HANDBOOK ON
TESTING INSTRUMENTS REQUIRED
FOR
CONDITION BASED MAINTENANCE
OF
TRD ASSETS

CAMTECH/E/2009/TI-TRD/1.0
August 2009

egkjktiqj, Xokfy;j & 474 005


005
Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
Maharajpur, GWALIOR - 474 005
CAMTECH\E\2007\SVCB\1.0 2

TESTING INSTRUMENTS REQUIRED


FOR
CONDITION BASED MAINTENANCE
OF
TRD ASSETS

QUALITY POLICY

“To develop safe, modern and cost


effective Railway Technology
complying with Statutory and
Regulatory requirements, through
excellence in Research, Designs and
Standards and Continual
improvements in Quality
Management System to cater to
growing demand of passenger and
freight traffic on the railways”.

Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 3

FOREWORD

The present trend world over is to minimize maintenance on the equipment as


disadvantages of over maintenance are well known and understood. This can be
achieved by the concept of condition based maintenance wherein the condition of the
equipment is judged based upon the “trend of values of certain parameters over a
period of time and not upon their absolute values”.

This handbook covers details of such instruments which are useful in condition
based monitoring of TRD assets. Necessary information such as make, model, technical
specifications and sources of supply have been included for reference.

CAMTECH, GWALIOR S. C. SINGHAL


Date:29.09.2009 EXECUTIVE DIRECTOR

Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 4

PREFACE

With the increase in traffic, getting a block to maintain the different Railway assets
is increasingly becoming more and more difficult. To carry out the optimum maintenance
(in right quantity and at the right moment) condition monitoring techniques are of great
help.

By employing condition based maintenance techniques the disadvantages of


‘breakdown maintenance’ & ‘scheduled maintenance’ can be avoided. The maintenance can
be planned just at the time it is really required, thus avoiding failures and also saving the
precious block time.

This document has been compiled by CAMTECH and gives a ready reference of
all the condition based maintenance equipments available which can be used for the above
purpose.

It is clarified that this handbook does not supersede any existing provisions laid
down by RDSO or Railway Board. This handbook is for guidance only and it is not a
statutory document.

Technological upgradation & learning is a continuous process. Please feel free to


write to us for any addition/ modification in this handbook. We shall highly appreciate your
contribution in this direction.

CAMTECH, Gwalior JAIDEEP


Date: 25.09.2009 Director Electrical

Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 5

CONTENTS

Serial No. Description Page No.

Foreword iii
Preface iv
Contents v
Correction Slip vii
1.0 OBJECT 01
1.1 BENEFITS OF CONDITION MONITORING 01
1.2 VARIOUS EQUIPMENTS TO BE MONITORED 01
2.0 TESTING INSTRUMENTS FOR TRANSFORMERS 02
2.1 PARAMETER TO BE MONITORED AND WHY 02
2.2 WINDING RESISTANCE MEASUREMENT 04
2.3 WINDING INSULATION RESISTANCE MEASUREMENT 05
2.4 CAPACITANCE & TAN DELTA MEASUREMENT 06
2.5 TRANSFORMER TURN RATIO MEASUREMENT 08
2.6 DISSOLVED GAS ANALYSIS 10
2.7 FAULT GAS AND MOISTURE MONITORING 12
2.8 OIL TAN DELTA MEASUREMENT 14
2.9 OIL BREAK DOWN VOLTAGE MEASUREMENT 16
2.10 SWEEP FREQUENCY RESPONSE ANALYSIS 18
3.0 TESTING INSTRUMENT FOR CIRCUIT BREAKERS/ INTERRUPTERS 20
3.1 PARAMETERS TO BE MONITORED AND WHY 20
3.2 DYNAMIC CONTACT RESISTANCE MEASUREMENT 21
3.3 CONTACT RESISTANCE MEASUREMENT 23
3.4 TIME INTERVAL MEASUREMENT 24
4.0 TESTING INSTRUMENTS FOR CURRENT TRANSFORMER 25
4.1 PARAMETERS TO BE MONITORED AND WHY 25
4.2 CURRENT TRANSFORMER EXCITATION, RATIO AND POLARITY
MEASUREMENT 26
4.3 CURRENT TRANSFORMER BURDEN MEASUREMENT 27
5.0 TESTING INSTRUMENT FOR SURGE ARRESTER 28
5.1 PARAMETERS TO BE MONITORED AND WHY 28
5.2 LEASKAGE CURRENT MEASUREMENT 29
6.0 TESTING INSTRUMENT FOR RELAYS 31
6.1 PERFORMANCE TESTS TO BE DONE ON RELAYS AND WHY 31
6.2 PRIMARY CURRENT INJECTION TEST 32
6.3 SECONDARY CURRENT INJECTION TEST 34

Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 6

7.0 CHECKING OF ELECTICAL CONNECTIONS 35


7.1 LOOSE CONNECTIONS AND HIDDEN FAULTS CHECKING 35
7.2 INFRARED THERMAL IMAGING CAMERA 35
8.0 TESTING INSTRUMENT FOR MEASURING EARTH RESISTANCE 37
8.1 EARTH RESISTANCE 37
8.2 EARTH RESISTANCE AND RESISTIVITY MEASUREMENT 38
9.0 TESTING INSTRUMENTS FOR BATTERIES 39
9.1 PARAMETERS TO BE CHECKED AND WHY 39
9.2 BATTERY ANALYSIS 40
10.0 TESTING INSTRUMENTS FOR WIRES/ CABLES 42
10.1 WIRE TRACER/ CABLE LOCATOR 42
10.2 CABLE ROUTE TRACER 43
11.0 TESTING INSTRUMENTS FOR OVER HEAD EQUIPMENT 45
11.1 CONTACT WIRE SPARK CHECKING 45
11.2 CONTACT WIRE HEIGHT & STAGGER MEASUREMENT 47
11.3 LIVE LINE CONTACT WIRE WEAR MONITORING 48
11.4 LIVE LINE INSULATOR CLEANING 49

ANNEXURE – I Sources of Supply 50

Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH\E\2007\SVCB\1.0 7

ISSUE OF CORRECTION SLIP

The correction slips to be issued in future for this handbook will be numbered as follows:

CAMTECH/E/2009/TI-TRD/1.0/ C.S. # XX date---

Where “XX” is the serial number of the concerned correction slip (starting from 01
onwards).

CORRECTION SLIPS ISSUED

Sr. No. Date of issue Page no. and Item no. modified Remarks

Maintenance Handbook on Single Interrupter Vacuum Circuit Breaker (Type 22CB) February,
2007
CAMTECH/E/2009/TI-TRD/1.0 1

1.0 OBJECT

Indian Railway is one of the largest railway system in the world using 25 kV AC
single phase, 50Hz traction supply system. It employs various equipments and infrastructure
in PSI & OHE to keep the system working efficiently. It has been experienced that
significant numbers of failures of PSI & OHE are because of components failure and lack of
maintenance due to non availability of power block.

Keeping the increasing trend of traffic in mind it is desired to reduce maintenance


time by employing modern instruments in the field of maintenance.

It is felt that condition based maintenance instruments should be available with the
TRD maintenance staff. These instruments may play key role to improve quality of work,
with least block time which will improve system reliability and availability.

In order to minimize outages due to equipment failures, modern condition based


maintenance techniques needs to be implemented in maintenance of TRD assets to predict
deterioration of various components.

1.1 BENEFITS OF CONDITION MONITORING

• Reduction of un-planned outage.


• Predictable maintenance schedule.
• Prevention of costly failure.
• Minimize the severity of damages.
• Increase the system stability.
• Helps to plan future renovation.
• Use of equipment for maximum economical efficiency.

1.2 VARIOUS EQUIPMENTS TO BE MONITORED


• Transformers
• Circuit Breakers/ Interrupters
• Current Transformers
• Surge Arrestors
• Relays
• Electrical connections
• Earth pits
• Batteries
• Cables
• Machines
• Contact wire
• Insulators

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 2

2.0 TESTING INSTRUMENTS FOR TRANSFORMERS

2.1 PARAMETERS TO BE MONITORED AND WHY

2.1.1 Winding Resistance

The measurement of DC resistance of winding of transformers, motors etc. are


required.
 to verify manufacturer test readings.
 to check winding health during regular maintenance.
 to locate the presence of defects such as loose connections, open circuit etc.

