Anda di halaman 1dari 7

Voltage stability assessment for real-time operation

R.B. Prada, E.G.C. Palomino, J.O.R. dos Santos, A. Bianco and L.A.S. Pilotto

Abstract: Network voltage stability is represented by nodal conditions associated with the
maximum active and reactive power flow that can be transmitted from generators to loads. An
analytical assessment tool is derived, based on a simple but sound mathematical background,
modelling a straightforward physical characterisation of the phenomena. Comprehensive and
meaningful indices are introduced. They indicate the MVA margin to the maximum, the region of
operation, the relative importance among buses, the loading ranlung of the buses, the sensitivity to
control actions, and a measure of difficulty for power transmission. Numerical results are presented
for the Itaipu bulk transmission network in the SjSE of Brazil immediately before a voltage
stability blackout in April 1997. Computational efficiency is no burden for real time operation
including contingency analysis.

1 Introduction indices should be necessarily based on real-time measure-


ments of the network and its controls, and have to be
Power systems are operated under increasingly loaded computed in a short time (few seconds). Such indices could
conditions. Open access, few new transmission lines, and trigger an automatic network control and protective action
increased energy consumption necessitate much greater to delay or avoid unstable operating conditions [5]. With
levels of power transfer. The system is operating near its this objective, t h s paper presents a comprehensive and
limits to achieve maximum economic benefit. Online real- meaningful network voltage stability assessment tool.
time network analysis is required to maintain adequate
security margins. This paper addresses the voltage stability 2 Analytical tool
limit. If it is dynamically calculated using actual system
conditions, a typical benefit might be a 15% increase in The primary objective is to identify whether a load voltage
transmission capacity across a constrained 1000 MW inter- at bus i is in the upper or lower half of the V x P, Q curve
face. Assuming that 30% of this increased capacity could be [I], as well as the distance to the 'tip of the nose'. The upper
used on average over a year and a US$lO/MWh price half is the usual region of operation whle the lower half is
differential across the line, t h s could result in an annual the abnormal region of operation where voltage control
financial benefit of US$ 3.9 million [l]. actions may have the opposite effect if loads behave as a
Voltage stability operation problems originate from the constant power sink. The 'tip of the nose' is the maximum
higher use of transmission lines, which was made possible amount of active and reactive power that can be transmitted
through extensive use of reactive power compensation [2]. to a load or from a generator. The corresponding voltage
The ability to maintain voltage stability depends on magnitude is the minimum voltage for normal operation [6].
appropriate analysis of the operating conditions. There is The linearised system of load flow equations is
still a need for analytical tools capable of assessing voltage
collapse proximity, accurately quantifying stability margins
and power transfer limits, identifying voltage-weak points
and areas susceptible to voltage instability. Rearranging terms by putting the equations related to the
Modal analysis based on the calculation of 'small eigen- bus under analysis to the bottom of the system (1)
values' [3] or 'small singular values' [4] although adequate
for expansion planning studies, has never being recommended
for operational purposes. The establishment of voltage
stability indices representing the instantaneous margin of
the current operating point with respect to the instability
limit should be the objective for real-time analysis [5]. These where submatrices'A, B, C and D originate from a partition
of full Jacobian matrix [Jl. Assuming incremental load (or
0IEE, 2002 generation) variation AP and AQ only on bus i, Le.
IEE Procredinys online no. 20020282 A€" = AQ' = 0, the system (2) is reduced to dimension
DOL IO. 1049/ip-gtd:20020282 (2 x 2)
Paper first received 1 Ith December 2000 and in revised form 21st June 2001
R.B. Prada and E.G.C. Palomino are with the Department of Electrical (3)
Engineering, Catholic University of Rio de Janeiro, Rua Marquss de SBo
Vicente, 225 Gavea, Rio de Janeiro 22453 900, Brazil
where
J.O.R. dos Santos is with the Department of Electrical Engineering, Federal
Foundation of Superior Education of SHo Joio del-Rei - FUNREI, P r a y Frei [D'] = [D] - [C]* [A-'1 * [B] (4)
Orlando 170, SBo Joio del-Rei, Mina Gerais, 36300 000, Brazil
A. Bianco and L.A.S. Pilotto are with the Electric Power Research Center - Therefore, the voltage magnitude and angle sensitivity
CEPEL, Av. Um sino, Cidade Universitaria, Rio de Janeiro, 21941 590, Brazil relationships in relation to active and reactive power at bus i
IEE Proc.-Gener. Transnz. Distrih., Vol. 149, No. 2,March 2002 175
taking into account the whole system, can be verified by (3) As in (4): p’]= [D]-[C] * [A-.’] * PI, and using (12) and
[7]. It is to be demonstrated that the determinant sign and (13) it may be written as
magnitude of matrix [D’] indicate, respectively, the region of
operation and the distance to the maximum. det[D’]=det[(’ y i ) + ( b l
2! b2 b4
b3)] (14)

