Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


I Scope
This specification defines the mandatory requirements that shall apply to metal‐enclosed low‐voltage, power circuit 
breaker switchgear and drawout power circuit breakers. This equipment is designed, manufactured and tested to  Comply with Equivalent IEC 
Comply with note
International Electrotechnical Commission (IEC) Standards or North American (NA) Standards. This equipment is to be used  standard as applicable
in three phase electrical systems having a maximum RMS AC voltage not higher than 600 volts.
A. If there are any conflicts between this specification and associated purchasing, project, or engineering documents, this 
Noted
specification shall take precedence.
B. Any conflicts between this document and other applicable Mandatory Saudi Aramco Engineering Requirements 
Noted
(MSAERs) shall be addressed to the EK&RD Coordinator.
II Conflicts and Deviations
C. Any deviation from the requirements herein shall follow internal company procedure SAEP‐302. Noted
D. The designation “Commentary” is used to label a sub‐paragraph that contains comments that are explanatory or 
advisory. These comments are not mandatory, except to the extent that they explain mandatory requirements contained in  Noted
this SAMSS.
The following is a summary of all the documents which have been mentioned within this specification. The specific part(s) 
III References Noted
of these documents which are applicable have been identified throughout this specification.
Saudi Aramco Engineering Procedure
     SAEP‐302                    Waiver of a Mandatory Saudi Aramco Engineering Requirement
Saudi Aramco Materials System Specification
    16‐SAMSS‐503             Indoor Controlgear ‐ Low Voltage
A. Saudi Aramco References Saudi Aramco Forms and Data Sheets Noted as applicable
     NMR‐7910                  Non‐material Requirements for Metal‐enclosed Low‐voltage Switchgear and   Motor Control 
Centers
Saudi Aramco Inspection Requirements
     Form 175‐160100       Metal Enclosed, Low‐Voltage Switchgear Assemblies
American National Standard Institute / Institute of Electrical and Electronics Engineers
ANSI/IEEE C37.16                Standard for Switchgear Low‐Voltage Power Circuit Breakers and AC  Power
Noted as applicable
                                            Circuit Protectors; Preferred Ratings, Related Requirements, and Application 
                                            Recommendations
ANSI/IEEE C37.17                Standard for Trip Devices for AC and General Purpose DC Low‐Voltage Power 
Noted as applicable
                                            Circuit Breakers
ANSI/IEEE C37.50                Standard Test Procedures for Low‐Voltage AC Power Circuit Breakers Used in
Noted as applicable
                                            Enclosures
ANSI/IEEE C37.51                Standard for Metal‐Enclosed Low‐Voltage AC Power Circuit Breaker Switchgear
Noted as applicable
                                            Assemblies Conformance Test Procedures
ANSI/IEEE C37.13                Low‐Voltage AC Power Circuit Breakers Used in Enclosures Noted as applicable
ANSI/IEEE C37.20.1             Metal‐Enclosed Low‐Voltage Power Circuit‐Breaker Switchgear Noted as applicable
ANSI/IEEE C39.1                  Requirements for Electrical Analog Indicating Instruments Noted as applicable
ANSI/IEEE C57.13                IEEE Standard Requirements for Instrument Transformers Noted as applicable
National Electrical Manufacturers Association
Noted as applicable
NEMA AB 1                          Molded Case Circuit Breakers and Molded Case Switches
NEMA ST 20                         Dry Type Transformers for General Application Noted as applicable
National Fire Protection Association
Noted as applicable
NFPA 20                               Standard for the Installation of Centrifugal Fire Pumps

Page 1 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


NFPA 70                               National Electrical Code (NEC) Noted as applicable
NFPA 70E                             Standard for Electrical Safety in the Workplace Noted as applicable
Underwriters Laboratories, Inc.
Noted as applicable
UL 198D                               Standard for Safety Class K Fuses
Industry Codes and Standards
UL 198E                               Standard for Safety Class R Fuses Noted as applicable
UL 489                                 Molded Case Circuit Breakers and Circuit Breaker Enclosures Comply with equivalent IEC 
Comply with note
standard "IEC 60947‐2"
International Electrotechnical Commission
Comply
IEC 60947Series                  Low‐voltage Switchgear and Controlgear
IEC 61439‐1                         Low voltage Switchgear and Controlgear Assemblies Comply
IEC 60947                            Low‐voltage Switchgear and Controlgear Comply
IEC 60947‐1                         Part 1: General Rules Comply
IEC 60947‐2                         Part 2: Circuit Breakers Comply
IEC 60947‐5‐1                      Part 5: Control Circuit Devices and Switching Elements. Section One 
Comply
                                             Electromechanical Control Circuit Devices
IEC 60947‐6‐1                      Part 6: Multiple Function Equipment ‐ Transfer Switching Equipment Comply
IEC 60947‐7‐1                      Part 7: Ancillary Equipment. Section 1 ‐ Terminal Blocks for Copper Conductors Comply
IEC 60051                             Direct Acting Analog Electrical Measuring Instruments Noted as applicable
IEC 60044‐1                         Current Transformers Comply
IEC 60186                             Voltage Transformers Comply
IEC 60227                             Polyvinyl Chloride Insulated Cables of Rated Voltages Up to and Including 
Noted
                                             450/750 Volts
IEC 60269                            Low Voltage Fuses Comply
IEC 60414                            Safety Requirements of Indicating and Recording Instruments Comply
IEC 60473                            Dimensions for Panel Mounted Indicating and Recording (IP Code) Instruments Comply
IEC 60529                            Degrees of Protection Provided by Enclosures Comply
IEC 60947‐2                         Low Voltage Switchgear and Controlgear Part 2: Circuit Breakers Comply
The following list of information shall be supplied with the Quotation: ‐
A. A detailed listing of all deviations from this specification with an explanation against each item. In addition, written 
IV Information Required with Quotation certification shall be provided that the proposed equipment shall fully comply with all other items within this specification. Noted

