HANDBOOK ON
TESTING INSTRUMENTS REQUIRED
FOR
CONDITION BASED MAINTENANCE
OF
TRD ASSETS
CAMTECH/E/2009/TI-TRD/1.0
August 2009
QUALITY POLICY
Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 3
FOREWORD
This handbook covers details of such instruments which are useful in condition
based monitoring of TRD assets. Necessary information such as make, model, technical
specifications and sources of supply have been included for reference.
Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 4
PREFACE
With the increase in traffic, getting a block to maintain the different Railway assets
is increasingly becoming more and more difficult. To carry out the optimum maintenance
(in right quantity and at the right moment) condition monitoring techniques are of great
help.
This document has been compiled by CAMTECH and gives a ready reference of
all the condition based maintenance equipments available which can be used for the above
purpose.
It is clarified that this handbook does not supersede any existing provisions laid
down by RDSO or Railway Board. This handbook is for guidance only and it is not a
statutory document.
Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 5
CONTENTS
Foreword iii
Preface iv
Contents v
Correction Slip vii
1.0 OBJECT 01
1.1 BENEFITS OF CONDITION MONITORING 01
1.2 VARIOUS EQUIPMENTS TO BE MONITORED 01
2.0 TESTING INSTRUMENTS FOR TRANSFORMERS 02
2.1 PARAMETER TO BE MONITORED AND WHY 02
2.2 WINDING RESISTANCE MEASUREMENT 04
2.3 WINDING INSULATION RESISTANCE MEASUREMENT 05
2.4 CAPACITANCE & TAN DELTA MEASUREMENT 06
2.5 TRANSFORMER TURN RATIO MEASUREMENT 08
2.6 DISSOLVED GAS ANALYSIS 10
2.7 FAULT GAS AND MOISTURE MONITORING 12
2.8 OIL TAN DELTA MEASUREMENT 14
2.9 OIL BREAK DOWN VOLTAGE MEASUREMENT 16
2.10 SWEEP FREQUENCY RESPONSE ANALYSIS 18
3.0 TESTING INSTRUMENT FOR CIRCUIT BREAKERS/ INTERRUPTERS 20
3.1 PARAMETERS TO BE MONITORED AND WHY 20
3.2 DYNAMIC CONTACT RESISTANCE MEASUREMENT 21
3.3 CONTACT RESISTANCE MEASUREMENT 23
3.4 TIME INTERVAL MEASUREMENT 24
4.0 TESTING INSTRUMENTS FOR CURRENT TRANSFORMER 25
4.1 PARAMETERS TO BE MONITORED AND WHY 25
4.2 CURRENT TRANSFORMER EXCITATION, RATIO AND POLARITY
MEASUREMENT 26
4.3 CURRENT TRANSFORMER BURDEN MEASUREMENT 27
5.0 TESTING INSTRUMENT FOR SURGE ARRESTER 28
5.1 PARAMETERS TO BE MONITORED AND WHY 28
5.2 LEASKAGE CURRENT MEASUREMENT 29
6.0 TESTING INSTRUMENT FOR RELAYS 31
6.1 PERFORMANCE TESTS TO BE DONE ON RELAYS AND WHY 31
6.2 PRIMARY CURRENT INJECTION TEST 32
6.3 SECONDARY CURRENT INJECTION TEST 34
Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 6
Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 7
The correction slips to be issued in future for this handbook will be numbered as follows:
Where “XX” is the serial number of the concerned correction slip (starting from 01
onwards).
Sr. No. Date of issue Page no. and Item no. modified Remarks
Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH/E/2009/TI-TRD/1.0 1
1.0 OBJECT
Indian Railway is one of the largest railway system in the world using 25 kV AC
single phase, 50Hz traction supply system. It employs various equipments and infrastructure
in PSI & OHE to keep the system working efficiently. It has been experienced that
significant numbers of failures of PSI & OHE are because of components failure and lack of
maintenance due to non availability of power block.
It is felt that condition based maintenance instruments should be available with the
TRD maintenance staff. These instruments may play key role to improve quality of work,
with least block time which will improve system reliability and availability.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 2
Capacitance and Tan Delta are most important parameters of insulating materials. In
particulars tan delta gives the true picture of health of insulation.
