www.tyco-fire.com
Contacts

Series TY-L – 5.6 and 8.0 K-factor


Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General quently, it is recommended that the
end-user be consulted about the suit-
Description ability of these coatings for any given
corrosive environment. The effects of
The TYCO Series TY-L 5.6 and ambient temperature, concentration of
8.0 K-factor Upright, Pendent, chemicals, and gas/chemical velocity,
and Recessed Pendent Sprin- should be considered as a minimum,
klers described herein are stan- along with the corrosive nature of the
dard response, standard coverage, chemical to which the sprinklers will be
solder type spray sprinklers. They are exposed.
designed for use in light, ordinary, and An intermediate level version of the
extra-hazard commercial occupan- Series TY-L Pendent Sprinkler can be
cies such as banks, hotels, shopping obtained by utilizing the Series TY-L
malls, factories, refineries, and chemi- Pendent Sprinkler in combination with
cal plants. the Model S Shield.
The Series TY-L Recessed Pendent
Sprinkler, where applicable, is NOTICE
intended for use in areas with a fin- The Series TY-L 5.6 and 8.0 K-fac-
ished ceiling. It uses a two-piece tor Upright, Pendent, and Recessed
Style 20 (1/2 in. NPT) or Style 30 Pendent Sprinklers described herein
(3/4 in. NPT) Recessed Escutcheon. must be installed and maintained in
The Recessed Escutcheon provides compliance with this document, as
1/4 in. (6,4 mm) of recessed adjust- well as with the applicable standards
ment or up to 1/2 in. (12,7 mm) of total of the NATIONAL FIRE PROTECTION
adjustment from the flush pendent ASSOCIATION (NFPA), in addition to
position. The adjustment provided by the standards of any other authorities
the Recessed Escutcheon reduces the having jurisdiction. Failure to do so
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
may impair the performance of these
devices.
Sprinkler
Corrosion-resistant coatings, where The owner is responsible for main- Identification
Number (SIN)
applicable, are utilized to extend the life taining their fire protection system
of copper alloy sprinklers beyond what and devices in proper operating con-
would be obtained when exposed to dition. Contact the installing contrac-
corrosive atmospheres. Although cor- TY3111 ������� Upright 5.6K, 1/2 in. NPT
tor or product manufacturer with any
rosion-resistant coated sprinklers have questions. TY3211 ����Pendent 5.6K, 1/2 in. NPT
passed the standard corrosion tests of TY4111 ������� Upright 8.0K, 3/4 in. NPT
the applicable approval agencies, the NFPA 13 prohibits installation of 1/2 TY4211 �����Pendent 8.0K, 3/4 in. NPT
testing is not representative of all pos- inch NPT sprinklers with K-factors
greater than 5.6 in new construction. TY4811 ����� Upright 8.0K, 1/2 in. NPT
sible corrosive atmospheres. Conse- TY4911 ����Pendent 8.0K, 1/2 in. NPT
They are intended for retrofit in existing
sprinkler systems only. TY3111 is a re-designation for S1800 and G3111
TY3211 is a re-designation for S1801 and G3112
IMPORTANT TY4111 is a re-designation for S1810 and G3101
Refer to Technical Data Sheet TY4211 is a re-designation for S1811 and G3102
TY4811 is a re-designation for S1805
TFP2300 for warnings pertaining to TY4911 is a re-designation for S1806
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 6 AUGUST 2018 TFP110


TFP110
Page 2 of 6

* Temperature rating ** Pipe thread connections per 1 - Frame 3 - Ejection 5 - Strut


is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Sealing Spring 6 - Hook
Deflector. special request. PLATE SEATING Button 4 - Fusible 7 - Deflector *
SURFACE Element
1

WRENCH
2-5/8" AREA 2
(66,7 mm)
2-5/8"
7/16" 4
(66,7 mm) 3
(11,1 mm)
NOMINAL 2" STYLE 20 5
MAKE-IN (50,8 mm) RECESSED
ESCUTCHEON
6

