1. A,B,C TYPE
ENSURE 230V AC CONTROL SUPPLY IS ON.
ENSURE 415V AC FAN SUPPLY IS ON.
ENSURE 24V-48V DC VOLTAGE CONNECTED TO MODULE.
STEP1: PRESS F3
STEP 2: TYPE MB BCHOSEI ; 1 ADJUSTMENT MODE ENABLE
STEP 3: TYPE MB BTOOLT ; 1 TOOL MODE ENABLE
STEP 4: TYPE MB BDBG ; 1 DISABLE DIGITAL ILK
STEP 5: TYPE V 38 ; 1700 72 CONTACTOR MALFUNCTION
STORE THE VALUE IN FLASH BY SELECTING Y
STEP 6: TYPE RST APL APPLICATION RESET
AFTER RESET START AFRESH AND RE-ENTER VALUES AS PER STEP 1~4
IT IS VERY LIKELY THAT ZERO NOTCH AND CONV ABNORMAL FAULT S MAY STILL BE ACTIVE.
CONNECT A SWITCH/ MCB BETWEEN TERMINAL 13 -14 OF TB2 AND PUT A JUMPER BETWEEN
TERMINALS 15-16 IN TB2 OF HRD 450 CARD.
CHECK INTERLOCK AND FAULTS BY ENTERING F8.
NEXT:
IN CASE DRIVE IS FAULTY, PRESS YELLOW (FAULT) PB AND RESET THE DRIVE.
2. D- TYPE
ENSURE 230V AC CONTROL SUPPLY IS ON.
ENSURE 415V AC FAN SUPPLY IS ON.
ENSURE 24V-48V DC VOLTAGE IS CONNECTED TO THE MODULE.
ENSURE DIPSW2 ON HMD931 HAS JUMPER SHORTING PIN 7 AND PIN 10, IT MEANS
16 10
DRIVE IS ONLINE.
1 7
9
OFFLINE= JUMPER ON PIN 8 AND PIN 9
8
STEP1: PRESS F3
STEP 2: TYPE MB BCHOSEI ; 1 ADJUSTMENT MODE ENABLE
STEP 3: TYPE MB BTOOLT ;1 TOOL MODE ENABLE
CONNECT A SWITCH/ MCB BETWEEN TERMINAL A10- A25 OF TB2 IN HRD 455 CARD.
NEXT:
RELAY B9,B10,B11 WILL PICK UP IF THERE IS NO WIRING PROBLEM.