The above results can be interpreted to reveal the quality of insulating system and
manufacturing process defects like contamination, fracture or puncture. It can also be used
to find out defects which develop in field due to ageing and other factors.
Transformer turn ratio is the ratio of the number of turns in the high voltage winding
to that in the low voltage winding.
The phase angle deviation, displayed in either degree (minutes) or radians, is the
phase relationship between the voltage signal applied to the high voltage winding and the
voltage signal extracted from the low voltage winding.
This phase deviation, together with ratio error can be used as a low cost method of
verifying accurately class of all types of PTs, CTs at zero burdens.
The thermal & electrical stresses caused during short circuits, overloads and over
voltages and deterioration of dielectric properties of insulating oil produces appreciable
amount of gases in the system. These gases are soluble and are absorbed in oil.
Dissolved Gas Analysis (DGA) provides an important means in the art of condition
monitoring of power transformer and other oil filled equipments. This is well suited for
detection of growing faults which are not always revealed by established routine tests.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 3
Break down voltage test of insulating oil is carried out to test its dielectric strength to
reveal the extend of physical pollution by water and other suspended matters.
By this test need of carryout drying out, filtration treatment of the oil can be
predicted.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 4
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 5
Advantages:
i. Healthiness of winding insulation can be checked.
ii. Testing of under grounded as well as grounded objects can be carried out.
iii. The equipment has a LED based provision for visual indication for discharge
condition. This LED shall glow after the HT is switch OFF, till the voltage on test
object/ HV terminal is below 50 V approximate.
iv. Equipment have HV, LV & Guard and Internal discharge of object after test, memory
for measurement results, ability to transfer the data to a PC, polarization index and
dielectric absorption ratio.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 6
Technical Specification
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 7
Advantages:
i. These results can be interpreted to reveal the quality of insulating system and
manufacturing process defects like contamination, fracture or puncture.
ii. It can also be used to find out the defects which develop in field due to ageing and
other factor.
iii. This instrument can measure the capacitance & Tan delta automatically by auto
balancing.
iv. This instrument is suitable for extraneous conditions in 400 kV switch yard under
heavy induction.
v. This instrument indicates leakage current, magnetizing current & leakage reactance.
vi. The instrument can take measurement at line frequency as well as fixed generated
frequency so that the out put frequency is independent of change in input frequency.
vii. Data logging with graph of voltage Vs Tan Delta to know the Tan Delta gradient &
data analysis for comparison with old results, printout can be taken at site.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 8
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 9
Advantages:
i. It is a remote controllable and can works in the presence of high interference/ high
voltage.
ii. It measures phase deviation of the transformer primary vs. secondary, quickly
indicates problems in the transformer such as partial shorted turns and core faults.
iii. It is also useful in verifying phase error in PTs, CTs at zero burdens.
iv. This instrument have auto operation, no balancing is required, LCD display, fully
protected against any wrong connections.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 10
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 11
Advantages:
i. Dissolved Gas Analysis (DGA) provides an important means in the art of condition
monitoring of power transformer and other oil filled equipments.
ii. This is well suited for detection of growing faults which are not always revealed by
established routine tests.
iii. This equipment is designed and developed with an improved method for extraction of
dissolved gases, considering the fact that even small traces of certain dissolved gases
in transformer oil are to be detected, to identify a fault in transformer.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 12
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 13
Advantages:
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 14
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 15
Volume 45 ml
Oil test cell heater
Power supply 230 V AC ± 10% 50Hz
Test temperature Adjustable from 200C (room temp) to 1500C with an
accuracy ± 0.5%, accuracy of temp. control ± 20C
Display printer & data storage
Display Alphanumeric LCD display
Printer Inbuilt dot matrix printer
PC compatibility RS 232 port
Data storage upto 250 test results
Power supply 230V AC ± 10%
Operating temp (-10 to 50°C)
Humidity ambient to 90% RH
Advantages:
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 16
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 17
Advantages:
i. Oil BDV test set is a fully automatic microprocessor controlled testing equipment.
ii. It is an operator friendly test kit.
iii. The test carried out automatically.
iv. It is a portable and laboratory unit.
v. It has pass/ fail limit and custom test facility.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 18
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 19
Advantages:
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 20
Contact resistance meter measures the resistance of circuit breaker/ interrupter when
it is in close condition i.e. both main & arching contacts are in close condition and the
system current flows through the main contacts due to its low resistance. If resistance value
is found lesser than specified value than it shows healthiness of main contacts.
