly, pump clip, cotter pin, mix (See Figure 47.)
feed tube assembly, and agitator in the bottom of
the mix hopper for sanitizing. (See Figure 45.)
Figure 47
Note: For ease in installing the pump, position the
ball crank of the drive shaft in the 3 o'clock position.
Repeat these steps for the other side of the
Figure 45 Model C716.
120209
Figure 48
Note: You have just sanitized the mix hopper and
parts; therefore, be sure your hands are clean and
sanitized before going on in these instructions.
Step 3
While the solution is flowing into the freezing
cylinder, take particular care to brush-clean the mix
level sensing probe on the bottom of the hopper, the
mix hopper, the mix inlet hole, the air/mix pump, the Figure 50
pump clip, the mix feed tube, and the locking clip.
Step 6
Step 4 Prepare another pail of approved 100 PPM sanitiz-
Install the pump assembly at the rear of the mix ing solution (examples: 2-1/2 gal. [9.5 liters] of
hopper. To position the pump on the drive hub, align Kay-5R or 2 gal. [7.6 liters] of Stera-SheenR).
the drive hole in the piston with the drive crank of USE WARM WATER AND FOLLOW THE MANU-
the drive shaft. Secure the pump in place by slipping FACTURER'S SPECIFICATIONS.
the pump clip over the collar of the pump, making
sure the clip fits into the grooves in the collar. Step 7
(See Figure 49.) Pour the sanitizing solution into the mix hopper.
080617
Step 10
Touch the WASH symbol . This will cause the
sanitizing solution in the freezing cylinder to be
agitated. Wait at least 5 minutes before proceeding
with these instructions.
Step 11
With a pail beneath the door spout(s), open the draw
valve and touch the PUMP symbol . Open and
close the draw valve 6 times. Figure 52
Note: Momentarily open the center draw valve to Note: If agitator should stop turning during normal
sanitize the center door spout (C716 only). operation, with sanitized hands, remove agitator
from agitator drive shaft housing and brush clean
Draw off the remaining sanitizing solution. with sanitizing solution. Install the agitator back onto
the agitator drive shaft housing.
Step 12 Step 14
Touch the WASH and PUMP symbols and Remove the cotter pin from the pump. Remove the
close the draw valve. (See Figure 51.) feed tube and position it as shown in the illustration
below. Place the cotter pin in position on the outlet
fitting of the pump assembly.
(See Figure 53.)
Figure 51
Figure 53
Note: Be sure your hands are clean and Repeat these steps for the other side of the
sanitized before going on in these instructions. Model C716.
120209
Step 1
Remove the hopper cover(s).
Step 2
Remove the agitator(s) from the mix hopper(s).
Step 3
Remove the design caps (C716 only).
Step 4
Figure 54 Take the agitator(s), hopper cover(s) and design
cap(s) to the sink for further cleaning and sanitizing.
Step 4
Step 5
Select the AUTO symbol . Rinse these parts in cool, clean water.
Step 5 Step 6
Fill the hopper with fresh mix and place the mix Prepare a small amount of an approved 100 PPM
hopper cover in position. cleaning/sanitizing solution (example: Kay-5® or
Stera-Sheen®). USE WARM WATER AND FOL-
Repeat these steps for the other side of the LOW THE MANUFACTURER'S SPECIFICATIONS.
Model C716. Brush clean the agitator(s) and the hopper cover(s).
140718
Step 8
Install the agitator(s) back onto the agitator drive
shaft housing(s). Replace the hopper cover(s).
140722
Figure 58
100507
Step 1
With a pail beneath the door spout(s), open the draw
Rinsing
valve. Touch the WASH and PUMP symbols .
(See Figure 59.) Step 1
Pour two gallons (7.6 liters) of cool, clean water into
the mix hopper. With the white hopper brush, scrub
the mix hopper, mix level sensing probe and the
outside of the agitator drive shaft housing. Using the
double ended brush, brush clean the mix inlet hole.
(See Figure 61.)
Figure 59
Note: Do not allow the pump to keep running
when the draw valve is closed. Excessive
pressure will build up, causing product to spurt
out when the draw valve is opened.
Figure 61
Step 2
Drain the product from the freezing cylinder and the Note: Do not brush clean the mix inlet hole while
mix hopper. the machine is in the WASH mode.
121008
Step 5
Place an empty pail beneath the door spout(s).
Step 6
Open the draw valve on the freezer door and draw
off all the solution.
Step 7
Once the cleaning solution stops flowing from the
door spout, close the draw valve and touch the
WASH symbol , cancelling the WASH mode.
Step 3
Drain all the rinse water from the door spout. Close
the draw valve and touch the WASH symbol,
Disassembly
cancelling the WASH mode.
Note: Failure to remove the parts specified below
Step 4 for brush cleaning and lubrication will result in
Repeat this procedure using clean, warm water, until damage to the machine. These parts must be
the water being discharged is clear. removed within the maximum number of days
allowed between brush clean cycles or the machine
Repeat these steps for the other side of the will hard lock and will not operate.
Model C716.
140718
Step 1
Prepare an approved 100 PPM cleaning solution
(examples: 2-1/2 gal. [9.5 liters] of Kay-5R or 2
gal. [7.6 liters] of Stera-SheenR). USE WARM WA-
TER AND FOLLOW THE MANUFACTURER'S
SPECIFICATIONS. Make sure all brushes provided
with the freezer are available for brush cleaning.
Step 2
Thoroughly brush clean all disassembled parts in the
Figure 63 cleaning solution, making sure all lubricant and mix
film is removed. Be sure to brush all surfaces and
Step 7 holes, especially the holes in the pump components
Remove the two small o-rings and one large o-ring and the draw valve hole in the freezer door.
from the pump drive shaft.
Repeat these steps on the other side of the Rinse all parts with clean, warm water. Place the
Model C716. parts on a clean, dry surface to air dry overnight.
Step 8
Remove the front drip tray and splash shield. Step 3
Return to the freezer with a small amount of
Step 9 cleaning solution. Using the black brush, clean the
Remove all drip pans. Take them to the sink for rear shell bearing at the back of the freezing
cleaning. (See Figure 64.) cylinder. (See Figure 65.)
Figure 64
Note: If the drip pans are filled with an excessive
amount of mix, it is an indication that the drive shaft Figure 65
080617
Figure 66
During Cleaning and Sanitizing j 7. Discard remaining mix from the freezer during
“Cleaning Procedures”.
Troubleshooting Bacterial Count j 3. Using a screwdriver and cloth towel, keep the
rear shell bearing and the female hex drive
socket clean and free of lubricant and mix
j 1. Thoroughly clean and sanitize the machine
regularly, including complete disassembly and deposits.
brush cleaning.
j 4. Dispose of o-rings and seals if they are worn,
j 2. Use all brushes supplied for thorough torn, or fit too loosely, and replace with new
cleaning. The brushes are specially designed ones.
to reach all mix passageways.
j 3. Use the white bristle brush to clean the mix j 5. Follow all lubricating procedures as outlined in
inlet hole which extends from the mix hopper “Assembly”.
down to the rear of the freezing cylinder.
j 6. If your machine is air cooled, check the
j 4. Use the black bristle brush to thoroughly condensers for accumulation of dirt and lint.
clean the rear shell bearing located at the rear Dirty condensers will reduce the efficiency
of the freezing cylinder and the drive hub and capacity of the machine. Condensers
opening in the rear wall of the mix hopper. Be should be cleaned monthly with a soft brush.
sure there is a generous amount of cleaning Never use screwdrivers or other metal probes
solution on the brush. to clean between the fins.
Note: For machines equipped with an air
j 5. Properly prepare the cleaning and sanitizing filter, it will be necessary to vacuum clean the
solutions. Read and follow the label directions
filters on a monthly schedule.
carefully. Too strong of a solution may
damage the parts and too weak of a solution
will not do an adequate job of cleaning or
sanitizing.
Caution: Always disconnect
j 6. The temperature of the mix in the mix hopper electrical power prior to cleaning the
and walk-in cooler should be below 40_F condenser. Failure to follow this instruction
(4.4_C). may result in electrocution.
121008
080222
3. No control panel functions a. Machine is unplugged. a. Plug into wall receptacle. ---
with power switch ON.
b. Circuit breaker OFF or b. Turn the breaker ON or ---
blown fuse. replace the fuse.
5. No product is being a. Low on mix. The MIX a. Add mix to the hopper. 43
dispensed. OUT light is on. Return to AUTO mode.
h. Feed tube or check ring h. Make sure feed tube and 39, 43
not properly installed. rubber check ring are
properly installed.
9. The mix in the hopper is a. The hopper temperature is a. Call an authorized service ---
too cold. out of adjustment. technician.
10. Mix Low and Mix Out a. Milkstone build-up in the a. Clean hoppers thoroughly. 48
probes are not hopper.
functioning.
11. Product is collecting on a. The top o-ring on draw a. Lubricate properly or 36
top of the freezer door. valve is improperly replace the o-ring.
lubricated or worn.
12. Excessive mix leakage a. Bottom o-ring on draw a. Lubricate properly or 36
from the bottom of door valve is improperly replace the o-ring.
spout. lubricated or worn.
15. The freezing cylinder a. Missing or worn front a. Install or replace the front 33, 36
walls are scored. bearing and beater shoes. bearing and beater shoes.
16. The product makes a a. Draw rate is set too fast. a. Adjust draw rate of 5 to 7 19
popping sound when 1/2 oz. (142 g. to 213 g.)
drawn. of product by weight in 10
seconds.
b. Pump assembled b. Assemble and lubricate 38
incorrectly. according to instructions
in this manual.
c. Freezing cylinder not c. Drain the freezing cylinder 43
primed correctly. and reprime the machine.
Door A. X
Scraper Blade X
Drive Shaft Seal X
Freezer Door Gasket X
Front Bearing X
Front Beater Shoes X
Draw Valve O-Ring X
Mix Feed Tube O-Ring X
Pump O-Ring X
Pump Valve Gasket X
Mix Feed Tube Check Ring X
Pump Drive Shaft O-Ring X
White Bristle Brush, 3” x 7” Inspect & Replace Minimum
if Necessary
White Bristle Brush, 3” x 1/2” Inspect & Replace Minimum
if Necessary
White Bristle Brush, 1-1/2” x 3” Inspect & Replace Minimum
if Necessary
White Bristle Brush, 1” x 2” Inspect & Replace Minimum
if Necessary
130227
131121
LEGAL REMEDIES
The owner must notify Taylor in writing, by certified or registered letter to the following address, of any defect or
complaint with the Product, stating the defect or complaint and a specific request for repair, replacement, or other
correction of the Product under warranty, mailed at least thirty (30) days before pursuing any legal rights or
remedies.
Taylor Company
750 N. Blackhawk Blvd.
Rockton, IL 61072, U.S.A.
1, 2Except that Taylor Part #032129SER2 (Compressor-Air-230V SERV) and Taylor Part #075506SER1
(Compressor-Air-115V 60HZ) shall have a limited warranty period of twelve (12) months when used in Taylor
freezer equipment and a limited warranty period of two (2) years when used in Taylor grill equipment.
131121
2. Normal maintenance, cleaning and lubrication as outlined in the Taylor Operator’s Manual, including cleaning
of condensers or carbon and grease buildup.
3. Required service, whether cleaning or general repairs, to return the cooking surface assemblies, including
the upper platen and lower plate, to an operational condition to achieve proper cooking or allow proper
assembly of release sheets and clips as a result of grease build-up on the cooking surfaces, including but
not limited to the platen and plate, sides of the shroud or top of the shroud.
4. Replacement of cooking surfaces, including the upper platen and lower plate, due to pitting or corrosion (or
in the case of the upper platen, due to loss of plating) as a result of damage due to the impact of spatulas or
other small wares used during the cooking process or as a result of the use of cleaners, cleaning materials
or cleaning processes not approved for use by Taylor.
