Anda di halaman 1dari 12

Page: 1+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR

BASIC DATA
1 CUSTOMER
COMPANY MMTE
2 OPERATING AND AMBIENT CONDITIONS
2.1 Site ambient conditions shall be as follows:
2.2 Min. / Max. Temperature: 25.6 / + 41.8 ºc
2.3 Sun Shine Temperature:
2.4 Humidity: 70%
2.5 Altitude above sea level: 1100 m
2.6 Environment: Dusty(Iron Dust), Corrosive Climmate: Plain
3 ELECTRICAL DATA
3.1 RATED VOLTAGE 36 kV
3.2 SERVICE VOLTAGE 33 kV
3.3 VOLTAGE FLUCTUATION STATIONARY ± 5% INSTANTANEOUS ± 10%
3.4 RATED FREQUENCY 50 Hz
3.5 FREQUENCY FLUCTUATION ± 1 Hz
3.6 COMBINED VOLTAGE AND FREQUENCY FLUCTUATION, STEADY STATE ± 2 %
3.7 NO. OF PHASES / WIRES 3/3
3.8 PE CONDUCTOR YES
3.10 MAX ... MVA MIN
SHORT CIRCUIT FAULT LEVEL
MAX 31.5 kA(rms) MIN kA (rms)
3.11 SHORT TIME CURRENT 31.5 kA(rms) 1s 3s X
3.12 SHORT CIRCUIT CURRENT BREAKING 25 kA(rms)
MAKING 80 kA(peak)
3.14 FROM: UPS-SYSTEM TAG-NO. : DC UPS
CONTROL VOLTAGE FAILSAFE VOLTAGE 110 V DC 2 WIRE
NEUTRAL ISOLATED
3.15 FROM: LV SWITCHGEAR TAG-NO. : LV SWITCHGEAR
AUXILIARY VOLTAGE FOR PANEL
VOLTAGE 230 V AC 1 PH, 2 WIRE
HEATER AND LIGHTING
NEUTRAL SOLIDLY EARTHED

3.16 RATED INSULATION LEVEL FOR ONE MINUTE:


TO EARTH AND BETWEEN PHASES 70 kV rms
ACROSS THE ISOLATING DISTANCE 80 kV rms
3.17 IMPULSE WITHSTAND VOLTAGE
TO EARTH AND BETWEEN PHASES 170 kV peak
ACROSS THE ISOLATING DISTANCE 195 kV peak

REMARKS:

TO BE FILLED BY VENDOR
X TO BE SUPPLIED BY VENDOR
N.A. NOT APPLICABLE
Page: 2+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR
Page: 3+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR

GENERAL DATA
1 GENERAL
1.1 MANUFACTURER/COUNTRY /
1.2 MODEL TYPE/DESIGNATION /
1.3 CUBICLE TYPE WITHDRAWABLE X
FIXED-TYPE
1.4 TEST POSITION X
1.5 INSULATION AIR INSULATED (WITH PVC COVER) X
GIS FOR DIRTY INCOMING X
1.6 MIMIC DIAGRAM ON EACH CUBICLE X
1.7 WIRING IDENTIFICATION WIRE FERRULES WITH TERMINAL NO: X
SYSTEM PRINTED NUMBERS ON WIRES
1.8 PER CUBICLE X
SEPARATE CONTROL VOLTAGE PER BUS SECTION X
CIRCUITS INDIVIDUALLY FUSED
BY MCB FOR PANEL HEATERS X
FOR DISPLAYS & ALARMS X
CUBICLE
1.9 SPACE HEATER WITH THERMOSTAT 230 V AC X
1.10 CUBICLE INTERNAL LIGHTING WITH ON/OFF SWITCH 230 V AC X
1.11 WASTE HEAT OF SWITCHGEAR FULL LOAD kW STANDBY kW
1.12 PAINT FINISH COLOUR TYPE RAL 7032 X
1.13 PERSONNEL PROTECTION ACC. TO IEC RECOMMENDATION & PEHLA test X
2 CONSTRUCTION
2.1 DEGREE OF PROTECTION IP 42 DEGREE OF PROTECTION WITH OPEN DOOR IP 20
2.2 ENCLOSURE METAL ENCLOSED & METAL CLAD X
METAL ENCLOSED, CUBICLE TYPE
2.3 PARTITIONS BETWEEN CUBICLES (EXCEPT BUS BAR COMPARTMENT) X
2.4 SEPARATE BUS BARS X
PARTITIONED SWITCHING EQUIPMENT X
COMPARTMENTS MV CABLE CONNECTION X
LV COMPARTMENT X
3 BUSBARS AND BUS DUCTS
3.1 BUSBARS
3.1.1 SINGLE BUSBAR SYSTEM
3.1.2 DOUBLE DUAL-FEEDER BREAKER
BUSBAR SINGLE-FEEDER BREAKER
SYSTEM SINGLE BUSBAR FEEDER
3.1.3 BUSBAR INSULATION INSULATED X NON-INSULATED
3.1.4 BUSBAR SECTIONS
3.1.5 BUSBAR RATED CURRENT
Page: 4+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR
Page: 5+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR

