CT337

Installation Considerations When Applying Variable


Frequency Drives

PUBLIC INFORMATION

Rev 5058-CO900E Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Agenda

Today You Will Learn:

• How to correctly size your VFD

• How to properly install to minimize problems.

• How to mitigate Reflective Wave voltage spikes

• How to dampen the effects of Common Mode Current

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 2
Collect the Motor Data

Select Your VFD Based


on Motor Nameplate
Amps
Record:
Volts
Amps
RPM
Hz

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Read the Nameplate

Confirm the Input Voltage


Confirm the Output Current
Current needs to be greater than
or equal to the motor nameplate
value
Always Select the VFD Based on
Motor Nameplate Current!
Horsepower is a nominal rating

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Plan the Installation

UVW RST
PE
A PE
ASD Output ASD Input
Conduit / Armor Conduit / Armor
bond to cabinet Bond to cabinet

Cabinet Back Plane


ASD - 1 ASD - 2

B A Transient Common
Mode Current on Armor
PLC or
PE PE
Electronics
ASD - 3 ASD - 4
B Transient Common
Mode Current on PE Wire

PE PE Optional PE to
Building Structure
PE Copper Bus
B

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Pay Attention to Clearances

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Pay Attention to Clearances?

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Heat Is Your Enemy!
Just because it fits in the
box, doesn’t make the
enclosure the correct
size!

5.98”

Think of it as a 100 watt light bulb!


Don’t bake your VFD in an Easy
Bake Oven!
3.15”

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Heat Is Your Enemy!

Heat rises, give it a


path to flow.

Install the unit vertically to


allow airflow through the heat-
sink cooling fins.
Don’t block the cooling fan!

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Pay Attention to Clearances?

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Power to Power
Motor to Motor

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Pay Attention to the Control Voltage

Don’t let the Magic Smoke out!


PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Proper Grounding is a Must!

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Is Your Input Power Grounded or
Floating?

L1
L2
L3

Ungrounded Power Systems may require the removal of the Input


MOV jumper

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
AC Drive and Motor Installation Practices

Line Transients
A little protection
and good
technique
ACME INCORPORATED go a long way to
insure a good
drive installation

Common Mode
&
Capacitive Coupling
Tell me again
why I’m using
drives?
? Harmonics

Reflected Wave

Grounding
&
Bonding

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Why Should I use a DRIVE ?

• To improve process control though speed and torque


control

• To improve system efficiencies

• To extend life of equipment by reducing mechanical


stress

• Reduce power demand –Save Energy

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Why Develop the Variable Frequency Drive?

• The Promise:

• To be able to electronically vary the speed and


torque of any constant speed AC Motor.

• Torque is proportional to applied Voltage.


• Speed is proportional to applied Frequency.

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
A Little Motor Fodder?

• Most Common Enclosure


is “TEFC”
• Totally Enclosed, Fan Cooled
• Fan attached to motor shaft
rotates at same speed as
motor shaft
• Blows air over outside of motor
frame to dissipate internal heat
• Designed to provide sufficient
cooling on line power to keep
motor from overheating
• Remember: HEAT KILLS

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
What Do We Know About Fans?

• Governed by the “Laws of Affinity”


• It’s a LAW, which means it applies under all
circumstances
• Law # 1
• The volume of air moved by a fan is directly proportional to its speed.
• Faster = More Air
• Slower = Less Air
• If That Fan is Being Used to Cool an AC Motor, and the
AC Motor is Operating at Less than Nameplate Speed,
the Fan is Moving Less Air and Providing Less Cooling!

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
A Little History Lesson About AC Motors

• Late 1980’s/Early 1990’s


• No general supplier of “Inverter Rated” motors
• VFDs applied to motors caused failures due to overheating!
• A few niche suppliers modified general purpose motors to keep
them cool when operating at reduced speeds.
• De-rated Higher Horsepower Motors
• Larger metal mass = better heat transfer
• Added Constant Speed Blowers
• Constant cooling regardless of motor speed
• Addressed Only the Motor Thermal Issues
• IGBT Start to be Used By VFD Manufacturers
• Motor Service Centers Started Seeing Increased Volume of Motor Winding
Failures

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
What is an IGBT?

• Insulated Gate Bipolar Transistor


• Hybrid cross between a MosFET and a Darlington Power Transistor

An Insulated Gated Bipolar Transistor is a power


switching device capable of interfacing with low signal
level logic control.
RMOD
C1
POWER OUTPUT

Power Bipolar
SIGNAL INPUT G1
RBE

Power MOSFET
E1
Conventional model of IGBT
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
IGBT Advantages in AC drives

• Higher Switching (Carrier) Frequencies than Bipolar


Transistors
– Lower Motor Noise
– Higher Switching Frequency
– 4kHz Typical
– Lower Motor Heating
– Motor Friendly Current Waveform Due to Higher Switching Frequency
producing Less Waveform Ripple
– Better Field Oriented Control
– Higher Switching Frequency Allowing for Faster Response Time

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
IGBT vs. Bipolar
Transistor Current

