PCP0902A

Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.

AIR COOLED PACKAGED


Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical

AIR CONDITIONERS
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
FLOOR STANDING TYPE
DUCT TYPE
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
COOLING ONLY 50Hz
the outdoor unit close to the sea shore, contact your local distributor.

DUCT TYPE

f o r
a b le s
u i t orie
S act
f

Specifications, designs and other content appearing in this brochure are current as of August 2018 but subject to change without notice. FLOOR STANDING TYPE
c All rights reserved DIRECT AIR BLOW TYPE DUCT CONNECTION TYPE
AK
HFC R-410A Line Up DIRECT AIR BLOW TYPE
Direct air blow from indoor unit
with plenum
DUCT CONNECTION TYPE
DUCT TYPE
Air blow via connected ducts

for Factories and Offices Comfortable factory air conditioning using multiple indoor
units installed in accordance with the space.
Installation is next to walls, so units will not affect the
factory layout even if the changes are made.
Comfortable air conditioning of the entire factory by connecting a
blow duct at the top of the indoor unit.

Note: Ducts to be procured locally.

We have entered an era in which being recognized as an environmentally


responsible corporate citizen has taken utmost importance.
Even when selecting air conditioners, a new model featuring HFC R-410AR-410A
could
refrigerant could
be the perfect stepbeinthe perfect step
promoting yourincorporate
promotingimage.
your corporate image.

Product Line Up
FLOOR STANDING TYPE Cooling only
50Hz
HP 5 6 8 10 13 15 18 20 Nice,
kW 14.7 17.6 23.5 29.3 35.2 46.9 52.8 58.6
Capacity cool air in the factory
1, 2

Btu/h 50,000 60,000 80,000 100,000 120,000 160,000 180,000 200,000


kcal/h 12,600 15,100 20,200 25,200 30,200 40,300 45,400 50,400
or in the cafeteria
DIRECT AIR BLOW
TYPE
FLOOR STANDING TYPE

Specifications Page 5
Dimensions Page 10 Indoor unit FVGR05NV1 FVGR06NV1 FVGR08NV1 FVGR10NV1
Outdoor unit RUR05NY1 RUR06NY1 RUR08NY1 RUR10NY1

DUCT CONNECTION
TYPE
Specifications Page 5
Dimensions Page 11 Indoor unit FVPGR10NY1 FVPGR13NY1 FVPGR15NY1 FVPGR18NY1 FVPGR20NY1
Outdoor unit RUR10NY1 RUR13NY1 RUR15NY1 RUR18NY1 RUR20NY1

OUTDOOR UNIT
Dimensions Page 14,15

DUCT TYPE Cooling only


50Hz
HP 5 6 8 10 13 15 18 20
kW 14.7 17.6 23.5 29.3 35.2 46.9 52.8 58.6
Capacity
1, 2

Btu/h 50,000 60,000 80,000 100,000 120,000 160,000 180,000 200,000


kcal/h 12,600 15,100 20,200 25,200 30,200 40,300 45,400 50,400

DUCT TYPE
Specifications Page 6
Dimensions Page 12,13 Indoor unit FDR05NY1 FDR06NY1 FDR08NY1 FDR10NY1 FDR13NY1 FDR15NY1 FDR18NY1 FDR20NY1
Outdoor unit RUR05NY1 RUR06NY1 RUR08NY1 RUR10NY1 RUR13NY1 RUR15NY1 RUR18NY1 RUR20NY1

OUTDOOR UNIT
Dimensions Page 14,15

Note : 1Rated cooling capacities are based on the following conditions: Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Capacity includes indoor fan motor heat.
Thailand models (AFVR-N, AFVPR-N and AFDR-N series) use same specifications as FVGR-N, FVPGR-N and FDR-N series.

1 2
AIR COOLED PACKAGED AIR CONDITIONERS

FLOOR STANDING TYPE


DIRECT AIR BLOW TYPE Enhanced varieties of factory Easy operation
modification and optional Digital remote control comes standard Refrigerant pre charged for up to 7.5 metres
with indoor unit.
accesories Standard model
Allowable refrigerant pipe length and level difference
Temperature setting is possible by button operation. The set Pre-charged 1 Max. length Max. level
Factory modification difference
Contact sales for more infomation temperature is conveniently displayed on the LED. 50 m
RUR05NY1-20NY1 7.5 m (Equivalent length 70 m) 30 m
Floor Standing Type
Direct Duct Duct Type Floor standing type (Standard accessory) 1
Note: Additional refrigerant charging is required if the refrigerant pipe is longer than the
Connection
Air Blow Type indicated length.