2.1.2 Winding Insulation Resistance

The monitoring of winding insulation resistance is very essential to predict the


following defects.
 Insulation failure between winding and core (earth).
 Insulation failure between winding to winding.
 Insulation failure of bushings, internal connections etc.

2.1.3 Capacitance and Tan Delta

Capacitance and Tan Delta are most important parameters of insulating materials. In
particulars tan delta gives the true picture of health of insulation.

The above results can be interpreted to reveal the quality of insulating system and
manufacturing process defects like contamination, fracture or puncture. It can also be used
to find out defects which develop in field due to ageing and other factors.

2.1.4 Transformer Turn Ratio & Phase Angle Deviation

Transformer turn ratio is the ratio of the number of turns in the high voltage winding
to that in the low voltage winding.

The phase angle deviation, displayed in either degree (minutes) or radians, is the
phase relationship between the voltage signal applied to the high voltage winding and the
voltage signal extracted from the low voltage winding.

This phase deviation, together with ratio error can be used as a low cost method of
verifying accurately class of all types of PTs, CTs at zero burdens.

2.1.5 DGA of Transformer Oil

The thermal & electrical stresses caused during short circuits, overloads and over
voltages and deterioration of dielectric properties of insulating oil produces appreciable
amount of gases in the system. These gases are soluble and are absorbed in oil.

Dissolved Gas Analysis (DGA) provides an important means in the art of condition
monitoring of power transformer and other oil filled equipments. This is well suited for
detection of growing faults which are not always revealed by established routine tests.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 3

2.1.6 Oil Break Down Voltage

Break down voltage test of insulating oil is carried out to test its dielectric strength to
reveal the extend of physical pollution by water and other suspended matters.

By this test need of carryout drying out, filtration treatment of the oil can be
predicted.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 4

2.2 WINDING RESISTANCE MEASUREMENT

2.2.1 Winding Resistance Meter


Name of Instrument : Transformer winding resistance meter
Application : Transformer winding resistance meter measures the winding
resistance of transformers, inductors, generators, motors, tap
changers etc.
Models (make) : TRM – 104 (M/s.ScopeT&M Pvt Ltd Mumbai)
830280 – 47 (Megger Ltd.)
WR50-12 (Raytech GmbH, Switzerland)
WINDAX (Pax Diagnostics)
TWRM-10A (SIVANANDA Electronics, Devlali)
Technical Specifications :
Power supply 220 – 240 V AC, 50 Hz Single φ
Test Current Ranges 10A, 5A, 1A and 0.1 Amp DC
Resistance Range 1 milli ohm to 199.99 ohms
Resolution 0.1 micro ohm on 2 mili ohm
Indication 4½ digital panel meter LCD dual channel
Accuracy 1 microΩ to 1999 microΩ ± 0.5% ± 1 digit
20 mΩ to 999 mΩ ± 1.0% ± 1 digit
1Ω to 200Ω ± 1.5% ± 1 digit
DC Power Supply 50 Volt/ 10A
Test current range 10 Amp. (auto range selection)
Data Acquisition Window based
software
Memory record 45 Records
Controls Power on switch
Current range selection switch
Operating temp - 10°C to 50°C
Storage temp - 10 °C to 70° C
Open circuit voltage 30 V DC
Advantages:
i. This instrument can measure the DC resistance of all types of winding safely and
accurately.
ii. It is safe for user as it’s built in discharge circuit safely discharges the specimen when
test is completed, if lead accidentally disconnected or if power is lost.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 5

2.3 WINDING INSULATION RESISTANCE MEASUREMENT

2.3.1 Winding Insulation Resistance Meter

Name of equipment : Winding insulation resistance meter


Application : To measure Insulation Resistance of all the high voltage
components like transformer winding, CTs, PTs, bushings,
cables and motor windings etc.
Models (make) : 3541 (HIOKI E.E Corporation)
MI – 5000 (Sonel S.A, Poland)
5K4 (M/s. Sivananda Electronics, Devlali)
Technical Specifications :
Test voltage 500 V to 5000 V DC
IR Range 0 – 5 TΩ
Accuracy As per IS 2992
Display Analogue, Digital
Short circuit current < 2mA
Temperature range
i. Storage – (-40°C to +65°C)
ii. Operating – (-15°C to+ 55°C)
iii. Humidity range – 90% RH at 40°C

Advantages:
i. Healthiness of winding insulation can be checked.
ii. Testing of under grounded as well as grounded objects can be carried out.
iii. The equipment has a LED based provision for visual indication for discharge
condition. This LED shall glow after the HT is switch OFF, till the voltage on test
object/ HV terminal is below 50 V approximate.
iv. Equipment have HV, LV & Guard and Internal discharge of object after test, memory
for measurement results, ability to transfer the data to a PC, polarization index and
dielectric absorption ratio.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 6

2.4 CAPACITANCE AND TAN DELTA MEASUREMENT

2.4.1 Capacitance and Tan Delta Test Kit

Name of Instrument Capacitance & Tan Delta test kit

Application Capacitance & Tan Delta tests the health of insulation.


It can be used for testing of transformers, bushings, cables,
insulators, switchgear, rotating machine, capacitors and
lightning arresters.
Models (make) : MLS – 11DA/ HLS – 12A ( M/s Sivananda Electronics,
Devlali)
TD – 30 (M/s HV Diagnostics S.a.r.l Switzerland)
DELTA 3000 ( Megger Ltd.)

Technical Specification

S.N. Parameter Range Resolution Accuracy


1. Capacitance 1PF – 1.1 microF 4 digits ± 0.2% of the reading
(with range ± 1 PF (UST)
extension CT upto ± 1 PF (GST)
2.6 microF)
2. Tan Delta 0% - 100% (infinity) 0.00001 ± 1% of the reading
± 0.05%
3. Voltage 0 – 12 kV 1.0V ± 1%, ± 1 digit
measurement
4. Current 0 – 2000 mA 1mA ± 1%, ± 1 digit
measurement
5. Power factor 0.01% - 100% 0 – 00001 ± 1.0% of the reading
± 0.05%

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 7

S.N. Parameter Range Resolution Accuracy


6. Power 0 – 2 kW 0.1 mW ± 1% of reading
7. Interference current 0 – 100 mA 1 mA ± 1% of reading
8. Analysis software Windows based analysis software for Tan delta Vs time,
Tan delta Vs voltage
9. Temperature range - 10°C to 50°C
10. Humidity range Ambient to 95%

Advantages:
i. These results can be interpreted to reveal the quality of insulating system and
manufacturing process defects like contamination, fracture or puncture.
ii. It can also be used to find out the defects which develop in field due to ageing and
other factor.
iii. This instrument can measure the capacitance & Tan delta automatically by auto
balancing.
iv. This instrument is suitable for extraneous conditions in 400 kV switch yard under
heavy induction.
v. This instrument indicates leakage current, magnetizing current & leakage reactance.
vi. The instrument can take measurement at line frequency as well as fixed generated
frequency so that the out put frequency is independent of change in input frequency.
vii. Data logging with graph of voltage Vs Tan Delta to know the Tan Delta gradient &
data analysis for comparison with old results, printout can be taken at site.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 8

2.5 TRANFORMER TURN RATIO MEASUREMENT

2.5.1 Transformer Turn Ratio Meter

Name of instrument Transformer turn ratio meter


Application Microprocessor based Turn ratio meter is used for
automatic measurement of voltage/ turn ratio, current and
phase displacement of power transformers, CTs and PTs.
Model ( make) TR mark – II ( Raytech GmbH, Switzerland)
TTR 300 (Megger Ltd.)
ATRM-RM-1uP (M/s Sivananda Electronics, Devlali)
Technical Specification
Power supply 240 V AC, 50Hz single phase
Test voltage 110V AC 60 Hz on request
4.8 V, 48 V ac
Auto ranging Ranges
Indication 4½ digit LED display of ratio
LCD display
Accuracy ± 0.2 % for ratio reading 5 to 1000
± 1.5% for range beyond 1000.
Test plan storage 120 test plans
Weight app. 8 kg to 17 kg.