Time interval measurement is carried out to measure the timings of the closing &
opening operations of the circuit breaker/ interrupter during close, trip, close-open, open-
close & open-close-open operations with a provision of user defined time delay between two
operations.
If these timings are found within the specified limits than it shows healthiness of
operating mechanism as well as gap between the fixed & movable contacts.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 21
Model (make) Hisac ultima with DCRM 100 B(M/s Scope T&M Pvt. Ltd.,)
Technical Specifications
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 22
DCRM channels 1/2/3/6: each for 1000, 2000, 0.1% of Value ±1%
resistance & test 4000, 8000 µΩ selected
± 1 digit (12
current as per range
bit)
configuration
ordered
Advantages:
i. With the help of this instrument, it is possible to measure the length of arching contact
when travel transducer is connected.
ii. During measurement 100 A DC is injected which ensures excellent accuracy and
repeatability of results.
iii. It is a High speed V/I measurement.
iv. MCB protection saves battery from accidental short circuits.
v. It is a portable and user friendly instrument.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 23
Advantages:
i. This instrument injects 100 Amps DC to ensure reliable measurement in accordance
with IEC 56.
ii. It is a battery as well as mains operated instrument.
iii. It displays contact resistance values direct in micro-ohms.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 24
Application Time interval meter measures and indicates close, open and C-O
time of circuit breakers and interrupters.
Models (make) M3K SCOT (M/s Scope T&M Pvt. Ltd. Mumbai.)
TM 1600 (Programma Electric AB, Sweden)
Technical Specifications
Channels Three
Weight 11 kg approx.
Advantages:
i. It is suitable for working in EHV switchyard and ideal for field.
ii. This instrument can measure the timings in milli-seconds of three poles
simultaneously.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 25
Current transformer excitation test provides a variable voltage output and digital
instrumentation for measuring the excitation voltage and excitation current those results as
the voltage applied to the CT under test is increased. As the CT begins to saturate, a large
increase in current will be detected for a small increase in voltage.
The ratio test is performed by comparing a voltage applied to the secondary winding
to the resulting voltage produced on the primary winding.
Polarity of the CT under test is determined by special circuitry that divides the
voltage applied to the secondary winding by either 10 or 100, depending on switch position,
and then adds the results to the primary voltage. An increase in magnitude indicates correct
polarity, and a decrease shows incorrect polarity.
4.1.2 Burden
Within the accuracy limits of the CT, a good CT should not have a noticeable change
in ratio when a secondary burden is added. This is because the primary effect of additional
burden on a good CT is a rise in the secondary voltage.
If one or more turns of a CT are shorted, a substantial amount of the total available
ampere- turns is diverted into the shunt path created by the short. Thus, the current to the
circuit connected to the CT is less than the CTs total secondary current.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 26
Advantages:
i. It provides a variable voltage output and precision instrumentation for testing single
and multi-ratio CTs.
ii. All three tests excitation, ratio and polarity can be performed without changing any
leads.
iii. It can test bushing CT, mounted inside transformer or switchgear.
iv. It has inbuilt overload and short- circuit protection.
v. It has a RUN/HOLD switch which freezes readings on instrument when switched to
the HOLD position.
vi. A zero-start interlock is incorporated. This minimizes the possibility of energizing
the CT under test with sudden high voltages.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 27
Burden ratings (VA at nominal current of 5 6.25, 12.5, 25, 50 & 100 VA
amps)
Weight 1.1 kg
Advantages:
i. It is designed to ensure that the secondary of the CT under test will not be
accidentally opened.
ii. It uses make-before-break construction for ammeter range and burden selector
switch.
iii. The burdens are normally shorted out, but can be put in series with the ammeter by a
spring-loaded momentary switch.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 28
Failure of surge arrester take place mainly due to ingress of moisture inside surge
arrester and/or ageing of oxide blocks causing severe damages to surge arrester poles and
also to the neighboring equipments.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 29
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 30
Advantages:
i. It provides quick and reliable information about the heath of the surge arrester and
allows for storing of all the measurement data’s in the field.
ii. It measures following parameters & displays directly on LCD display
a. Total leakage current.
b. Third order harmonic current.
c. Resistance leakage current.
d. Correct value of resistive leakage current.
e. Waveform display
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 31
Most of the electric supply protective systems are fed from CTs connected to the
supply cable or bus-bar. Primary current injection test checks all the components of the
protective system. A high test current, enough to cause the protection equipment to operate,
is injected into the supply cable. Time taken for the protection relay to operate is then
measured.