Auto restart 9 8 Note.1 3


Modify wiring for central control
adapter kit (DTA107A55) installation 6 4-direction piping affords more freedom
Change fan motor and pulley – – 7
of layout (Applies to RUR05N/06N)
Discharge grill plenum chamber – 5 1
2
Piping can be run from the front, bottom, right or rear surface
Side discharge grillon discharge plenum chamber –
according to how the unit is installed.
FVGR10NV1
RUR10NY1 Factory Modificaion Lower drain pan – –
Note.1
4
Front suction high efficiency filter chamber – – In case of RUR08–20N, piping can be drawn out in two
Front suction base flange for front suction directions-front, and under side.
– –
high efficiency filter chamber 1 On/Off button 4 Temp. setting down 7 Compressor operation lamp.
Suction grill for front suction 2 Fan button 5 Mode button 8 Fan operation lamp.
– –
DUCT CONNECTION TYPE high efficiency filter chamber 3 Temp. setting up 6 LED display 9 Cool operation lamp.
Durability
Note.1 It cannot be used for FVPGR10–20NY1
Fresh air inlet –

Rear suction –
Duct type (optional accessory) Heat exchange fins provided with
Drain pump – 9 8 7 6 anti-corrosion treatment (Applies to all outdoor units)
Remote sensor(Thermistor for suction air) –
To achieve increased durability by improved resistance to salt
All fresh air application
corrosion and atmospheric pollution, coated PE fins (with
Low outdoor temp.15ºC application
and long pipe 70m application
special acryl pretreatment) are used for the heat exchanger of
Central control adaptor kit
the outdoor unit.
DTA107A55
(external terminal for ON/OFF , abnormal)1
LCD remote controller2 BRC1C62 10 2 3 5 4 1
intelligent Touch Controller2 DCS601C51
Space savings
Option

Central remote controller2 DCS302CA61


1 Power 5 Next setting 9 Compressor 1 indicator lamp

RUR10NY1
Unified ON/OFF controller3 DCS301B61 2 Temperature scale 6 Fan indicator lamp 10 Temperature sensor Installation space is saved thanks to a more
FVPGR10NY1 Schedule timer3 DST301BA61 3 Temperature setting 7 Cool indicator lamp compact outdoor unit. This also makes it
4 Mode setting 8 Compressor 2 indicator lamp
Remote sensor (thermistor for suction air)3 KRCS01-1B easier to install.
Remote controller BRC1NU64
53%

Note:
Previous 20HP outdoor unit RUR20NY1 space saved

Design flexibility
1
Wiring modification is needed on floor stand model to connect with central control ADP kit. RUG10AUY1 X 2 (20HP) compared to

DUCT TYPE
2
Need to use central control adapter kit for option connection. previous model
3
Central control adapter kit and LCD remote controller is necessary for option connection.

Designed for long refrigerant piping.


50 m maximum length and 30 m maximum level difference

Quiet Operation to cover medium- and large-scale building needs.


2,560mm
690
mm 765
mm
1,240mm
Equipped with scroll compressor for Outdoor unit roof
installation possible
RUR10NY1 quiet operation for plenty of leeway.
FDR10NY1
Smooth running, low
vibration, low operating
sound. Max. length

