SUPPLY DUCTING INSULATION CALCULATION SHEET

1 Insulation thickness calculation follow below formular:

X=(λ/α) x ((To-Ts)/(Ts-Tn)) (1)

λ: Thermal conductivity of insulation (kcal/mhdeg)


α: Surface conductance (kcal/m2hdeg). General 7kcal/m2hdeg
To: Temperature inside of insulation (12*C)
Tn: Outside temperature
Ts:Dew point temperature of air
X: Thickness of insulation

2 Specification of PE insulation
λ= 0.0416 (kcal/mhdeg)

3 Design condition : On the ceiling.

Insulation
No Temperature (Tn) Humidity Dewpoint (Ts) x (mm)
1 30 90% 28.2 53.485714
2 30 80% 26.2 22.207519
3 30 75% 25.1 15.888047
4 30 70% 23.9 11.593443
SUPPLY DUCTING INSULATION CALCULATION SHEET
1 Insulation thickness calculation follow below formular:

X=(λ/α) x ((To-Ts)/(Ts-Tn)) (1)

λ: Thermal conductivity of insulation (kcal/mhdeg)


α: Surface conductance (kcal/m2hdeg). General 7kcal/m2hdeg
15 To: Temperature inside of insulation (Pipe 12*C, Air duct 15*C)
Tn: Outside temperature
Ts:Dew point temperature of air
X: Thickness of insulation

2 Specification of PE insulation
λ= 0.028 (kcal/mhdeg) 0.032 (W/mK)

3 Design condition : On the ceiling.

Insulation
No Temperature (Tn) Humidity Dewpoint (Ts) x (mm)
1 27 90% 26.1 48.487619
2 27 85% 25.2 22.278095
3 27 80% 24.2 12.917551
4 27 75% 23.2 8.483609

1 30 90% 28.1 27.106165


2 30 85% 27.1 16.403547
3 30 80% 26.1 11.189451
4 30 75% 25.1 8.1035569