GENERAL DATA
4 SWITCHING DEVICES
4.1 GENERAL SF6 CIRCUIT BREAKER
SWITCHING DEVICES CHOICE MOTOR FEEDER
TRANSFORMER FEEDER SF6 CIRCUIT BREAKER
4.2 CIRCUIT BREAKER
4.2.1 MANUFACTURER
4.2.2 MODEL TYPE/DESIGNATION
4.2.3 VACUUM
C.B. TYPE SF6 X
MINIMUM OIL
4.2.4 MIN. NO. OF SPARE AUX. CONTAC 6 N.O. + 6 N.C.
4.2.5 NO-VOLT TRIP X
C.B. TRIP CIRCUIT RELEASE
SHUNT TRIP X
4.2.6 IF REQUIRED
C.B. VENTILATION
NOT VENTILATED X
5 PROTECTION
5.1 ELECTROMECHANICAL WITHDRAWABLE X
SOLID STATE X PROGRAMMABLE X
PROTECTION RELAY FEATURES
MICROPROCESSOR BASED X SERIAL DATA INTERFACE X
MULTIFUNCTION TYPE X
5.1.1 MANUFACTURER
5.1.2 MODEL TYPE FOR EACH RELAY
5.1.3 SEPARATE LOCKOUT RELAY X
5.3 HEALTHY TRIP CIRCUIT LAMP/LED X
SUPERVISION ALARM X
5.4 TEST PLUGS (1 SET FOR EACH TYPE) X
6 CURRENT TRANSFORMERS & VOLTAGE TRANSFORMERS
6.1 GENERAL TYPE CAST RESIN X OTHER
6.2 CURRENT TRANSFORMERS
6.2.1 SECONDARY CURRENT 1A X 5A
6.2.2 ACCURACY CLASS & BURDEN FOR MEASURING 0.5,….VA
FOR PROTECTION 5 P 20,…. VA and class X
6.2.3 TEST BLOCK FOR EACH CORE (WITH 1 SET OF TEST PLUG) X
6.3 CORE BALANCE (SLIP-OVER) TYPE 5 P 10,... VA RATIO 60/1 A
6.4 VOLTAGE TRANSFORMERS
6.4.1 ACCURACY CLASS & BURDEN .5+3P …. VA
6.4.2 WITHDRAWABLE ON BUS BAR ON INCOMER X
6.4.3 FUSE FAILURE SUPERVISION (STRIKER PIN) X
6.4.4 TEST BLOCK FOR EACH WINDING (WITH 1 SET OF TEST PLUG) X
7 INSTRUMENTS
ACCURACY CLASS CLASS 0.5 1 1.5 3
A-METER, V-METER, COS PHI METER X
kWh-METER, kVAr-METER X
kWh-METER FOR TARIFF METERING X
FREQUENCY METER X
Page: 6+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR
Page: 7+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR

GENERAL DATA
8 CONTROL UNIT
8.1 CONTROL TASK: CONTROLLER TYPE: (RELAY LOGIC, PLC, NETWORK CONTROL CENTRE, OTHER)
8.1.1 AUTOMATIC TRANSFER N.A.
8.1.2 MANUAL TRANSFER N.A.
8.1.3 AUTOMATIC REACCELERATION X
8.1.4 LOAD SHEDDING N.A.
8.1.5 POWER FACTOR CONTROL N.A.
9 SIGNALS, INDICATIONS, ALARMS
9.1 SIGNAL TRANSFER METHOD: HARD-WIRED Serial Interface
9.1.1 ALARMS X
9.1.2 START, STOP, RUNNING, ETC. X
9.1.3 START, STOP, FROM LCS X
9.1.4 EMERGENCY STOP X
9.1.5 SERIAL BUS TYPE N.A.
9.2 INDICATIONS: LAMP MECHANICAL
9.2.1 C.B. ON X X
9.2.2 C.B. OFF X X
9.2.3 C.B. TRIPPED X
9.2.4 MV MOTOR STARTER ON X
9.2.5 EARTHING SWITCH X
9.2.6 CUBICLE COMMON FAULT X
9.2.7 CUBICLE READY FOR OPERATION X
9.2.8 CUBICLE IN TEST POSITION X
9.2.9 CUBICLE SPACE HEATER ON X
9.2.10 MOTOR SPACE HEATER ON X
9.2.11 DC FAILURE X
9.2.12 CAPACITIVE VOLTAGE INDICATOR X
FROM
9.3 TRANSFER SIGNALS: TO CONTROL ROOM CONTROL
ROOM
9.3.1 MV MOTOR START N.A. N.A.
9.3.2 MV MOTOR STOP N.A. N.A.
9.3.3 MV MOTOR LOCAL/REMOTE N.A. N.A.
9.3.4 MV MOTOR INTERLOCK N.A. N.A.
9.3.5 MV MOTOR RUN INDICATION N.A. N.A.
9.3.6 CUBICLE COMMON FAULT X
9.3.7 CUBICLE READY FOR OPERATION X
9.3.8 SWITCHGEAR GENERAL ALARM X
9.3.9 CUBICLE TEST POSITION X
9.3.10 EARTHING SWITCH X
9.4 ALARM ANNOUNCIATION* WINDOWS Push Botton
9.4.1 Transformer Winding Temp. Alarm
9.4.2 Transformer Winding Temp. Trip
9.4.3 Transformer Oil Temp. Alarm
9.4.4 Transformer Oil Temp. Trip
9.4.5 Transformer BuchHolz Relay Alarm
9.4.6 Transformer BuchHolz Relay Trip
9.4.7 Transformer Pressure Relief Trip
9.4.8 Transformer Oil Level Alarm
Page: 8+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR

9.4.9 Transformer Oil Level Trip


9.4.10 Up-stream Feeder Trip
9.4.11 Up-stream Earth Switch Closed
9.4.12 Differential Protection Trip
9.4.13 Acknowledge, Lamp Test , Reset
Page: 9+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR

GENERAL DATA
10 MECHANICAL ARRANGEMENT
BACK TO BACK
10.1 CUBICLE ARRANGEMENT BACK TO WALL
BACKSIDE ACCESSIBLE X
10.2 CONCRETE FLOOR X
ROOM FLOOR DESIGN
FALSE FLOOR
10.3 SWITCHGEAR MAIN FRAME 2.5 mm STEEL
10.4 CUBICLE GLAND PLATE & GLANDS YES
10.5 CABLE ENTRY FROM ABOVE FROM BELOW X
SEALED WITH CABLE GLAND X
10.6 BUS DUCT ENTRY N.A. FROM ABOVE FROM BELOW
10.7 SWITCHGEAR EXTENDIBLE FROM BOTH SIDES X FROM ONE SIDE
10.8 SPARE CUBICLES WITH BREAKER X WITHOUT BREAKER
10.9 WEIGHT TOTAL kg EACH CUBICLE kg
LENGTH mm mm
10.10 SWITCHGEAR DIMENSIONS WIDTH mm mm
HEIGHT mm mm
11 ACCESSORIES & TOOLS
11.1 C.B. OPERATING HANDLE & C.B. WITHDRAWING HANDLE 2 Pcs. (each)
11.2 C.B. HANDLING TROLLEY 1 Pcs.
11.3 EARTHING HANDLE 2 Pcs.
11.4 KEY FOR LV COMPARTMENT DOOR 6 Pcs.
11.5 KEY FOR MV COMPARTMENT DOOR 6 Pcs.
11.6 PADLOCKS FOR BREAKER COMPARTMENT 6 Pcs.
11.7 PAINT SET FOR REPAIRS 2 kgs.
12 SPARE PARTS
12.1 C.B. 1250 A Pcs.
12.2 C.B. 630 A Pcs.
12.3 C.B. TRIP COIL & CLOSE COIL 1 Pcs. (each)
12.4 C.B. MOTOR for spring charging 1 Pcs.
12.5 PROTECTION RELAY TYPE 50/51/50N/51N Pcs.
12.6 PROTECTION RELAY TYPE 51 G Pcs.
12.7 PROTECTION RELAY TYPE 27M/59 Pcs.
12.8 PROTECTION RELAY TYPE 86 Pcs.
12.9 PROTECTION RELAY TYPE 87N/87T/87M Pcs.
12.10 C.B. AUXILIARY CONTACT BLOCK 2 Sets
12.11 MV HRC FUSE Set
12.12 MCB 2P & 3P 2 Pcs. (each)
12.13 AUXILIARY RELAY & LIMIT SWTCH 2 Pcs. (each)
12.14 BULB FOR INDICATOR LAMPS 20 Pcs.
13 REMARKS:
Page: 10+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR
Page: 11+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR

INCOMING CLEAN BUS FEEDER


IDENTICAL PANELS: 1 PCS.
TAG NO.:
1 SWITCHING SF6 CIRCUIT BREAKER X 8 PROTECTION RELAYS
DEVICE FUSED CONTACTOR 8.1 PROTECTIVE FUNCTION ANSI / IEEE RELAY
SWITCH DISCONNECTOR CODE NO. QTY.
1.1 RATED CURRENT 2500 A THERMAL OVERCURRENT 49 N.A.
1.2 AUXILIARY CONTACTS (SPARE) 6 N.O. + 6 N.C. OVERCURRENT INSTANT. 50 1
2 EARTHING SWITCH X INVERSE TIME OVERCURRENT 51 1
2.1 AUXILIARY CONTACTS (SPARE) 2 N.O. + 2 N.C. EARTH FAULT INSTANTANIOUS 50 N 1
2.2 INDICATOR MECHANICAL DRIVEN EARTH FAULT INV. TIME 51 N 1
3 SURGE ARRESTOR UNDERVOLTAGE 27 1
TYPE VARISTOR Pcs. OVERVOLTAGE 59 1
4 INSTRUMENT TRANSFORMERS SENSETIVE EARTH FAULT 50G/51G N.A.
4.1 CURRENT TRANSFORMER X DIRECTIONAL POWER 32 N.A.
RATIO 2000/1/1/1 A TRANS.DIFFERENTIAL PROT. 87T 1
CORES: CLASS RATING RESTRICTED EARTH FAULT 87N 1
MEASURING CORE 0.5 ….VA PILOT WIRE PROTECTION 85 N.A.
PROTECTION CORES 5 P 20, CLASS X …. VA SYNCHRO-CHECK 25 N.A.
4.2 CORE BALANCE CT 5 P 10 LOCKOUT 86 1
RATIO A TRIP CIRCUIT SUPERVISION 95 1
CLASS RATING ….VA 8.2 RELAY TYPE 1 VA
4.3 VOLTAGE TRANSFORMER & HRC Fuse X & BURDEN 2 VA
RATIO [33kV/SQRT(3)]/[110V/SQRT(3)] 3 VA
CLASS 0.5+ 3 P RATING …. VA 9 REMOTE SIGNALS: TO FROM
V.T PROTECTION FUSE WITH STRIKER PIN x CONTROL CONTROL
RATED CURRENT 2A QTY. 3 Nos. C.B. OPEN POSITION X
5 PUSH- ON X C.B. CLOSED POSITION X
BUTTONS OFF X COMMON FAULT X
AND SWITCHES MANUAL-OFF-AUTO SELECTOR CUBICLE READY for Operation X
LAMP TEST X TRIP FROM UPSTREAM SIDE X
6 INDICATING C.B. Open X C.B. ON X
C.B. Closed X C.B. OFF X
LAMPS Cubicle Common Fault X ANALOG SIGNALS FOR
X
Ready for Operation X (U,I,F,P,Q,PF)

C.B. Tripped X 10 MAIN POWER CONNECTION


OR INDICATOR CAPACITIVE VOLTAGE INDICATORS X 10.1 CABLE X

7* INDICATING VOLTMETER 1 pcs. NO. AND CROSS-SECTION ……

SELECTOR SWITC 4 POSITION 1 pcs. TYPE XLPE/PVC


INSTRUMENTS A-METER 3 pcs. OUTER DIAMETER mm
AND SELECTOR SWITCH ENTRY FROM BOTTOM ENTRY TYPEGLAND
COUNTERS OPERATIONS COUNTER X 10.2 BUS DUCT N.A. pcs.
kWh METER X DIMENSIONS mm
kVARh METER X 11 CUBICLE WEIGHT kg
COS PHI METER X 12 CUBICLE DIMENSION LxWxH mm
FREQUENCY METER X 13 CUBICLE WASTE HEAT W
WATT METER X 14 ACCESSORIES X
Page: 12+2 of 12+2 .

MIYANEH STEEL COMPLEX MME ELCO MMTE

Steel Making Plant Project


ASCOTEC MMAH
NISCO
Document No. : Rev.

Document Title : Project Document No. : MISP1301ETS121 1-1 Date : NOV. 2009
230/33 KV SUBSTATION
Designer Document No. : MWES1U43E001210011
DATA SHEET FOR MV SWITCHGEAR

VAR METER X
REMARKS: * All metering devices can be integrated in one multi-meter as an alternative.
Note: All alarm & trip signals from transformer & up stream S/S shall be indicated
on the alarm windows

REFRENCES:

Anda mungkin juga menyukai