Outdoor unit
Sound level Max. level difference
380V 415V

RUR05NY1 59 dB 60 dB
RUR06NY1 59 dB 60 dB

3 4
FLOOR STANDING TYPE
DIRECT AIR BLOW TYPE DUCT TYPE
5HP 6HP 8HP 10HP 5HP 6HP 8HP 10HP
Model Indoor unit FVGR05NV1 FVGR06NV1 FVGR08NV1 FVGR10NV1 Model Indoor unit FDR05NY1 FDR06NY1 FDR08NY1 FDR10NY1
Name Outdoor unit RUR05NY1 RUR06NY1 RUR08NY1 RUR10NY1 Name Outdoor unit RUR05NY1 RUR06NY1 RUR08NY1 RUR10NY1
Power supply 380–415 V, 50 Hz, 3 Phase, 4 Wires Power supply 380–415 V, 50 Hz, 3 Phase, 4 Wires
Cooling capacity 1, 3 kW 14.7 17.6 23.5 29.3 Cooling capacity 1, 3 kW 14.7 17.6 23.5 29.3
Btu/h 50,000 60,000 80,000 100,000 Btu/h 50,000 60,000 80,000 100,000
kcal/h 12,600 15,100 20,200 25,200 kcal/h 12,600 15,100 20,200 25,200
Power consumption 1 kW 5.5 6.4 8.6 11.2 Power consumption 1 kW 5.6 6.5 9.0 11.4
Running current A 9.0 10.5 14.0 18.2 Running current A 9.5 10.9 15.3 19.4
Starting current A 72.7 80.9 118.2 135.0 Starting current A 70.0 78.2 115.5 129.5
Power factor % 88.0 87.8 88.4 88.3 Power factor % 86.2 86.2 85.1 85.3
Colour lvory White Colour Galvanized steel
Indoor Indoor
Air flow rate (H) m3/min 42 42 54 80 Airflow rate (H) m3/min 46 54 68 78
unit unit
cfm 1,480 1,480 1,910 2,830 cfm 1,620 1,910 2,400 2,750
Fan Drive Direct Drive 3 Speed Fan External static pressure mmH2O 9 10
Sound level (H/M/L) 2 dBA 59/54/50 59/54/50 60/56/51 61/57/52 Driving system Belt drive
Dimensions (HXWXD) mm 1,870X750X510 1,870X750X510 1,870X950X510 1,870X1,170X510 Sound level (H) 2 dB(A) 49 51 53
Machine weight kg 90 90 107 143 Dimensions (HXWXD) mm 450X900X850 450X1,130X850 500X1,130X850 500X1,330X850
Operation range °CWB 14 to 25 Machine weight kg 72 79 93 104
Colour Ivory white Operation range °CWB 14 to 25
Outdoor
unit Compressor Type Hermetically sealed scroll type Colour Ivory white
Outdoor
Motor output kW 4.5 4.5 6.7 9.0 Compressor Type Hermetically sealed scroll type
unit
Refrigerant Model DAPHNE FVC68D POLYOL ESTER Motor output kW 4.5 4.5 6.7 9.0
oil Charge L 1.4 1.8 3.3 Refrigerant charge (R-410A) kg 2.5 (Charged for 7.5 m) 3.5 (Charged for 7.5 m) 4.5 (Charged for 7.5 m) 6.0 (Charged for 7.5 m)
Refrigerant charge (R-410A) kg 2.5 (Charged for 7.5 m) 3.5 (Charged for 7.5 m) 4.5 (Charged for 7.5 m) 6.0 (Charged for 7.5 m) Refrigerant Model DAPHNE FVC68D POLYOL ESTER
Sound level 2 380V dBA 59 59 60 61 oil Charge L 1.4 1.8 3.3 3.3
415V dBA 60 60 61 62 Sound level 2 380V dBA 59 59 60 61
Dimensions (HXWXD) mm 1,345X900X320 1,680X930X765 415V dBA 60 60 61 62
Machine weight kg 92 105 203 206 Dimensions (HXWXD) mm 1,345X900X320 1,680X930X765
Operation range °CDB 21 to 46 Machine weight kg 92 105 203 206
Refrigerant Indoor Liquid mm o/ 9.5 (Brazing) o/ 12.7 (Brazing) Operation range °CDB 21 to 46
Piping unit Gas mm o/ 19.1 (Brazing) o/ 22.2 (Brazing) o/ 28.6 (Brazing) Piping Indoor Liquid mm o/ 9.5(Brazing) o/ 12.7(Brazing)
Drain mm PS 1B Internal thread connections unit Gas mm o/ 19.1(Brazing) o/ 22.2(Brazing) o/ 28.6(Brazing)
Outdoor Liquid mm o/ 9.5 (Flare) o/ 12.7 (Flare) Drain mm PS 3/4B Internal thread
unit Gas mm o/ 19.1 (Flare) o/ 22.2 (Brazing) o/ 28.6 (Brazing) Outdoor Liquid mm o/ 9.5(Flare) o/ 12.7(Flare)
Drain mm o/ 26.0 (Hole) ---------- unit Gas mm o/ 19.1(Flare) o/ 22.2(Brazing) o/ 28.6(Brazing)
Max. interunit piping length m 50 (equivalent length 70 m) Drain mm o/ 26.0 (Hole) ----------
Max. installation level difference m 30 Max. interunit piping length m 50 (equivalent length 70 m)
Max. installation level difference m 30
FLOOR STANDING TYPE
DUCT CONNECTION TYPE
10HP 13HP 15HP 18HP 20HP 13HP 15HP 18HP 20HP
Model Indoor unit FVPGR10NY1 FVPGR13NY1 FVPGR15NY1 FVPGR18NY1 FVPGR20NY1 Model FDR13NY1 FDR15NY1 FDR18NY1 FDR20NY1
Indoor unit
Name Outdoor unit RUR10NY1 RUR13NY1 RUR15NY1 RUR18NY1 RUR20NY1 Name Outdoor unit RUR13NY1 RUR15NY1 RUR18NY1 RUR20NY1
Power supply 380–415 V, 50 Hz, 3 Phase, 4 Wires Power supply 380–415 V, 50 Hz, 3 Phase, 4 Wires
Cooling capacity 1, 3 kW 29.3 35.2 46.9 52.8 58.6 Cooling capacity 1, 3 kW 35.2 46.9 52.8 58.6
Btu/h 100,000 120,000 160,000 180,000 200,000 Btu/h 120,000 160,000 180,000 200,000
kcal/h 25,200 30,200 40,300 45,400 50,400 kcal/h 30,200 40,300 45,400 50,400
Power consumption 1 kW 11.4 14.9 17.8 21.2 24.8 Power consumption 1 kW 15.0 17.9 21.5 25.1
Running current A 19.4 25.3 30.3 36.1 42.0 Running current A 25.5 30.3 36.5 42.5
Starting current A 129.5 118.0 130.3 143.4 146.3 Starting current A 118.0 130.3 143.4 146.3
Power factor % 85.3 85.4 85.1 85.0 85.3 Power factor % 85.3 85.6 85.3 85.5
Colour lvory White Galvanized steel
Indoor Colour
Air flow rate (H) m /min
3
80 120 162 Indoor
unit Airflow rate (H) m3/min 136 166
cfm 2,830 4,240 5,720 unit
cfm 4,800 5,860
Fan Drive Belt Drive Fan External static pressure mmH2O 15
Ext. Static Pressure Pa(mmH2O) 15 Driving system Belt drive
Sound level 2 dBA 61 62 62 63 63 Sound level (H) 2 dB(A) 58 60
Dimensions (HXWXD) mm 1,740X1,170X510 1,870X1,170X720 1,870X1,470X720 mm 625X1,620X850 625X1,980X850
Dimensions (HXWXD)
Machine weight kg 150 180 240 Machine weight kg 161 187
Operation range °CWB 14 to 25 Operation range °CWB 14 to 25
Colour Ivory white Ivory white
Outdoor Colour
Compressor Type Hermetically sealed scroll type Outdoor
unit Compressor Type Hermetically sealed scroll type
Motor output kW 9.0 5.0+5.0 6.7+6.7 7.5+7.5 9.0+9.0 unit
Motor output kW 5.0+5.0 6.7+6.7 7.5+7.5 9.0+9.0
Refrigerant Model POLYOL ESTER Refrigerant charge (R-410A) kg 4.5 (Charged for 7.5 m) 8.0 (Charged for 7.5 m)
oil Charge L 3.3 5.0 6.5
Refrigerant Model POLYOL ESTER
Refrigerant charge (R-410A) kg 6.0 (Charged for 7.5 m) 4.5 (Charged for 7.5 m) 8.0 (Charged for 7.5 m) oil Charge L 5.0 6.5 6.5 6.5
Sound level 2 380V dBA 61 61 62 63 63 Sound level 2 380V dBA 61 62 63 63
415V dBA 62 62 63 64 64 415V dBA 62 63 64 64
Dimensions (HXWXD) mm 1,680X930X765 1,680X1,240X765 Dimensions (HXWXD) mm 1,680X1,240X765
Machine weight kg 206 243 319 322 329 Machine weight kg 243 319 322 329
Operation range °CDB 21 to 46 °CDB
Operation range 21 to 46
Refrigerant Indoor Liquid mm o/ 12.7 (Brazing) o/ 15.9 (Brazing) Piping Indoor Liquid mm o/ 12.7(Brazing) o/ 15.9(Brazing)
Piping unit Gas mm o/ 28.6 (Brazing) o/ 34.9 (Brazing) unit
connections Gas mm o/ 28.6(Brazing) o/ 34.9(Brazing)
Drain mm PS 1B Internal thread Drain mm PS 1B Internal thread
Outdoor Liquid mm o/ 12.7 (Flare) o/ 15.9 (Flare) Outdoor Liquid mm o/ 12.7(Flare) o/ 15.9(Flare)
unit Gas mm o/ 28.6 (Brazing) o/ 34.9 (Brazing) unit Gas mm o/ 28.6(Brazing) o/ 34.9(Brazing)
Drain mm ---------- ----------
Drain mm
Max. interunit piping length m 50 (equivalent length 70 m) Max. interunit piping length m 50 (equivalent length 70 m)
Max. installation level difference m 30 m 30
Max. installation level difference
Note : 1Rated cooling capacities are based on the following conditions : Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
2 Note : 1Rated cooling capacities are based on the following conditions : Suction temp., 27°CDB, 19.5°CWB ; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 2
3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Capacity includes indoor fan motor heat. 3
Capacity includes indoor fan motor heat.
Thailand models (AFVR-N, AFVPR-N and AFDR-N series) use same specifications as FVGR-N, FVPGR-N and FDR-N series.