2.1 Matrix [D’l determinant magnitude Therefore


The power flow arriving at the load bus i in a two-bus
det[D’] = [ x . u - y . z ] + [ x . b 4 - y y b 3 ]
system is equal to the power consumed by the load.
Considering k as the generator bus, the matrix p’] + [bl . u - 6 2 . + [bl . b4 - b2 . b3]
Z]
(15)
determinant is calculated by But
det[D] = [ x . u - y . z ] (16)
and then
where
= y2GI,+ K & ( GfkCOS d , k + Blk Sin e l k )
+
det[D’] = det[D] [x . b4 - y . b3]
(6)
+ +
[bl . u - 62 ’ z ] [bl ‘ 6 4 - 62. b3]
(17)

+
Qf = - y2Blz E & ( GfkSin e l k - Blk COS Q l k ) (7) The result obtained in (11) for a two-bus system where
Solving (5) with (6) and (7) p’] [D], is now extended to a multinode system. Multi-
plying both sides of (17) by V ,
det[D’] = - K b2( G i +B i )
det[D’] * = dct[D] * V; - S,2 (18)
+ 2 K2BII( &GIkSin elk - &BIk COS e l k ) (8)
where
- 2 Y2G,,( VkGIk COS e l k + VkBzk Sin elk)
= -K{[xbq yb3] + [biu 6221 + [bib4 b2b3]}
Making Y;, = (e&+ and multiplying both sides of (8)
@k)
- - -

(19)
by VI
det[D’] * K =- [K&xkl2
or
det[D’] * K S,2
+ 2 y2Bll[ 6 & (GZk Sin efk - Blk COS e l k ) ]
=S i - (20)
- S:

-2 c2GI,[ K & (G,k COS e l k f B,k sin elk)]


Expression (20) is the generalisation of (1 1) for a multinode
system. From (18), the new term s‘, of (20) is
(9) Si = (det[D] - det[D’]) * K (21)
On the other hand, the power injected into bus i may be
written as SI = PI+jQI. From (6) and (7) For a multinode system it may be stated that

S,” =e2+ = K4(G: + B:) + Y2. G 2 .qi Sfis the power injected into bus i at the operating point
under analysis
+ 2 y 2 G , ,K &(Gk cos + Blk sin
OLk 8ik) (10) SI, is the ‘maximum maxirnorum’ power that may be
- 2y2B,,6 &(G,k Sin e l k - Btk COS e l k ) injected into bus i (gven by S,,= V?. Y,,)
Making SI, = Vf . x, and comparing (9) with (lo), finally S, is the power related to the whole system and which
limits the injection into bus i (given by
we obtain
det[D’] * V; = S i - S,’
Si = (detp]-det[D’]* VJ
(11) S, = is the maximum power that could be
This is an important result. The term S$ is a function of the injected into bus i
admittance matrix diagonal element and of the voltage det[D’]*V, is the distance frcpm Sf to S$
magnitude. Supposing constant voltage, and increasing the
load SI,maximum transmission is achieved when is equal 2 Therefore, S,-Sf is the margin between the injected power
to goand therefore det[D’]* V , = 0. and the maximum calculated for that operating point.
For a two-bus system it may be stated that
2.2 Matrix D l determinant sign
SI is the power injected into bus i at the operating point Fig. 1 shows voltage magnitude and angle locus for Pi
under analysis constant, Q, constant and 4, constant where PI is the active
SI, is the maximum power flow that can be transmitted to power flow arriving at a load bus i, Q, is the reactive power
bus i (given by S,, = Vf . Y J . flow and 4, is the power factor angle of the active and
detp’]+ V, is an indicator of the distance from S: to Si. reactive flows. Two voltage solutions are shown: point
A is the upper half of the V < P, Q curve and point B is
The result may be extended to a multinode system. Let [D] the lower half. When load increases, the two solutions
be the matrix of the linear relationships of active and come closer and only one exists at the maximum: point C.
reactive power with voltage magnitude and angle at bus i. The active and reactive power flow gradient vectors are
shown at operating points A, B and C. They may be
written as