B. Completed Data Sheet. Noted
V Definitions  ‐
25 Synchronizing or synchrocheck device. Noted
27 Undervoltage relay. Noted
86 Lock‐out relay. Shall not require control power to maintain the locked‐out condition. Noted
Bus Tie Breaker A breaker used to connect the two busses of secondary‐selective system. Noted
In a secondary‐selective system, during a breaker transfer operation, the bus tie breaker is closed while both the incoming 
Closed Transition breakers are closed. In general terms, if there are two possible sources of power, both may be connected temporarily. Noted

Controlgear Equipment manufactured to 16‐SAMSS‐503 (Indoor Controlgear ‐ Low Voltage). Noted


Discrete Device which only performs one function. For example, a discrete voltmeter only displays voltage. Noted

Page 2 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


Primary switchgear protection, breaker control functions and metering are integrated within a common system within the 
switchgear lineup. This means that breaker control/trip decisions may not be resident within the individual breakers. 
Integrated Protection and Control System (IPCS) Primary protection, control and interlock systems shall be 100% redundant. The IPCS systems shall be supplied by the  Noted
switchgear manufacturer during the time of manufacturer and shall be manufactured as a fully engineered functional 
system.
Line The terminal of the switching device to which the source of voltage/power is connected. Noted
Load The terminal of the switching device to which the equipment receiving the voltage/power is connected. Noted
In a secondary‐selective system, during a breaker transfer operation, the bus tie breaker is closed after one of the 
Open‐Transition incoming breakers is open. In general terms, if there are two possible sources of power, there will only be one connected at  Noted
any time.
The manufacturer who designed the equipment and who confirmed the design performance through certified design/type 
Noted
tests. This manufacturer
Parent Equipment Manufacturer (PEM) (1) has the legal authority to license the assembly of this equipment to others  Noted
(2) is responsible for the technical performance of the equipment and  Noted
(3) will be able to provide after‐sales support and parts for the equipment. Noted
A switchgear assembly consisting of two buses connected with a single bus tie breaker. Each bus has one breaker to 
Secondary‐Selec ve receive incoming power. (i.e., power flow into and between the two busses is controlled with three breakers). Noted

Space A compartment the same as a  spare but without the power circuit breaker installed. Noted


A compartment completely developed (including a power circuit breaker, protective relays, control switches, indicating 
lights, etc.) and ready for operation when the feeder and control cables are connected with the load.The “Spare” power 
Spare Noted
circuit breaker shall have the same rating as the other feeder circuit breakers.

Used in the context of protective relay circuits. The supervised devices shall be continuously checked for circuit continuity 
Supervised by having a small amount of current pass through the device. Loss of this current flow shall change the status of either a  Noted
visual indicator or relay.
Switchgear or Assembly The complete assemblage of switching assemblies as it will appear after installation by the Buyer. Noted
The assembly of switching devices and associated control and auxiliary equipment which controls or distributes power to a 
single load or via a single circuit. For this specification, all switching assemblies are withdrawable circuit breakers; 
Switching Assembly Noted
therefore, the terms “switching assembly” and “withdrawable circuit breaker” are synonymous.

Switching Device A device designed to make or break current. Noted


An energy‐reducing maintenance switch allows a worker to set a circuit breaker trip unit to “no intentional delay” to 
Energy Reducing Maintenance Switch reduce the clearing time while the worker is working within an arc‐flash boundary as defined in NFPA 70E. Noted

VI General ‐
A. Terms in bold font are defined within Section 5. Noted
The switchgear and air circuit breakers shall also fully comply with either IEC or NA standards. Switchgear built utilizing a 
mixture of standards is unacceptable (e.g., It is not acceptable for devices only tested and rated by IEC standards to be 
B. Noted
installed within a switchgear assembly tested and rated per NA standards, or vice versa).

All requirements of this specification must be implemented using standard designs which have been approved, have been 
C. Noted
fully tested, and are fully supported by the PEM.