7*
1/2" NPT ** WRENCH 2-7/8" (73,0 mm) DIA.
FLANGES
UPRIGHT PENDENT RECESSED PENDENT CROSS SECTION
FIGURE 1
SERIES TY-L UPRIGHT (TY3111) AND PENDENT (TY3211) SPRINKLERS, 5.6 K-FACTOR, 1/2 IN. NPT

* Temperature rating ** Pipe thread connections per 1 - Frame 3 - Ejection 5 - Strut


is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Sealing Spring 6 - Hook
Deflector. special request. PLATE SEATING Button 4 - Fusible 7 - Deflector *
SURFACE Element
1

WRENCH
2-11/16" AREA 2
(68,3 mm)
1/2" 2-11/16" 4
(12,7 mm) (68,3 mm) 3
NOMINAL
MAKE-IN 2" STYLE 30 5
(50,8 mm) RECESSED
ESCUTCHEON
6

3/4" NPT** WRENCH 2-7/8" (73,0 mm) DIA. 7*


FLANGES
UPRIGHT PENDENT RECESSED PENDENT CROSS SECTION
FIGURE 2
SERIES TY-L UPRIGHT (TY4111) AND PENDENT (TY4211) SPRINKLERS, 8.0 K-FACTOR, 3/4 IN. NPT

* Temperature rating ** Pipe thread connections per 1 - Frame 3 - Ejection 5 - Strut


is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Sealing Spring 6 - Hook
Deflector. special request. PLATE SEATING Button 4 - Fusible 7 - Deflector *
SURFACE Element
1

WRENCH
2-5/8" AREA 2
(66,7 mm)
2-5/8"
7/16" 4
(66,7 mm) 3
(11,1 mm)
NOMINAL 2" STYLE 20 5
MAKE-IN (50,8 mm) RECESSED
ESCUTCHEON
6

7*
1/2" NPT ** WRENCH 2-7/8" (73,0 mm) DIA.
FLANGES
UPRIGHT PENDENT RECESSED PENDENT CROSS SECTION
FIGURE 3
SERIES TY-L UPRIGHT (TY4811) AND PENDENT (TY4911) SPRINKLERS, 8.0 K-FACTOR, 1/2 IN. NPT
TFP110
Page 3 of 6

Frame Sprinkler Finish


Temp.
K Type Color Natural Chrome Lead Wax Wax Over
Rating Code Brass Plated Coated Coated Lead Coated
165°F (74°C) Unpainted
Pendent (TY3211) 1, 2, 3
and 212°F (100°C) White 1, 2, 3, 5
5.6 Upright (TY3111)
1/2 in. 280°F (138°C) Blue 1, 2 4 N/A
NPT
Recessed Pendent 165°F (74°C) Unpainted 1, 2, 3, 5
N/A6
(TY3211 w/Style 20) 212°F (100°C) White 1, 2, 3, 5
165°F (74°C) Unpainted
1, 2, 3
Pendent (TY4211) 212°F (100°C) White 1, 2, 3
280°F (138°C) Blue 1, 2 4 N/A
8.0 165°F (74°C) Unpainted
3/4 in. 1, 2, 3
NPT Upright (TY4111) 212°F (100°C) White 1, 2, 3, 5
280°F (138°C) Blue 1, 2 4 N/A

Recessed Pendent 165°F (74°C) Unpainted


1, 2, 5 N/A
(TY4211 w/Style 30) 212°F (100°C) White
165°F (74°C) Unpainted
Pendent (TY4911) 1, 2, 3
and 212°F (100°C) White 1, 2, 3, 5
8.0 Upright (TY4811)
1/2 in. 280°F (138°C) Blue 1, 2 N/A
NPT
Recessed Pendent 165°F (74°C) Unpainted
1, 2 N/A
(TY4911 w/Style 20) 212°F (100°C) White
NOTES:
1. UL Listed 4. FM Approved for maximum 150°F (68°C) ambient temperatures
2. C-UL Listed 5. LPCB Approved (LPCB Ref. No. 094a/03)
3. FM Approved 6. Not Available (N/A)
TABLE A
LABORATORY LISTINGS AND APPROVALS