VP --
ap, .i 4--
aP,
.j + 0.k
- ae, aK
Let OQ, = 2.i -t 2.j + 0.k
aQ aQ
-[C] * [A-I] * [B] = [:: it] 88,
where i, j and k are the vectors of an orthonormal basis

116 IEE Proc -Gener Trunsm Dwtrib , Vol 149, No 2, Murch 2002
and SI = 1, 'then the margin is nine times the injection. If
S, = 99 and S, = 100, then the margin is around 0.01 of
the amount injected.
The second problem is the relative importance a
buses e.g. for the location of operational control actions or
the installation of new compensation devices. The question
is solved by looking at (S,-SI) (the smaller it is, the worse
the situation) divided by S, (the larger it is, the more
important the bus).
A margin in per unit of S, may be defined, including the
region of operation, for each bus i

Fig. 1 Locution of gradient vectors oj P,and Q, in the V x Bplane


x-axis voltage angle
M=
(I - -):
y-axls: voltage magmtude The critical bus is the one with the smallest margin M.
Therefore, it is straightforward to classify buses according
to their degree of loading.
A sensitivity index (ST)may also be defined for
i to translate the eff'ects of a control action or load
The vectorial product is on the margin

and therefore,
SI = (sign of Po)
E:
-- 1
I
where Mo is the orignal margin and M , is the margin after
VP, x OQ, = det[D'] the control action or load increase. If SI is positive, the
(24)
control action was beneficial to the margin. If SI is negative,
As the control action was detrimental to the margin. Therefore,
OP,x OQ, = IVP,/ * lOQ,l * sin fi (25) the effect of reinforcement actions is easily evaluated: it is
straightforward to compare the network loadability of two
then different operating points.
det[D'] = IVP,I * lOQ,I * sinp (26) Angle translates a measure of transmission difficult.
where p is the angle between V P , and OQ,. The maximum is nearby when it approaches 180" even if the
As the sign of detp'] is a function of sin jonly, then injection is small and the margin large. In that case, a s
increase in SI would cause a substantial reduction in Sn2.
det[D']>O if sinp>O i.e. O"<p< 180" The linearised system model (1) includes local and remote
voltage control mechanisms such as LTCs and variable
det[D']<O if sinp<O i.e. O">p> - 180" reactive power sources. Their inclusion affects the indices
det[D'] = Oif sinp = 0 Le. ,!I= h180" S, and p. Generator reactive production/abso@tion limits
depends on the terminal voltage and active power output.
Taking VP, as the reference axis in Fig. 1, it may be When a limit is reached, a constant voltage behind the
observed that O o < ~ < 1 8 0 0 in the normal region of synchronous reactance models the generator. The location
operation and Oo>p>-lSOo in the abnormal region. At and number of generation buses responsible for supplying
the maximum, the gradient vectors VP, and OQ, are the incremental generation to balance incremental load
aligned and the angle p is _+ 180". Therefore, det[D'] > O change at bus i and losses variation also affect the indices
indicates the upper half of the V x P, Q curve and S, and /3 and therefore, are modelled in (1).
det[D']<O indicates the lower half. Obviously, det[D'] = 0 The value of indices S,wand fi 'jump' whenever voltage
indicates the 'tip of the nose'. It is easy to infer that the control in a nearby bus is lost. There is no index capable of
angle p is also an indicator of the region of operation and of predicting that. However, as the nodal indices SI, and p
the (angular) distance to the maximum. were designed for real-time operation, and the voltage
stability assessment tool is executed periodically say, every
2.3 Interpretation of indices 10min, then the index traclung is retained. All events, which
The value (Slw-SJis the margin between the injected power may lead to 'index jump', are considered as contingencies.
and the maximum calculated for the operating point under These events include reactive power production exhaustion,
analysis. The sign of the angle p is an indicator of the region LTC taps reaching limits, tripping of generators and SVCs.
of operation.
All calculated values are only valid instantaneously 3 Computational aspects
because they are calculated for a specific operating point.