Page 3 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


Whenever this specification requires compliance to a third party document such as ANSI or IEC standards this document 
D. Noted
shall be the edition which was in effect on the date of the Quotation Request.
E. All documentation shall be in English. Noted
F. All temperatures expressed within this specification are in Celsius units. Noted
The Buyer's nonmaterial requirements are presented within Saudi Aramco Form NMR‐7910. This form is included with the 
G. Noted
Quotation Request or the Purchase Order documents.
VII Modifications to Industry Standards ‐
The following paragraph numbers refer to IEC 60947 series, “Low‐Voltage Switchgear and Controlgear” and IEC 61439 
“Low‐Voltage Switchgear and Controlgear Assemblies” which are part of this specification. The text in each paragraph 
below is an addition, exception, modification, or deletion to IEC 60947 and IEC 61439 series as noted.” Paragraph numbers 
Noted
not appearing in IEC 60947 and IEC 61439 are new paragraphs to be inserted in numerical order. System built to North 
American (NA) based Standards shall comply with “NA Supplement”, and it shall also comply with all applicable sections 
within this document.
A. Service Conditions (IEC 61439‐1) ‐
Service Condition (IEC 61439‐1) (Modification‐1) Switchgear shall be suitable for continuous operation under the following service conditions:
Noted
a) A maximum of 40 degrees.                           Noted
7 Ambient air temperature:
b) A minimum of 0 degrees.   Noted
a)  For a period of 24 hours, does not exceed 75%. Noted
Relative humidity (average value):
b)  For a period of 1 month, does not exceed 70%. Noted
B. Construction Requirements (IEC 61439‐1) ‐
8 Constructional Requirements (IEC 61439‐1) ‐
(Exception‐1) Each switchgear assembly shall consist of free‐standing, vertical, dead‐front steel structures containing draw‐
out power circuit breakers, power and ground buses, instruments, switches, wiring, terminations, painting, and nameplates  Comply
as required.
(Exception‐2) The switchgear assembly shall have a three‐phase, RMS symmetrical short circuit current rating equal to the 
Comply
short circuit rating of the lowest rated power circuit breaker utilized within the assembly.
(Exception‐3) The continuous rating of the complete switchgear assembly shall not be dependent on the use of cooling fans 
Comply
1)  General or other auxiliary cooling means.
(Exception‐4) The main circuit bus systems of switchgear and controlgear shall not be connected together. Noted As per requirement
Exception:
Noted
If the  switchgear/controlgear  is a direct replacement for existing equipment that is physically connected
NA Supplement
Switchgear designed to NA standards shall meet, as a minimum, the requirements of ANSI/IEEE C37.20.1, and conformance  Not applicable Panel designed as per IEC 61439
requirements of ANSI/IEEE C37.51.
(Exception‐1) The stationary steel structure assembly shall be a self‐contained multiple unit housing having the required 
Noted
number of vertical sections.
(Exception‐2) Sheet steel barriers shall be provided between the vertical sections, the breaker compartments in each 
Noted
vertical section, and control and power compartments.
(Exception‐3) Switchgear shall meet as a minimum “FORM 4” internal separation requirements as specified in 
IEC 61439‐1. Noted

Page 4 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


(Exception‐4) The complete assembly shall have a minimum of IP20 “Degree of Protection”, as specified in 
Noted
IEC 60529 with all doors closed.
(Exception‐5) With a compartment door open and the circuit breaker in the connected or disconnected position, the 
interior assembly shall have a minimum of IP 40 “Degree of Protection”, as specified in IEC 60529. Noted

(Addition‐1) The bus tie breaker shall be in a separate vertical section (one‐high arrangement). Noted
(Addition‐2) Spare and Space requirements shall be as follows: ‐
a) Within the assembly, a minimum of one space shall be provided for each breaker rating Noted
b) There shall be a minimum of one space on each bus section. Noted
c) The switchgear shall be designed to permit the utilization of the locations identified spare or space: Noted
i) Without de‐energizing the switchgear main circuit and Noted
ii) By the use of simple fasteners and standard tools and Noted
d) Refer to associated engineering documents for spare requirements and space requirements beyond the minimum 
Noted
indicated above.
2) Stationary Structure (Addition‐3) There shall be a minimum of one space on each bus section for each secondary‐selective switchgear lineup. 
Refer to associated engineering documents for spare requirements and space requirements beyond these minimums. Noted

