“a” OPERATOR
FAULT ANALYSIS
FORTESCUE’S THEOREM
EXAMPLE 1
𝑉𝐴 = 𝑉𝐴1 + 𝑉𝐴2 + 𝑉𝐴0
What is for the resultant of 1 +a + a2?
𝑉𝐵 = 𝑉𝐵1 + 𝑉𝐵2 + 𝑉𝐵0
𝑉𝐶 = 𝑉𝐶1 + 𝑉𝐶2 + 𝑉𝐶0
POSITIVE NEGATIVE ZERO SEQUENCE
SEQUENCE SEQUENCE COMPONENTS
COMPONENTS COMPONENTS
1
10/27/2017
2
10/27/2017
CHOICE OF SB CHOICE OF VB
3
10/27/2017
EXAMPLE 6 FAULT
At a certain point in an electric power A fault is a failure in any circuit that
system, the available fault MVA is interfere the normal flow of current
given to be as 400 MVA. At that point, to any given loads.
a 15MVA, 34.5 kv / 6.24 kv, 2.5%
impedance, wye-wye grounded
transformer is installed. At this
condition, determine the short circuit
MVA at the secondary side of the
transformer.
4
10/27/2017
EXAMPLE 4 EXAMPLE 5
A 150-MVA, 13.8-kV, Y-connected, 3- A 150-MVA, 13.8-kV, Y-connected, 3-
Φ, 60-Hz alternator is operating at Φ, 60-Hz alternator is operating at
rated voltage and at no-load when a rated load and at 0.866 lagging power
three-phase fault occurs at its factor when a three-phase fault
terminals. If X’’d is equal to j0.2 p.u., occurs at its terminals. If X’’d of the
solve for the current the instant the alternator is j0.2 p.u., calculate the
fault occurs. current the instant the fault occurs.
𝑉𝐹
𝐼𝑎1 =
𝑍1 + 𝑍2 + 𝑍0
𝐼𝐹
𝐼𝐹 = 3𝐼𝑎1
𝑉𝑎 = 0 𝐼𝑏 = 𝐼𝑐 = 0
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE
5
10/27/2017
EXAMPLE 7 EXAMPLE 8
A 150-MVA, 13.8-kV, Y-connected, 3-Φ, 60- A 10-MVA, 6.9-kV, Y-connected, 3-Φ, 60-Hz
Hz alternator has a sub-transient reactance alternator has a sub-transient reactance of
of j0.25 pu, its negative-sequence reactance j0.25 pu, its negative-sequence reactance is
is j0.30 pu, and its zero-sequence reactance j0.25 pu, and its zero-sequence reactance is
is j0.15 pu. The neutral of the alternator is j0.05 pu. The neutral of the alternator is
solidly grounded. The alternator has no- grounded through a reactor having an
load when a single-line-to-ground fault actual impedance of 0.375-Ω. The
occurs on phase a of the alternator’s alternator is operating without a load when
terminals. Determine the currents and a line-to-ground fault occurs in one of its
voltages on each phase with the occurrence terminals. Determine the current in the
of the fault. faulted phase.
𝑉𝐹
𝐼𝑎1 =
𝑍1 + 𝑍2
𝐼𝐹
𝐼𝐹 = 3𝐼𝑎1
𝑉𝑏 = 𝑉𝑐 𝐼𝑎 = 0 𝐼𝑏 = −𝐼𝑐
Prepared by: ENGR. CABANTE Prepared by: ENGR. CABANTE
6
10/27/2017
END