Auto ranging Ranges

S.No. Ratio Range Display Resolution Accuracy


1. 10 1 – 9.999 0.001 ± 0.2% for ratio 5 to 1000
2. 100 10 – 99.99 0.01
3. 1000 100 – 999.9 0.1 ± 1.5% for ratio beyond
4. 10000 1000 – 10000 1 1000
5. 14000 10 000 - 14000 1

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 9

Advantages:

i. It is a remote controllable and can works in the presence of high interference/ high
voltage.

ii. It measures phase deviation of the transformer primary vs. secondary, quickly
indicates problems in the transformer such as partial shorted turns and core faults.

iii. It is also useful in verifying phase error in PTs, CTs at zero burdens.

iv. This instrument have auto operation, no balancing is required, LCD display, fully
protected against any wrong connections.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 10

2.6 DISSOLVED GAS ANALYSIS

2.6.1 Transformer Oil Multiple Gas Extraction System

Name of instrument Transformer oil multiple Gas Extraction System


Application Dissolved Gas Analysis is carried out to detect the
dissolved gases in transformer oil.
It deals with the methods of sampling, extraction and
analysis of incipient fault gases in part per million (PPM)
levels from a small quantity of transformer oil sample.
Model (make) D Tomget-1207, (M/s Dakshin Lab Agencies,Banglore)
ASTM 3612 and IEC 567 (Energy Support, Germany)
Technical Specification
Vacuum pump Direct drive rotary vacuum pump (air cooled) with single
phase motor of displacement capacity 250 ltr./ min.
particle discharge pressure with gas ballast closed 5 x 10-
4
m bar.
Vacuum guage Digital Pirani gauge with pressure range 0.999 to 0.001
m bar.
Display – 3 digit LED numeric with under range and over
range indicators.
Gas extractor Designed for exposing same sample oil to multiple
(Patented) extractions. To hold vacuum of 0.1 m bar with minimum
efficiency of 97% gas extraction,
Stand Vibration free heavy duty stands with suitable clamp to
hold gas extractor.
Mercury 10 kgs
Magnetic stirrer
Power distribution board with pirani gauge fixed on it.
Accessories Hand pump, vacuum tubes, keck clips, vacuum grease,
and spares like septum, magnetic bar and screw cap.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 11

Advantages:

i. Dissolved Gas Analysis (DGA) provides an important means in the art of condition
monitoring of power transformer and other oil filled equipments.

ii. This is well suited for detection of growing faults which are not always revealed by
established routine tests.

iii. This equipment is designed and developed with an improved method for extraction of
dissolved gases, considering the fact that even small traces of certain dissolved gases
in transformer oil are to be detected, to identify a fault in transformer.

iv. Efficiency is more than 98%.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 12

2.7 FAULT GAS AND MOISTURE MONITORING

2.7.1 M2 Fault Gas & Moisture Monitor

Name of instrument M2 fault gas & moisture monitor


Application This instrument is applicable in oil filled equipments to regularly
monitor the fault gases and moisture as an early warning device
that will alert personnel about developing fault conditions that
could lead to equipment failure and unscheduled outages.
This instrument combines two products in one. First is fault
monitor that reads a composite value of gases in ppm, generated
by faults and provides output capability for communication.
Second is moisture level sensor for the evaluation of dangerous
condition such as bubbling, temperature and asset management
information such as rate of ageing of the insulation.
Model (make) HYDRAN – M2 (M/s PCI. Pvt. Ltd. New Delhi)
Technical Specification
Components Combined dual function sensor and electronic enclosure.
Response Relative humidity in oil (%), hydrogen (H2), carbon monoxide
(Co), acetylene (C2H2), ethylene (C2H4)
Medium Mineral, insulating oil for transformer
Measurement Moisture 0 – 100% RH
range Gas 0 – 2000 ppm
Accuracy Moisture - ± 2% RH
Gas - ± 10% reading ± 25 ppm
Response time Moisture – 5 minute, sensor, response (90% of step change)
Gas – 10 minutes, sensor, response (90% of step change)
Hardware Microprocessor, watch dog, clock
Software Real- time operating system, menu-driven interface
Display Backlit liquid crystal display (LCD)
Power supply Universal 80 – 200V AC 50 Hz 350 VA
Weight 6.0 kg

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 13

Advantages:

i. This instrument alerts personnel about developing fault conditions at an early


stage.
ii. It requires single valve for both fault gas and moisture monitoring.
iii. The use of optional analog input allows basic transformer monitoring.
iv. This can be installed with no additional oil lines and uses no pumps or other
moving parts for maximum long term reliability.
v. It can test continuous field measurement.
vi. It reduces unplanned outages and it is useful for predictable maintenance
schedule.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 14

2.8 OIL TAN DELTA MEASUREMENT

2.8.1 Oil Tan Delta Test Kit

Name of instrument Oil tan delta test kit


Application Oil tan delta tests the dielectric dissipation factor &
resistivity measurement of oil.
Model (make) Nil (M/s Sivananda Electcronics Devlali.)
Technical Specification
Test voltage Capacitance tan delta dielectric constant
Adjustable from 0 to 3000 V AC in steps with an
accuracy of ± 1.0%
Test frequency 50 Hz
Dielectric constant range 1.0 to 13.0 accuracy ± 0.2% ± 0.001
best resolution – 0.001
Dielectric tan delta range 10-5 to 10 accuracy ± 1% ± 0.3% full scale, best
resolution 0.00001
Resistance & resistivity
Test voltage DC : 500 V DC in step with an accuracy of ± 1.0%
Resistance range 106 – 1012 Ω resolution: 3 digit
Resistance accuracy ± 3% of reading up to 1 GΩ & ± 10% at high end
Resistivity range 109 – 1015 Ω-cm best resolution : 0.01
Resistivity accuracy ± 3% of reading ± 0.2% full scale
Oil test cell
Construction 3 terminal configuration
Cell capacitance 55PF ± 1 PF
Material Stainless steel with Teflon spacers
Electrode spacing 2mm

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 15

Volume 45 ml
Oil test cell heater
Power supply 230 V AC ± 10% 50Hz
Test temperature Adjustable from 200C (room temp) to 1500C with an
accuracy ± 0.5%, accuracy of temp. control ± 20C
Display printer & data storage
Display Alphanumeric LCD display
Printer Inbuilt dot matrix printer
PC compatibility RS 232 port
Data storage upto 250 test results
Power supply 230V AC ± 10%
Operating temp (-10 to 50°C)
Humidity ambient to 90% RH

Advantages:

i. Fully automatic dielectric constant, dielectric dissipation factor and resistivity


measurement.
ii. Easy storage of the data.
iii. It has PC compatibility and inbuilt printer facility for test report printing.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 16

2.9 OIL BREAK DOWN VOLTAGE MEASUREMENT

2.9.1 Automatic Oil Break Down Voltage Tester

Name of Instrument Automatic oil BDV tester


Application Automatic oil BDV tester is used for determining the dielectric
strength of liquid insulation such as the insulating oils used in
transformers, switch gears and other electrical apparatus.
Model (make) OTSPR – 100 (C.G), (M/s Sivananda Electronics Devlali)
OTS AF/2 (Megger Ltd.,)
Technical Specification
Power supply 230V AC ± 10%, 50Hz ± 3%

Voltage range 0 to 100 kV AC


Trip current 10 mA
Indication 3½ digit panel meter
Resolution 0.1kV
Accuracy ± 2% of normal value
Variac Motorized
Shut down 5 mA
sensitivity
Shut down < 20 milli second
Oil test cell Transparent acrylic material, 36 mm removable mushroom head
electrodes
Gap gauge 2.5 mm
Controls mains ON/OFF, HT ON/OFF, hold, stirrer ON/OFF, timer ON/OFF,
auto/ manual mode reset switch.
Features Microprocessor – control with following feature fully automatic
option to set
(a) stand time
(b) stir time,
(c) Rate of rise of voltage 0.005 kV to 5.0kV adjustable,
(d) No. of test carried out as per selected standard.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 17

Printer Built in alphanumeric printer. Time dated result with standard


deviation printed.
Software Windows based data acquisition software
Keypad Quick test selection through 12 keys soft touch key pad.
Display Large backlite LCD display to display test menu set up screens.
Storage memory 100 test results
Safety feature Interlock on high voltage test chamber, zero start protection,
double ground protection. All safety interlocks to avoid shocks
with indications. Protected against overloads & short circuits.
Temperature Operating 0 – 50°C
range
Humidity range 80 % RH at 40°C
Storage 5 to 70°C.