Commentary 8.2.2.4:
Noted
Note that per Section 8.2 and Section 4, all the feeder and spare breakers shall be of the same rating.
(Addition‐4) Rear sections of all vertical sections shall be developed as separate spaces for main and incoming buses or 
Noted
cables and for outgoing power cables and power cable terminations.
(Exception‐6) Feeder breakers shall be limited to a three high arrangement. The top compartment in a four high vertical 
Noted
section shall be reserved for controls, meters, and relays.
(Exception‐7) Automatic safety shutters shall be provided as a protective barrier in the stationary structure to prevent 
incidental contact with live parts of the primary circuit when a circuit breaker is moved to its disconnected or withdrawn  Noted as applicable For ACB only
position.
(Addition‐5) Breaker Handling Mechanism as follow: ‐
a) One manual racking lever or ratchet handle shall be provided with each switchgear assembly. Noted
b) The racking mechanism shall move the circuit breaker between the connected, test, and disconnect positions.
Noted
c) One circuit breaker lifting device shall be provided for each switchgear assembly. Can be offered separately as per 
Noted as applicable
contract.
(Exception‐8) Space heaters shall not be installed within the switchgear assembly. Noted
NA Supplement
Enclosures for switchgear built to ANSI standards shall, as a minimum, meet the requirements of ANSI/IEEE C37.20.1. Not applicable Panel designed as per IEC 61439

(Addition‐1) Metal‐enclosed low‐voltage switchgear assemblies shall be furnished complete with three‐phase main and 
feeder buses and ground bus. Compartmentalization as specified above requires that the main bus be isolated from contact  Comply
from the front and rear of the switchgear.
(Exception‐1) Switchgear buses (power and ground) shall be constructed of electrical grade copper and mounted (except 
the ground bus) on insulators manufactured from ceramic or other low‐hygroscopic, high‐temperature, flame‐retardant,  Noted
non‐tracking, insulating material.

Page 5 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


(Addition‐2) All buses shall be designed for future extension and it shall not be necessary to disturb any equipment or 
Comply
wiring when an extension is made.
(Exception‐2) Neutral buses shall not be installed. Noted
Exception:
Noted
If the  switchgear  is a direct replacement for existing switchgear that has a neutral bus system.
(Exception‐3) Power bus phase arrangement shall be 1‐2‐3, counting from front to back, top to bottom, or left to right, as 
Noted
viewed from the front of the switchgear assembly.
(Exception‐4) Continuous current rating of the main buses shall be at least equal to the continuous current rating of the 
Noted
highest rated circuit breaker installed in the switchgear assembly.
3) Buses
(Exception‐5) Each bus shall be braced to withstand, without damage, the sustained mechanical forces imposed by the 
Noted
maximum short‐circuit current available at the location of the switchgear.
(Addition‐3) The short circuit bus bracing and short time withstand ratings shall be a minimum of 50 kA symmetrical 
amperes at a rated maximum of 600 Volts AC. The duration of the short time withstand rating shall not less than 30 cycles  Comply
and the duration of the short circuit withstand shall not be less the 4 cycles.
(Exception‐6) The entire length of main power buses shall be equally rated. Tapered bus sizing is prohibited.
Noted
Commentary 8.3.2.5:
Noted
Reduced bus size is permitted for the taps to the main power bus.
(Exception‐7) Cable is not allowed for use as a power bus, either main horizontal or vertical buses. Noted
(Addition‐4) A solid copper ground bus shall be furnished and shall extend the entire length of the switchgear. The ground 
Comply as applicable
bus shall be capable of carrying the rated short circuit current.
(Addition‐5) A ground bus shall be firmly secured to each vertical section structure. It shall be positioned to allow easy 
accessibility for ground cable connections, but must be positioned so as not to interfere with feeder cable connections  Comply
within the cubicles.
(Exception‐1) All copper bus connection surfaces shall be silver‐plated or tin‐plated. Comply
(Addition‐1) All bus connections (splices) shall be bolted utilizing SAE Grade 5 minimum, 105 psi (7.3815 kg/cm²) tensile 
strength bolts or ISO Metric Grade 8.8 high tensile steel bolts. Flat washers and split lock‐washers or Belleville washers shall  Comply as applicable
be used to secure the bolted connection.
(Exception‐2) The total temperature (hottest spot) of bolted bus connections shall not exceed 105 degrees. Noted
(Addition‐2) Connections at butted bus joints (splices) shall be made with help of two overlapping (splicing) plates. Splice 
Comply as applicable
plates are not required for overlapping bus joints (splices).
4) Bus Connections and Cable Terminations (Addition‐3) Butted bus joint connections shall be made with a minimum of four bolts, two bolts at each bus end section 
for a total of at least four bolts in the splice plates. Overlapping bus joints shall have a minimum of 2 bolts at the end of  Comply as applicable
each bus.
(Exception‐3) Feeder Tee‐off connections from the main bus shall have the same short circuit rating as the main bus. Noted
(Addition‐4) The load side buses of each circuit breaker compartment shall have provisions (be predrilled) for terminating 2‐
Comply with note As per requirement
hole lugs for the required number of cables as indicated on the Engineering Drawings.
(Addition‐5) Provisions shall be made for supporting power cables and/or cable terminators so the weight of the cables is 
Comply
not imposed upon the terminations.
(Exception‐1) The manufacture's factory standard paint system for switchgear and circuit breakers manufactured in 
Noted as applicable
compliance with the above referenced standards is acceptable.
5) Finish