Technical Operation Design


Data A copper tube sealed by two stainless
steel balls holds a fusible alloy. When
Criteria
Approvals the rated temperature is reached, the The TYCO Series TY-L 5.6 and
UL and C-UL Listed alloy melts and the balls are forced 8.0 K-factor Upright, Pendent, and
FM and LPCB Approved toward each other. This releases the Recessed Pendent Sprinklers are
Refer to Table A for complete approval infor- tension mechanism and allows the intended for fire protection systems
mation including corrosion resistant status. sprinkler to operate. designed in accordance with the stan-
dard installation rules recognized by
Maximum Working Pressure the applicable Listing or Approval
175 psi (12,1 bar) agency, such as the UL Listing based
Discharge Coefficient on the requirements of NFPA 13 and
K=5.6 GPM/psi½ (80,6 LPM/bar½) FM Approval based on the require-
K=8.0 GPM/psi½ (115,2 LPM/bar½) ments of FM Loss Prevention Data
Sheets. Use only the Style 20 or 30
Temperature Ratings Recessed Escutcheon, as applicable,
Refer to Table A
for recessed pendent installations.
Finishes
Sprinkler: Refer to Table A Recessed
Escutcheon: White Coated, Chrome
Plated, or Brass Plated
Physical Characteristics
Frame ���������������������������������������������������������Brass
Sealing Button ����������������������Bronze w/TEFLON
Ejection Spring ���������������������������� Stainless Steel
Strut ��������������������������������������������������������MONEL
Hook. . . . . . . . . . . . . . . . . . . . . . Bronze/MONEL
Deflector ���������������������������������������������������Bronze
Fusible Element �������������������������Solder, Copper,
Stainless Steel
TFP110
Page 4 of 6

7/16±1/8" 2-7/8" DIA. 1/2" (12,7 mm)


(11,1±3,2 mm) (73,0 mm) 1/4" (6,4 mm)

FACE OF 2-1/4" DIA. MOUNTING WRENCH


SPRINKLER (57,2 mm) PLATE RECESS
FITTING
1/8"
(3,2 mm)

MOUNTING FIGURE 7
SURFACE W-TYPE 9 SPRINKLER
1-3/4" (44,5 mm) WRENCH
1-1/2" (38,1 mm)

CLOSURE TY-L WRENCH


RECESS
FIGURE 4
SERIES TY-L (TY3211) RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 IN. NPT

7/16±1/8" 2-7/8" DIA. 1/2" (12,7 mm)


(11,1±3,2 mm) (73,0 mm) 1/4" (6,4 mm)
FIGURE 8
FACE OF 2-1/4" DIA. MOUNTING W-TYPE 10 RECESSED
SPRINKLER (57,2 mm) PLATE SPRINKLER WRENCH
FITTING
1/8"
(3,2 mm)

MOUNTING
SURFACE 1-3/4" (44,5 mm)
1-1/2" (38,1 mm)

CLOSURE TY-L
FIGURE 5
SERIES TY-L (TY4211) RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 IN. NPT

7/16±1/8" 2-7/8" DIA. 1/2" (12,7 mm)


(11,1±3,2 mm) (73,0 mm) 1/4" (6,4 mm)
FACE OF 2-1/4" DIA. MOUNTING
SPRINKLER (57,2 mm) PLATE
FITTING
1/8"
(3,2 mm)

MOUNTING
SURFACE 1-3/4" (44,5 mm)
1-1/2" (38,1 mm)

CLOSURE TY-L
FIGURE 6
SERIES TY-L (TY4911) RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON 8.0 K-FACTOR, 1/2 IN. NPT
TFP110
Page 5 of 6