Advantages:

i. Oil BDV test set is a fully automatic microprocessor controlled testing equipment.
ii. It is an operator friendly test kit.
iii. The test carried out automatically.
iv. It is a portable and laboratory unit.
v. It has pass/ fail limit and custom test facility.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 18

2.10 SWEEP FREQUENCY RESPONSE ANALYSIS

2.10.1 Sweep Frequency Response Analyser

Name of instrument Sweep frequency response analyzer for power


transformer
Application This instrument detects internal mechanical
displacements without extended downtime. This
instrument detects problems such as
(i) Winding deformations and displacements
(ii) Shorted turn and open winding
(iii) Loosened clamping structure
(iv) Broken clamping structure
(v) Core connection problems
(vi) Partial winding collapse
(viii) Faulty cone ground
(viii) Core movements
(ix) Hoop buckling

Model (make) FRAX – 101( Pax Diagnostics)


FRAX – 101(Megger Ltd.)
Technical Specification
FRA method Sweep frequency
Frequency range 0.1 Hz – 25 MHz, user selectable
Number of points Default 1046, User selectable up to 32,000
Measurement time Default 64s, fast setting, 37s, ( 20 Hz- 2 MHz)
Accuracy ± 0.3 dB down to -105 dB( 10Hz- 10MHz)
Software FRAX for windows 2000/XP/ vista
PC communication Blue tooth and USB
Channels One
Compliance Voltage 0.2 – 20V peak-to- peak
Measurement Voltage at 0.1-10V peak-to- peak
50w

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 19

Voltage output 10V peak to peak in 50 ohms.


Output impedance 50 W
Protection Short circuit protection
Instrument weight 1.4 kg
Input Voltage 11-16V dc or 90-135V ac and 170-264V ac, 47- 63 Hz
Operating ambient temp. -20°C to 50°C
Operating Relative < 90% non- condensing
Humidity
Storage ambient temp. -20°C to 70°C
Storage Relative Humidity < 90% non- condensing

Advantages:

i. Sweep frequency response analyzer detects potential mechanical and electrical


problems.
ii. The measurement is easy to perform and will capture a unique “Fingerprint” of the
transformer and compared to a reference “Fingerprint” and gives direct answer if the
mechanical parts of the transformer are unchanged or not.
iii. Deviations indicate geometrical and electrical changes within the transformer.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 20

3.0 TESTING INSTRUMENT FOR CIRCUIT BREAKERS/ INTERRUPTERS

3.1 PARAMETERS TO BE MONITORED AND WHY

3.1.1 Dynamic Contact Resistance Measurement (DCRM)

Failure of circuit breakers is because of component failure in the interrupter


assembly. Mechanical breakage/damage, misalignment of contacts/ operating links, erosion
of arcing contacts have been the causes of failures causing severe damage to CB poles and
also to the neighboring equipments.
Dynamic contact resistance measurement (DCRM) is a very effective tool to assess
the condition of main & arching contacts, erosion/ length of arcing contact, main & arching
contacts insertion, misalignment of contacts/ operating links, without opening the
interrupter.
The DCRM measurement can detect above faults in incipient stage and accordingly
the corrective measures can be taken at right time to avoid subsequent break downs.

3.1.2 Contact Resistance

Contact resistance meter measures the resistance of circuit breaker/ interrupter when
it is in close condition i.e. both main & arching contacts are in close condition and the
system current flows through the main contacts due to its low resistance. If resistance value
is found lesser than specified value than it shows healthiness of main contacts.

3.1.3 Time Interval

Time interval measurement is carried out to measure the timings of the closing &
opening operations of the circuit breaker/ interrupter during close, trip, close-open, open-
close & open-close-open operations with a provision of user defined time delay between two
operations.

If these timings are found within the specified limits than it shows healthiness of
operating mechanism as well as gap between the fixed & movable contacts.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 21

3.2 DYNAMIC CONTACT RESISTANCE MESUREMENT (DCRM)

3.2.1 Dynamic Contact Resistance Measurement Meter

Name of instrument Dynamic contact resistance measurement meter

Application The dynamic contact resistance measurement meter is a very


effective tool to assess the condition of main & arching contacts,
erosion/ length of arching contact, main & arcing contact
insertion, misalignment of contacts/ operating links, without
opening the CB or interrupter.
The DCRM measurement can detect above fault in incipient stage
and accordingly the corrective measures can be taken at right time
to avoid subsequent break downs.

Model (make) Hisac ultima with DCRM 100 B(M/s Scope T&M Pvt. Ltd.,)

Technical Specifications

Channels Configuration Range Resolution Accuracy

Contact status 24:4 main + 4 Measurement 1 mS at 1 Value ± 0.05%


PIR per pole, on duration 1 mS kC 0.05
± 1 digit
3 poles to 40 Sec at 1 mS at 20
simultaneously kC, 0.05 mS to kC
2 Sec at 20 kC

Auxiliary contacts 4: 2 dry, 2 wet, 24 to 250 V DC 1 mS at 1 Value ± 0.05%


optionally kC 0.05 ± 1 digit
expandable to 12 mS at
dry, 12 wet 20kC

Coil current 3: Trip/ close coil 1, 2, 5, 10 ,25 0.1 % of Value ± 0.5 % ±


current A DC selected 1 digit (12 bit)
range

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 22

Channels Configuration Range Resolution Accuracy

Voltage 3: Travel 0-5 V DC 1.2 mV Value ± 0.5%


characteristics ± 1 digit (12
bit)

DCRM channels 1/2/3/6: each for 1000, 2000, 0.1% of Value ±1%
resistance & test 4000, 8000 µΩ selected
± 1 digit (12
current as per range
bit)
configuration
ordered

Configurable 3: optional for 0-5 V DC 1.2 mV Value ± 0.5%


channel analog signal ± 1 digit (12
inputs
bit)

Advantages:
i. With the help of this instrument, it is possible to measure the length of arching contact
when travel transducer is connected.
ii. During measurement 100 A DC is injected which ensures excellent accuracy and
repeatability of results.
iii. It is a High speed V/I measurement.
iv. MCB protection saves battery from accidental short circuits.
v. It is a portable and user friendly instrument.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 23

3.3 CONTACT RESISTANCE MEASUREMENT

3.3.1 Contact Resistance Meter

Name of instrument Contact resistance meter


Application Contact resistance meter measures contact resistance of circuit
breakers, isolators, bus-bars, welded joints etc. under the
hostile electrostatic noise found in EHV line switch yard.
Contact resistance meter directly measures micro-ohm values at
100 amps. DC under live switch yard condition.
Model (make) IRM 100 B(M/s Scope T&M Pvt. Ltd.)
MOM 200A/ 600A (Programma Electric AB, Sweden)
Technical Specifications
Range 199.9 µΩ and 1999 µΩ
Resolution 0.1 µΩ and 1 µΩ
Accuracy Value ± 2% ± resolution
Current 100 A DC
Display Two, 3½ digit ½ inch LCD, for current and resistance value
Power 230 V AC ± 15%, 50 Hz ± 5%, 30 VA
Battery Instrument operation in input rechargeable battery (12V – 7AH
maintenance free)
Weight 10kg approx.
Environment 0 to 50°C max. 95% RH

Advantages:
i. This instrument injects 100 Amps DC to ensure reliable measurement in accordance
with IEC 56.
ii. It is a battery as well as mains operated instrument.
iii. It displays contact resistance values direct in micro-ohms.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 24

3.4 TIME INTERVAL MEASUREMENT

3.4.1 Time Interval Meter

Name of instrument Time interval meter

Application Time interval meter measures and indicates close, open and C-O
time of circuit breakers and interrupters.