Page 6 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


5) Finish
(Addition‐1) Carbon steel switchgear and circuit breaker parts that are not painted shall be plated with cadmium, yellow 
Comply as applicable Galvanized sheet metal
zinc‐chromate or similar corrosion resistant materials.
(Addition‐1) The Manufacturer's shop order number, date, and catalog designation should be indicated on the switchgear 
Comply
nameplate in addition to the nameplate information required by the standards.
(Addition‐2) Device nameplates shall be provided for the identification of each breaker and auxiliary unit, indicating the 
Comply
circuit number and load served or equipment contained within an auxiliary cubicle.
(Addition‐3) All front panel mounted devices shall be identified by an escutcheon or nameplate on the front of the panel 
Comply
and by a nameplate on the rear of panel adjacent to each device terminal.
(Addition‐4) Protective relay nameplates shall be provided to indicate protective function, ANSI/IEC device number, and 
Comply
phase(s) which is/are monitored.
6) Nameplate (Addition‐5) Device nameplates shall be engraved laminated plastic with black 6‐mm characters on a white 60‐mm by 25‐
Comply
mm background as a minimum.
(Addition‐6) Device nameplates shall be in the English language according to American usage. Comply
(Addition‐7) Exterior mounted nameplates shall be attached with mechanical hardware. Comply
(Addition‐8) Warning nameplates shall be provided on each compartment door in which an external voltage source is 
terminated reading: “CAUTION ‐ THIS UNIT IS SUPPLIED BY AN EXTERNAL VOLTAGE SOURCE!”. Warning nameplates shall 
be engraved laminated plastic with white letters on a red background and shall be written in both Arabic and English. Comply
 (If noted on the purchase order Arabic nameplates may be provided and mounted by others in the field.)

C. Power Circuit Breakers (IEC 60947‐2)
(Exception‐1) Power circuit breaker maximum continuous current rating shall not exceed 4,000 amperes. The interrupting 
rating shall not exceed a maximum of 85 kA RMS symmetrical amperes. Noted

4.3 Rated and Limiting Values of the Main Circuit NA Supplement


Low voltage power circuit breakers utilized in switchgear compliant with ANSI/IEEE C37.20.1 shall be designed, rated, 
Not applicable Breakers designed as per IEC
manufactured, and tested in accordance with the most current issue of the following standards: ANSI/IEEE C37.13, C37.16, 
C37.17, and C37.50.
(Exception‐1) Only dead‐front, draw out design, low‐voltage power circuit breakers shall be used. Noted
(Exception‐2) Stationary mounted type power circuit breakers, series‐connected, series‐rated or cascade rated circuit 
Noted
breakers shall not be used.
(Exception‐3) Fused power circuit breakers shall not be used. Noted
(Exception‐4) Insulated case (encased) and molded case circuit breakers shall not be used in lieu of power circuit breakers.
Noted
4 Characteristics of Circuit‐breakers
(Exception‐5) The continuous current rating of each low‐voltage power circuit breaker shall not be dependent on fan 
Noted
cooling or other auxiliary cooling.
(Addition‐1) Feeder circuit breakers in the switchgear assembly shall be electrically operated, have the same ratings and be 
Comply
interchangeable.
(Addition‐2) The incoming and bus tie breakers within a secondary‐selective switchgear assembly shall be electrically 
Comply
operated, have the same rating and be interchangeable.
(Exception‐1) Low‐voltage power circuit breakers shall be equipped with a spring type, stored‐energy mechanism 
(electrically and mechanically charged), designed to close and latch the circuit breaker mechanism at rated short circuit  Noted
current conditions.

Page 7 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


(Addition‐1) Electrically operated circuit breakers, in addition to a direct acting, integral, solid state trip system, shall be 
equipped with an electrically operated, stored‐energy, operating mechanism, a shunt trip coil, trip push‐button, close push‐ Comply
button, control devices as specified and must also be manually operable.
(Addition‐2) The power circuit breakers shall be equipped with the necessary disconnecting contacts, wheels, rollers, slide 
Comply
plates, etc., and interlocks for draw out application.
(Addition‐3) Construction shall permit the compartment door to be closed with the power circuit breaker in the connected, 
disconnected test, and fully withdrawn or removed positions. The fully withdrawn position is the position when the breaker  Comply
is removed from the cubicle drawout rails.
Auxiliary Devices
(Addition‐1) Each circuit breaker shall be equipped with a position indicator, mechanically connected to the circuit breaker  Comply
7.1 Constructional Requirements mechanism.
(Addition‐2) Each circuit breaker shall have a minimum of four (4) convertible auxiliary contacts or two normally open and 
two normally closed contacts available for BUYER use, wired to terminal blocks. These contacts shall be in addition to those  Comply as applicable
required for circuit breaker operation and indication.
(Addition‐3) An alarm switch shall be provided for remote annunciation of an automatic trip by over‐current, or other 
Comply
protective device. This switch shall not be operated by other trips.
Safety Lockout Provisions
(Addition‐1) Padlocking provisions shall be provided on all circuit breakers, racking (levering) mechanisms or cubicles that 
will enable personnel to secure the cubicle. Provisions for pad locking the circuit breaker shall ensure the circuit breaker is  Comply
open, prevent manual or electrical closing and secure the breaker in the test or disconnected position.

