x) Rated short circuit making 63 kA
I
pressure (ms)
xv) Closing time (rms) ; <150ms
xvi) Mounting • Hot dip galvanized lattices steel support
structured bolted type
xvii) Phase to phase spacing in the *
400
switch yard i.e., interpole spacing
for breaker (min.)
xviii) Required ground clearance from 2820
the lowest line terminal if both the
terminals are not in same
horizontal plane (cum)
xix) Height of concrete plinth (mm) 150
xx) Minimum creepage distance of 900
support insulator (mm)
xxi) Standard value of rated transient •
As per IEC-56
recovery voltage for terminal fault
\
xxii) Standard value of rated line RRRV
*.
Characteristics Surge Peak Factor
For Short Line faults Impedance
Factor K= 1.6 A
KV/ms = 0.214
Z (ohms) = 450
'.
xxiii) Rated operating
'
a) duty cycle 0-0.3 Second - CO-3 Minutes - CO
b) Auto reclosing
*
Suitable for three phase Auto / reclosing
duty
xxiv) Rated insulation level under heavy 170 kV
pollution condition 1.2/50 micro
second lightening Impulse
withstand voltage (kV Peak) to
earth
xxv) 1 min. Power Frequency Withstand 70 kV
Voltage kV (rms) to Earth (kV rms)
±15%
d) Combined variation of
frequency and voltage
xxviii) Number of auxiliary contacts 10 NO and 10 NC on each pole
Continuous current rating 10 Amps,
DC at 110/30 volts DC or 240 V AC
xxii)
1)1 10 y DC/SO VDC
}
±15%
frequency and voltage
1 0 NO and 10 NC on each pole Continuous
• ••x .••
xxiv) Number of coils '• 2(Two) trip coils and 1 close coil with anti-
pumping arrangement
xxv) Rated terminal load 100kg. Static. The breaker shall be designed
to withstand the rated terminal load, wind,
load, earthquake load and short circuit
forces.