Anda di halaman 1dari 7

10/27/2017

“a” OPERATOR

FAULT ANALYSIS

Prepared by: ENGR. CABANTE

FORTESCUE’S THEOREM
EXAMPLE 1
𝑉𝐴 = 𝑉𝐴1 + 𝑉𝐴2 + 𝑉𝐴0
What is for the resultant of 1 +a + a2?
𝑉𝐵 = 𝑉𝐵1 + 𝑉𝐵2 + 𝑉𝐵0
𝑉𝐶 = 𝑉𝐶1 + 𝑉𝐶2 + 𝑉𝐶0
POSITIVE NEGATIVE ZERO SEQUENCE
SEQUENCE SEQUENCE COMPONENTS
COMPONENTS COMPONENTS

Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

POSITIVE SEQUENCE NEGATIVE SEQUENCE


0 -120 120 0 120 -120
𝑉𝐴1 = 𝑉𝐴1 ∠0 𝑉𝐴2 = 𝑉𝐴2 ∠0
𝑉𝐵1 = 𝑉𝐴1 ∠ − 120 = 𝑎2 𝑉𝐴1 𝑉𝐵2 = 𝑉𝐴2 ∠120 = 𝑎𝑉𝐴1
𝑉𝐶1 = 𝑉𝐴1 ∠120 = 𝑎𝑉𝐴1 𝑉𝐶2 = 𝑉𝐴2 ∠ − 120 = 𝑎2 𝑉𝐴1

Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

1
10/27/2017

ZERO SEQUENCE HOW TO GET THE SEQUENCES?


0 0 0 1
𝑉𝐴1 = (𝑉𝐴 + 𝑎𝑉𝐵 + 𝑎2 𝑉𝐶 )
𝑉𝐴0 = 𝑉𝐴0 ∠0 3
1
𝑉𝐵0 = 𝑉𝐴0∠0 𝑉𝐴2 = (𝑉𝐴 + 𝑎2 𝑉𝐵 + 𝑎𝑉𝐶 )
3
𝑉𝐶0 = 𝑉𝐴2 ∠0 1
𝑉𝐴0 = (𝑉𝐴 + 𝑉𝐵 + 𝑉𝐶 )
3
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

HOW TO GET THE SEQUENCES?


EXAMPLE 2
1
𝐼𝐴1 = (𝐼𝐴 + 𝑎𝐼𝐵 + 𝑎2 𝐼𝐶 ) Obtain the symmetrical components
3 of the following unbalanced currents.
1 Ia = 1.5∠30°amps.
𝐼𝐴2 = (𝐼𝐴 + 𝑎2 𝐼𝐵 + 𝑎𝐼𝐶 )
3 Ib = 1.5∠-120° amps.
Ic = 0.777∠135° amps
1
𝐼𝐴0 = (𝐼𝐴 + 𝐼𝐵 + 𝐼𝐶 )
3
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

STEPS IN DETERMINING BASE


PER UNIT SYSTEM
VALUES
𝑎𝑐𝑡𝑢𝑎𝑙 1. Choose base voltage (VB) and
𝑝𝑢 = base apparent power (SB)
𝑏𝑎𝑠𝑒 2. Solve base current (IB)
3. Solve base impedance (ZB)
𝑆𝐵
𝐼𝐵 =
3𝑉𝐵
Note: Be consistent with line and phase values
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

2
10/27/2017

CHOICE OF SB CHOICE OF VB

Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

CHOICE OF VB PER UNIT VALUES

Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

PER UNIT TO ACTUAL CHANGE OF BASE


VALUES FORMULA

Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

3
10/27/2017

EXAMPLE SHORT CIRCUIT KVA

Generator: 𝐾𝑉𝐴𝑆𝐶 = 3 𝑘𝑉𝑔𝑒𝑛 ∗ 𝐼𝑆𝐶


Any point along the system:
Generator: 15 MVA, 13.8 kV, x = 0.15 pu
Load 1: 10 MVA at 0.9 pf lead 𝑉𝑝𝑢 𝑘𝑉𝐴𝑏𝑎𝑠𝑒
T1: 25 MVA, 13.2/161 kV, x = 0.10 pu 𝐾𝑉𝐴𝑆𝐶 =
𝑍𝑢𝑝 𝑡𝑜 𝑓𝑎𝑢𝑙𝑡
T2: 15 MVA, 161/13.8 kV, x = 0.10 pu
Load 2: 4 MVA at 0.8 pf lag
If the load bus voltage is 15.18 kV, find the
voltage at the generator terminals, Vg.

Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

EXAMPLE 6 FAULT
At a certain point in an electric power A fault is a failure in any circuit that
system, the available fault MVA is interfere the normal flow of current
given to be as 400 MVA. At that point, to any given loads.
a 15MVA, 34.5 kv / 6.24 kv, 2.5%
impedance, wye-wye grounded
transformer is installed. At this
condition, determine the short circuit
MVA at the secondary side of the
transformer.

Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

IMPEDANCES TYPES OF FAULT


Positive Sequence --------- Z1
• Synchronous (X) – used in power
swing calculations
• Transient (X’) – for fault current few
cycles after fault (25 cycles)
• Subtransient (X’’) – for fault current
immediately after fault (2-5 cycles)
Negative Sequence --------- Z2
Zero Sequence --------------- Z0
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

4
10/27/2017

3-PHASE FAULT (BOLTED) EXAMPLE 3


The fault occurs on the low side of T2.
Calculate the fault current on the
generator side and the fault current on
the high side of T2.
Generator: 350 MVA, 18 kV, X’’d=18%
T1: 350 MVA 18 kV- 345kV X = 20%
T2: 200 MVA 345kV-138kV X = 15%
𝑉𝑎 = 𝑉𝑏 = 𝑉𝑐 = 0 𝑉𝐹 T3: 400 MVA 345kV-230kV X = 15%
𝐼𝑎 = 𝐼𝑏 = 𝐼𝑐 =
𝑍1
𝐼𝑎 = 𝐼𝑏 = 𝐼𝑐 𝐼𝐹 = 3𝐼𝑎
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

EXAMPLE 4 EXAMPLE 5
A 150-MVA, 13.8-kV, Y-connected, 3- A 150-MVA, 13.8-kV, Y-connected, 3-
Φ, 60-Hz alternator is operating at Φ, 60-Hz alternator is operating at
rated voltage and at no-load when a rated load and at 0.866 lagging power
three-phase fault occurs at its factor when a three-phase fault
terminals. If X’’d is equal to j0.2 p.u., occurs at its terminals. If X’’d of the
solve for the current the instant the alternator is j0.2 p.u., calculate the
fault occurs. current the instant the fault occurs.

Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

1-LINE TO GROUND FAULT 1-LINE TO GROUND FAULT

𝐼𝑎1 = 𝐼𝑎2 = 𝐼𝑎0

𝑉𝐹
𝐼𝑎1 =
𝑍1 + 𝑍2 + 𝑍0
𝐼𝐹
𝐼𝐹 = 3𝐼𝑎1
𝑉𝑎 = 0 𝐼𝑏 = 𝐼𝑐 = 0
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

5
10/27/2017

EXAMPLE 7 EXAMPLE 8
A 150-MVA, 13.8-kV, Y-connected, 3-Φ, 60- A 10-MVA, 6.9-kV, Y-connected, 3-Φ, 60-Hz
Hz alternator has a sub-transient reactance alternator has a sub-transient reactance of
of j0.25 pu, its negative-sequence reactance j0.25 pu, its negative-sequence reactance is
is j0.30 pu, and its zero-sequence reactance j0.25 pu, and its zero-sequence reactance is
is j0.15 pu. The neutral of the alternator is j0.05 pu. The neutral of the alternator is
solidly grounded. The alternator has no- grounded through a reactor having an
load when a single-line-to-ground fault actual impedance of 0.375-Ω. The
occurs on phase a of the alternator’s alternator is operating without a load when
terminals. Determine the currents and a line-to-ground fault occurs in one of its
voltages on each phase with the occurrence terminals. Determine the current in the
of the fault. faulted phase.

Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

LINE TO LINE FAULT LINE TO LINE FAULT


𝐼𝑎1 = 𝐼𝑎2

𝑉𝐹
𝐼𝑎1 =
𝑍1 + 𝑍2
𝐼𝐹
𝐼𝐹 = 3𝐼𝑎1
𝑉𝑏 = 𝑉𝑐 𝐼𝑎 = 0 𝐼𝑏 = −𝐼𝑐
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

DOUBLE LINE TO GROUND


EXAMPLE 9 FAULT
A 150-MVA, 13.8-kV, Y-connected, 3-Φ, 60-
Hz alternator has a sub-transient reactance
of j0.25 pu, its negative-sequence reactance
is j0.30 pu, and its zero-sequence reactance
is j0.15 pu. The neutral of the alternator is
solidly grounded. The alternator is
operating without a load when a line-to-line
fault occurs between the alternator’s 𝐼𝐹
terminals b and c. Determine the currents
and voltages on each phase with the
occurrence of the fault.
𝑉𝑏 = 𝑉𝑐 = 0 𝐼𝑎 = 0
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

6
10/27/2017

LINE TO LINE FAULT EXAMPLE 10


A 150-MVA, 13.8-kV, Y-connected, 3-Φ,
60-Hz alternator has a sub-transient
reactance of j0.25 pu, a negative-
sequence reactance of j0.30 pu, and a
zero-sequence reactance of j0.15 pu. The
neutral of the alternator is solidly
grounded. The alternator is unloaded
when a fault occurs between the
𝑉𝐹 alternator’s terminals b and c and
𝐼𝑎1 = 𝐼𝐹 = 3𝐼𝑎0 ground. Calculate the currents and
𝑍1 + 𝑍2 ‖ 𝑍0 voltages on each phase with the
3𝑍2 𝑉𝐹 occurrence of the fault.
𝐼𝐹 =
𝑍1 𝑍2 + 𝑍1 𝑍0 + 𝑍2 𝑍0
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE

END

Prepared by: ENGR. CABANTE

Anda mungkin juga menyukai