Models (make) M3K SCOT (M/s Scope T&M Pvt. Ltd. Mumbai.)
TM 1600 (Programma Electric AB, Sweden)

Technical Specifications

Channels Three

Output 4 line 20 characteristic backlit LCDR 3232 port for downloading


to PC.

Range 999 milliseconds maximum

Resolution 1 milli second

Accuracy Value ± 0.05 % ± resolution

Power 230 V AC ± 15 %, 50Hz ± 5%

Weight 11 kg approx.

Advantages:
i. It is suitable for working in EHV switchyard and ideal for field.
ii. This instrument can measure the timings in milli-seconds of three poles
simultaneously.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 25

4.0 TESTING INSTRUMENTS FOR CURRENT TRANSFORMER

4.1 PARAMETERS TO BE MONITORED AND WHY

4.1.1 Excitation, Ratio and Polarity

Current transformer excitation test provides a variable voltage output and digital
instrumentation for measuring the excitation voltage and excitation current those results as
the voltage applied to the CT under test is increased. As the CT begins to saturate, a large
increase in current will be detected for a small increase in voltage.

The ratio test is performed by comparing a voltage applied to the secondary winding
to the resulting voltage produced on the primary winding.

Polarity of the CT under test is determined by special circuitry that divides the
voltage applied to the secondary winding by either 10 or 100, depending on switch position,
and then adds the results to the primary voltage. An increase in magnitude indicates correct
polarity, and a decrease shows incorrect polarity.

4.1.2 Burden

Within the accuracy limits of the CT, a good CT should not have a noticeable change
in ratio when a secondary burden is added. This is because the primary effect of additional
burden on a good CT is a rise in the secondary voltage.

If one or more turns of a CT are shorted, a substantial amount of the total available
ampere- turns is diverted into the shunt path created by the short. Thus, the current to the
circuit connected to the CT is less than the CTs total secondary current.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 26

4.2 CURRENT TRANSFORMER EXCITATION, RATIO AND POLARITY


MEASUREMENT

4.2.1 Current Transformer Excitation, Ratio & Polarity Tester

Name of instrument Current transformer excitation, ratio & polarity tester


Application This instrument tests the excitation, ratio and polarity of current
transformer using the voltage comparison method.
Model (make) CTER-91(Megger Limited)
Technical Specifications
Input 120 V, single phase, 50 Hz/ 60 Hz.
240 V, single phase, 50 Hz/ 60 Hz.
Output Continuously variable in four ranges
0 to 40 V at 1.5A
0 to 150 V at 1.5 A
0 to 600 V at 1.5 A
0 to 1000 V at 1.0 A
Instrumentation
Voltmeters Two 4½ - digit, auto ranging
Accuracy ± 0.25% of reading, ± 1digit for 1 to 1000V, ± 1% of reading,
± 1digit for 0.2 to 1V
Ammeter One 4½ digit
Accuracy ± 0.85% of reading, ± 1 digit
Weight 16.8 kg.

Advantages:
i. It provides a variable voltage output and precision instrumentation for testing single
and multi-ratio CTs.
ii. All three tests excitation, ratio and polarity can be performed without changing any
leads.
iii. It can test bushing CT, mounted inside transformer or switchgear.
iv. It has inbuilt overload and short- circuit protection.
v. It has a RUN/HOLD switch which freezes readings on instrument when switched to
the HOLD position.
vi. A zero-start interlock is incorporated. This minimizes the possibility of energizing
the CT under test with sudden high voltages.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 27

4.3 CURRENT TRANSFORMER BURDEN MEASUREMENT

4.3.1 Current Transformer Burden Ammeter

Name of instrument Current transformer burden ammeter


Application The current transformer burden ammeter is a rugged, portable
instrument, designed to field test current transformer installation for
a. Short circuit secondary turns
b. Short circuited primary turns
c. Short circuited secondary wiring
d. High – resistance connection in the secondary circuit.
e. Grounding of secondary winding when mounted on a
grounded structure.
f. Grounding of a normally under grounded wire.
Model (make) BA – 185 (Megger Limited)
Technical Specifications
Ammeter ranges 1.25, 2.5, 10 Amps
Burden 0.25, 0.5, 1, 2 & 4 ohms

Burden ratings (VA at nominal current of 5 6.25, 12.5, 25, 50 & 100 VA
amps)

Weight 1.1 kg

Advantages:
i. It is designed to ensure that the secondary of the CT under test will not be
accidentally opened.
ii. It uses make-before-break construction for ammeter range and burden selector
switch.
iii. The burdens are normally shorted out, but can be put in series with the ammeter by a
spring-loaded momentary switch.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 28

5.0 TESTING INSTRUMENT FOR SURGE ARRESTOR

5.1 PARAMETERS TO BE MONITORED AND WHY

5.1.1 Leakage Current

Failure of surge arrester take place mainly due to ingress of moisture inside surge
arrester and/or ageing of oxide blocks causing severe damages to surge arrester poles and
also to the neighboring equipments.

Monitoring of leakage current is required to measure the third harmonic resistive


component (THRC) of surge arrester. It provides quick and reliable information about the
health of the surge arrester in incipient stage and accordingly the corrective measures can be
taken at right time to avoid subsequent failures.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 29

5.2 LEAKAGE CURRENT MEASUREMENT

5.2.1 Leakage Current Meter

Name of instrument Leakage current meter for surge arrester


Application This instrument is suitable for measurement and analysis of
resistive leakage current of surge arrester in live switch yard
condition without any need for shut down.
The system is based on the measurement of 3rd harmonic resistive
current with compensation for harmonic in the system voltage.
Model LCM III ( M/s. Applid Techno Gurgaon,)
SA 302 ( M/s Scope T&M Pvt. Ltd., Mumbai.)
SCAR – 10( ISA srl, Italy)
Technical Specification
Range Total leakage current 100 microA to 10mA
resistive leakage current 1 microA to 10mA
Field probe current 10 microA to 1mA
Resolution 1microA for both resistive & total currents
Accuracy ± 5% for both currents
Input External clamp – on CT, field probe, external PT (110 V AC)
Output Self – calibration output
Display 4 line x 20 character large backlit LCD.
Key board 5 keys
Measurement Total current, resistive current
Temperature In-built silicon, thermometer for compensation
Power 12V DC, 2.4AH. SLA rechargeable battery

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 30

Battery charging 230V AC ± 15%, 50Hz ± 10%


Environment 0 to 5°C, 95% RH
Weight 7.5 kg approx.

Advantages:

i. It provides quick and reliable information about the heath of the surge arrester and
allows for storing of all the measurement data’s in the field.
ii. It measures following parameters & displays directly on LCD display
a. Total leakage current.
b. Third order harmonic current.
c. Resistance leakage current.
d. Correct value of resistive leakage current.
e. Waveform display

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 31

6.0 TESTING INSTRUMENT FOR RELAYS

6.1 PERFORMANCE TESTS TO BE DONE ON RELAYS AND WHY

6.1.1 Primary Current Injection Test

Most of the electric supply protective systems are fed from CTs connected to the
supply cable or bus-bar. Primary current injection test checks all the components of the
protective system. A high test current, enough to cause the protection equipment to operate,
is injected into the supply cable. Time taken for the protection relay to operate is then
measured.

The primary current injection test is essential when commissioning new protection
systems and after major repair and component replacement, since it tests the whole system.
It will detect CTs connections with incorrect polarity or relays that have been set in the
wrong sequence in differential systems.