5. Replacement of wear items designated as Class “000” Parts in the Taylor Operator’s Manual, as well as any
release sheets and clips for the Product’s upper platen assembly.
6. External hoses, electrical power supplies, and machine grounding.
7. Parts not supplied or designated by Taylor, or damages resulting from their use.
8. Return trips or waiting time required because a service technician is prevented from beginning warranty
service work promptly upon arrival.
9. Failure, damage or repairs due to faulty installation, misapplication, abuse, no or improper servicing,
unauthorized alteration or improper operation or use as indicated in the Taylor Operator’s Manual, including
but not limited to the failure to use proper assembly and cleaning techniques, tools, or approved cleaning
supplies.
10. Failure, damage or repairs due to theft, vandalism, wind, rain, flood, high water, water, lightning, earthquake
or any other natural disaster, fire, corrosive environments, insect or rodent infestation, or other casualty,
accident or condition beyond the reasonable control of Taylor; operation above or below the gas, electrical or
water supply specification of the unit in which a part is installed; or Parts or the units in which they are
installed repaired or altered in any way so as, in the judgment of Taylor, to adversely affect performance, or
normal wear or deterioration.
LEGAL REMEDIES
The owner must notify Taylor in writing, by certified or registered letter to the following address, of any defect or
complaint with the Part, stating the defect or complaint and a specific request for repair, replacement, or other
correction of the Part under warranty, mailed at least thirty (30) days before pursuing any legal rights or remedies.
Taylor Company
750 N. Blackhawk Blvd.
Rockton, IL 61072, U.S.A.
06/14
BRN/WHT
EXTERNAL EQUIPOTENTIAL
GROUND GROUND
(SEE FIG.4)
L1 L2
BLK
TERMINAL BLOCK
BLK BLU
ORN PUR
BLK
M
MIX
GRN/YEL
PUMP
RED
MOTOR
CLR (+5v) - 8 LEDS
YEL
J1 USER - LCD SCREEN
BLK (GRD) INTERFACE - 9 KEYS START 3 2
J3 BOARD - BEEPER RELAY 4
WHT
WHT WHT
BRN/WHT
JUMPER SETTINGS
JUMPER
UVC4
GRN/YEL GRN/YEL
FIG 2 FUNCTION INSTALLED
BOARD
INITIALLY
BLK BLK
L1 LINE L2
WHT WHT
ALTERNATE MIX PUMP MOTOR WIRING
CABLE
4
WHT
8
A PERIOD OF TIME. LOCKOUT OCCURS WHEN
RED
BARREL
HOT GAS
INTERFACE BOARD SOLENOID
PINS 1 AND 2 BARREL OR HOPPER IS ABOVE 45 F (7 C) YES
POWER TRANSFORMER J16 J4 J2 J7 RELAY
FOR MORE THAN ONE HOUR OR ABOVE 41 F
WHT
RED
BLU/WHT
JP1
BLK
3
2
7
0
RED
BLU
16V STEPS:
(5 C) FOR MORE THAN FOUR HOURS.
4 3 2 1
8 7 6 5
1 23
4 56
SHIELD CUT
NO CONNECTION
UNIVERSAL CONTROL PCB A. WARM FOR A PERIOD OF TIME.
THIS END GRA
BLUE INTERNAL BEATER MOTOR
J17 GRD HOPPER
8
CONTACTOR PINS 3 AND 4 NO
J1
RESERVED (DO NOT USE)
RED
1
BLU
SOLENOID BLACK
CLR J10 J11 T1 L1
RELAY
AGITATOR BLU/WHT
2 DOMESTIC CONFIGURATION-JUMPER INSTALLED.
3
2
7
0
+5V MOTOR
SEE
BLUE HOPPER TEMPERATURE NOT DISPLAYED ON
RIBBON CABLE RIBBON CABLE
DETAIL BLK YEL/BLK 3 SCREEN/HEAT SYMBOL KEYS ONLY ACTIVE
RIBBON
WHT
T2 L2
J2
BLU
BLUE
BLACK INTERNAL
BLU/WHT START BY SELECTING HEAT SYMBOL/STANDBY
8 7 6 5 4 3 2 1 J10 10 9 8 7 6 5 4 3 2 1
J3
BLU/WHT
RED/BLK BLK
KEYS FUNCTIONAL.
J14
GND
BLU
BLK
NC +5V
GRN/YEL COM
GRA/BLK
GRN/YEL
CLR JP3 RESERVED (DO NOT USE) NO
PRP/WHT LEESON BEATER MOTOR WIRING
1 2345678
MIX
PRP/WHT
BLK
JP6 RESERVED (DO NOT USE) NO
BLK
MIX CONTACTOR
SELF SERVICE BLK T8
YEL
LOW
BLK
PROBE
ENABLE
(OPTIONAL) INTFC PCB A.
T1
1 BLACK
JP7 NO
WITH SOFT SERVE
T1 L1 JUMPER INSTALLED DISABLES RESET.
ENABLE PERSONALITY PCB A.
BLK
ON RED BLUE
RTCK RESERVED (DO NOT USE) NO
J9
YEL
4 5 WHT WHT
2
BRN/WHT
L2
L1
J8
J7
J6
DISABLE
OFF BARREL HOPPER BLK BLUE DBGEN RESERVED (DO NOT USE) NO
5 3 11 234567 1 234567 CP CP
--THERMISTOR PROBES--
WHT/RED FUSE
BLK
15A
T7
3 T3 L3
JUMPER
WHT
USE T3 AND L3 WHEN INTERFACE
ON BRN/WHT BRN/WHT
CP CONTACTS ARE NOT AVAILABLE FUNCTION INSTALLED
BOARD
BLK
BLK
BLK
BLK 4 BLACK INITIALLY
POWER OFF BEATER T4 T2 L2
ONE SIDE OF A T5
DPDT TWO WIRE CORD WHT/ORN
BRN/WHT
WHT/ORN
RELAY
*C708* W2 JUMPER INSTALLED-FORCE BRUSH CLEAN STATUS. NO
#3 #1 1
ORN/WHT BLK
BLK BLK ORN OVERLOAD
9 W3 RESERVED (DO NOT USE) NO
5
BARREL SWITCH
W4 JUMPER INSTALLED-OPEN ALL SOLENOIDS. NO
TAN
GE/RBC BEATER MOTOR WIRING
L /
SUCTION
Y RN
COMPRESSOR 4 NOTE: FOR CCWLE - BLUE INTERNAL ON #1,YELLOW INTERNAL ON #2
BLK
BLK
SOLENOID
G
E
HIGH PRESSURE WHT/ORN
12 BEATER MOTOR
LIMIT SWITCH
8 CONTACTOR W5 RESERVED (DO NOT USE) NO
ORN
RED PURPLE J12 OR PURPLE INTERNAL BLACK
M T1 L1
COMPRESSOR MIX 13 14 5
W6 JUMPER INSTALLED-REDUCED MIX LOW SENSITIVITY. NO
BLK
ORN
CONTACTOR PUMP
RED
BLK
WHT
T8 OR RED INTERNAL 4
COIL MOTOR 1
WHT
W7 JUMPER INSTALLED-REDUCED MIX OUT SENSITIVITY. NO
YEL
BLUE
(SEE FIG 2)
SNUBBER
BLK BLK BEATER CP CP
2
START 3 2 MOTOR BEATER BLK J9 OR BLACK INTERNAL A
T3 L3
BEATER STARTER
RELAY MOTOR USE T3 AND L3 WHEN CP JUMPER INSTALLED-ENABLES 59 F HOPPER
MOTOR 4 COIL WHT
INTERLOCK BLK CONTACTS ARE NOT AVAILABLE PINS 1 & 2 YES
OVERLOAD TEMPERATURE CHECK.
BLK
BLK
BLACK
WHT
WHT
SWITCH N.O. SWITCH T4 OR YELLOW INTERNAL T2 L2
WHT J10 JUMPER INSTALLED W/SWITCH-SELF SERVE
FIG. 3 APPLICATION ONLY. LOCKS OUT TOUCH
BLK PINS 7 & 8 NO
PANEL. NEW SWITCH ACTS AS THE ON/OFF
WHT/GRA
BLK
HOPPER
LIQUID
ABILITY TO ACTIVATE THE TOUCH PANEL.
SOLENOID BLK
SOFT SERVE
WHT/BRN LIV A PERSONALITY 0-6 AMP BEATER MOTOR AMPERAGE RANGE NO
SOLENOID BLK
M ADDITIONAL DRAW SWITCH BOARD
GRA/WHT
BLK BLK BLK
FOR FLAVORBURST
BARREL
SOFT SERVE
LOAD
LIQUID GRN/YEL
LINE
BLUE
SOLENOID BLK M B PERSONALITY 0-12 AMP BEATER MOTOR AMPERAGE RANGE YES
WHT
PANEL
LINE
GRN/
YEL
WHT JACK BOARD
SOFT SERVE WHT BLK BLK
BLK
RED
BLK
BEATER MOTOR
BLK BLK
L1 T1 M T2 L2 LINE FILTER SE NC
GRN/
BLK BEATER MOTOR
YEL
SOFT SERVE STARTER (SEE FIG 3) C0M THERMOSTAT
COMPRESSOR BEATER MOTOR
STARTER SPINNER MOTOR WIRING 140° OPEN O.T.
BLUE
BLK BLK
L1 T1 M T2 L2
BLK DRAW 100° CLOSE
012626
GRN/
FIG. # 1 SWITCH NO WHT WHT WHT
YEL
COMPRESSOR
BLU/WHT
BRN/WHT CONTACTOR
L /
Y RN
208-230 VAC
G
E
CONDENSER LEFT SYRUP HEATER
BLU BLU BLU BLU BLUE FAN MOTOR BLK
AGITATOR MOTOR C
M BLK
DETAIL NO
GRN
LOW PRESSURE BROWN BLU
FAN SWITCH
THERMOSTAT
140° OPEN O.T.
100° CLOSE
WHT WHT WHT
AIR COOLED ONLY
BLK BLK WHT
BLK M RIGHT SYRUP HEATER
YEL
GRN/
BLK WHT
A
PANEL SPINNER OPTION
SEE FIG. 1
WHT
WIRE COLORS - BASED ON INCOMING POWER
OPTIONAL HEATED SYRUP RAIL
208/230 VOLTS, 60HZ 208/230 VOLTS, 60HZ
(DOMESTIC) (INTERNATIONAL)
INTERNAL OVERLOAD
WHITE(120 VOLTS)
BLACK(230 VOLTS)
COMPRESSOR
TERMINAL
L1 L2 L1 L2 OR N NOTE: GROUND FRAME SECURELY
WHITE
C C S COVER
LINE
1. STATIC ELECTRICITY MAY CAUSE
BLACK
R DAMAGE TO SOLID STATE COMPONENTS.
RELAY
RELAY RUN
ELIMINATE STATIC ELECTRICITY BY
BROWN
CAP. TOUCHING GROUNDED UNIT BEFORE
5 2 S
HANDLING SOLID STATE COMPONENTS.
BLK
BLK
2
BLK
5
BLK
BROWN LINE
EQUIPMENT 2. RED WIRE ON RIBBON CABLES MUST BE
GROUND 4 1
4 1 CONNECTED TO PIN 1 AT EACH END.
BLACK
BLUE R
RUN CAPACITOR
START CAP.
FIG. 4
START CAPACITOR
BLEED RESISTOR
ABOVE ELECTRICAL DIAGRAM SHOWS WIRING NECESSARY
SCHEMATIC WIRING DIAGRAM - CSR 052396-1 TO HOOK UP A COMPRESSOR USING A STAR T AND RUN
CAPACITOR (CSR) WITH A RELAY.