5 6
FAN PERFORMANCE
FLOOR STANDING TYPE
DUCT CONNECTION TYPE DUCT TYPE
FVPGR10NY1 FVPGR13NY1 FDR05NY1 FDR06NY1
500
FVPGR15NY1 50 14
00 Upper limit of ESP
rpm (standard ESP) 250 250
25 25
400 450
40 1500 45
rpm Upper limit of ESP Upper limit of ESP
Upper limit of ESP
(standard ESP) (standard ESP)
(standard ESP)
350 40 400
35 A160-24 13
1400 00 A170-28 200 200
External static pressure (mmH2O)

External static pressure (mmH2O)

External static pressure (mmH2O)


rpm 20 20

External static pressure (mmH2O)


rpm

External static pressure (Pa)

External static pressure (Pa)


External static pressure (Pa)

350

External static pressure (Pa)


300 35 120
30 1200
rpm A125-19 0rp
m A118-19
A150-24
1300
rpm 30 300
250 12 15 150 15 150
25 00 A118-19 A112-19
1200 A140-24 rp A160-28 1100rp 110
rpm m m 0rp
m
250
200
25 A112-19
20 A106-19
A132-24 100 100
1100 10 1000 10 100
20 200 11 rpm
rpm 00 A150-28 A106-19 0rp
m
15 150 A125-24 A100-19
rp
1000 m
rpm A118-24
15 150 900rp
m
A100-19 900 A95-19
rpm
10 100 A112-24 A140-28 5 50 A95-19 5 50
900r 10
pm 00 800rp
A90-19
A106-24 10 100 rp
m A132-28 m A90-19
80
5 50 0rp
m
800r A125-28
pm 5 50
0 0 0 0
0 0 90 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 49 51 53 55 57 59 61 63 64
0rp
68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 m Air flow rate (m3/min) Air flow rate (m3/min)
0 0
Air flow rate (m3/min) 102 106 110 114 118 120 122 126 130 134 140 144 4D064277A 4D064279A
4D064265 Air flow rate (m3/min) 4D064275