6.1.2 Secondary Current Injection Test

Secondary current injection test checks the operation of the protective relay etc. but
does not test the overall system including the CTs. A secondary injection test is easier since
there is no need to break the primary circuit and it requires less current through the operating
coil of the protective device. The time taken for the protection device to operate is then
measured.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 32

6.2 PRIMARY CURRENT INJECTION TEST

6.2.1 Primary Current Injection Relay Test Set

Name of instrument Primary current injection test


Application Primary current injection test sets have two main applications.
The first of these is the testing of complete relay protection
system as well as the entire chain current transformer,
conductors, connection points and circuit breakers etc.
The second role of the primary current injection test set is to
test the current transformer in a protection system.
Model (make) PCITS 2000/2,( Megger Limted.)
ODEN A/AT,( Programma Electric AB, Sweden)
T- 2000 (ISA srl, Italy)
Technical Specifications
Maximum current output 2000 A at 0 to 3V
AC 1000A at 0 to 6v
Auxiliary voltage output 0 to 250 V, 2A
AC 0 to 125v, 2A
Display Dat matrix LCS
Current 0 – 2000A, resolution 1A
Auxiliary voltage range 2 – 250 V, resolution 1 V
0 – 2A, resolution 0.01A
Accuracy ± 3% of reading, ± 2 digits
Timer 0 – 600 seconds, resolution 0.01 seconds
Temperature range 0°C to 40°C (operation)
- 20°C to +60°C (Storage)
Weight 61 kg (Approx.)

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 33

Advantages:

i. Primary current injection tests the complete relay protection systems comprising the
isolated high voltage conductor, CT, protection relay and the circuit breaker.
ii. Primary current injection tests the testing of the current transformer in a protection
system.
iii. It is provided with built-in timer to record protection relay operation.
iv. As current level is maintained though out the test, circuit resistance may rise due to
heating.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 34

6.3 SECONDARY CURRENT INJECTION TEST

6.3.1 Secondary Current Injection Relay Test Set

Name of instrument Secondary current injection relay test set


Application Secondary current injection test set checks the operation of the
protective relays etc. but does not test the overall system
including the current transformer.
A secondary injection test is easier since there is no need to
break the primary circuit and it requires a less current through
the operating coil of the protective device.
Model (make) T-1000, SVERKER,( M/s Scope T&M Pvt.Mumbai)
750/760, ( Programma Electric AB, Sweden)
T-1000 plus, (ISA srl, Italy)
Technical Specifications
Range 0.5A ∼ 10A
05 A ∼ 100A
Accuracy ± 0.5%
Output voltage 60 V ∼ 50V; 10V ∼ 8V
Power 500 VA (10A), 800 VA (100A)
Load time
Output 100 A, 50A < 50A
Time 750 sec, 3000 sec. continuous

Advantages:
i. A secondary current injection test is easier since there is no need of break the primary
circuit.
ii. It can test relays and CT and it can be used as multi-meter also.
iii. It is easy to control and can also be controlled via external PC.
iv. It has an advance high power constant current source with pulse width modulation
technology.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 35

7.0 CHECKING OF ELECTRICAL CONNECTIONS

7.1 LOOSE CONNECTIONS AND HIDDEN FAULTS CHECKING

Failure of electrical & mechanical devices is because of component failure or


electrical loose connections. Failure such as overhead line problem, problem in electric
connections, overheating, hidden faults and insulation defect etc results in thermal heating.
Infrared thermal imaging camera can detect electrical hot spots on faulty equipment and
hidden faults, when conducting routine survey of electrical system.

7.2 INFRARED THERMAL IMAGING CAMERA

Name of instrument Infrared thermal imaging camera

Application Thermal imaging infrared camera identifies electrical and


mechanical problems like hot spots, heat development on loose
connections etc. before they result in failures.
It is a non-contact device which detects infrared radiations and
converts it into electronic signals. These signals are then
processed to produce thermal image of the object.

Models (make) Flir T – 200 (FLIR Systems, Canada)


Ti45FT-20/54 (Fluke South East Asia Pte Ltd Singapore)

Technical Specifications

1. Temperature measurement range from – 20°C to 1200°C.

2. Temperature measurement accuracy of ± 2%; ± 2°C of reading

3. Image quality of 200 x 150 pixels

4. Thermal sensitivity of 0.1°C

5. IFOV of lens should be 2.18 mrad or less.

6. Spectral range of 7.5 to 13 µm

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 36

7. Built in digital visual camera of 1.3 m pixels

8. Standard lens with FOV of 25° x 19°

9. Permissible relative humidity range 10% to 95% non-condensing

10 Operating & storage temperature range with all accessories in -15°C to 50°C & -
40°C to 70°C respectively.

11. Software should have the feature to prepared report & can be saved in PDF format.

12. At least 3 palettes should be available with 2 color palettes; grey with white hot &
grey with black hot etc.

13. LCD color display 3.5 should be available in camera.

14. Data can be stored in removable SD card with storage capacity of 1000 + images

15. Menu operation should be available via touch screen as well as via toggle button.

16. Auto focuses facility available in camera along with manual focus.

17. Focusable from 0.4mt. to infinity.

Advantages:

i. It helps to find out electrical hot spots and faulty equipments in incipient conditions.
ii. It is an ideal means for professionals looking for safety and reliability when
conducting routine surveys of electrical systems, switchgear and electrical
components.
iii. It is a light weight, comfortable and sensitive test instrument with touch screen, text
features.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 37

8.0 TESTING INSTRUMENT FOR MEASURING EARTH RESISTANCE

8.1 EARTH RESISTANCE

The object of an earthing system is to provide as nearly as possible a surface under


and around a station, which shall be at a uniform potential and as nearly as zero or absolute
earth potential as possible. The purpose is to ensure that generally all parts of the equipment,
other than live parts are at earth potential. The attending personnel are at earth potential at
all times.

The primary requirements of a good earthing system are:


• It protects men and material from injury or damage due to over voltage.
• It keeps the maximum voltage gradient along the surface inside and around the
station within safe limits during earth faults.
• It stabilizes circuit potentials with respect to ground and limit the over all
potential rise.
• It provides low impedance path to fault current to ensure prompt and
consistent operation of protective devices during ground faults.
Earth resistance measurement is very essential to maintain low values of resistance
under all weather conditions.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 38

8.2 EARTH RESISTANCE AND RESISTIVITY MEASUREMENT

8.2.1 Earth Resistance and Resistivity Meter

Name of instrument Earth resistance and resistivity meter


Application This instrument is suitable to measure earth systems in
substations, industries, distribution networks etc.
It is also suitable for soil resistivity measurements in order to
optimize the earth systems projects.
Models (make) MRU – 103,( Sonel S.A Swidnica Poland)
DET 4TC,( Megger Limited)
EM-4055(M/s Megabras Industrial Eletronica Ltd. Brazil)
Technical Specifications
Noise Voltage Range : 0 - 40V
measurement DC + AC Resolution:– 1V
Accuracy: ± (10% m.V + 1digit)
Earth resistance Range: 0.12Ω - 20.0 KΩ
measurement
Earth resistance Range: 0.00 – 9.99 Ω to 10.0 – 20.0 KΩ
measurement using clamp Accuracy : ± (8% mV – 2 digit)
Soil resistivity Range: 0.00 – 9.99 ΩM to 100 – 999 kΩM
measurement
Accuracy ± (2% mV + 2 digit)

Advantages:
i. This instrument is portable and can be used in the field under severe weather
conditions.
ii. This instrument can measure resistance using 2, 3 or 4 pole methods, automatic
calculation and displays the resistance value in ohms.
iii. It has four ranges that are automatically selected, covering measurement requirements.
iv. This meter can be powered from NI-MH batteries or standard ‘C’ size batteries.
v. Measurements can be simplified using current clamps and the test results can be
stored in the internal memory and print out can be taken with built-in printer.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 39

9.0 TESTING INSTRUMENTS FOR BATTERIES

9.1 PARAMETERS TO BE CHECKED AND WHY

Repeated recharging of a secondary battery can lead to battery deterioration and


increase in its internal resistance. Problem can intensify when there is a short circuit in the
internal cell leading to voltage drop, increase in internal resistance, overheating and
complete battery malfunction. These problems can cause severe fires and other accidents.

It is important and necessary to conduct battery testing to check the above defects
periodically.