Taylor Company
Model C708
057010-33
BLK
06/14
BLU
ORN PUR
M
MIX
PUMP
RED
MOTOR
YEL
3 2
START
RELAY 4
WHT
FIG 2
ALTERNATE MIX PUMP MOTOR WIRING
JUMPER SETTINGS
BLK BLK
JUMPER
UVC4
BRN/WHT
FUNCTION INSTALLED
BOARD
EXTERNAL EQUIPOTENTIAL
GROUND GROUND
INITIALLY
L1 L2 L3
SE JUMPER INSTALLED- BARREL AND HOPPER
TERMINAL BLOCK
TEMPERATURES ARE CHECKED DURING
BLK AUTO/STANDBY. UNIT IS LOCKED OUT IF
EITHER BARREL OR HOPPER IS TOO WARM FOR
BLK
BLK
M
GRN/YEL
BLUE
WHT
BRN/WHT
WHT WHT NO JUMPER INSTALLED-NO LOCKOUT DURING
AUTO/STANDBY IF BARREL OR HOPPER IS TOO
GRN/YEL GRN/YEL WARM FOR A PERIOD OF TIME.
RED
BLK BLK WHT WHT
PINS 3 AND 4 RESERVED (DO NOT USE) NO
CABLE
4
WHT
8
RED
BARREL
HOT GAS
INTERFACE BOARD SOLENOID
STANDBY KEYS DISABLED.
BLUE
J16 J4 J2 J7
JP2 PINS 1 AND 2 YES
WHT
J9
GRN
RED
BLK
3
6
7
0
INTERNATIONAL CONFIGURATION-NO JUMPER
RED
BLU
16V
4 3 2 1
8 7 6 5
1 23
4 56
J13
BLK GRA
INSTALLED. HOPPER TEMPERATURES
J12 DISPLAYED ON SCREEN/MANUAL HEAT CYCLE
BLU/WHT
J15 J8 BARREL BRN/WHT
HOT GAS
SOLENOID
START BY SELECTING HEAT SYMBOL/STANDBY
BRN/WHT
SHIELD CUT
UNIVERSAL CONTROL PCB A.
NO CONNECTION
THIS END
KEYS FUNCTIONAL.
J17 GRD GRA
HOPPER
8
J1
JP3 RESERVED (DO NOT USE) NO
RED
BLU
CLR SOLENOID
J10 J11
AGITATOR BLU/WHT
RELAY AGITATOR MOTOR JP4 RESERVED (DO NOT USE) NO
3
2
7
0
+5V MOTOR
RIBBON CABLE SEE DETAIL
DETAIL BLK YEL/BLK JP5 RESERVED (DO NOT USE) NO
RIBBON
BLU/WHT
SOLENOID
WHT
WHT BLK
GRN/YEL GRN/YEL
SV CABLE SV CABLE JP7 JUMPER INSTALLED DISABLES RESET. NO
BLU BLU/WHT
24 VAC RTCK RESERVED (DO NOT USE) NO
RED
BA
WHT
J2
BLU
BLU/WHT BLUE DBGEN RESERVED (DO NOT USE) NO
8 7 6 5 4 3 2 1 J10 10 9 8 7 6 5 4 3 2 1
J3
BLU/WHT
RED/BLK BLK
J14
GND
JUMPER
BLU
BLK
+5V
NC
GRA/BLK CLR
ADDITIONAL DRAW SWITCH INTERFACE
GRN/YEL COM GRN/YEL FUNCTION INSTALLED
BLK
BLK
FOR FLAVORBURST INITIALLY
1 2345678
NO
J13
HOPPER
J5
MIX
PRP/WHT
BLK
W2 JUMPER INSTALLED-FORCE BRUSH CLEAN STATUS. NO
BLK
MIX
SELF SERVICE BLK
PANEL
YEL
LOW
BLK
ENABLE
PROBE (OPTIONAL) INTFC PCB A.
WITH SOFT SERVE JACK W3 RESERVED (DO NOT USE) NO
ENABLE PERSONALITY PCB A.
ON
BLK
RED
W4 JUMPER INSTALLED-OPEN ALL SOLENOIDS. NO
J9
L2
L1
J8
J7
J6
BLK
BLK
BLK
BLK
POWER OFF BEATER
JUMPER INSTALLED-ENABLES 59 F HOPPER
BLU
ONE SIDE OF A
DPDT TWO WIRE CORD WHT/ORN
DRAW TEMPERATURE CHECK.
BRN/WHT
WHT/ORN
RELAY
#3 #1 *C708* 1
SWITCH NO J10 JUMPER INSTALLED W/SWITCH-SELF SERVE
ORN/WHT BLK
9 APPLICATION ONLY. LOCKS OUT TOUCH
BLK BLK ORN OVERLOAD
5 PINS 7 & 8 NO
BARREL SWITCH GRN/
YEL
PANEL. NEW SWITCH ACTS AS THE ON/OFF
TAN
COMPRESSOR SUCTION 4
ABILITY TO ACTIVATE THE TOUCH PANEL.
BLK
BLU
HIGH PRESSURE SOLENOID WHT/ORN
12
LIMIT SWITCH
ORN
8
RED PUR SOFT SERVE
ORN
M
13
COMPRESSOR MIX 14 A PERSONALITY 0-6 AMP BEATER MOTOR AMPERAGE RANGE NO
BLK
CONTACTOR PUMP
RED
BLK
WHT
SNUBBER
WHT COIL MOTOR BEATER BOARD
YEL
(SEE FIG 2) MOTOR
BLK BLK
START 3 2 STARTER BEATER BLACK SOFT SERVE
BEATER COIL
RELAY MOTOR
MOTOR 4
B PERSONALITY 0-12 AMP BEATER MOTOR AMPERAGE RANGE YES
BLK
BLK
WHITE
WHT
BLK
INTERLOCK BLACK
WHT
OVERLOAD
SWITCH N.O. SWITCH BOARD
WHT WHT
BLK
WHT/GRA
BLK
HOPPER THERMOSTAT
LIQUID 140° OPEN
SOLENOID O.T.
BLK 100° CLOSE
012626 WHT WHT WHT
WHT/BRN
LIV BLK BLK BLK
SOLENOID BLK
BLK
GRA/WHT
BARREL
LOAD
LIQUID GRN/YEL 200-240 VAC
LINE
SOLENOID BLK LEFT SYRUP HEATER
M BLK C
YEL
GRN/
LINE
WHT
SOFT SERVE NO
GRN GRN/YEL
BLK
BLK
BEATER MOTOR
BLK BLK BLK
L1 T1 M T2 L2
WHT BLK BLK
GRN/
THERMOSTAT
YEL
BLK BEATER MOTOR BLK BLK
SOFT SERVE STARTER T3 L3 140° OPEN O.T.
COMPRESSOR BEATER MOTOR 100° CLOSE
BLK BLK BLK STARTER WHT WHT WHT
L1 T1 M T2 L2
COMPRESSOR
T3 L3
BLK LINE FILTER
GRN/
CONTACTOR
YEL
GRN/
I3 I4 YEL
CONDENSER RIGHT SYRUP HEATER
BLU BLU BLU BLUE FAN MOTOR
M
BLK
SPINNER MOTOR WIRING
FIG. # 1 BLK
A WHT
OPTIONAL BROWN BLU
LOW PRESSURE
FAN SWITCH
WHT
AIR COOLED ONLY OPTIONAL HEATED SYRUP RAIL
BLK BLK WHT
BRN/WHT BLK M
GROUND FRAME SECURELY
GRN/
YEL
PANEL SPINNER OPTION
SEE FIG. 1
NOTE:
1. STATIC ELECTRICITY MAY CAUSE
DAMAGE TO SOLID STATE COMPONENTS.
ELIMINATE STATIC ELECTRICITY BY
TOUCHING GROUNDED UNIT BEFORE
HANDLING SOLID STATE COMPONENTS.
2. RED WIRE ON RIBBON CABLES MUST BE
CONNECTED TO PIN 1 AT EACH END.
Taylor Company
Model C708
057010-40
BLK
BLU
ORN PUR
M
06/14
MIX
PUMP
RED
MOTOR
YEL
3 2
START
RELAY 4
WHT
FIG 2
BLK BLK ALTERNATE MIX PUMP MOTOR WIRING
BRN/WHT
EXTERNAL EQUIPOTENTIAL
GROUND GROUND
L1 N
TERMINAL BLOCK
BRN
JUMPER SETTINGS
A.O. SMITH BEATER MOTOR WIRING
BLUE
GRN/YEL
STEPS: JUMPER
1) REMOVE BROWN JUMPER FROM BETWEEN TERMINAL #1 TO TERMINAL #5 UVC4
CLR (+5V)
J1 - 8 LEDS FUNCTION INSTALLED
BLK (GRD)
USER - LCD SCREEN 2) MOVE BLUE INTERNAL (FROM MOTOR MAIN WINDING) BOARD
J3 INTERFACE - 9 KEYS INITIALLY
BOARD - BEEPER FROM TERMINAL #5 TO TERMINAL #1.
BRN/WHT
NOTE: FOR CCWLE - BLUE INTERNAL ON #1, YELLOW INTERNAL ON #6 JUMPER INSTALLED- BARREL AND HOPPER
WHT WHT
TEMPERATURES ARE CHECKED DURING
AUTO/STANDBY. UNIT IS LOCKED OUT IF
GRN/YEL GRN/YEL ELECTRICAL EITHER BARREL OR HOPPER IS TOO WARM FOR
ENCLOSURES A PERIOD OF TIME. LOCKOUT OCCURS WHEN
BLK BLK WHT WHT
L1 LINE L2 BLUE INTERNAL BEATER MOTOR PINS 1 AND 2 BARREL OR HOPPER IS ABOVE 45 F (7 C) YES
CABLE
RIBBON CABLE
EMI FILTER
L1 LOAD L2 BRN/WHT CONTACTOR JP1 FOR MORE THAN ONE HOUR OR ABOVE 41 F
240V
RIBBON CABLE ORANGE INTERNAL 1 BLACK
(5 C) FOR MORE THAN FOUR HOURS.
BLK
NOT
CONNECTED WHT T1 L1
NO JUMPER INSTALLED-NO LOCKOUT DURING
GRA/BLK
2
ORN
BLK
4
WHT
8
RED
BARREL
AUTO/STANDBY IF BARREL OR HOPPER IS TOO
HOT GAS BLUE
INTERFACE BOARD SOLENOID WARM FOR A PERIOD OF TIME.
J16 J4 J2 J7
3
WHT
J9
GRN
RED
BLK
3
2
7
0
RED
BLU
16V
4 3 2 1
8 7 6 5
SHIELD CUT
UNIVERSAL CONTROL PCB A.
NO CONNECTION
THIS END
HOT GAS
SOLENOID
SCREEN/HEAT SYMBOL KEYS ONLY ACTIVE
J17 GRD GRA
HOPPER
USE T3 AND L3 WHEN WHEN A LOCKOUT CONDITION HAS OCCURRED/
8
J1
RED
3
2
7
0
INTERNATIONAL CONFIGURATION-NO JUMPER
BLU/WHT
BLU
BLU BLU BLU
M
RED
HOPPER DISPLAYED ON SCREEN/MANUAL HEAT CYCLE
HOT GAS COM 240 START BY SELECTING HEAT SYMBOL/STANDBY
WHT
JP4 NO
J2
BLU/WHT
RED/WHT BLU BLK/RED
1) DISCONNECT WIRE T7 FROM TERMINAL 3 RESERVED (DO NOT USE)
8 7 6 5 4 3 2 1 J10 10 9 8 7 6 5 4 3 2 1
J3
BLU/WHT
GRN/YEL
RED/BLK BLK
J14
GND
BLUE
BLK
NC +5V
GRA/BLK CLR BEATER MOTOR JP6 RESERVED (DO NOT USE) NO
GRN/YEL COM GRN/YEL
PRP/WHT
T8 CONTACTOR
1 2345678
NO
1 BLACK JP7 JUMPER INSTALLED DISABLES RESET. NO
J13
HOPPER T1
J5
MIX T1 L1
PRP/WHT
BLK
BLK
LOW
2
BLK
ENABLE
PROBE (OPTIONAL) INTFC PCB A.