FDR08NY1 FDR10NY1
FVPGR18NY1 UPPER : FAN PULLEY 350
LOWER : MOTOR PULLEY 35
FVPGR20NY1 1400rpm Upper limit of ESP 350
500 (standard ESP) 35
50
1
Upper limit of ESP 2 2B-180-25
00
(standard ESP) rpm 2B-140-28 300
30
45 450 300
30
11
00 A160-24 130
0rp
m
Upper limit of ESP
rp 130 A150-24

External static pressure (mmH2O)

External static pressure (mmH2O)


m 0rp (standard ESP)
m
400 250

External static pressure (Pa)

External static pressure (Pa)


40
External static pressure (mmH2O)

25
2B-180-25 250
External static pressure (Pa)

2B-132-28 25
A150-24 120
350 0rp
35 120 m
0rpm
20 200
20 200
30 300
110 110
A140-24 0rp
10

0rp m
2B-180-25 m
00

2B-125-28 15 150 A140-24


rp

250 15 150
m

25
100
100
A132-24 0rp
m A132-24
0rpm
20 200 100
10 10 100
A125-24
900
rpm
A125-24
15 150 900
rpm
A118-24
90

2B-180-25 5 50 5 50
0r

A118-24
pm

100
2B-115-28 A112-24
10

0 0 0 0
5 50 80 61 63 65 67 69 71 73 74 75 79 81 82 70 72 74 76 78 80 82 84 86 88 90 92 94
0r
pm
Air flow rate (m3/min) A106-24 Air flow rate (m3/min) A112-24
0 0
A106-24
4D064278 4D064280
138 142 146 150 154 158 162 166 170 174 178 182 186 190 194 198
2B-225-25
2B-125-28 Air flow rate (m3/min)
4D064276B
FDR13NY1 B224-28 FDR18NY1
350
FDR15NY1 35 FDR20NY1
Upper limit of ESP 350
35
(standard ESP)
Upper limit of ESP
(standard ESP)
300 120 120
30 0rp 0rp
m m
300
30

External static pressure (mmH2O)

External static pressure (mmH2O)


250

External static pressure (Pa)

External static pressure (Pa)


25
250
110 25 110
0rp
m B200-28 0rp
m 2B-225-30
2B-180-28
20 200
20 200

100
0rp
B186-28 2B-250-30
m 100
15 150
0rp
m 2B-186-28
15 150
B180-28
900
rpm 2B-250-30
10 100 2B-180-28
900
rpm B170-28 10 100

2B-250-30
B160-28 800 2B-170-28
rpm
50
5
800
5 50 2B-250-30
rpm 2B-160-28

0 0 0 0
123 127 131 135 139 143 147 151 155 159 163 150 154 158 162 164 166 170 174 178 182 186 190 196 199

Air flow rate (m /min) 3


4D064281A Air flow rate (m3/min) 4D064282A

7 8
WIRING AND PIPING DIMENSIONS (Unit: mm)
FLOOR STANDING TYPE FLOOR STANDING TYPE
DIRECT AIR BLOW TYPE DIRECT AIR BLOW TYPE

FVGR05N/06N FVGR08N/10N FVGR05NV1


A B C D
RUR05N/06N RUR08N/10N FVGR06NV1 A FVGR05NV1 750 720 o/ 9.5 o/ 19.1
FVGR08NV1 FVGR06NV1 750 720 o/ 9.5 o/ 19.1
Power Power
FVGR08NV1 950 920 o/ 12.7 o/ 22.2

1 Liquid pipe conn. (C) C1220T brazing

510
2 Gas pipe conn. (D) C1220T brazing
3 Upper drain outlet (PS 1B Internal thread)
4 Power supply & control wire intake
5 Digital remote controller
Wiring Wiring

A 510
Refrigerant Refrigerant
piping piping
(Liquid, Gas) (Liquid, Gas)

330
Ground Ground
Ground Ground

370
35
FLOOR STANDING TYPE
DUCT CONNECTION TYPE

1870

1870
740
FVPGR10N FVPGR13N/15N/18N/20N
150 50
RUR10N RUR13N/15N/18N/20N 1

2
Power Power

100 100
4 3
Power

325
Power

250
70
SDR3150151C
SDR3150152B
B 474 SDR3150153C
Wiring Wiring

Refrigerant Refrigerant
piping piping
(Liquid, Gas) (Liquid, Gas)
Ground
Ground Ground Ground FVGR10NV1
1170

1 Liquid pipe conn. (ø 12.7) C1220T brazing


2 Gas pipe conn. (ø 28.6) C1220T brazing
3 Upper drain outlet (PS 1B Internal thread)
4 Power supply & control wire intake

510
5 Digital remote controller
DUCT TYPE
FDR05N/06N FDR08N/10N FDR13N/15N/18N/20N
RUR05N/06N RUR08N/10N RUR13N/15N/18N/20N
1170 510