Following parameters can be checked to determine the health of the battery:

• Voltage
• Impedance
• Specific gravity
• Sulfation (relative to the amount of battery charge capacity degradation due to
sulfation)
• Dryout (relative to the amount of battery charge capacity degradation due to
dryout)

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 40

9.2 BATTERY ANALYSIS

9.2.1 Electro Chemical Battery Analyser

Name of instrument Electro chemical battery analyser

Application Electro chemical battery analyser accurately measures health


of lead acid battery (chemical and electrical) in terms of
sulfation, dry out, voltage and impedance.
All four parameters can be measured simultaneously in a
single measurement.

Models (make) Interrogator 4210 (M/s World Energy Labs Switzerland)


Hikoi battery Hi-tester 3554(M/s HIOKI E.E.Corporation
Japan)

Technical Specifications

Voltage

Range 0 to 17 V DC

Resolution 10mV

Accuracy ± 0.5%

Repeatability ± 0.5%

Impedance

Measurement range 50 µΩ to 1Ω

Resolution 0.001 mΩ for all measurable impedance value.

Accuracy ± 1.0 % (for impedance > 1mΩ to 1Ω)


± 1.0 % (for impedance > 100 µΩ to mΩ)

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 41

Amp–Hour capacity range 5 Ah to 2,000 Ah; specified performance range


for batteries under test 1 Ah to 9,999 Ah, operating range

Sulfation
Range 0 to 100%
Accuracy ± 5%

Dryout
Range 0 to 100%
Accuracy ±5%

Cell terminal strap


impedance (µΩ)
50 µΩ to 1Ω
Measurement range
0.001mΩ
Resolution
±1.0%
Accuracy

Specific Gravity Manual logging

Safety Feature Trigger point – 17VDC


Over voltage auto reset Warning – 50VDC
breaker Damage point – 600VDC max.

Advantages:
i. It can store large amount of data and auto hold and auto-data storage facility also
available.
ii. It has ability to measure AC voltage and low resistance.
iii. It can memorize the value on the spot.
iv. It can enhance resistance against noise.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 42

10.0 TESTING INSTRUMENTS FOR WIRES/ CABLES

10.1 WIRE TRACER/ CABLE LOCATOR


It is very difficult and time consuming task to detect or trace a break in cable, cables
in ceilings, walls, floors, underground cables, shield cables and short circuits locations.
Cable locator is designed to locate above faults very easily.
The cables can be detected regardless whether they are live or not and transmitter
operation mode can be automatically selected.

Name of instrument Cable/ Wire locator


Application This instrument can be used to trace wires in walls,
locate breaks in cables and short circuits, associate
electrical outlets with circuit breakers etc.
Models 2042,( M/s Fluke Corporation WA USA)
LKZ – 700(( Sonel S.A Swidnica Poland,)
Technical Specifications
Transmitter output signal 125 kHz
External voltage detection - Voltage 12 to 400 V
range
Frequency range 0 to 60 Hz
Display LCD with display of functions
External voltage detection Max., 400 V AC/DC
Pollution degree 2
Power supply 6 x 1.5V, (M/s Khandela Electronic Indore) IECLR
6(M/s. PCI Pvt Ltd New Delhi)
Power consumption Max. 40mA
Temperature range 0°C to 40°C, max. 80% humidity
Storage (-20 to + 60°C)
Weight 400 gms.

Advantages:
i. It has automatic and manual sensitivity adjustment features.
ii. It can be used for residential as well as commercial applications.
iii. It displays with bar graph along with audible detection.
iv. It can locate faults in underground cables/ wires in three phase installations also.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 43

10.2 CABLE ROUTE TRACER

It is difficult to trace, locate and measure the depth of buried power cables which are
neither having cable route markers nor their route diagram record etc.

This instrument is designed to locate, trace and measure the depth of buried
energized power cables. It consists a compact, all steel control box. It is attached to a
precision-wound, swivel-mounted detecting coil.

Name of Instrument Cable Route Tracer

Application The cable route tracer locates, traces and measures the depth of
buried energised power cables.
This instrument can also be used to locate grounded electrical
faults on un-shielded cables, particularly in direct buried
installations.

i. Horizontal For maximum deflection over the cable.

ii. Vertical For a null over the cable

iii. 450 angle For a null at a horizontal distance from the cable that is
equivalent to the cable depth.

Model (make) Nil (Magger Limited)

Technical Specifications

 Locates and traces energised power cables with supply of 50/60 Hz.

 Three way swivel detector also measures cable depth.

 Portable (weight only1.1 kg) and overall length is 26 inches only.

 It can be used indefinitely with little fatigue.

 Two sensitivity ranges enables tracing of cables as much as 8ft. (2.4m) deep.

 Battery 9-volt transistor type.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 44

Advantages:
i. It has fully transistorized amplifier with 10 turn gain control for wide adjustment
range.
ii. It is not affected by telephone lines, gas or water pipes, steel reinforcing or
metallic conduit.
iii. It responds current flowing in the cable, even in the metallic conduit.
iv. It has special feature of battery test circuit which provides upto 150 hours of
operation.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 45

11.0 TESTING INSTRUMENTS FOR OVER HEAD EQUIPMENT

11.1 CONTACT WIRE SPARK CHECKING

Sparking occurs when there is loss of contact between the pantograph and the contact
wire. The spark is developed in contact wire due to a kink in contact wire. It is important to
attend the kink roughened surface of the contact wire to avoid further rapid deterioration,
with successive passage of pantographs resulting in reduced life of contact wire.

It is necessary to carry out periodic tests to detect points at which contact between
the contact wire and pantograph is unsatisfactory resulting in sparking. Current collection
shall be carried out during night time for better results.

11.1.1 OLIVIR-G Plus

The OLIVIR-G Plus is developed to assist Over Head Equipment (OHE) spark
detection using a video camera. The hardware units consist of a GPS receiver which track
the current position of the locomotive in which the ‘OLIVIR-G plus’ is mounted.

The OLIVIR mate RT software supplied with the unit identities sparks in real time
and save them as images with locations, at the same time continuous video film is also
recorded in hard drive. These images can be analyzed to recognize the type of spark (mega
pixel) with their locations.

Name of Instrument Olivir – ‘G’ plus


Application The OLIVIR-G Plus is developed to observe OHE (Contact
wire) spark detection using the video camera. The hardware
units consist of a GPS receiver which track the current position
of the locomotive in which the OLIVIR is mounted.
OLIVIR-G Plus is generate two types of reports:
i. Graphical Report
ii. Text Report
Model (make) OLIVIR – G plus(M/s Total solution, Bhopal)

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 46

Accessories:
i. Focus light operated at 110V AC/DC supply.
ii. Camera and light
iii. GPS antenna
iv. Processing & login unit
v. GPS unit
vi. Serial cable
vii. Battery charger
viii. Track feature collection unit

Advantages:
i. It can show total number of images recorded during current collection test.
ii. The category of spark can be adjusted as per customer requirement.
iii. It gives the correct position of spark with its location.
iv. The size of spark value can be adjusted during current collection.
v. It automatically saves all recorded data in the laptop datewise.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 47

11.2 CONTACT WIRE HEIGHT & STAGGER MEASUREMENT

Any change in alignment due to slewing of tracks will affect the setting distance and
the stagger of the contact wire. Change in rail level due to variation in ballast cushion or
packing down of the track will also result in change in contact wire height.
Though provision exists in the cantilever assembly for adjustments of the stagger and
height, such adjustments are not to be made unless absolutely necessary. It is best to
maintain the position of OHE and tracks as in the SEDs.

11.2.1 Rail Rod Ultrasonic Height & Stagger Gauge

Rail Rod Ultrasonic Height & Stagger Gauge is used for measurement of height of
contact wire and catenary wire without power block both on meter and broad gauge tracks.