WITH SOFT SERVE
BLUE
ON
ENABLE PERSONALITY PCB A.
CP CP JUMPER
BLK
RED/WHT
INTERFACE
J9
BOARD
L1
L2
J8
J7
J6
BLK
BLK
BLK
BLK T4 T2 L2
POWER OFF
GRN/YEL GRN/YEL BEATER W3 RESERVED (DO NOT USE) NO
SWITCH INTERLOCK T5
BLK
BLK
ONE SIDE OF A
DPDT
BLU
BLU/WHT
ORG/WHT BLK
1 W5 RESERVED (DO NOT USE) NO
9
BLK BLK ORN OVERLOAD
BARREL SWITCH
5 W6 JUMPER INSTALLED-REDUCED MIX LOW SENSITIVITY. NO
BLUE
TAN
COMPRESSOR SUCTION L 4
E
BLK
SOLENOID
HIGH PRESSURE
R
N
/Y WHT/ORN
12 W7 JUMPER INSTALLED-REDUCED MIX OUT SENSITIVITY. NO
ORN
LIMIT SWITCH
ORN
G
8
RED PUR
M GE/RBC BEATER MOTOR WIRING JUMPER INSTALLED-ENABLES 59 F HOPPER
COMPRESSOR MIX 13 14 NOTE: FOR CCWLE - BLUE INTERNAL ON #1,YELLOW INTERNAL ON #2 PINS 1 & 2 YES
BLK
TEMPERATURE CHECK.
SNUBBER
CONTACTOR PUMP
RED
BLK
WHT
COIL MOTOR BEATER BEATER MOTOR
GRN/YEL
WHT
YEL
96 95 (SEE FIG 2) MOTOR CONTACTOR
BLK BLK
START 3 2 STARTER
BEATER BLK J12 OR PURPLE INTERNAL BLACK J10 JUMPER INSTALLED W/SWITCH-SELF SERVE
BEATER COIL T1 L1
RELAY MOTOR 5 APPLICATION ONLY. LOCKS OUT TOUCH
MOTOR 4
WHT BLK PINS 7 & 8 NO
WHT
WHT
INTERLOCK T1 OR BLUE INTERNAL PANEL. NEW SWITCH ACTS AS THE ON/OFF
BLK
BLUE
BLK
OVERLOAD
SWITCH N.O. SWITCH T8 OR RED INTERNAL 4
1 ABILITY TO ACTIVATE THE TOUCH PANEL.
ORN
BLUE
WHT CP CP
WHT J9 OR BLACK INTERNAL A
2 SOFT SERVE
T3 L3
A PERSONALITY 0-6 AMP BEATER MOTOR AMPERAGE RANGE NO
USE T3 AND L3 WHEN CP
WHT/GRA
HOPPER BLK
CONTACTS ARE NOT AVAILABLE BOARD
LIQUID GRN/YEL BLK
SOLENOID BLACK
T4 OR YELLOW INTERNAL T2 L2 SOFT SERVE
WHT
B PERSONALITY 0-12 AMP BEATER MOTOR AMPERAGE RANGE YES
WHT/BRN GRN/YEL
LIV BOARD
FIG. 3
GRA/WHT
SOLENOID WHT
BARREL GRN/YEL
LIQUID
SOLENOID WHT
SOFT SERVE THERMOSTAT
BLK
BLK
BEATER
MOTOR
GRN/YEL
SE 140° OPEN O.T.
100° CLOSE
BLK BLK
012626 WHT WHT WHT
L1 T1 M T2 L2
BLK BEATER MOTOR
SOFT SERVE STARTER M
COMPRESSOR BEATER MOTOR
BLK BLK BLK
BRN BLK BLK BLUE STARTER 200-240 VAC
L1 T1 M T2 L2
LEFT SYRUP HEATER
LOAD
COMPRESSOR GRN/YEL C
LINE
GRN/YEL
BLUE
CONTACTOR GRN/YEL BLK
WHT
COMPRESSOR M NO
LINE
CONTACTOR CONDENSER GRN GRN/YEL
FAN MOTOR
BLU BLU BLU BLUE BLK
WHT BLK BLK
RED
M THERMOSTAT
140° OPEN O.T.
100° CLOSE
LOW PRESSURE
FAN SWITCH
LINE FILTER WHT WHT WHT
BRN BLU
AIR COOLED ONLY SPINNER MOTOR WIRING
BLUE
FIG. # 1 RIGHT SYRUP HEATER
BLK
BLU/WHT
WHT
A
BLK BLK WHT
BRN/WHT BLK M
WHT
PANEL SPINNER OPTION
SEE FIG. 1
GRN/YEL
AGITATOR MOTOR
DETAIL OPTIONAL HEATED SYRUP RAIL
ADDITIONAL DRAW SWITCH
INTERNAL OVERLOAD
WHITE(120 VOLTS) COMPRESSOR
FOR FLAVORBURST GROUND FRAME SECURELY
BLACK(230 VOLTS) WHITE TERMINAL
C C S COVER
LINE
BLACK
R
PANEL
RELAY JACK NOTE:
RELAY RUN
CAP.
BROWN
5 2 S 1. STATIC ELECTRICITY MAY CAUSE
5 2
BROWN LINE DAMAGE TO SOLID STATE COMPONENTS.
NC
ELIMINATE STATIC ELECTRICITY BY
EQUIPMENT C0M
GROUND 4 1
4
TOUCHING GROUNDED UNIT BEFORE
1
BLACK HANDLING SOLID STATE COMPONENTS.
BLUE R DRAW
START CAP.
SWITCH NO
START CAPACITOR
RUN CAPACITOR 2. RED WIRE ON RIBBON CABLES MUST BE
BLEED RESISTOR ABOVE ELECTRICAL DIAGRAM SHOWS WIRING NECESSARY
TO HOOK UP A COMPRESSOR USING A STAR T AND RUN CONNECTED TO PIN 1 AT EACH END.
SCHEMATIC WIRING DIAGRAM - CSR 052396-1 CAPACITOR (CSR) WITH A RELAY.
Taylor Company
Model C708
057010-58
06/14
BLK
BLU
ORN PUR
M
MIX
PUMP
RED
MOTOR
YEL
3 2
START
BLK BLK RELAY 4
WHT
BRN/WHT BRN/WHT
EXTERNAL EQUIPOTENTIAL
GROUND GROUND
L1 L2 L3 N
FIG 2
TERMINAL BLOCK
ALTERNATE MIX PUMP MOTOR WIRING JUMPER SETTINGS
BRN
JUMPER
GRN/YEL
UVC4
BLU
BLK
BLK
FUNCTION INSTALLED
CLR (+5V) BOARD
J1 USER
- 8 LEDS INITIALLY
BLK (GRD) - LCD SCREEN
INTERFACE
J3 - 9 KEYS
BOARD
- BEEPER JUMPER INSTALLED- BARREL AND HOPPER
TEMPERATURES ARE CHECKED DURING
AUTO/STANDBY. UNIT IS LOCKED OUT IF
BRN
WHT WHT
ADDITIONAL DRAW SWITCH EITHER BARREL OR HOPPER IS TOO WARM FOR
ELECTRICAL
GRN/YEL GRN/YEL
A PERIOD OF TIME. LOCKOUT OCCURS WHEN
ENCLOSURE
FOR FLAVORBURST BARREL OR HOPPER IS ABOVE 45 F (7 C)
BLK BLK WHT WHT PINS 1 AND 2 YES
L1 LINE L2
JP1 FOR MORE THAN ONE HOUR OR ABOVE 41 F
CABLE
WHT
EMI FILTER
L1 LOAD L2 BRN/WHT (5 C) FOR MORE THAN FOUR HOURS.
WHT
240V
BLK
NOT
WHT
RIBBON CABLE PANEL NO JUMPER INSTALLED-NO LOCKOUT DURING
CONNECTED
JACK AUTO/STANDBY IF BARREL OR HOPPER IS TOO
ORN
GRA/BLK
BLK
4
WHT
8
RED
BARREL
HOT GAS WARM FOR A PERIOD OF TIME.
INTERFACE BOARD J7
SOLENOID
J16 J4 J2
WHT
J9
GRN
RED
BLK
RELAY
POWER TRANSFORMER BLU/WHT
PINS 3 AND 4 RESERVED (DO NOT USE) NO
3
2
7
0
RED
BLU
16V
4 3 2 1
8 7 6 5
1 23
4 56
J13
GRN/YEL
BRN/WHT DOMESTIC CONFIGURATION-JUMPER INSTALLED.
NC
J12
J15 J8 BLK GRA HOPPER TEMPERATURE NOT DISPLAYED ON
BARREL C0M SCREEN/HEAT SYMBOL KEYS ONLY ACTIVE
BRN/WHT
SHIELD CUT
UNIVERSAL CONTROL PCB A. HOT GAS
NO CONNECTION
THIS END SOLENOID
WHEN A LOCKOUT CONDITION HAS OCCURRED/
J17 GRD GRA
HOPPER STANDBY KEYS DISABLED.
8
J1
DRAW
RED
BLU
CLR SOLENOID
J10 J11
BLU/WHT RELAY SWITCH INTERNATIONAL CONFIGURATION-NO JUMPER
AGITATOR NO
3
2
7
0
BLU/WHT
BLU RED
BLU BLU BLU
M HOPPER START BY SELECTING HEAT SYMBOL/STANDBY
HOT GAS
COM 240
KEYS FUNCTIONAL.
WHT
BLK/RED
J2
GRN/YEL
RESERVED (DO NOT USE)
8 7 6 5 4 3 2 1 J10 10 9 8 7 6 5 4 3 2 1
J3
BLU
BLU/WHT
RED/BLK BLK
J14
GND
JP6 RESERVED (DO NOT USE) NO
BLUE
BLK
NC +5V CLR
GRA/BLK
GRN/YEL GRN/YEL BEATER MOTOR WIRE MUST GO
COM
PRP/WHT THRU SENSOR CORE TWICE
JP7 JUMPER INSTALLED DISABLES RESET. NO
1 2345678
NO
J13
MIX
SE
PRP/WHT
BLK
BLK
MIX BLK
SELF SERVICE
YEL
LOW
BLK
ENABLE
PROBE (OPTIONAL) INTFC PCB A.
JUMPER
ON
ENABLE
WITH SOFT SERVE
PERSONALITY PCB A. M INTERFACE
FUNCTION INSTALLED
BLK
RED/WHT
BOARD
J9
L2
L1
J8
J7
J6
BLK
BLK
RED
5 3 11 234567 1 234567
W1 RESERVED (DO NOT USE) NO
BLUE
WHT/RED
--THERMISTOR PROBES-- FUSE
WHT
BLK
15A
W2 JUMPER INSTALLED-FORCE BRUSH CLEAN STATUS. NO
BRN
WHT
ON BRN/WHT BRN/WHT
BLK
BLK
GRN/YEL GRN/YEL
W3 RESERVED (DO NOT USE) NO
POWER OFF BEATER
SWITCH W4 JUMPER INSTALLED-OPEN ALL SOLENOIDS. NO
BLU
INTERLOCK
BLK
BLK
ONE SIDE OF A
DPDT TWO WIRE CORD WHT/ORG WHT/ORG
BRN/WHT
RELAY
W5 RESERVED (DO NOT USE) NO
BLU/WHT
*C708*
ORG/WHT BLK
1
9 W6 JUMPER INSTALLED-REDUCED MIX LOW SENSITIVITY. NO
BLUE
BLK BLK ORN OVERLOAD
5
BLU/WHT
BARREL SWITCH
W7 JUMPER INSTALLED-REDUCED MIX OUT SENSITIVITY. NO
BLUE
COMPRESSOR SUCTION L 4
E
TAN
BLK
HIGH PRESSURE SOLENOID /Y WHT/ORN
N 12
ORN
ORN
LIMIT SWITCH R
G
8 JUMPER INSTALLED-ENABLES 59 F HOPPER
RED
M
PUR PINS 1 & 2 YES
COMPRESSOR MIX BLK 13 14 TEMPERATURE CHECK.