330
Power Power Power Power Power Power

370
35
Wiring Wiring Wiring

1870

1870
Refrigerant Refrigerant Refrigerant
piping piping piping

740
Ground Ground Ground
(Liquid, Gas) (Liquid, Gas) (Liquid, Gas)
Ground Ground Remote
Ground 150 50
Remote Remote 1
Controller Controller Controller
2

100 100
4 3

325

250
70

1140 474 SDR3150154C

9 10
DIMENSIONS (Unit: mm)
FLOOR STANDING TYPE
DUCT CONNECTION TYPE DUCT TYPE

FVPGR10NY1 FDR05NY1
1170

216 334 140 334 146 1 Liquid pipe conn. (ø 12.7) C1220T brazing
2 Gas pipe conn. (ø 28.6) C1220T brazing

31
6
3 Upper drain outlet (PS 1B Internal thread) 35 850 35
4 Lower drain outlet (PS 1B Internal thread) 756 3
5 Power supply & control wire intake

292
510
6 Digital remote controller

9
4XP.150=600

4XP.150=600

1000
735

735
900
950
510 1170

177

9 9

9
390

800 or more
40 250
571

50
6 Service Space
3
290

250

1200 or more
50

1 Liquid pipe connection (ø 9.5)


290 148 2 Gas pipe connection (ø 19.1)
2 5 4
1670

63
3 Drain pipe connection (PS 3/4B Internal thread)
1740

50

50
4 Earth terminal

75
724

58
58
5 Power supply

261
50 6 Suspension bracket

150
266
266
150
1

418
450
2
150 2-M4 Burring holes 9 9

100 100
5 3 (Both sides) 2-M4 Burring holes
(Both sides)
325

46
3 1

250
90 85
70

1140
474
4 3D062899C
1199 SDR3150155C

DUCT TYPE

FVPGR13NY1 A
FDR06NY1
A B C D E F G H J K L
FVPGR15NY1 B C D
FVPGR13NY1 1170 477 398 295 344 1210 1170 1144 205 o/ 12.7 o/ 28.6
33 6
FVPGR18NY1 FVPGR15NY1 1170 477 398 295 344 1210 1170 1144 205 o/ 15.9 o/ 34.9 35 850 35
756 3
52

FVPGR20NY1 FVPGR18NY1 1470 558 474 438 407 1510 1470 1444 237 o/ 15.9 o/ 34.9

9
FVPGR20NY1 1470 558 474 438 407 1510 1470 1444 237 o/ 15.9 o/ 34.9
E
602

720

1 Liquid pipe conn. ( K ) C1220T brazing


2 Gas pipe conn. ( L ) C1220T brazing
3 Upper drain outlet (PS 1B Internal thread)
4 Lower drain outlet (PS 1B Internal thread)

5XP.180=900

5XP.180=900
5 Power supply & control wire intake

1130
1180
1230
967

967
F 6 Digital remote controller
720

G J
6-M4 6-M4
Burring holes Burring holes
(Both sides) (Both sides)

9 9
510

50
9
800 or more
Service Space 3
50

1200 or more
1 Liquid pipe connection (ø 9.5)
1800

2 Gas pipe connection (ø 19.1)


1870

148 3 Drain pipe connection (PS 3/4B Internal thread)


915

2 5 4 4 Earth terminal

63

50
5 Power supply

75
50
150 58

150 58
50
1 6 Suspension bracket

261
266

266

450
418
2
150
5
100 100

3 2-M4 Burring holes 9 9


2-M4 Burring holes
(Both sides)
(Both sides)
325

SDR3150156C 46
3 1
250

SDR3150157C 90 85
3D062900C
SDR3150158C
H
70

11 12
DIMENSIONS (Unit: mm)
DUCT TYPE OUTDOOR UNIT

FDR08NY1 / 10NY1
RUR05NY1
Hole for anchor
6 RUR06NY1 bolt 4-M12

30
39 850 39
732 3

(345 355)
9

320
350

61
48
41

30
96
140 620 140
30 900

C
D
B
A

E
A
B
4
2
F F
(Both sides) (Both sides) 1
3
10 10 7
6

1345
7

58
9
800 or more

Service Space 3 5 6
[FDR08NY1G] [FDR10NY1G]
5 5

55
1200 or more
1 Liquid pipe connection (ø 12.7)

435

55
60

410
2 Gas pipe connection (G)

223
155

95

95
95
1 5 47 4 3 Drain pipe connection

84
63

(PS 3/4B Internal thread)

54
24

89
50

50

53
54
100
4 Earth terminal
160 67

160 67
89 19 19 80 52
5 Power supply
311
294

294
6 Suspension bracket

468
79 142 145 13 67

500
8
10 10 71 16
2-M4 Burring holes 2-M4 Burring holes

16
(Both sides) (Both sides)
1 Gas pipe connection

70 102 117
46 2 Liquid pipe connection
3 2

58
3 Service port (in the unit)
A B C D E F G 4 Grounding terminal M5 (in switch box)