They may become meaningless in the following minute The analysis is to be performed for each bus, for the base-
because of load and generation change, reactive compensa- case and for the contingency cases. Although heuristic rules
tion or LTC tap hits limits, the system behaviour is may be applied to select a set of representative buses of the
nonlinear, etc. Therefore, the analysis is to be performed whole system, and also to select subsets of buses affected by
with caution especially in relation to margins. There is no each contingency, it is imperative that the calculation of
index based on a specific operating point capable of matrix [D'] be extremely efficient.
prediction. Let [Jl be the load flow Jacobian matnx, with dimension
The proposed set of indices solved two classical problems. (2nbus x 2nbus) which may be partitioned into four
The first is the interpretation of index size: Is S,, = 100 large submatrices A, B, C and D as previously shown. (The
or small? Is it large for one bus and small for another? diagonal elements of [Jl,which are the derivatives of the
Looking at SI solves the question. For example, if S, = 10 active equation in relation to the voltage angle of the swing
IEE Proc -Gener T,unrm Dlstrrh , Vol 149 No 2, Mrrrch 2002 177
bus, and the derivatives of the reactive equations in relation Table 1: Network voltage stability assessment results at
to the voltage magnitudes of the voltage controlled buses, 6.00 p.m.
are all substituted by very large numbers).
Matrix @)I' with dimension (2 x 2), is calculated by (4). Bus number and Voltage Si S, M
As 2nbus >>2, all the computational effort consists of name
solving [A] p]= [B] where [XI has the same dimension as
10 ANGRA-lMQ* 1.035 6.85 7.5 178 0.09
PJ
Each system bus analysis requires a new partition of [Jl. 44 GRAJAU-2CSK 0.978 0.35 23.3 -136 -0.98
However, each matrix [A] is exactly as [Jl except that two 48 IBIUNA3CS* 1.039 2.08 67.5 -49 -0.97
rows and columns were taken out. This does not need to be 50 T.PRET0-ICs* 1.000 3.03 11.6 160 0.74
explicitly done, only it is necessary to substitute the two 60 F.IGUACU-765 0.968 639 63.5 41 0.90
diagonal elements by very large numbers. The problem 61 FOZ-500-60HZ 1.024 000 79.6 36 1.oo
summary is
65 IVAIPORA-765 0.990 0 00 46.0 72 1.oo
matrix [Jl dimension (2nbus x 2nbus) is known 66 IVAIPORA-525 0.970 000 48.7 82 1.oo
triangular factors [L] and M are known 67 IVAIPORA-69 1.024 0.00 25.9 85 1.oo
matrix [Jl is (implicitly) modified by the exclusion of two 72 ITABERA-765 0.97 1 6.41 38.8 95 0.83
rows and columns, resulting in matrix [A] 76 T.PRET0-765 0.909 3.00 36.9 134 0.92
solve the modified linear system [A] p]= [B] 77 T.PRET0-500 1.049 0.00 33.5 142 1.oo
78 T.PRET0-345 1.020 6.12 42.5 150 0.86
The problem may be efficiently solved by well known
compensation methods, based on the inverse matrix 79T.PRETO-69 0.896 0.00 18.5 124 1.oo
modification lemma [8]. 86 IBIUNA-345 1.033 80.27 90.0 130 0.1 1
It has been proved [9] that the elements of the inverse of 87 IBIUNA-500 1.067 Ct.00 34.8 130 1.oo
matrix [D'] are triangular factors of [J and to take them 104 C.PAULIS-500 1.021 Cl.00 32.9 160 1.oo
from there only four fast forward substitutions are
105 ANGRA-500 1.028 Cl.00 30.4 157 1.oo
necessary.
It is desirable to assess the reactive power injection into 106 ADRIANO-500 q.999 0.00 27.0 167 1.oo
PV buses. If only incremental reactive power variation is 107 GRAJAU-500 1.005 0.00 26.9 167 1.oo
possible, the critical conditions is to be verified by d e t v ] 108 S.JOSE-500 1.oob 0.00 25.0 166 1.oo
divided by dl,', element of [D']., Each system PV bus 140 ADRIANO-345 0.967 3.14 19.3 165 0.84
analysis requires a new partition of [Jl as before for load 173 ADRIANO-I38 1.023 0.00 12.2 158 1.oo
buses. Each matrix [A] is exactly as [Jl, except that only one
178 GRAJAU-138 0.999 0.00 34.1 169 1.oo
row and column were removed [9].
183 C.PAULIS-I38 0.994 0.00 17.8 144 1.oo
3. I Contingency analysis 185 ANGRA-138 1.032 0.41 5.9 110 0.93
The scheme to avoid the calculation of matrix [D'] for all 1106 ITAIPU60-500 1.026 0.00 83.6 356 1.oo
system buses for every contingency is very simple although 1107 ITAIPUGO-7MQ' 1.030 54.48 72.9 -98 -0.25
efficient: calculate detp'] in the buses directly associated ~~ ~