Commentary Note 9.5:
Padlocking supplied on the breaker cubicle drawout rails to prevent installation of circuit breakers if maintenance is being  Noted
performed on downstream loads is acceptable.
Instrument and Control Transformers 
D. Noted
(IEC 60044 and IEC 60186)
(Exceptoin‐1) Current transformers or sensors shall be installed in a manner that does not alter or modify their nameplate 
Noted
ratios.
D.1 Current Transformers (CT) (IEC 60044)
(Exception‐2) The looping of feeder cables or secondary conductors through window type current transformers or sensors 
Noted
is prohibited.
Voltage Transformers (VT) and Control Power Transformers (CPT's) (IEC 60186) Noted
(Exception‐1) Voltage transformer secondary voltage shall be 120 volts and the VA rating compatible with the control and 
Noted
metering loads and of the connected devices.
(Addition‐1) Over current protection of voltage transformers shall be provided by dual‐element or fast‐acting fuses placed 
Comply
D.2 on the primary and secondary side.
(Addition‐2) Fuse holders shall be conveniently located for replacement of fuses. Comply
NA Supplement
Instrument transformers utilized in switchgear manufactured in compliance with ANSI standards shall conform to the  Noted as applicable
requirements of ANSI/IEEE C57.13. Voltage transformers shall comply with NEMA ST 20.
E. Protective Relaying (IEC 60947‐1)
(Exception‐1) Circuit breakers shall be equipped, with integral, direct acting, adjustable, solid‐state tripping systems. These 
shall be completely self‐contained requiring no external power source or control circuits for automatic tripping. Noted

Page 8 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


(Addition‐1) The solid state trip systems shall be furnished with adjustable long‐time, instantaneous, short‐time, and 
ground protective functions or their combinations. The continuous current rating shall be adjustable from 100% to at least 
50% of the current rating of the circuit breaker frame. The instantaneous trip function shall only be provided if specified  Comply
within the Buyers engineering documents. Refer to the Buyers engineering documents for the specific trip function 
requirements for each breaker.
Trip Devices
(Addition‐2) The integral, solid state trip systems shall be capable of being field tested with a Buyer supplied portable test 
E.1 device capable of simulating fault conditions and providing verification of the selected setting and characteristics desired  Comply
for all protective functions.
(Addition‐3) Power circuit breakers shall be equipped with integral, self‐powered SST trip units. These SST trip units shall 
trip the breaker for all protective functions (i.e., external protective relays shall not be used to trip the breakers). Comply

(Addition‐4) Power circuit breakers shall be equipped with Energy Reducing Maintenance Switch with local status 

indicator.
(Exception‐1) The protection schemes for Fire Pump Unit (FPU) packages shall comply with NFPA 20 and NFPA 70. In 
general, these standards require that the motor be allowed to operate under locked rotor condition continuously and is  Noted
only automatically disconnected under short‐circuit conditions.
Exception:
E.2 Fire Pump System Protection
The exception to these requirements is that where a FPU package is fed from a bus that has ground overcurrent protection 
on the incomers or supply transformers, the feeder to the FPU package shall have ground overcurrent protection, and all  Noted
other feeders connected to the same buses or transformers shall have ground overcurrent protection.

F. Control (IEC‐60947‐5)
(Addition‐1) Over‐current protection of instrument transformers, closing and tripping circuits, and other control circuits 
F.1 General Noted
shall be provided.
(Addition‐1) The control voltage level for all tripping circuits which are not integral to the breaker shall be 125 VDC supplied 
Noted
by the Buyer.
(Addition‐2) If control power for closing circuits or auxiliary systems is derived from control transformers within the 
switchgear, there shall be one control transformers for every incoming breaker. These control transformers shall be 
connected to the line side of the breaker. For secondary selective systems, an instantaneous open‐transition transfer  Noted
scheme shall ensure that there is control power available so long as there is voltage on one of the CPT primaries.

(Addition‐3) A molded case circuit breaker or fuses shall be provided for protection and isolation of tripping and closing 
circuits which are external to the circuit breaker. A dedicated breaker or fuse set shall be used for both the trip and close 
F.2 Control Power circuits for each electrically operated circuit breaker. These shall be mounted within the low voltage compartment of each  Noted
operational circuit breaker, spare or space. Separate breakers or fuses shall be provided for the auxiliary circuits (e.g., 
metering or synchronizing devices).
(Addition‐4) Voltages and current signals to protective relays shall pass through a set of isolation test switches either 
integral to the relay or mounted within the low voltage compartment. These shall be configured to allow isolation of the  Noted
relays for testing purposes.
Exception:
Noted
Switchgear with IPCS.
(Exception‐1) The rated control voltage of all devices (e.g., protective relays) shall be the same as the control supply voltage 
Noted
(i.e., intermediate voltage converters shall not be used).