Installation • Inspect the sprinkler wrench flats


and frame arms and retouch (repair) Care and
The TYCO Series TY-L 5.6 and
8.0 K-factor Upright, Pendent, and
the wax coating whenever the coat-
ing has been damaged and bare Maintenance
Recessed Pendent Sprinklers must metal is exposed. The TYCO Series TY-L 5.6 and
be installed in accordance with this • Retouch the wax coating on the 8.0 K-factor Upright, Pendent, and
section. wrench flats by gently applying a Recessed Pendent Sprinklers must be
heated 1/8 inch diameter steel rod maintained and serviced in accordance
General Instructions
to the damaged areas of the wax, with this section.
A leak tight 1/2 in. NPT sprinkler joint
should be obtained with a torque of to smooth it back over areas where Before closing a fire protection system
7 to 14 ft-lb (9,5 to 19,0 Nm). A bare metal is exposed. main control valve for maintenance
leak- tight 3/4 in. NPT sprinkler joint work on the fire protection system that
should be obtained with a torque of NOTICE it controls, permission to shut down the
10 to 20 ft-lb (13,4 to 26,8 Nm). Higher Only retouching of the wax coating affected fire protection system must be
levels of torque may distort the sprin- applied to the wrench flats and frame obtained from the proper authorities
kler inlet and cause leakage or impair- arms is permitted, and the retouching and all personnel who may be affected
ment of the sprinkler. is to be performed only at the time of by this action must be notified.
Do not attempt to compensate for the initial sprinkler installation. Absence of an escutcheon, which is
insufficient adjustment in the escutch- The steel rod should be heated only to used to cover a clearance hole, may
eon plate by under- or over-tightening the point it can begin to melt the wax, delay the time to sprinkler operation in
the sprinkler. Re-adjust the position of and appropriate precautions need to be a fire situation.
the sprinkler fitting to suit. taken when handling the heated rod to Sprinklers that are found to be leaking
Series TY-L Upright and Pendent prevent the installer from being burned. or exhibiting visible signs of corrosion
Sprinklers Installation If attempts to retouch the wax coating must be replaced.
The Series TY-L Pendent and Upright with complete coverage are unsuc- Automatic sprinklers must never be
Sprinklers must be installed in accor- cessful, additional wax can be ordered painted, plated, coated or otherwise
dance with the following instructions: in the form of a wax stick, the end of altered after leaving the factory. Modi-
which is color coded. Only the correct fied or over-heated sprinklers must be
Step 1. Install pendent sprinklers in the
color coded wax is to be used, and replaced. Care must be exercised to
pendent position. Install upright sprin-
retouching of wrench flats and frame avoid damage to the sprinklers before,
klers in the upright position.
arms is only permitted at the time of during, and after installation. Sprin-
Step 2. With pipe thread sealant initial sprinkler installation. klers damaged by dropping, striking,
applied to the pipe threads, hand- wrench twist/slippage, or the like, must
With the steel rod heated as previ-
tighten the sprinkler into the sprinkler be replaced.
ously described, touch the rod to the
fitting.
area requiring additional wax with the Frequent visual inspections are rec-
Step 3. Tighten the sprinkler into the rod angled downward, and then touch ommended to be initially performed
sprinkler fitting using only the W-Type the wax stick to the rod approximately for corrosion resistant coated sprin-
9 Sprinkler Wrench (Ref. Figure 7). For 1/2 in. (12,7 mm) away from the area klers, after the installation has been
wax coated sprinklers, use an 8 or 10 requiring retouching. The wax will melt completed, to verify the integrity of the
in. adjustable Crescent wrench. With and run down onto the sprinkler. corrosion-resistant coating. Thereafter,
reference to Figures 1, 2, and 3, apply annual inspections per NFPA 25 should
the W-Type 9 Sprinkler Wrench to the Series TY-L Recessed Pendent
Sprinklers Installation suffice; however, instead of inspecting
wrench area, or as applicable, apply from the floor level, a random sampling
the adjustable Crescent wrench to the The Series TY-L Recessed Pendent
Sprinkler must be installed in accor- of close-up visual inspections should
wrenching flanges. be made so as to better determine the
dance with the following instructions:
Wax Coated Sprinklers exact sprinkler condition and the long-
When installing wax-coated sprinklers Step 1. After installing the Style 20 term integrity of the corrosion resistant
with the adjustable Crescent wrench, or 30 Mounting Plate, as applicable, coating, as it may be affected by the
take care to prevent damage to the over the sprinkler threads and with corrosive conditions present.
wax coating on the sprinkler wrench pipe thread sealant applied to the pipe
threads, hand-tighten the sprinkler into The owner is responsible for the inspec-
flats or frame arms and, consequently, tion, testing, and maintenance of their
exposure of bare metal to the corrosive the sprinkler fitting.
fire protection system and devices in
environment: Step 2. Tighten the sprinkler into the compliance with this document, as well
• Open the jaws of the wrench suffi- sprinkler fitting using only the W-Type as with the applicable standards of the
ciently wide to pass over the wrench 10 Recessed Sprinkler Wrench (Ref. NATIONAL FIRE PROTECTION ASSO-
flats without damaging the wax Figure 8). With reference to Figure 1, CIATION (e.g., NFPA 25), in addition to
coating. 2, or 3, apply the W-Type 10 Recessed the standards of any other authorities
Sprinkler Wrench to the sprinkler having jurisdiction. Contact the install-
• Before wrench tightening the sprin- wrenching flanges. ing contractor or product manufacturer
kler, adjust the jaws of the wrench to with any questions.
just contact the sprinkler flats. Step 3. After the ceiling has been
installed or the finish coat has been It is recommended that automatic
• After wrench tightening the sprin- applied, slide on the Style 20 or 30 sprinkler systems be inspected, tested,
kler, loosen the wrench jaws before Closure over the Series TY-L Recessed and maintained by a qualified Inspec-
removing the wrench. Pendent Sprinkler and push the Closure tion Service in accordance with local
After Installation over the Mounting Plate until its flange requirements and/or national codes.
After installation, complete the comes in contact with the ceiling.
following:
TFP110
Page 6 of 6