FDR08NY1G 876 4XP.180=720 1130 1180 1230 5-M4


Burring holes ø22.2 3D062901C
5 5 Refrigerant piping intake
6-M4 6 Power supply wiring intake
FDR10NY1G 1076 5XP.180=900 1330 1380 1430 ø28.6 3D062902C
Burring holes 45 376 191 7 Control wiring intake
3D063042A
8 Drain pipe connection

DUCT TYPE OUTDOOR UNIT

FDR13NY1 / 15NY1 / 18NY1 / 20NY1 RUR08NY1


50 or more
RUR10NY1 792 4-15 22.5-mm-Oblong holes Notes)1.Detail For Front Side And Detail For Bottom Side
Supporting plate (Pitch of foundation bolt holes) (Foundation bolt hole) Indicate The Dimensions After Fixing The Attached Piping.
(Commercially available) 2.Gas pipe

(Pitch of foundation bolt holes)


100 or more

50 or more (D) Brazing connection


Service Space 5 Liquid pipe
800 or more

Supporting plate 8

722 737
(Commercially available) 12.7 Flare connection
100 or more

1
*1
A
(Upward and downward) 2
6XP.150=900
1045

*1
7- o/ 3.1 holes

393
(Upward and
G
C
D
B

E
F

downward)

C
6 6 163 A
3 176
72.5

224
10
476.5

1680
7 DETAIL FOR FRONT SIDE

1570
7 64 64
4 4
10
172

6 1
H
55

(knock-out hole)
2
55

800 or more

205 80 205 80
9 8

393
577
(knock-out hole)

577
Service Space
5

100 177
3 4
[FDR13NY1G] [FDR18NY1G]

234
163
[FDR15NY1G] [FDR20NY1G] 500 or more 123 176

B
100 600 1 Evaporator air inlet connection 129 160 67 67 163 224
35 850 35 2 Evaporator air outlet connection 661
5
(knock-out hole) 765 DETAIL FOR BOTTOM SIDE
*1 738
*1 4- o/ 3.1 holes 3 Liquid pipe connection (J) 930
3- o/ 3.1 holes (Both sides) 4 Gas pipe connection (K)
(Both sides) 1 Liquid pipe connection port
1 5 Drain pipe connection 746
2 2 Gas pipe connection port
A B C D E F G H J K (PS 1B Internal thread) 215
3 Grounding terminal
22.5 2XP.150=300

6 Earth terminal

70

17
3XP.150=450

FDR13NY1G 10- o/ 3.1 holes 9XP.150=1350 1402 1620 1710 1750 1770 24 ø12.7 ø28.6 4 Power cord routing hole (side)
349

8
7 Power supply intake

133
5 Power cord routing hole (front)

160
544
625

FDR15NY1G 10- o/ 3.1 holes 9XP.150=1350 1402 1620 1710 1750 1770 24 ø15.9 ø34.9 8 The holes for anchor bolts 6 Power cord routing hole (front)
10 7 Power cord routing hole (bottom)
A B C D
257

FDR18NY1G 10
11XP.150=1650 1762 1980 2070 2110 2220 54 ø15.9 ø34.9
FDR20NY1G 12- o/ 3.1 holes 3D062912C
RUR08NY1 69 16 165 22.2 (knock-out hole) 45 7 (knock-out hole)
8 Wire routing hole (front)
3D062913C 9 Pipe routing hole (front) 3D062886B
38
45
61

Notes: 1Prepared holes for M4 tapping screw. 763 3D062914C RUR10NY1 75 22 171 28.6 10 Pipe routing hole (bottom) 3D062887B
805 10

13 14
DIMENSIONS (Unit: mm) Space required for indoor unit installation (Unit: mm)
OUTDOOR UNIT

RUR13NY1 1102 4-15 22.5-mm-Oblong holes FVGR05NV1 FVPGR10NY1


(Pitch of foundation bolt holes) 3D062890A
RUR15NY1
(Foundation bolt hole)
3D062891A
FVGR06NV1 FVPGR13NY1

(Pitch of foundation bolt holes)


RUR18NY1 FVGR08NV1 FVPGR15NY1
RUR20NY1 FVGR10NV1 FVPGR18NY1

737
FVPGR20NY1

722
1

2
100 or more
100 or more

393
100 or more 500 or more
100 or more 500 or more
3

171
900 or more 900 or more
163 48 176
64
64 224 Service Area Service Area

1680

1570
4 DETAIL FOR FRONT SIDE
4
6 1
(knock-out hole)
2
FDR05NY1 FDR13NY1
9
8 FDR06NY1 FDR15NY1

393
FDR08NY1 FDR18NY1
577

577
(knock-out hole)
100 177

FDR10NY1 FDR20NY1
234
163

123 176

A
129 160 163 224
972 67 67
1049 5 765 DETAIL FOR BOTTOM SIDE
1240 (knock-out hole)

1056 1 Liquid pipe connection port

213 Notes)1.Detail For Front Side And Detail For Bottom Side 2 Gas pipe connection port
Indicate The Dimensions After Fixing The Attached Piping. 3 Grounding terminal 800 or more
17
70