7.5HP MOTOR

1336 @ 60HZ NO LOAD


SWITCHING FREQUENCY
Bi-Polar 1.26KHZ

1336 PLUS @ 60HZ


NO LOAD SWITCHING
FREQUENCY 8KHZ
IGBT

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
IGBT Advantages in AC drives

• Drive Size Reduction


– High Input Impedance – IGBT
– Voltage “Gated (Switch on/off)” Device
– Reduces Base Driver Power Consumption
– Reduces Base Driver Board Size
5Hp 1333
Darlington Pwr
5Hp PowerFlex40
IGBT

4” x 8.4” x 5.4”
10.2” x 13.6” x 7”

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
IGBT’s in VFDs

• IGBT Associated Phenomenom


• Reflective Wave or dv/dt
Energy stored in distribution system
Long Wires Runs to Motor between drive and motor is released
Input Power during switching and produces voltage
spikes.
AC DRIVE Output Power
[PWM]
typical

Hotter motors Distribution network


IGBTs can stress motor insulation
because of faster rise times
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
The Physics of it All

• Rapid voltage rise times


• The cable surge impedance does not match
the motor surge impedance----
– Voltage reflection WILL occur !! Physics! Agh!
Just tell me what
I need to do!

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Reflected Wave Investigation

• FACT: Reflected wave voltage at motor is a function of :


• Cable Length
• Cable distance between VFD and Motor

• Output Voltage Risetime


• When you turn on the switch (IGBT), how long does
it take the voltage being sent to the motor to go from
0 to Max (DC Bus Voltage).
• Typically in Micro/Nano seconds.

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Reflected Wave

VLL @ Drive
Drive

Motor

VLL @ Motor

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Effect: Peak voltage levels that search
and find insulation voids

Breakdown, Corona or Partial Discharge of motor windings

Eventual motor turn-to-turn, winding-to-winding or winding-to-


motor frame shorts

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Reflected Wave Result

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Motor Manufacturers Step to the Plate

• Most Manufacurers Now Provide a “Inverter Duty” Product


Offering
• Motors are built with “Spike Resistant” Wire
• Special Coating on Wire to Resist Voids Caused by Their
Manufacturing Process, Handling for Forming Prior to Stator
Insertion

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Protect the Motor

• Output Reactor between drive & motor


– Slopes off the waveform (lengthens rise time)
– Reduces destructive force for same amplitude
– Allows longer lead lengths
– Does create Voltage drop
• Output Filters
– dV/dt
• 1204-RWR2, 1204-RWC-17A
• 1204-TFA1, TFB2 “terminator”
• Third party devices
– Sine Wave Filter
– Distances Beyond 1000’
– Expensive Solution

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
GENERATION OF COMMON MODE
or
LINE-GROUND ELECTRICAL NOISE

Common
Mode
Issues

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
What is Common Mode Current &
How is it Generated?

DRIVE FRAME MOTOR


C FRAME
MODULE

MOTOR
WINDINGS

LOGIC C CONDUIT
MODULE

DRIVE FRAME
C
MODULE

MOTOR
FRAME
PE
X INCIDENTAL
CONTACT OF
X CONDUIT TO
BUILDING STEEL
MOTOR
LOGIC C WINDINGS
MODULE

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
IGBT Switching Creating Common Mode Current

Occurs at every IGBT switching

Top Vl-l output voltage vs. I line-ground stray cable & motor current

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
How to Measure Common Mode Current

Current to motor = current from motor.


Resultant should be zero!
Current seen is real current going somewhere?
Common Mode to Ground grid.

Oscilloscope
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
The Paths of Common Mode Current and
it’s affect on Sensitive Electronic Equipment

Input Transformer AC Drive Ilg Motor Frame


A R U
Ilg (+)
XO B S V
Vdc Motor Tach
Ilg bus W
T
(-) C lg-m
PE C Ilg
Logic
Ilg
C lg-c I
Common Mode PE lg
Current Path Vng

EARTH Potential #1 Potential #2 Potential #3


GROUND Interface Electronics
0-10V, communication,
4-20 ma,sensor interface,etc

Potential # 4 True Earth Ground (TE)


Common Mode Noise Current Path causing ground EMI
Interference
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Containing Common Mode Current

Input Transformer AC Drive Conduit Motor Frame


A R U
(+)
Ilg
XO B S V Ilg s
Vdc t Motor
bus W r
Ilg T a
p C lg-m
PE C (-)
Ilg PE
Motor PE
Ilg PE GND wire
Ilg Accidental Ilg
Common Mode Current Path Contact of
conduit

Potential #1 Potential #2 Potential #3


EARTH GROUND
Potential 4

CONDUIT PROVIDES GOOD WIRING NOISE CONTROL


BUT ACCIDENTAL CONDUIT CONTACT TO GROUND MAY
ALLOW Ilg NOISE PATH BACK TO GROUND

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Additional Containment

Shielded Cable / Armor


Input Transformer AC Drive with PVC Jacket Motor Frame
A R U
(+)
Ilg
XO B S V
Vdc Motor
bus W PVC
Ilg T
C lg-m
PE C (-)
Ilg PE
Ilg
Ilg PE
Ilg Additional
Common Mode Current Path Motor PE
GND wire

