Project :

Location :
Structural Analysis
COLUMN

Properties: UM Inputs UM
*b = 500 mm
*d = 500 mm
*fc' = 20.7 mPa
*fy = 275 mPa

Pg = 0.03 Constants
Ø = 0.7

Design Axial Load

Axial Load = 200 kN

Design Criteria

Agactual = bd UM
Agactual = 250000 mm²

Design Formula

Agtheoretical = Pux10^3/(Ø)(0.80)(0.85f'c(1-Pg)+fyPg) UM
Agtheoretical = 14106.76

250000 > 14106.76 ADEQUATE mm²

*Required Reinforcement
As = PgAg
As = 7500
UM
*try : 20 mmØ R.S.B.
Ab = 314.16 mm²
n = As/Ab
n = 23.87

*say : 24 pcs.

Ast = Abn UM
Ast = 7539.82 mm²

Check Capacity
Pu = Ø(0.80)(0.85f'c(Ag-Ast)+fyAst) UM
Pu = 3550141.27
Pu = 3550.14 kN
3550.141 > 200 kN ADEQUATE