The primary current injection test is essential when commissioning new protection
systems and after major repair and component replacement, since it tests the whole system.
It will detect CTs connections with incorrect polarity or relays that have been set in the
wrong sequence in differential systems.
Secondary current injection test checks the operation of the protective relay etc. but
does not test the overall system including the CTs. A secondary injection test is easier since
there is no need to break the primary circuit and it requires less current through the operating
coil of the protective device. The time taken for the protection device to operate is then
measured.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 32
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 33
Advantages:
i. Primary current injection tests the complete relay protection systems comprising the
isolated high voltage conductor, CT, protection relay and the circuit breaker.
ii. Primary current injection tests the testing of the current transformer in a protection
system.
iii. It is provided with built-in timer to record protection relay operation.
iv. As current level is maintained though out the test, circuit resistance may rise due to
heating.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 34
Advantages:
i. A secondary current injection test is easier since there is no need of break the primary
circuit.
ii. It can test relays and CT and it can be used as multi-meter also.
iii. It is easy to control and can also be controlled via external PC.
iv. It has an advance high power constant current source with pulse width modulation
technology.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 35
Technical Specifications
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 36
10 Operating & storage temperature range with all accessories in -15°C to 50°C & -
40°C to 70°C respectively.
11. Software should have the feature to prepared report & can be saved in PDF format.
12. At least 3 palettes should be available with 2 color palettes; grey with white hot &
grey with black hot etc.
14. Data can be stored in removable SD card with storage capacity of 1000 + images
15. Menu operation should be available via touch screen as well as via toggle button.
16. Auto focuses facility available in camera along with manual focus.
Advantages:
i. It helps to find out electrical hot spots and faulty equipments in incipient conditions.
ii. It is an ideal means for professionals looking for safety and reliability when
conducting routine surveys of electrical systems, switchgear and electrical
components.
iii. It is a light weight, comfortable and sensitive test instrument with touch screen, text
features.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 37
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 38
Advantages:
i. This instrument is portable and can be used in the field under severe weather
conditions.
ii. This instrument can measure resistance using 2, 3 or 4 pole methods, automatic
calculation and displays the resistance value in ohms.
iii. It has four ranges that are automatically selected, covering measurement requirements.
iv. This meter can be powered from NI-MH batteries or standard ‘C’ size batteries.
v. Measurements can be simplified using current clamps and the test results can be
stored in the internal memory and print out can be taken with built-in printer.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 39
It is important and necessary to conduct battery testing to check the above defects
periodically.
• Voltage
• Impedance
• Specific gravity
• Sulfation (relative to the amount of battery charge capacity degradation due to
sulfation)
• Dryout (relative to the amount of battery charge capacity degradation due to
dryout)
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 40
Technical Specifications
Voltage
Range 0 to 17 V DC
Resolution 10mV
Accuracy ± 0.5%
Repeatability ± 0.5%
Impedance
Measurement range 50 µΩ to 1Ω
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 41
Sulfation
Range 0 to 100%
Accuracy ± 5%
Dryout
Range 0 to 100%
Accuracy ±5%
Advantages:
i. It can store large amount of data and auto hold and auto-data storage facility also
available.
ii. It has ability to measure AC voltage and low resistance.
iii. It can memorize the value on the spot.
iv. It can enhance resistance against noise.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 42
Advantages:
i. It has automatic and manual sensitivity adjustment features.
ii. It can be used for residential as well as commercial applications.
iii. It displays with bar graph along with audible detection.
iv. It can locate faults in underground cables/ wires in three phase installations also.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 43
It is difficult to trace, locate and measure the depth of buried power cables which are
neither having cable route markers nor their route diagram record etc.
This instrument is designed to locate, trace and measure the depth of buried
energized power cables. It consists a compact, all steel control box. It is attached to a
precision-wound, swivel-mounted detecting coil.
Application The cable route tracer locates, traces and measures the depth of
buried energised power cables.