EARTH GROUND Potential #1 Potential #2 Potential #3


Potential 4

Shielded output cable/armor with PVC jacket


PROVIDES BETTER WIRING & NOISE CONTROL WITH NO ACCIDENTAL ARMOR
CONTACT TO GROUND. BUT IF NOT USED ON INPUT MAY ALLOW Ilg NOISE PATH
BACK TO GROUND

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Additional Containment

Transformer Cable / Armor Cable / Armor


Cabinet Frame & PVC JacketAC Drive & PVC Jacket Motor Frame
A
R U
Ilg
XO
B
S V Motor
Ilg PVC PVC
T W C lg-m
C PE
PE
PE Ilg
HRG or
Ilg Common Mode
SOLID GND Current Path Additional
Motor PE
GND wire

EARTH GROUND Potential #1 Potential #2 Potential #3


Potential 4

Shielded input & output cable/armor with PVC jacket


PROVIDES BETTER WIRING & NOISE CONTROL WITH NO ACCIDENTAL ARMOR
CONTACT TO GROUND. Prevents Ilg NOISE inteference PATH BACK TO GROUND.

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Common mode cores and
common mode capacitors as a solution
Common Mode
AC Drive Choke Motor Frame
A R U
Vdc bus
(+)
XO B S V Ilg
Motor
T W
(-)
C lg-m
PE C Common Mode PE
Bus Capacitors Ilg Motor PE
PE GND wire
C lg-c Ilg
IlgCommon Mode
Current Path

EARTH GROUND Potential #1 Potential #2 Potential #3


Potential 4

Implementation of CM core in drive output, CM


cores are smaller than output line reactors.

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Common mode core solution

Inverter 70 nS
output
Voltage
Vu-v
Ipeak
6 MHz Oscillation
Common
Mode
Ilg Current

Ilg Current
With Slower 1.5 us to 5 us risetime
Common
Mode Lower 200 kHz to 63 kHz Oscillation
Chokes

Lower 1/3 Ipeak


CM ferrite cores attenuate the high frequency noise peak
amplitude and more importantly the ILG noise current
rise time that develops CM noise ground voltage

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
CE or RFI filter solution

Main Plant Xfmr.LISN Drive EMI Filter AC Drive Motor Frame


A R U
XO B
S
Ilg
V Motor
Lf W
T C lg-m
C PE
Cf PE Motor PE
HRG GND wire
Unit C lg-c Ilg
Ilg

EARTH GROUND Potential #1 Potential #2 Potential #3


Potential 4
* EMI filters re-direct noise current back to drive input leads
and out of ground , must be used with shielded output
cables.
* (+) and (-) DC Bus capacitors to Ground also perform the
same function

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Isolation transformer solution

Main Plant Xfmr. Drive Isolation Xfmr. AC Drive Motor Frame


A A
R U
B Ilg Ilg
XO XO B
S V Motor
Ilg W C lg-m
C T PE
C Ilg PE Motor PE
HRG GND wire
Unit to other Ilg C lg-c Ilg
plant loads

EARTH GROUND Potential #1 Potential #2 Potential #3


Potential 4

* solidly ground drive isolation XFMR re-directs noise current back


to drive input leads and out of ground. Mount close to drive. Must
be used with shielded output cables.
* NO Ground noise in upstream ground from XFMR

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Using common mode (ferrite) cores on signal wires

SEND RECEIVE

Hi
Isignal

Load
Isignal
Lo
Z

Common Mode
Choke on Shield
Interface Leads

Ground Potential #1 Ground Potential #2

Implementation of CM core in signal lines between noisy grounds works

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Panel layout is important

U VW RST
B A ASD Output A PE ASD Input
Conduit / Armor Conduit / Armor
bond to cabinet Bond to cabinet
PE Cabinet Back Plane
ASD - 1 ASD - 2
AB
A Transient Common
Mode Current on Armor
PLC or
PE PE
Electronics
ASD - 3 ASD - 4
B Transient Common
Mode Current on PE Wire
AB
PE PE

PE Copper Bus
B
B Poor panel layout allows Ilg noise on
output armor to flow back to ground
Wire To System PE behind the PLC ground , causing
of Building Structure possible interference
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Better panel layout

UVW RST
PE
A PE
ASD Output ASD Input
Conduit / Armor Conduit / Armor
bond to cabinet Bond to cabinet

Cabinet Back Plane


ASD - 1 ASD - 2

B A Transient Common
Mode Current on Armor
PLC or
PE PE
Electronics
ASD - 3 ASD - 4
B Transient Common
Mode Current on PE Wire

PE PE Optional PE to
Building Structure
PE Copper Bus
B

Better panel layout allows Ilg noise on output armor to


flow back to input armor and out of PLC ground
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Strategy to Reduce or Eliminate CM Noise Issues

•Follow grounding recommendations to the letter


•Use recommended panel layout
•Keep motor cables short
•Use shielded cable whenever possible
•Route wires intelligently
•Use drives with CM internal cores
or
•Use external CM cores
•Set drives for the lowest carrier frequency
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
QUESTIONS and ANSWERS

PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.