Page 9 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


(Exception‐1) Auxiliary lockout relays (Device 86) shall be hand‐reset type and have separate contacts connected in the 
Noted
closing and tripping circuits of the circuit breakers.
(Addition‐1) The electrical continuity of the Device 86 operating coil circuit shall be supervised by a relay. Noted
F.3 Lockout Relays (Addition‐2) A minimum of two normally‐open and two normally‐closed spare contacts shall be provided on each lockout 
Noted
relay.
(Addition‐3) The lockout relays shall be equipped with a mechanical target indicating the tripped and reset positions.
Noted
(Addition‐1) Trip‐isolation test switches (not ganged) shall be installed in the lockout trip circuits of the incoming circuit 
F.4 Isolation Test Switches breakers. The test switches shall be mounted on the front door of compartment containing the protective relaying. Noted

(Exception‐1) Circuit protection for switchgear built to IEC standards shall be provided by fuses of the cylindrical cap design 
and meet the requirements of IEC 60269 or molded case circuit breakers that comply with IEC 60947‐2. Noted

F.5 Fuses NA Supplement


Circuit protection for switchgear built to NA standards shall be provided by dual‐element or fast‐acting fuses Class K or R or 
Noted as applicable Panel designed as per IEC
Midget type in compliance with UL 198D or UL 198E or UL 428 or molded case circuit breakers in compliance with NEMA 
AB 1 and UL 489.
Metering and Indication
G.
(IEC‐60947‐5 and IEC 60051)
(Addition‐1) Meters and instruments shown on the drawings for each circuit breaker unit shall be mounted in the 
G.1 General Noted
compartment associated with the circuit breaker or in the compartment directly above.
(Addition‐1) Each compartment containing an electrically operated power circuit breaker shall be equipped with status 
indicating lights. The red and green lights shall show the position of the power circuit breaker's main contacts: red in closed  Noted
position and green in open position.
(Exception‐1) Indicating lights shall be high intensity Light Emitting Diode (LED) type. LED lamps shall provide a light 
Noted
G.2 Indicating Lights (IEC‐60947‐5‐1) intensity similar to a incandescent fixture.
(Addition‐2) The light fixtures shall be constructed to withstand permanent shorting out of the lamp terminals without 

damage or interference to the lighting circuit power supply.
(Exception‐2) Indicating lights shall be installed in the front panel‐door or the cubicle frame next to the control switch they 
Noted
operate with and be replaceable from the front.
(Addition‐1) Main incoming amperage and voltage metering shall be provided for each main circuit bus of the switchgear 
Comply
assembly. This metering shall have the following requirements:
Discrete voltmeter(s) shall be used with the following characteristics: ‐
i) Shall display a voltage indication of the bus on at least one phase. Comply
ii) If operated through a selector switch, switch shall not have an 'OFF' position. (i.e., there will not be a situation where the 
Noted
main incoming circuit is energized and the meter is not reading a voltage).
iii) These meters shall not require a control power to function. Comply
G.3 Metering (IEC 60051) iv) If a main incoming breaker is used, voltage shall be measured on the load side (bus side) of the breaker. Noted
(Exception‐1) Discrete meters (e.g., ammeters, voltmeters, pf meters, etc.) shall not be installed within feeder breakers or 
Noted
bus tie breaker.
(Exception‐2) Panel meters utilized in IEC standard switchgear shall be circular or quadrant scale type and conform to the 
Noted
requirements of IEC 60051, IEC 60414, and IEC 60473.

Page 10 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


NA Supplement
Panel meters utilized in switchgear manufactured in compliance with NA standards shall conform to the requirements of  Noted as applicable
ANSI/IEEE C39.1.
(Addition‐1) The contacts from the following shall be series connected to a termination point within one of the low voltage 
compartments. These will be connected by the Buyer to a local annunciator panel. Loss of continuity at these termination  Noted
points will be alarmed at this panel.
G.4 Alarms a) 86 relays which have blocked an automatic transfer Noted
b) 86 coil monitoring relays Noted
c) Loss of DC control power on each bus Noted
d) Incoming transformer alarms for each bus (to be field connected by Buyer). Noted
(Addition‐1) Within a secondary‐selective assembly, an open‐transition transfer shall be automatically initiated by a 
loss/reduction of voltage on any of the two buses. If specified within the system design, after this transfer has occurred: Noted as applicable As per requirement