2.Gas pipe 4 Power cord routing hole (side)


8

A B C (B) Brazing connection 5 Power cord routing hole (front)


133

800 or more
160

1200 or more
RUR13NY1 22 28.6 12.7 Liquid pipe 6 Power cord routing hole (front)
(C) Flare connection 7 Power cord routing hole (bottom)
RUR15NY1 10 8 Wire routing hole (front)
RUR18NY1 24 34.9 15.9 7 (knock-out hole)
(knock-out hole) 45 9 Pipe routing hole (front) 800 or more
RUR20NY1
10 Pipe routing hole (bottom)
800 or more

230 230
or more or more
When installing the switch box, the suspension bolt should be When installing the switch box, the suspension bolt should be
230 mm or more away from the unit 230 mm or more away from the unit
(so that maintenance can easily be carried out the switch box). (so that maintenance can easily be carried out the switch box).

Provide enough clearance between the unit and Provide enough clearance between the unit and
the surrounding walls to prevent contact. the surrounding walls to prevent contact.
Ceiling surface
Ceiling surface

720 or more
A or more

60 or more
Return air filter
(commercially avaliable)
Drain pan
Supporting plate
Return air filer (commercially avaliable)
(commercially
available)

Model
FDR05-06 type FDR08-10 type

A 520 570

15 16
Space required for outdoor unit installation (Unit: mm)

For RUR05NY1/06NY1 For RUR08NY1/10NY1/13NY1/15NY1/18NY1/20NY1 (Please refer to engineering databook for other installation patterns.)

When there is an obstruction When there is an obstruction For single unit installation For installation in rows
on the inlet side on the outlet side
Pattern 1 Pattern 1
When the overhead space is open When the overhead space is open
300 or more 300 or more
1. For single unit installation 1. For single unit
installation
When there is an
obstruction only 10 Front 10 10 Front 10
or more or more or more 20 or more 20 or more or more
on the inlet side 2. For series installation 500 or more 500 or more
ore
or m
(more than two units) 500

ore Pattern 2 Pattern 2


rm
0o 100 or more 100 or more
10
When there are
obstructions on
both sides
ore
rm 50 Front 50 50 Front 50
0o or more or more or more 100 or more 100 or more or more
100 500 or more 500 or more
100
or m
ore
ore
When there is an obstruction ss
100 rm or le
or m
ore 10
0o in the overhead space 500
Pattern 3 Pattern 3

1000 or more
Wall height unrestricted

1. For single unit Wall height


installation 300 or more unrestricted 300 or more

2. For series installation


An obstruction
(more than two units) in the overhead space
When there are
Front 400 or more Front 400 or more
obstructions on rm
ore
o 200 or more 200 or more
both sides 2. For series installation 500

(more than two units) or le


ss
500
For centralized group layout

1000 or more
100
0o
rm
ore Pattern 1
An obstruction
200 ore in the overhead space 300 or more 300 or more
rm
or m 0o
ore 30

ore
rm 10 Front 10 10 Front 10
0o or more 20 or more or more or more 20 or more or more
100
600 or more 500 or more Front
When there is an obstruction
in the overhead space
When there are obstructions on both
1. For single unit installation
the inlet and outlet sides 10
or more Front 20 or more
10
or more
300 or more
When there is an r les
s
1000 or more

o For other patterns, please refer 500 or more


500 Pattern 1 10 10
obstruction on the to engineering databook. or more 20 or more or more

inlet side When the obstruction on the outlet side is higher than
the unit itself (There is no limit to the height of the
An obstruction
obstruction on the outlet side.) Pattern 2
in the overhead space 100 or more 100 or more
ore When the overhead space is open
rm
10 0o
When there are obstructions 1. For single unit installation
on the inlet side and ss
or le
1000 or more

both lateral sides 500 50 Front 50 50 Front 50


or more 100 or more or more or more 100 or more or more
500 or more 500 or more Front
H
L

An obstruction
in the overhead space
ore
or m
100
150
or L H or mo
re
50 50
mo
re 500 or more Front 100 or more or more
150 ore 50 100 or more 50
or o rm 500 or more or more 100 or more or more
mo
re 150
2. For series installation Unit : mm
2. For series installation (more than two units) (more than two units)
When there are obstructions Notes:
on the inlet side and
1
Heights of walls in case of Patterns 1 and 2:
Front : 1500 mm
both lateral Suction side : 500 mm
Side : Height unrestricted.
sides
L

ss Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
1000 or more

or le

h2
500 When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much
An obstruction ore generation load of heat in all outdoor unit,take the suction side space more broadly than the space to be shown in this drawing.
in the overhead space L H or m 2
If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces
300
ore respectively as shown in the figure on the right.

1500 mm
rm
100 0o 3 Suction

h1
0o 100
When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in Front
Side
rm the space available always bearing in mind the need to leave enough space for a person to pass between units and wall and
ore
for the air to circulate freely.

500 mm
If more units are to be installed than are catered for in the above patterns
ore your layout should take account of the possibility of short circuits.
200 o rm
or
mo 3 00 4
The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out
re
comfortably.

17 18