P/N 53 - XXX - X - XXX

SPRINKLER TEMPERATURE
SIN FINISH RATING

111 5.6K UPRIGHT (1/2 in. NPT) TY3111 1 NATURAL BRASS 165 165°F (74°C)

WAX COATED
112 5.6K PENDENT (1/2 in. NPT) TY3211 6 212 212°F (100°C)
165°F TO 280°F ONLY

101 8.0K UPRIGHT (3/4 in. NPT) TY4111 7 LEAD COATED 280 280°F (138°C)

WAX OVER LEAD


102 8.0K PENDENT (3/4 in. NPT) TY4211 8 165°F TO 212°F ONLY

106 8.0K UPRIGHT (1/2 in. NPT) TY4811 9 CHROME PLATED

107 8.0K PENDENT (1/2 in. NPT) TY4911

TABLE B
SERIES TY-L PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION

Limited Ordering Wax Sticks (for retouching wrench-


damaged wax coating)
Warranty Procedure Specify: Series TY-L Sprinklers,
(specify color), color coded Wax Stick
For warranty terms and conditions, visit Contact your local distributor for avail- for retouching, (specify) temperature
www.tyco-fire.com. ability. When placing an order, indicate rated, P/N (specify):
the full product name and Part Number Red for 165°F (74°C) ��������������� P/N 56-065-1-155
(P/N). Blue for 212°F (100°C)
and 280°F (138°C) . . . . . . . . . . P/N 56-065-1-286
Sprinkler Assemblies with NPT
Thread Connections Note: Each wax stick is suitable for
Specify: Series TY-L (specify SIN), retouching up to twenty-five sprin-
(specify K-factor), (specify Upright, klers. The wax used for 280°F (138°C)
Pendent, or Recessed Pendent) Sprin- sprinklers is the same as for 212°F
kler, Standard Response, Standard (100°C)sprinklers. Therefore, the 280°F
Coverage, (specify) temperature rating, (138°C) sprinkler is limited to the same
(specify) finish or coating, P/N (specify maximum ceiling temperature as the
from Table B) 212°F (100°C) sprinkler, which is 150°F
(65°C).
Recessed Escutcheon
Specify: Style (specify) Recessed
Escutcheon, (specify material) with
(specify*) finish, P/N (specify*)
*Refer to Technical Data Sheet TFP770

Sprinkler Wrench
Specify: W-Type 9 Sprinkler Wrench,
P/N 56-000-1-849
Specify: W-Type 10 Sprinkler Wrench,
P/N 56-000-1-948

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL is a registered trademark of Special Metals Corporation;