with the contingency and in the bus layers around the * voltage controlled bus
disturbance until the postcontingency value becomes equal
to the precontingency ones. Tolerances are to be compatible
with those used in power flow calculations [9].
-180". However, in meshed networks, it may be that
4 Network loading assessment SI << S, and there are negative values of 8, far from - 180".
These negative angles appear especially in voltage controlled
The ltaipu bulk transmission network in the SjSE Brazilian buses when voltage control actions have the opposite effect.
system was used for demonstration purposes. The operating Table 1 shows negative angles for PV buses 44 GRAJAU-
point corresponds to 6:OO p.m. minutes before a major 2CS, 48 IBIUNA-3CS, and 1107 ITAIPU60-7MQ. Table 1
bhckout occurred on the 24th April 1997. The active power indicates there was proper koltage control at buses 10
consumption was going to break the record established nine ANGRA-1MQ and 50 T.PRET0-ICs.
days previously. Some reactive power compensation devices The calculation of M provides the most critical buses.
were out-of-service. They are 1107 ITAIPU60-7MQ, 48 IBIUNA-3CS, and 44
Table 1 shows the results for selected buses: the voltage in GRAJAU-2CS with negative values followed by 10
per unit, the injected power S, in per unit of 100 MVA, the ANGRA-1MQ and 86 IBIUNA-345. This order may vary
maximum power which may be injected into bus i S,, in per from one operating point to another.
unit of 100 MVA, the angle /3 in degrees, and the margin A4 Table 2 shows the analysis results for the same system at
in per unit of Snl. At the maximum transmission flow, 3:OO p.m., i.e. three hours previously. It should be noted that
SI = s,,,, p = f180", M = 0. injections S, are smaller than those at 6:OO p.m. except at
At the end of radial lines (not shown in Table 1) SI z S, bus 44 whch has larger reactive generation, bus 185 with a
and p approaches 180". It may also appear in generator larger shunt capacitor, and at bus 1107 with a larger active
buses such the bus 10 ANGRA-1MQ in Table 1. and reactive generation. The margins M in MVA in Table 2
It may happen that SI << S, and p approaches 180". are larger than those in Table 1 for all buses (with SI # 0)
Therefore, the problem is not caused by the nodal injection denoting a stronger operating point.
into that bus but rather by the conditions of the system near Voltage controlled bus 44 GRAJAU-2CS presents
by. That is the case for bus 178 GRAJAU-138 in Table 1. proper voltage control at 3:OO p.m. (p>O) but not at 6:OO
In the case of buses at the end of radial lines (there is no p.m. (p<O). In other words, reactive power generation and
example in Table 1) it may be that S, z S,, and p is around voltage magnitude move in the same direction at 3:OO p.m.

178 IEE Proc.-Gerzer. Trarum. Dbtrib., Vol. 149, No. 2, Murch 2002
Table 2: Network voltage stability assessment results (3:OO p.m.1