a). A closed‐transition re‐transfer shall be automatically initiated within an adjustable time period of 0 to 30 minutes after 
Noted as applicable As per requirement
the voltage on the disconnected source has been restored, and
b). An open‐transition re‐transfer shall be automatically initiated within an adjustable time period of 1 to 10 seconds after 
Noted as applicable As per requirement
the supply to the switchgear fails while the voltage at the disconnected source is normal.
(Addition‐2) There shall be a manually initiated closed‐transition transfer. If all three breakers are closed, a timer 
Noted as applicable As per requirement
(adjustable from 5 to 50 seconds) shall automatically open the bus tie breaker.
H. Automatic Transfer Schemes (IEC 60947‐6‐1) (Exception‐1) Closed‐transition transfers shall be with permission of a 25 relay. Noted as applicable As per requirement
(Addition‐3) Automatic open‐transition transfers shall be delayed to: Noted as applicable As per requirement
a) Allow time for motor residual voltage to decay to a negligible value or the motors to be automatically disconnected.
Noted as applicable As per requirement
b) Ensure that transfer is not initiated because of a fault. Noted as applicable As per requirement
(Addition‐4) All transfers shall be blocked and locked out by the switchgear bus or incoming transformer 86 relays.
Noted as applicable As per requirement
(Addition‐5) Loss/reduction of voltage shall be detected by a 27 relay on the line side of each incoming breaker. The setting 
shall be 85% of nominal bus voltage and the time delay shall be adjustable from 1 to 10 seconds Noted as applicable As per requirement

I. Accessories (IEC‐60497)
(Exception‐1) Internal low voltage wiring shall be stranded copper conductors only and shall meet the following minimum 
I.1 Wiring ‐
requirements:
Conductors in switchgear manufactured to IEC standards shall be a minimum of 2.5 mm², 90°C, 600 volt, flame retardant, 
I.1.1 moisture, and heat resistant thermoplastic insulation conforming to the requirements of IEC 60227. Noted

Each wire shall be identified with heat‐shrinkable or plastic, slip‐on wire markers with permanently printed characters. 
I.1.2 Noted
Snap‐on or adhesive type markers are prohibited. All wiring shall be numbered at both ends.
The numbering of the wire markers shall correspond to the numbering of the connection points in the switchgear control 
I.1.3 Noted
and protection system's schematic drawings.
I.1.4 Each control circuit shall be easily traceable for inspection checks and modifications. Noted
Wiring shall be attached to inner panels by mechanical attachment hardware. Use of adhesives for supplemental support is 
Noted
acceptable.

Page 11 of 12
Compliance Statement (16‐SAMSS‐502)

Clause no. Topic Description Compliance Remarks


I.1.5 NA Supplement
Conductors in switchgear manufactured to NA standards shall be a minimum 14 AWG, 90°C, 600‐volt insulation type SIS,  Noted
THHN or XHHW as specified in NFPA 70 (NEC).
(Exception‐1) Connections to terminal blocks shall be made with insulated flanged fork, locking fork or similarly designed 
wire terminals. Wire terminals of these types are prevented from accidentally coming off a slightly loosened screw. Noted
I.2 Wire Terminals
(Addition‐1) Insulated Ring type wire terminals shall be used in current transformer wire terminations. Noted
(Exception‐2) Soldered terminals are not acceptable. Noted
(Exception‐1) All connection points between switchgear assembly auxiliary devices and field wiring shall be made with 
Noted
terminal blocks.
(Exception‐2) Terminal blocks shall be open style, barrier type, with screw terminals, rated 20 A, 600 volt minimum with 
Noted
pre‐numbered marking strips and suitable for two (2) terminations per point.
I.3 Terminal Blocks for Field Wiring (IEC 60947‐7‐1)
(Addition‐1) A maximum of two (2) wires per point shall be permitted. Noted
(Addition‐2) Current transformers shall be terminated on Shorting Type terminal blocks. Noted
(Addition‐3) 20% spare terminal block points shall be provided. Noted
(Exception‐3) Terminal blocks may be panel or rail mounted. Noted
(Addition‐1) All required special tools, such as non‐standard wrenches, sockets, etc., used to latch/unlatch, bolt/unbolt the 
I.4 Special Tools equipment supplied under this specification, shall be provided with each metal‐enclosed low‐voltage switchgear assembly. Noted As per contract

(Exception‐1) Completely assembled, wired, and adjusted metal‐enclosed low‐voltage switchgear assemblies shall be 
Comply
tested in order to verify compliance with the requirements of this specification.
(Exception‐2) At the time of delivery, the VENDOR shall furnish the BUYER with a list of standards and specifications to 
Comply
which the metal‐enclosed low‐voltage switchgear assemblies were tested.
J Tests (IEC 61439‐1 and IEC 60947‐1) (Exceptoin‐3) Routine production tests will be performed on the complete assembly of switchgear and circuit breakers.
Comply
(Exception‐4) Design or Type tests shall be provided for the switchgear and circuit breakers. Tests on representative 
Comply
equipment may be submitted for technical evaluation.
(Exception‐5) Accessory devices, other than functional components, of power circuit breakers and low‐voltage switchgear 
Comply
assemblies shall be tested in accordance with the VENDOR determined standards.

Page 12 of 12