Name of instrument Rail Rod Ultrasonic Height & Stagger Gauge


Application Rail Rod Ultrasonic Height & Stagger Gauge is use for
measurement of height of contact wire & catenary wire on
horizontally track gauge variable 1.0 mtr. to 1.7 mtr.
Model (make) Rail rod – ABT 4420 (ABTUS Limited, Haverhill, Suffolk UK)
Technical Specifications
Display menu
i. contact wire 1 or 2
ii. support cable 1 or 2( 1+1) Vertically
iii. track width 1.00 – 1.800
iv. sample size 1 or 10( 1st Faster)
v. memory standard or auto
vi. base height 0 to 1.000m( use on rail)
vii. extended blanking 0 to 8.000m
Temperature Automatic
Cant/ gradient Measurement option available
Memory Auto
Display Two wire stagger
Number of Ten
measurements

Advantages:
i. It can measure three wires vertically or two wires horizontally.
ii. It is a compact & portable system (weight around 3.5 kg) hence suitable for single hand
use.
iii. It can take measurement at cant/gradient locations.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 48

11.3 LIVE LINE CONTACT WIRE WEAR MONITORING

Following locations are generally prone to higher wear rate of contact wire:
• Stop Signal
• FOB/ ROB
• MEMU Locations
• Starter signal
It is therefore, becomes pertinent to monitor diameter of contact wire continuously at
these locations. Diameter of new contact wire is 12.24 mm & condemning limit for main
line is 8.25 mm. Present system over Indian Railways is checking diameter at one location
per km. once a year during Tower Wagon checking.
One location per km. & that to be checked once in a year does not appear adequate
since it is observed that new locations with dia less than 9 mm crop up at intermediate
location and during intermediate time.

11.3.1 25 kV Live Line Contact Wire Wear Monitoring


To have better & continuous monitoring of contact wire wear Jig has been developed
which gives measurement of contact wire dia at eye level without need of power block.

Name of instrument Contact Wire Wear Measuring Jig.


Application Continuous monitoring of contact wire diameter at eye level
without power block.
Model (make) Nil
Developed by Sr. D.E.E.(TRD), Western Railway, Vadodara
Gujarat
Technical Specifications
Material High insulated fiber glass epoxy Telescopic rod
(Jaw on top & Vernier calipers at eye level)
Length 5.15 m
Diameter of pipe 39mm outer, 30mm inner
Weight 5 kg
Electrical Type tested at 100 kV at ERDA BRC and capable with constant
high voltage up to 30 kV perfect in wet condition water absorption
is only 0.2 %

Advantages:
i. The contact wire locations having higher wear rate can be monitored more frequently.
ii. The number of locations to be checked per km. can also be increased.
iii. It can help in better monitoring of health of contact wire and consequent reduction in
contact wire parting cases.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 49

11.4 LIVE LINE INSULATOR CLEANING


The OHE insulators require regular cleaning for ensuring un-interrupted traction
supply. The periodicity of cleaning varies from area to area depending upon pollution level,
proximity to sea etc. Where pollution is heavy, the cleaning has to be done more frequently.
This cleaning is essential as the insulators are affected by dust/ smoke particles, industry/
chemicals deposits, accumulation of coal/ cement particles etc. which form conducting
layers on porcelain thereby causing CB tripping during night hours/ foggy weather/
drizzling. The insulators in light/ non- polluted zone are cleaned twice in a year i.e pre-
monsoon & pre- winter.
To overcome the problem of power block at aforesaid locations, a “Live Line
Insulator Cleaning Jig” has been developed by Sr. D.E.E. (TRD),Western Railway,
Vadodara (Gujarat)

11.4.1 Live Line Insulator Cleaning Jig


The jig consists of light weight “Two Insulated Rod”( Each rod comprising of 2 to3
detachable sections of 1.85 mt / 2.0 mt length each with push button locking arrangement)
provided with cotton pad on top. The cotton pad is fixed on one end to first to rod &
clamped to other rod after inserting on insulator through hook arrangement.

Name of Instrument Live Line Insulator Cleaning Jig


Application With the increasing trend of traffic on Railway system, the
construction of power block is likely to worsen further in
near future; resulting insulator cleaning will adversely
affect reliability of OHE supply causing traffic dislocations.
To overcome the problem of power block an insulator
cleaning jig has been developed. The jig consists of light
weight two insulated. Rods provided with cotton pad on top
& clamped to other. Rod after inserting on insulator
through hook arrangement.
Model (make) Nil
Developed by Sr. D.E.E.(TRD), Western Railway,
Vadodara Gujarat
Technical Specifications
i. Material Highly insulated fiber glass epoxy telescopic rod.
ii. Assembled length 6.0 (3 positions of 2.0m length two rods)
iii. Diameter of rod 39mm outer, 30mm inner
iv. Weight 6.0 kg
v. Electrical Type tested at 100 kV at ERDA BRC and capable to
specification withstand high voltage up to 30kV feet/ per ft. in wet
condition water absorption is only 0.2%
vi. Cotton pad 2 feet long and 5 inch wide pad made of woolen cloth &
spunge material.

Advantages:
i. It can save wastage of manpower for discharge Rod/ Power block/ E-socket/ Ladder etc.
ii. It can increase productivity.
iii. It gives better quality of insulator cleaning/ resultant reduction in CB transient trippings.

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 50

ANNEXURE – I

SUPPLIERS ADDRESSES:

S.No. Address Contact No.


1. M/s Scope T&M Pvt.Ltd., Phone : 022 – 24442129/ 24442163
12, Ganesh Apartment, Ist Floor, Fax : 022 – 2444 0720
376, L.J. road, Mahim, e-mail : marketing@scopetnm.com
Mumbai – 400 016 Website : www.scopetnm.com

2. M/s Khandela Electronika Phone : 0731 – 4020081, 4020082


Khandela House, 24-Gulmohar Fax : 0731 – 4020083
colony, e-mail : khandela@vsnl.com
Indore – 452018 Website : www.khandela.com

3. M/s M-Tekpro Engineering Pvt. Ltd. Phone : 011 – 46173333


B-229, LGF, Greater Kailash – 1 Fax : 011 – 1141825662
New Delhi – 110 048 e-mail : info@mtekpro.com
Website : www.mtekpro.net

4. M/s PCILtd., Phone : 011-41 888 999, 41 888 888


Prime Group Building,,11/5B, Fax : 0 11 25755815, 25821623
Pusa Road,New Delhi-110005 e-mail : pci@prime-pci.com &
primegroup@vsnl.com
Website: www.primegroupindia.com

5. M/s SIVANANDA ELECTRONICS Phone :0253– 2491423/ 2491504/2491816


Deepaks Mahal, Lam Road, Fax : 0253 – 2492291
DEVLALI – 422 401, e-mail : mkb@sivanandaelectronics.com
Nasik -(Maharastra).

6. M/s Dakshin Lab Agencies Ph no 080- 25291401, 25293599


Ashwini Complex, First floor (mob) 09845205110
6th main, LIC Colony
E mail: ramakrishnan@dakshinlab.com
New Thippasandra
Bangalore – 560075 Website : www.dakshinlab.com
M/s. Applied Techno Product Pvt. Phone: 0124- 4288186 /7 / 8,
7.
Fax : 0124- 4288189,
Ltd.
Plot no. 85, sector 44, Industrial area, e- mail : info@atplonline.net,
Website : www.atplonline net
Gurgaon -122002(HARYANA)
M/s SAM International Pvt. Ltd. Phone No. 022 – 23432037, 66370035
8.
Fax: 022 – 23434773
158/160, Narayan Dhuru Street, e- mail : samint@vsnl.com
3rd Floor, Mumbai – 400 003. Website : www.samint.in

Testing Instruments Required for Condition Based Maintenance of TRD Assets August, 2009
CAMTECH/E/2009/TI-TRD/1.0 51

OUR OBJECTIVE
To upgrade maintenance technologies and
methodologies and achieve improvement in
productivity, performance of all Railway
assets and manpower which inter-alia would
cover reliability, availability, utilisation and
efficiency.

If you have any suggestions and any specific


Comments please write to us.

Contact person : Director (Elect.)

Postal Address : Indian railways


Centre for Advanced
Maintenance technology,
Maharajpur, Gwalior.
Pin code – 474 005

Phone : 0751 – 2470740


0751 – 2470803

Fax : 0751 - 2470841