This instrument can also be used to locate grounded electrical
faults on un-shielded cables, particularly in direct buried
installations.
iii. 450 angle For a null at a horizontal distance from the cable that is
equivalent to the cable depth.
Technical Specifications
Locates and traces energised power cables with supply of 50/60 Hz.
Two sensitivity ranges enables tracing of cables as much as 8ft. (2.4m) deep.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 44
Advantages:
i. It has fully transistorized amplifier with 10 turn gain control for wide adjustment
range.
ii. It is not affected by telephone lines, gas or water pipes, steel reinforcing or
metallic conduit.
iii. It responds current flowing in the cable, even in the metallic conduit.
iv. It has special feature of battery test circuit which provides upto 150 hours of
operation.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 45
Sparking occurs when there is loss of contact between the pantograph and the contact
wire. The spark is developed in contact wire due to a kink in contact wire. It is important to
attend the kink roughened surface of the contact wire to avoid further rapid deterioration,
with successive passage of pantographs resulting in reduced life of contact wire.
It is necessary to carry out periodic tests to detect points at which contact between
the contact wire and pantograph is unsatisfactory resulting in sparking. Current collection
shall be carried out during night time for better results.
The OLIVIR-G Plus is developed to assist Over Head Equipment (OHE) spark
detection using a video camera. The hardware units consist of a GPS receiver which track
the current position of the locomotive in which the ‘OLIVIR-G plus’ is mounted.
The OLIVIR mate RT software supplied with the unit identities sparks in real time
and save them as images with locations, at the same time continuous video film is also
recorded in hard drive. These images can be analyzed to recognize the type of spark (mega
pixel) with their locations.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 46
Accessories:
i. Focus light operated at 110V AC/DC supply.
ii. Camera and light
iii. GPS antenna
iv. Processing & login unit
v. GPS unit
vi. Serial cable
vii. Battery charger
viii. Track feature collection unit
Advantages:
i. It can show total number of images recorded during current collection test.
ii. The category of spark can be adjusted as per customer requirement.
iii. It gives the correct position of spark with its location.
iv. The size of spark value can be adjusted during current collection.
v. It automatically saves all recorded data in the laptop datewise.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 47
Any change in alignment due to slewing of tracks will affect the setting distance and
the stagger of the contact wire. Change in rail level due to variation in ballast cushion or
packing down of the track will also result in change in contact wire height.
Though provision exists in the cantilever assembly for adjustments of the stagger and
height, such adjustments are not to be made unless absolutely necessary. It is best to
maintain the position of OHE and tracks as in the SEDs.
Rail Rod Ultrasonic Height & Stagger Gauge is used for measurement of height of
contact wire and catenary wire without power block both on meter and broad gauge tracks.
Advantages:
i. It can measure three wires vertically or two wires horizontally.
ii. It is a compact & portable system (weight around 3.5 kg) hence suitable for single hand
use.
iii. It can take measurement at cant/gradient locations.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 48
Following locations are generally prone to higher wear rate of contact wire:
• Stop Signal
• FOB/ ROB
• MEMU Locations
• Starter signal
It is therefore, becomes pertinent to monitor diameter of contact wire continuously at
these locations. Diameter of new contact wire is 12.24 mm & condemning limit for main
line is 8.25 mm. Present system over Indian Railways is checking diameter at one location
per km. once a year during Tower Wagon checking.
One location per km. & that to be checked once in a year does not appear adequate
since it is observed that new locations with dia less than 9 mm crop up at intermediate
location and during intermediate time.
Advantages:
i. The contact wire locations having higher wear rate can be monitored more frequently.
ii. The number of locations to be checked per km. can also be increased.
iii. It can help in better monitoring of health of contact wire and consequent reduction in
contact wire parting cases.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 49
Advantages:
i. It can save wastage of manpower for discharge Rod/ Power block/ E-socket/ Ladder etc.
ii. It can increase productivity.
iii. It gives better quality of insulator cleaning/ resultant reduction in CB transient trippings.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 50
ANNEXURE – I
SUPPLIERS ADDRESSES:
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 51
OUR OBJECTIVE
To upgrade maintenance technologies and
methodologies and achieve improvement in
productivity, performance of all Railway
assets and manpower which inter-alia would
cover reliability, availability, utilisation and
efficiency.
Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009