BLK
SNUBBER
CONTACTOR BEATER
PUMP
RED
BLK
WHT
COIL MOTOR MOTOR
GRN/YEL
WHT
J10 JUMPER INSTALLED W/SWITCH-SELF SERVE
YEL
96 95 (SEE FIG 2) RELAY
BLK BLK
3 2 COIL BEATER APPLICATION ONLY. LOCKS OUT TOUCH
START PINS 7 & 8 NO
BLK
BEATER
BLK
WHT
AGITATOR
WHT
MOTOR
RELAY 4
WHT
MOTOR BLK
PANEL. NEW SWITCH ACTS AS THE ON/OFF
INTERLOCK
OVERLOAD ABILITY TO ACTIVATE THE TOUCH PANEL.
SWITCH N.O. SWITCH
MOTOR DETAIL
WHT WHT
ORN SOFT SERVE
WHT WHT
A PERSONALITY 0-6 AMP BEATER MOTOR AMPERAGE RANGE NO
WHT/GRA
HOPPER GRN/YEL BLK
LIQUID GRN/YEL BOARD
SOLENOID BLK
WHT
SOFT SERVE
WHT/BRN
LIV GRN/YEL B PERSONALITY 0-12 AMP BEATER MOTOR AMPERAGE RANGE YES
SELENOID BOARD
GRA/WHT
WHT
BARREL GRN/YEL
LIQUID
SOLENOID WHT
SOFT SERVE
BLK
BLK
BEATER
GRN/YEL THERMOSTAT
BEATER MOTOR
MOTOR 140° OPEN O.T.
STARTER
BLK L1 T1 M
BLK
T2 L2
BLK
BLK BLK BLK 012626
100° CLOSE
WHT WHT WHT
BLK SOFT SERVE
BLK
LOAD
COMPRESSOR T3 L3
GRN/YEL
LINE
BRN BRN BLK
M
BLK BLK GRN/YEL
L1
COMPRESSOR
T1 T2 L2
M 200-240 VAC
LEFT SYRUP HEATER
LINE
BLK
T3 L3 C
CONTACTOR BLK
GRN/YEL NO
GRN GRN/YEL
CONDENSER
BLU BLU BLU BLU FAN MOTOR BLK WHT WHT BLK BLK
M
N THERMOSTAT
BR
140° OPEN O.T.
LOW PRESSURE 100° CLOSE
FAN SWITCH AIR COOLED ONLY
BRN BLU
LINE FILTER WHT WHT WHT
GRN/YEL
SPINNER MOTOR WIRING RIGHT SYRUP HEATER
FIG. # 1 BLK WHT
BLK BLK WHT
A
BRN/WHT
BLK M
PANEL SPINNER OPTION WHT
GRN/YEL
SEE FIG. 1
OPTIONAL HEATED SYRUP RAIL
NOTE:
GROUND FRAME SECURELY
1. STATIC ELECTRICITY MAY CAUSE
DAMAGE TO SOLID STATE COMPONENTS.
ELIMINATE STATIC ELECTRICITY BY
TOUCHING GROUNDED UNIT BEFORE
HANDLING SOLID STATE COMPONENTS.
2. RED WIRE ON RIBBON CABLES MUST BE
CONNECTED TO PIN 1 AT EACH END.
SE
BLUE
WHT
NOTE: FOR CCWLE - BLUE INTERNAL ON #1,YELLOW INTERNAL ON #2
BEATER MOTOR
RED
CONTACTOR
J12 OR PURPLE INTERNAL BLACK
T1 L1
5
T1 OR BLUE INTERNAL BLUE
T8 OR RED INTERNAL 4
1
BLUE
BLUE
CP CP
BLU/WHT
2
J9 OR BLACK INTERNAL A
T3 L3
USE T3 AND L3 WHEN CP
CONTACTS ARE NOT AVAILABLE
AGITATOR MOTOR BLACK
T4 OR YELLOW INTERNAL T2 L2
DETAIL
EXTERNAL EQUIPOTENTIAL
GROUND GROUND
GRN/YEL
2) MOVE BLUE INTERNAL (FROM MOTOR MAIN WINDING)
BLK
FROM TERMINAL #5 TO TERMINAL #1.
NOTE: FOR CCWLE - BLUE INTERNAL ON #1, YELLOW INTERNAL ON #6
- 8 LEDS BLUE INTERNAL
BLK/BLU
RED (+5v) USER BEATER MOTOR
J1 - LCD SCREEN CONTACTOR
INTERFACE
BLK/BLU
BLK (GRD) J2 - 9 KEYS ORANGE INTERNAL 1 BLACK
(+5v) J3 BOARD T1 L1
CLR - BEEPER
(GRD) 2
GRN BLUE
3
GRN/YEL GRN/YEL RED INTERNAL 4 BLUE
CP CP
BLK BLK WHT WHT
L1 LINE L2 5 T3 L3
RIBBON CABLE
EMI FILTER USE T3 AND L3 WHEN
L1 LOAD L2 CABLE CP CONTACTS ARE NOT AVAILABLE
240V YELLOW INTERNAL 6
RIBBON CABLE BLACK
NOT T2 L2
CONNECTED WHT BLACK INTERNAL
WHT
ORN
RED
BLK
WHT
GRN
RED
BLK
INTERFACE BOARD J16 J4 J2 J7 J9
POWER TRANSFORMER
RED
BLU
1 23
4 56
16V J13
STEPS:
BLK/BLU
J15 J8 WHT GRA
J12 GRD 1) DISCONNECT WIRE T7 FROM TERMINAL 3
BARREL 2) SPLICE BLUE WIRE AS SHOWN
UNIVERSAL CONTROL PCB A.
HOT GAS BEATER MOTOR
J17 SOLENOID T8 CONTACTOR
J1
RED
BLU
BLK 1 BLACK
21
T1 T1 L1
RIBBON
CLR AGITATOR
CABLE
J10 J11
WHT
MOTOR BLUE
+5V
SEE 2
RIBBON CABLE RIBBON CABLE DETAIL WHT YEL WHT BLK/BLU BLUE
RED RED RED BLU M RED CP CP
BLU BLU BLU
WHT
HOPPER
COM 208 3
HOT GAS T7 T3 L3
GRN/YEL GRN/YEL
SOLENOID USE T3 AND L3 WHEN
SV CABLE SV CABLE
BLU BLU/WHT CP CONTACTS ARE NOT AVAILABLE
RED
RED
24 VAC 4 BLACK T2 L2
T4
T
BA
GRN/YEL
WH
T5
J2
J3
8 7 6 5 4 3 21J10 10 9 8 7 6 5 4 3 21
BLU/WHT BLUE
ORN/WHT ORN/WHT GND GRN BLK
FIG. 1
J14
+5V CLR
NO YEL RED/BLK J19 2
BLK
GRN/YEL COM
PRP 1 TAN
BLU
NC
J13
J1
HOPPER WHT/RED
J5
MIX
1 234
J11
GROUND
J12
DRAW OUT
PRP
BLK TAN
B
TAN
A
SWITCH PROBE
YEL
WHT
BLK
BLK
YEL
MIX
BLK
BLK
BLK
LOW SELF-SERVICE
BLK
J18
TAN
PROBE ENABLE INTFC PCB A.
DISABLE ENABLE WITH SOFT SERVE
ON RED PERSONALITY PCB A. 2
1
J9
1 3 WHT WHT
L2
L1
J8
J7
J6
OFF BLK
BARRELHOPPER (OPTIONAL) 5 3 1 1 234567 1 23456 7 FUSE BLK
WHT/RED 15A SEE FIG. 4 WHT
--THERMISTOR PROBES--
OPTIONAL THERMOSTAT
BLK BLK 140 F OPEN
ON BLK/WHT BLK/WHT BLK WHT
RED
BLK 100 F CLOSE
O.T.
BLK WHT WHT WHT
POWER WHT
BLK/WHT
BLK
BLK
SWITCH INTERLOCK
DPDT WHT/ORN
WHT/ORN RELAY
BLK
BLU
BLK
SUCTION 4
TAN
COMPRESSOR
HIGH PRESSURE SOLENOID WHT/ORN 12
ORN
BLU
WHT
BLU
LIMIT SWITCH 8
RED ORN M PRP
FIG .4
BLK
BLK COMPRESSOR 13 14
BLU/WHT
MIX
RED
BLK
WHT
CONTACTOR PUMP
PANEL
YEL
C
COIL MOTOR
L
96 95
BLK
JACK BLK BLK WHT BEATER BLACK
START 3 2 MOTOR BEATER
BEATER RELAY STARTER MOTOR
4
WHT
COIL
BLK
MOTOR
BLK
WHT
OVERLOAD WHT INTERLOCK
SWITCH N.O. SWITCH
NC RED
C0M WHT
WHT/GRA
BLK
HOPPER BLK COMPRESSOR
DRAW LIQUID WHT TERMINAL
GRA/WHT
C S COVER
SWITCH NO SOLENOID WHT
LEFT FAN INTERNAL OVERLOAD
R
RUN
PRESSURE LIV WHITE(120 VOLTS) RELAY
CAP.
SWITCH SOLENOID BLACK(230 VOLTS)
WHT/BRN WHT
GRN/YEL
5 2
BARREL WHITE C
LINE
LIQUID LINE BLACK
RIGHT FAN SOLENOID WHT 4 1
PRESSURE SOFT SERVE RELAY
BLK
BLK
SWITCH BEATER MOTOR BROWN START CAP.
5 2 S
BLK
L1 T1 M BLKT2 L2 BROWN ABOVE ELECTRICAL DIAGRAM SHOWS WIRING NECESSARY
GRN/YEL TO HOOK UP A COMPRESSOR USING A STAR T AND RUN
BLK SOFT SERVE BEATER MOTOR EQUIPMENT CAPACITOR (CSR) WITH A RELAY.
STARTER BEATER MOTOR GROUND 4 1
COMPRESSOR
BLK BLK BLK (SEE FIG. 1) STARTER BLUE
BLACK R
L1 T1 M T2 L2
RUN CAPACITOR
START CAPACITOR
BLK
GRN/
BLEED RESISTOR
YEL
WHT
PRESSURE CONDENSER SCHEMATIC WIRING DIAGRAM - CSR
BLK
COMPRESSOR SWITCH BLOWER MOTOR
BLK BLK GRA GRA BLU BLK
CRANKCASE HEATER M
RIGHT FAN BLK
BLK PRESSURE BRN
SWITCH
BLK
BLK BLK
RED
RIGHT SIDE
BLK
RED
CONTROL
BLU/WHT
BLU
L1 L2
TERMINAL BLOCK
BLK
BLK
RED
BLU/WHT
WHT GRA
BLU/WHT
BARREL
HOT GAS
GRN/YEL
SOLENOID
AGITATOR
MOTOR
SEE
RIBBON
CABLE
DETAIL
WHT YEL
RED RED RED BLU M RED
BLU BLU BLU
WHT
HOPPER
HOT GAS
GRN/YEL GRN/YEL GRN/YEL SOLENOID
RED
BLU
BLK
BA
J2
J3
8 7 6 5 4 3 21J10 10 9 8 7 6 5 4 3 21
RED
+5V CLR
COM NO GRA/BLK 2
J19 TAN
1
BLK
PRP/WHT
PRP/WHT
BLU/WHT
NC
J13
J1
RED/BLK
J5
MIX
1 234
J11
J12
DRAW OUT
TAN
B
A
SWITCH PROBE
YEL
BLK
BLK
YEL
MIX
BLK
BLK TAN
BLK
LOW
J18
INTFC PCB A.
BLK
PROBE
BLU/WHT WITH SOFT SERVE 2
RED
PERSONALITY PCB A. 1
J9
2 4 WHT WHT
L2
L1
J8
J7
J6
BLK
WHT
BLK
BLK
BLU/WHT
BEATER
BLK
BLK
WHT/ORN WHT/ORN
L
RELAY
JACK
#3 #1 1
ORN/WHT BLK
WHT/PRP WHT WHT 9
BLK BLK OVERLOAD 5
BARREL SWITCH
NC RED
BLK
COMPRESSOR SUCTION 4
TAN
BLU
C0M BLU
LIMIT SWITCH 8
RED ORN M PRP
BLK
DRAW COMPRESSOR 13 14
RED
MIX
BLK
WHT
CONTACTOR PUMP
BLK
SWITCH
YEL
NO COIL
96 95 MOTOR BEATER
BLK BLK WHT MOTOR
3 2
START STARTER
BEATER 4 COIL
RELAY
BLK
WHT
MOTOR
BLK
WHT
OVERLOAD
SWITCH
BLK
WHT
WHT
NOTE:
BLK BLK
WHT/GRA
HOPPER BLK
LIQUID WHT
GRA/WHT
SOLENOID
WHT
CONNECTED TO PIN 1 AT EACH END.
LIV
COMPRESSOR SOLENOID
CRANKCASE HEATER WHT/BRN WHT
BARREL
BLK LIQUID
SOLENOID WHT
SOFT SERVE
BLK
BLK
BEATER MOTOR
BLK BLK T2
COPELAND COMPRESSORS L1 T1 M L2
COMPRESSOR
YEL
CONTACTOR
BLK BLK
*IF THE UNIT HAS THE INTEGRAL SYRUP OPTION -405, THEN THIS JUMPER SHOULD BE INSTALLED.
JUMPER SETTINGS
DBGEN
RTCK
JP7
JP6
JP5
JP4
JP3
JP2
JP1
J10
W7
W6
W5
W4
W3
W2
W1
W7
W6
W5
W4
W3
W2
W1
A
B
B
UVC4 BOARD
INTERFACE
INTERFACE
PERSONALITY BOARD
PERSONALITY BOARD
PERSONALITY BOARD
PERSONALITY BOARD
BOARD
BOARD
RIGHT
LEFT
PINS 1 AND 2
PINS 3 AND 4
PINS 1 AND 2
SOFT SERVE
SOFT SERVE
SOFT SERVE
SOFT SERVE
PINS 7 & 8
ABILITY TO ACTIVATE THE TOUCH PANEL.
PANEL. NEW SWITCH ACTS AS THE ON/OFF
APPLICATION ONLY. LOCKS OUT TOUCH
JUMPER INSTALLED W/SWITCH - SELF SERVE
SENSITIVITY.
JUMPER INSTALLED - REDUCED MIX OUT
.
RESERVED (DO NOT USE)
KEYS FUNCTIONAL.
START BY SELECTING HEAT SYMBOL/STANDBY
DISPLAYED ON SCREEN/MANUAL HEAT CYCLE
INSTALLED. HOPPER TEMPERATURES
INTERNATIONAL CONFIGURATION - NO JUMPER
HAS OCCURRED/STANDBY KEYS DISABLED.
ONLY ACTIVE WHEN A LOCKOUT CONDITION
DISPLAYED ON SCREEN/HEAT SYMBOL KEYS
INSTALLED. HOPPER TEMPERATURE NOT
DOMESTIC CONFIGURATION - JUMPER
RESERVED (DO NOT USE)
SENSITIVITY.
JUMPER INSTALLED - REDUCED MIX LOW
RESERVED (DO NOT USE)
.
RESERVED (DO NOT USE)
.
.
RESERVED
JUMPER INSTALLED DISABLES RESET.
.
RESERVED (DO NOT USE)
.
RESERVED (DO NOT USE)
.
RESERVED (DO NOT USE)
SOLENOIDS.
JUMPER INSTALLED - OPEN ALL LEFT
HEATERS
JUMPER INSTALLED - ACTIVATES SYRUP
STATUS.
JUMPER INSTALLED - FORCE BRUSH CLEAN
RESERVED (DO NOT USE)
0-12 AMP BEATER MOTOR AMPERAGE RANGE
FUNCTION
FUNCTION
FUNCTION
Taylor Company
INSTALLED
INSTALLED
INSTALLED
INITIALLY
INITIALLY
INITIALLY
JUMPER
JUMPER
JUMPER
Model C716
YES
YES
YES
YES
YES
NO*
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
059900-27
c 2014 Taylor Company 06/14
THERMOSTA
190 F OPEN
140 F CLOSE
O.T.
WHT WHT WHT WHT
EXTERNAL EQUIPOTENTIAL
GROUND GROUND SYRUP HEATER
TERMINAL BLOCK
L1 L2 L3
FIG .2
BLK
GRN/YEL
BLK
BLK
RED (+5v) USER - 8 LEDS
BLK/BLU
J1
INTERFACE - LCD SCREEN
BLK/BLU
BLK (GRD) J2 - 9 KEYS
(+5v) J3
BOARD
CLR - BEEPER
)
(GRD
GRN
GRN/YEL GRN/YEL
WHT
ORN
RED
BLK/BLU
BLK
WHT
GRN
RED
BLK
INTERFACE BOARD J16 J4 J2 J7 J9
RED
POWER TRANSFORMER
BLU
1 23
4 56
16V J13
WHT
J12
BARREL
UNIVERSAL CONTROL PCB A. HOT GAS
SOLENOID
J17
J1
RED
BLU
BLK
21
RIBBON
AGITATOR
CABLE
CLR J10 J11 MOTOR
+5V
SEE WHT BLK/BLU
RIBBON CABLE RIBBON CABLE DETAIL WHT YEL
RED RED RED BLU M RED HOPPER
BLU BLU BLU
WHT
HOT GAS COM 208
GRN/YEL SOLENOID
GRN/YEL
SV CABLE SV CABLE
BLU BLU/WHT
RED
RED
BLU
24 VAC
T
BA
GRN/YEL
WH
J2
BLU
J3
8 7 6 5 4 3 21J10 10 9 8 7 6 5 4 3 21
BLU/WHT
GND
BLU
ORN/WHT ORN/WHT GRN BLK
J14
+5V CLR
COM NO YEL RED/BLK J19 2
BLK
GRN/YEL 1 TAN SE
PRP
J13
NC
J1
HOPPER WHT/RED
J5
MIX
1 234
J11
J12
GROUND DRAW OUT M
PRP
BLK TAN
B
TAN
A
SWITCH PROBE
YEL
WHT
BLK
BLK
YEL
MIX
BLK
BLK
BLK
BLUE
LOW SELF-SERVICE
WHT
BLK
J18
PROBE
TAN
ENABLE INTFC PCB A.
DISABLE ENABLE WITH SOFT SERVE
ON RED PERSONALITY PCB A. 2
1 WHT
J9
1 3 WHT
RED
L1
L2
J8
J7
J6
OFF (OPTIONAL) BLK
BARRELHOPPER 5 3 1 1 234567 1 23456 7 FUSE
WHT/RED --THERMISTOR PROBES-- 15A BLK
BLK BLK OPTIONAL WHT
ON BLK/WHT BLK/WHT BLK WHT
RED
BLK
BLUE
BLK LEFT SYRUP HEATER
POWER
BLK/WHT
BEATER
BLK
BLK
OFF SEE FIG. 2
SWITCH INTERLOCK
BLU/WHT
3PDT WHT/ORN WHT/ORN
RELAY
BLK
#3 #1 1
ON ORN/WHT BLK
WHT 9
ADDITIONAL DRAW SWITCH BLK BLK WHT/PRP OVERLOAD 5
BARREL
OFF FOR FLAVORBURST SWITCH
BLU
BLK
SUCTION 4
TAN
COMPRESSOR AGITATOR MOTOR
SOLENOID WHT/ORN 12
HIGH PRESSURE
ORN
BLU DETAIL
WHT
BLU
LIMIT SWITCH 8
RED ORN M PRP
BLU/WHT
BLK
BLK COMPRESSOR 13 14
RED
MIX
BLK
WHT
CONTACTOR
PANEL PUMP
YEL
C
COIL MOTOR
L
96 95 BEATER
BLK
JACK BLK BLK
3 2
MOTOR BLACK
STARTER BEATER
BEATER START
4 COIL MOTOR
WHT
RELAY
BLK
BLK
WHT
MOTOR INTERLOCK
OVERLOAD WHT N.O. SWITCH
NC RED SWITCH
C0M
WHT/GRA
BLK
HOPPER BLK
DRAW LIQUID WHT
GRA/WHT
SOLENOID
SWITCH NO WHT
LIV
SOLENOID
WHT/BRN WHT
GRN/YEL
BLK
BLK
BLK T2 BLK
BLK L1 T1 M L2
BLK
GRN/YEL T3 L3
BLK BEATER MOTOR
SOFT SERVE
STARTER BEATER MOTOR
COMPRESSOR STARTER
BLK BLK BLK
L1 T1 M T2 L2
T3 L3
BLK
BLK
GRN/
COMPRESSOR
YEL
WHT
I3 I4
CRANKCASE HEATER PRESSURE CONDENSER
COMPRESSOR
BLK
SWITCH BLOWER MOTOR
CONTACTOR
BLK BLK BLK GRA GRA BLU BLK
M
RIGHT FAN BLK
PRESSURE BRN
SWITCH
BLK
BLK
COPELAND COMPRESSORS
ONLY
WATER COOLED
BLOWER MOTOR
BLK BLK
M
BLK
BLK
RED
LEFT SIDE
BLK
RED
CONTROL
BLU/WHT
BLU
L1 L2 L3
TERMINAL BLOCK
BLK
RIGHT SIDE
BLK
BLK
CONTROL
RED
BLU/WHT
WHT GRA
BLU/WHT
BARREL
GRN/YEL
HOT GAS
SOLENOID
AGITATOR
MOTOR
RIBBON
SEE
CABLE
HOT GAS
GRN/YEL GRN/YEL GRN/YEL SOLENOID
RED
BLU
BLK
BA
J2
J3
8 7 6 5 4 3 21J10 10 9 8 7 6 5 4 3 21
GND
RED
+5V CLR
COM NO GRA/BLK 2
J19 TAN
1
BLK
PRP/WHT
PRP/WHT
BLU/WHT
NC
J13
J1
RED/BLK
J5
MIX
1 234
J11
J12
DRAW OUT
TAN
B
A
SWITCH
YEL
PROBE
BLK
BLK
YEL
MIX
BLK
BLK TAN
BLK
LOW
BLK
J18
2 4 WHT WHT
RED RED
L1
L2
J8
J7
J6
BARRELHOPPER BLK
5 3 1 1 234567 1 23456 7 BLK
--THERMISTOR PROBES-- FUSE WHT
15A
OPTIONAL
BLK
WHT
ADDITIONAL DRAW SWITCH BLK
RIGHT SYRUP HEATER
BLU/WHT
5
L
BARREL SWITCH
JACK
BLK
SUCTION 4
TAN
COMPRESSOR
BLU
COMPRESSOR MIX 13 14
RED
BLK
WHT
BLK
MOTOR
WHT
SWITCH NO OVERLOAD
SWITCH
BLK
WHT
HOPPER BLK
LIQUID WHT
GRA/WHT
SOLENOID
WHT
LIV
WHT/BRN SOLENOID WHT
BLK BARREL
NOTE:
LIQUID
SOLENOID WHT
SOFT SERVE
BLK
BLK
BEATER MOTOR
COMPRESSOR BLK BLK
M BLKT2
CONNECTED TO PIN 1 AT EACH END.
L2
CRANKCASE HEATER L1 T1
BLK
DBGEN
RTCK
JP7
JP6
JP5
JP4
JP3
JP2
JP1
J10
W7
W6
W5
W4
W3
W2
W1
W7
W6
W5
W4
W3
W2
W1
A
A
B
UVC4 BOARD
JUMPER SETTINGS
INTERFACE
INTERFACE
PERSONALITY BOARD
PERSONALITY BOARD
PERSONALITY BOARD
PERSONALITY BOARD
BOARD
BOARD
RIGHT
LEFT
PINS 1 AND 2
PINS 3 AND 4
PINS 1 AND 2
SOFT SERVE
SOFT SERVE
SOFT SERVE
SOFT SERVE
PINS 7 & 8
SENSITIVITY.
JUMPER INSTALLED - REDUCED MIX LOW
RESERVED (DO NOT USE)
SOLENOIDS.
JUMPER INSTALLED - OPEN ALL RIGHT
RESERVED (DO NOT USE)
TEMPERATURE CHECK.
JUMPER INSTALLED - ENABLES 59F HOPPER
RESERVED (DO NOT USE)
GROUND FRAME SECURELY
FUNCTION
FUNCTION
FUNCTION
Taylor Company
INSTALLED
INSTALLED
INSTALLED
INITIALLY
INITIALLY
INITIALLY
JUMPER
JUMPER
JUMPER
YES
YES
YES
YES
YES
NO*
Model C716
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
059900-33
c 2014 Taylor Company 06/14
SE
BLUE
WHT
NOTE: FOR CCWLE - BLUE INTERNAL ON #1,YELLOW INTERNAL ON #2
BEATER MOTOR
RED
CONTACTOR
J12 OR PURPLE INTERNAL BLACK
T1 L1
5
T1 OR BLUE INTERNAL BLUE
T8 OR RED INTERNAL 4
1
BLUE
BLUE
CP CP
BLU/WHT
2
J9 OR BLACK INTERNAL A
T3 L3
USE T3 AND L3 WHEN CP
CONTACTS ARE NOT AVAILABLE
AGITATOR MOTOR BLACK
T4 OR YELLOW INTERNAL T2 L2
DETAIL
EQUIPOTENTIAL
EXTERNAL
GROUND
GROUND
L1 N A.O. SMITH BEATER MOTOR WIRING
TERMINAL BLOCK STEPS:
1) REMOVE BROWN JUMPER FROM BETWEEN TERMINAL #1 TO TERMINAL #5
BLK BRN
GRN/YEL
2) MOVE BLUE INTERNAL (FROM MOTOR MAIN WINDING)
BLU
FROM TERMINAL #5 TO TERMINAL #1.
NOTE: FOR CCWLE - BLUE INTERNAL ON #1, YELLOW INTERNAL ON #6
RED (+5v) - 8 LEDS BLUE INTERNAL BEATER MOTOR
USER
J1 BRN BLU
INTERFACE - LCD SCREEN CONTACTOR
BLK/RED
BLK (GRD) J2 - 9 KEYS ORANGE INTERNAL 1
BLK/RED
BLACK
(+5v) J3 BOARD T1 L1
CLR
BLK
- BEEPER
(GRD) 2
GRN BLUE
3
GRN/YEL GRN/YEL ELECTRICAL RED INTERNAL 4 BLUE
CP CP
ENCLOSURE
BLK BLK WHT WHT
L1 LINE L2 5 T3 L3
RIBBON CABLE
EMI FILTER USE T3 AND L3 WHEN
L1 LOAD L2 CABLE CP CONTACTS ARE NOT AVAILABLE
ORN
240V
BLK
YELLOW INTERNAL 6 BLACK
NOT RIBBON CABLE T2 L2
CONNECTED
WHT BLACK INTERNAL
WHT
RED
WHT
GRN
GRN/YEL
BLK/RED
RED
INTERFACE BOARD
BLK
J16 J4 J2 J7 J9
POWER TRANSFORMER
RED
BLU
WHT GRA
LEESON BEATER MOTOR WIRING
1 23
4 56
16V J13
BARREL STEPS:
J15 J8
J12 GRD HOT GAS 1) DISCONNECT WIRE T7 FROM TERMINAL 3
SOLENOID 2) SPLICE BLUE WIRE AS SHOWN
UNIVERSAL CONTROL PCB A.
BEATER MOTOR
AGITATOR
J17 T8 CONTACTOR
J1 MOTOR
RED
BLU
BLK 1 BLACK
WHT
21
SEE
BLK/RED
T1 T1 L1
RIBBON
CLR
CABLE
J10 J11 DETAIL
GRN/YEL BLUE
+5V
2
RIBBON CABLE RIBBON CABLE WHT YEL BLUE
RED RED RED BLU M RED CP CP
BLU BLU BLU HOPPER
WHT
HOT GAS COM 240 3
WHT T7 T3 L3
GRN/YEL GRN/YEL SOLENOID
SV CABLE SV CABLE USE T3 AND L3 WHEN
BLU BLU/WHT CP CONTACTS ARE NOT AVAILABLE
RED
RED
24 VAC 4 BLACK T2 L2
T4
T
BA
GRN/YEL
J2
GRN/YEL
WH
T5
J3
8 7 6 5 4 3 21J10 10 9 8 7 6 5 4 3 21
BLU
ORN/WHT GND GRN BLK
FIG. 1
J14
+5V CLR
COM NO RED/BLK
BLK
GRN/YEL J19 2 TAN
PRP 1
YEL
NC
J13
J1
HOPPER WHT/RED
J5
MIX
1 234
J11
J12
GROUND DRAW OUT
PRP
BLK TAN
B
TAN
A
SWITCH
YEL
PROBE
WHT
BLK
BLK
YEL
MIX
BLK
SELF-SERVICE BLK
BLK
LOW
BLK
J18
TAN
ENABLE
PROBE INTFC PCB A.
DISABLE ENABLE WITH SOFT SERVE 2
ON RED 1
PERSONALITY PCB A.
J9
1 3 WHT WHT
L1
L2
J8
J7
J6
OFF BLK
BARRELHOPPER (OPTIONAL) 5 3 1 1 234567 1 234 56 7 FUSE BLK
WHT/RED 15A SEE FIG. 4 WHT
--THERMISTOR PROBES--
RED
BLK
BLK 140 F CLOSE
POWER O.T.
BLK/WHT
OFF LEFT SYRUP HEATER BEATER
BLK
WHT
BLK
WHT WHT WHT
SWITCH INTERLOCK
DPDT WHT/ORN WHT/ORN
RELAY
GRN/YEL
BLK
GRN/YEL
#3 #1 1
ON ORN/WHT BLK
WHT 9 SYRUP HEATER
ADDITIONAL DRAW SWITCH BLK BLK WHT/PRP OVERLOAD 5
BARREL SWITCH
OFF FOR FLAVORBURST
BLU
BLK
SUCTION 4
TAN
COMPRESSOR
WHT/ORN
HIGH PRESSURE SOLENOID
BLU
12
FIG .4
WHT
BLU
LIMIT SWITCH 8
RED ORN M PRP
BLK
BLU/WHT
BLK
ORN
COMPRESSOR MIX 13 14
RED
BLK
WHT
CONTACTOR PUMP
PANEL
YEL
C
COIL MOTOR
L
96 95 BEATER
BLK
JACK BLK BLK WHT MOTOR BLACK
START3 2 STARTER BEATER
BEATER RELAY 4 COIL MOTOR
WHT
BLK
BLK
MOTOR
WHT
WHT INTERLOCK
OVERLOAD N.O. SWITCH
SWITCH
NC RED
C0M WHT
BLK
WHT/GRA
HOPPER BLK COMPRESSOR
DRAW LIQUID WHT TERMINAL
GRA/WHT
SOLENOID GRN/YEL C S COVER
SWITCH NO WHT
R
LIV GRN/YEL RUN
INTERNAL OVERLOAD RELAY
SOLENOID GRN/YEL WHITE(120 VOLTS) CAP.
WHT/BRN WHT
GRN/YEL
BLACK(230 VOLTS) 5 2
GRN/YEL
BARREL LINE
LIQUID WHITE
GRN/YEL C
SOLENOID WHT LINE BLACK 4 1
BLK
SOFT SERVE
BLK
RELAY START CAP.
BEATER MOTOR
BROWN
BLK L1 T1 M BLKT2 L2 5 2 S ABOVE ELECTRICAL DIAGRAM SHOWS WIRING NECESSARY
BLK SOFT SERVE BEATER MOTOR GRN/YEL BROWN TO HOOK UP A COMPRESSOR USING A STAR T AND RUN
COMPRESSOR STARTER BEATER MOTOR EQUIPMENT CAPACITOR (CSR) WITH A RELAY.
(SEE FIG. 1) BLK STARTER GROUND 4 1
BLK BLK L1 T1 M T2 L2 BLACK
COMPRESSOR BLUE R
BLK
L
COMPRESSOR GRN/YEL GRN/YEL START CAPACITOR
E
LEFT FAN BLEED RESISTOR
/Y
WHT
CRANKCASE HEATER PRESSURE CONDENSER 052396-1
BLK
R
SWITCH BLOWER MOTOR SCHEMATIC WIRING DIAGRAM - CSR
G
BLK BLK BLK GRA GRA BLU BLK
M
RIGHT FAN AIR COOLED
BLK
PRESSURE
SWITCH BRN
BLK
BLK BLK
COPELAND COMPRESSORS
ONLY
L
E
WATER COOLED
/Y
CONDENSER FAN
LEFT SIDE
N
R
G
BLK BLK
M
CONTROL
BLK
BLK
RED
RIGHT SIDE
BLK
RED
CONTROL
BLU/WHT
BLU
L1 N
TERMINAL BLOCK
BLK BRN BRN
GRN/YEL
BLU
ELECTRICAL
GRN/YEL
ENCLOSURE
BLK BLU
RED
BRN BLU
BLU/WHT
GRN/YEL
WHT GRA
BLU/WHT
BARREL
GRN/YEL
HOT GAS
SOLENOID
AGITATOR
MOTOR GRN/YEL
RIBBON
SEE
CABLE
HOT GAS
GRN/YEL GRN/YEL GRN/YEL SOLENOID
RED
BLU
BLK
BA
J2
GRN/YEL
J3
8 7 6 5 4 3 21J10 10 9 8 7 6 5 4 3 21
GND
RED
+5V CLR
COM NO GRA/BLK 2
J19 TAN
1
BLK
PRP/WHT
PRP/WHT
NC
J13
J1
RED/BLK
J5
MIX
1 234
J11
J12
DRAW OUT
TAN
B
A
PROBE
YEL
SWITCH
BLK
BLK
YEL
MIX
BLK
BLK TAN
BLK
LOW
BLK
J18
PERSONALITY PCB A. 1
J9
2 4 WHT WHT
L1
L2
J8
J7
J6
WHT WHT
BLK
BLU/WHT
BEATER
BLK
BLK
#3 #1 1
ORN/WHT BLK
WHT WHT 9
BLK BLK WHT/PRP OVERLOAD
BLK BARREL SWITCH
5
PANEL
BLK
COMPRESSOR SUCTION 4
TAN
C
BLU
L
13 14
RED
COMPRESSOR MIX
BLK
WHT
CONTACTOR PUMP
BLK
YEL
BLK
MOTOR
WHT
OVERLOAD
DRAW
NOTE:
SWITCH
BLK
WHT
SWITCH NO
GRN/YEL
WHT
2. RED WIRE ON RIBBON CABLES MUST BE
BLK BLK
WHT/GRA
HOPPER BLK
CONNECTED TO PIN 1 AT EACH END.
LIQUID WHT
SOLENOID
GRA/WHT
GRN/YEL
WHT
LIV
BLK SOLENOID GRN/YEL
WHT/BRN WHT
BARREL
COMPRESSOR LIQUID GRN/YEL
SOLENOID WHT
GRN/YEL
JUMPER SETTINGS
DBGEN
RTCK
JP7
JP6
JP5
JP4
JP3
JP2
JP1
J10
W7
W6
W5
W4
W3
W2
W1
W7
W6
W5
W4
W3
W2
W1
B
UVC4 BOARD
INTERFACE
INTERFACE
PERSONALITY BOARD
PERSONALITY BOARD
PERSONALITY BOARD
PERSONALITY BOARD
BOARD
BOARD
RIGHT
LEFT
PINS 1 AND 2
PINS 3 AND 4
PINS 1 AND 2
SOFT SERVE
SOFT SERVE
SOFT SERVE
SOFT SERVE
PINS 7 & 8
0-12 AMP BEATER MOTOR AMPERAGE RANGE
.
RESERVED (DO NOT USE)
.
.
RESERVED
JUMPER INSTALLED DISABLES RESET.
.
RESERVED (DO NOT USE)
.
RESERVED (DO NOT USE)
.
RESERVED (DO NOT USE)
.
RESERVED (DO NOT USE)
KEYS FUNCTIONAL.
START BY SELECTING HEAT SYMBOL/STANDBY
DISPLAYED ON SCREEN/MANUAL HEAT CYCLE
INSTALLED. HOPPER TEMPERATURES
INTERNATIONAL CONFIGURATION - NO JUMPER
HAS OCCURRED/STANDBY KEYS DISABLED.
ONLY ACTIVE WHEN A LOCKOUT CONDITION
DISPLAYED ON SCREEN/HEAT SYMBOL KEYS
INSTALLED. HOPPER TEMPERATURE NOT
DOMESTIC CONFIGURATION - JUMPER
RESERVED (DO NOT USE)
FUNCTION
FUNCTION
Taylor Company
INSTALLED
INSTALLED
INSTALLED
INITIALLY
INITIALLY
INITIALLY
JUMPER
JUMPER
JUMPER
YES
YES
YES
YES
NO*
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Model C716
059900-40
c 2014 Taylor Company 06/14
EQUIPOTENTIAL
EXTERNAL GROUND
GROUND
TERMINAL BLOCK
L1 L2 L3 N
BLK BRN
GRN/YEL
BLU
BLK
BLK
BLK/RED
RED (+5v) - 8 LEDS
J1 USER
- LCD SCREEN
BLK/RED
BLK (GRD) J2 INTERFACE - 9 KEYS
(+5v) J3 BOARD
CLR - BEEPER
) WHT THERMOSTA
(GRD
GRN 190 F OPEN
WHT
140 F CLOSE
O.T.
GRN/YEL WHT WHT WHT WHT
GRN/YEL ELECTRICAL
ENCLOSURE
BLK BLK WHT WHT
L1 LINE L2 RIBBON CABLE
EMI FILTER
L1 LOAD L2 SYRUP HEATER
CABLE
240V
RIBBON CABLE
FIG .2
WHT
MOTOR
ORN
RED
BLK
WHT
GRN
RED
BLK
DETAIL
INTERFACE BOARD J9
WHT
J16 J4 J2 J7
BLU M RED
RED
POWER TRANSFORMER
BLU
GRN/YEL
1 23
4 56
WHT
16V J13
SENSOR CORE.
J15 J8 WHT GRA
J12 GRD
BLU BARREL
BLK/RED
UNIVERSAL CONTROL PCB A. HOT GAS
SOLENOID
J17
J1
RED
BLU
BLK
21
RIBBON
CABLE
CLR J10 J11
GRN/YEL BLK/RED
+5V
RIBBON CABLE RIBBON CABLE WHT
WHT YEL
RED RED RED
BLU BLU BLU HOPPER
HOT GAS COM 240
GRN/YEL GRN/YEL SOLENOID
SV CABLE SV CABLE
BLU/WHT
RED
RED
WHT
24 VAC
BLK
BLK
HT
BA
GRN/YEL
GRN/YEL
J2
BLUE
W
BLU/WHT
J3
8 7 6 5 4 3 21J10 10 9 8 7 6 5 4 3 21
GND
BLU
ORN/WHT ORN/WHT GRN BLK
J14
+5V CLR
COM NO RED/BLK J19 2
BLK
GRN/YEL 1 TAN
PRP
YEL
NC
J13
J1
HOPPER WHT/RED
J5
MIX
1 234
J11
J12
GROUND DRAW OUT TAN SE
PRP
BLK TAN
B
A
SWITCH PROBE
YEL
WHT
BLK
BLK
YEL
MIX
BLK
BLK
BLK
LOW SELF-SERVICE
J18
BLK
PROBE
TAN
ENABLE INTFC PCB A. M
DISABLE ENABLE WITH SOFT SERVE 2
ON RED PERSONALITY PCB A. 1
J9
WHT WHT
BLUE
1 3
WHT
L1
L2
J8
J7
J6
OFF BLK
BARRELHOPPER (OPTIONAL) 5 3 1 1 234567 1 23456 7 FUSE BLK
WHT/RED 15A
--THERMISTOR PROBES-- WHT
RED
BLK BLK OPTIONAL
ON BLK/WHT BLK/WHT BLK WHT
RED
BLK
BLK LEFT SYRUP HEATER GRN/YEL
OFF
BLK/WHT
POWER BEATER
BLK
BLK
SEE FIG. 2
SWITCH WHT/ORN INTERLOCK
DPDT WHT/ORN
RELAY
GRN/YEL
BLK
BLUE
GRN/YEL
#3 #1 1
ON ORN/WHT BLK
WHT
BLU/WHT
9
ADDITIONAL DRAW SWITCH BLK BLK WHT/PRP OVERLOAD 5
OFF BARREL SWITCH
BLU
BLK
FOR FLAVORBURST SUCTION 4
TAN
COMPRESSOR
HIGH PRESSURE SOLENOID WHT/ORN 12
ORN
BLU
WHT
BLU
LIMIT SWITCH 8
RED ORN M PRP
BLU/WHT
BLK
COMPRESSOR MIX 13 14
RED
BLK
WHT
BLK CONTACTOR PUMP AGITATOR MOTOR
YEL
PANEL 96 95 COIL MOTOR BEATER DETAIL
BLK
BLK BLK WHT MOTOR BLACK
JACK START 3 2 STARTER BEATER
WHT
BLK
BEATER RELAY
BLK
4 COIL MOTOR
WHT
BLK
BLK
MOTOR
WHT
WHT INTERLOCK
OVERLOAD N.O. SWITCH
SWITCH
NC RED WHT
WHT/GRA
C0M HOPPER BLK
LIQUID BLK
GRA/WHT
DRAW SOLENOID WHT
WHT
SWITCH NO
LIV GRN/YEL
SOLENOID
GRN/YEL
WHT/BRN WHT
GRN/YEL
BARREL
LIQUID
SOLENOID WHT
SOFT SERVE
BLK
BLK
BLK
BLK
BEATER MOTOR
BLK L1 T1 M BLKT2 L2
T3 L3
BLK
BLK
COMPRESSOR
CONTACTOR GRN/YEL GRN/YEL
COMPRESSOR
WHT
E
LEFT FAN CONDENSER BLK
/Y
CRANKCASE HEATER BLOWER MOTOR
N
PRESSURE
BLK
BLK SWITCH BLK
G
BLK GRA GRA BLU BLK WHT
M
AIR COOLED
RIGHT FAN BRN
PRESSURE
COPELAND COMPRESSORS SWITCH BLK
L
E
ONLY WATER COOLED
/Y
N
FAN
BLK
R
G
BLK BLK
M
BLK BLK
RED
BLU
BLK
RED
LEFT SIDE
BLU/WHT
CONTROL
GRN/YEL
TERMINAL BLOCK
L1 L2 L3 N
RIGHT SIDE
BLK BRN BRN
CONTROL
BLU
ELECTRICAL
BLK
BLK
ENCLOSURE
GRN/YEL
WHT
RED
BEATER MOTOR LINE MUST
PASS TWICE THRU THE
BLU/WHT
GRN/YEL
SENSOR CORE.
AGITATOR
MOTOR WHT GRA
BLU/WHT
SEE BARREL
GRN/YEL
BLU GRN/YEL
RIBBON
CABLE
WHT YEL
RED RED RED
BLU BLU BLU HOPPER
HOT GAS
GRN/YEL GRN/YEL GRN/YEL SOLENOID
RED
BLK
BA
J2
GRN/YEL
J3
8 7 6 5 4 3 21J10 10 9 8 7 6 5 4 3 21
WHT
GND
RED
BLK
BLK
+5V CLR
COM NO GRA/BLK 2
J19
1 TAN
BLK
PRP/WHT
PRP/WHT
NC
J13
J1
RED/BLK
J5
MIX
1 234
J11
J12
DRAW OUT
TAN
B
A
SWITCH
YEL
PROBE
BLK
BLK
YEL
MIX
BLK
BLK TAN
BLK
LOW
BLK
J18
2
RED
PERSONALITY PCB A. 1
J9
2 4 WHT
L1
L2
J8
J7
J6
BEATER
BLK
BLK
SEE FIG. 2
WHT/ORN INTERLOCK
WHT/ORN
RELAY
GRN/YEL
GRN/YEL
#3 #1 1
ORN/WHT BLK
WHT 9
ADDITIONAL DRAW SWITCH BLK BLK WHT/PRP OVERLOAD 5
BARREL SWITCH
BLK
COMPRESSOR
BLU
SOLENOID WHT/ORN 12
HIGH PRESSURE BLU
LIMIT SWITCH 8
RED ORN M PRP
BLK
ORN
COMPRESSOR MIX 13 14
RED
BLK
WHT
WHT
BLK
BLK
MOTOR
WHT
OVERLOAD
BLK
GROUND FRAME SECURELY
SWITCH WHT
NC RED GRN/YEL
C0M WHT BLK BLK
WHT/GRA
HOPPER BLK
DRAW LIQUID WHT
GRA/WHT
SOLENOID WHT
SWITCH NO
LIV
SOLENOID
WHT/BRN WHT
BARREL
LIQUID
SOLENOID WHT
GRN/YEL
BLK
SOFT SERVE
BLK
BEATER MOTOR
BLK BLK T2
L1 T1 M L2
BLK BEATER MOTOR
T3 L3
BLK
STARTER
BEATER MOTOR
STARTER
NOTE:
BLK
SOFT SERVE
2. RED WIRE ON RIBBON CABLES MUST BE
COMPRESSOR
BLK
COMPRESSOR L1 T1 M T2 L2 BLK
CRANKCASE HEATER T3 L3
BLK
BLK BLK
COMPRESSOR GRN/YEL
CONTACTOR
COPELAND COMPRESSORS GRN/YEL
ONLY
*IF THE UNIT HAS THE INTEGRAL SYRUP OPTION -405, THEN THIS JUMPER SHOULD BE INSTALLED.
**IF THE UNIT HAS THE YUMOPTION THEN THIS JUMPER SHOULD BE INSTALLED.
JUMPER SETTINGS
DBGEN
RTCK
JP7
JP6
JP5
JP4
JP3
JP2
JP1
W7
W6
W5
W4
W3
W2
W1
J10
W7
W6
W5
W4
W3
W2
W1
A
B
UVC4 BOARD
INTERFACE
INTERFACE
PERSONALITY BOARD
PERSONALITY BOARD
PERSONALITY BOARD
PERSONALITY BOARD
BOARD
BOARD
RIGHT
LEFT
PINS 1 AND 2
PINS 3 AND 4
PINS 1 AND 2
SOFT SERVE
SOFT SERVE
SOFT SERVE
SOFT SERVE
PINS 7 & 8
SENSITIVITY.
JUMPER INSTALLED - REDUCED MIX OUT
SENSITIVITY.
JUMPER INSTALLED - REDUCED MIX LOW
RESERVED (DO NOT USE)
SOLENOIDS.
JUMPER INSTALLED - OPEN ALL RIGHT
POWER OUTAGE
JUMPER INSTALLED - YUM OPTION - 2 HOUR
TEMPERATURE CHECK.
JUMPER INSTALLED - ENABLES 59F HOPPER
RESERVED (DO NOT USE)
0-12 AMP BEATER MOTOR AMPERAGE RANGE
FUNCTION
FUNCTION
Taylor Company
INSTALLED
INSTALLED
INSTALLED
INITIALLY
INITIALLY
INITIALLY
JUMPER
JUMPER
JUMPER
NO**
YES
YES
YES
YES
NO*
Model C716
N/A
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
059900-58
c 2014 Taylor Company 06/14