Bus number and name Voltage Si srn P M SI


10 ANGRA-1MQ* 1.020 6.06 19.7 107 0.69 -0.87
44 GRAJAU-ZCS* 0.979 0.55 10.1 172 0.95 -0.04
48 IBIUNA-3CS“ 1.021 0.86 13.4 -127 -0.94 -0.04
507.PRETO-1CS* 1.050 2.92 26.2 108 0.89 -0.17
60 F.IGUACU-765 0.964 6.36 69.4 34 0.91 -0.01
61 FOZ-500-60HZ 1.021 0.00 84.1 32 1.oo 0.00
65 IVAIPORA-765 0.987 0.00 57.3 55 1.oo 0.00
66 IVAIPORA-525 1.014 0.00 57.2 64 1.oo 0.00
67 IVAIPORA-69 1.012 0.00 27.1 78 1.oo 0.00
72 ITABERA-765 0.980 6.47 52.3 73 0.87 -0.05
76T.PRETO-765 0.939 3.10 56.6 107 0.95 -0.03
77 T.PRET0-500 1.080 0.00 51.8 115 1.oo 0.00
78T.PRETO-345 1.029 8.23 . 71.1 125 0.88 -0.03
79 T.PRET0-69 0.930 0.00 24.6 102 1.oo 0.00
86 IBIUNA-345 1.042 78.92 104.9 105 0.25 -0.56
87 IBIUNA-500 1.089 0.00 50.5 106 1.oo 0.00
104 C.PAULIS-500 1.062 0.00 54.1 137 1.oo 0.00
105 ANGRA-500 1.061 0.00 46.9 129 1.oo 0.00
106 ADRIANO-500 1.055 0.00 46.0 146 1.oo 0.00
107 GRAJAU-500 1.043 0.00 44.3 145 1.oo 0.00
108 S.JOSE-500 1.054 0.00 41.9 144 1.oo 0.00
140 ADRIANO-345 1.025 3.33 34.2 140 0.90 -0.07
173 ADRIANO-I38 1.046 0.00 21.9 130 1.oo 0.00
178 GRAJAU-138 1.007 0.00 54.1 149 1.oo 0.00
183 C.PAULIS-138 1.044 0.00 25.3 116 1.oo 0.00
185 ANGRA-138 1.025 0.45 7.1 100 0.94 -0.01
1106 ITAIPU60-500 1.023 0.00 87.8 32 1.oo 0.00
1107 ITAIPU60-7MQ* 1.030 56.16 65.5 - 40 -0.14 -0.77

* voltage controlled bus

but in reverse direction at 6:OO p.m. This could have been index SI for the case when bus 50 is PQ in relation to the
the primary cause of the blackout since it has been case when bus 50 is PV. In this table SI is defined as
described as: ‘progressive voltage decay at bus 44, followed
by bus 1107, and the consequent AC/DC inverter trip-off at SI = (sign~fp~~)[(~~Q/~~~)-~]
bus 86 due to abnormal low voltage’. The voltage controlled For all buses, indices SI are negative indicating that the
bus 1107 ITAIPU60-7MQ presents inadequate voltage system with bus 50 PQ is weaker than that with bus 50 PV.
control at 3:OO p.m. and also at 6:OO p.m. (p<O). The operating point is the same in both situations.
Comparing Tables 1 and 2 one would conclude that Table 3 also shows that the relationship between the
conditions for system blackout were already present at 3:OO reactive power and voltage at bus 44 GRAJAU-2CS has
p.m. and deteriorated with load increase. Table 2 shows the moved from the upper half (/?= + 172) to the lower half
sensitivity index SI for 6:OO p.m. in relation to the 3:OO p.m. (p = - 179) of the V x Q curve. Furthermore, the relation-
conditions. For all buses with S, # 0, indices SIare negative ship between the reactive power and voltage at bus 48
indicating that the 6:OO pm operating point is weaker than IBIUNA-3CS has slipped down in the V x Q curve, from
the 3:OO p.m. one. S, = 13.4 and p = -127 to S, = 36.1 and p = -82).
Table 3 shows the effects of the loss of voltage control at Again, these indicate system downfall.
bus 50T.PRETO-1CS on indices S,,, and p. The operating Computational efficiency is adequate for real-time
point is that one of Table 2. Two situations are considered: operation including contingency analysis. The calculation
first, the voltage at bus 50 is controlled, i.e. bus 50 is PV; of the determinant of [D’] for all 1758 buses of the S/SE
and secondly, the voltage at bus 50 is not controlled because Brazilian system took 3.98s on a Pentium I1 300MHz
the synchronous compensator connected to the bus reached microcomputer. Each contingency affected 133 buses on
its limit, Le. bus 50 is PQ. Comparing the values of SLv and average. The time taken to select the affected buses is
SEQa reduction is recognised when the voltage is no longer negligible. The time taken to compute the determinant of
controlled, especially on nearby buses such as 76 T.PRE- [D’] for 133 buses is 0.3 s.
TO-765, 77 T.PRET0-500 and 78 T.PRET0-345. The
reduction of S,, indicates system deterioration. Comparing 5 Conclusions
the values of pPv and ppQ it seen that there is an increase
when the voltage is no longer controlled. The increase also This paper has presented a comprehensive and meaningful
indicates system worsening. Table 3 shows the sensitivity network voltage stability assessment tool suitable for
IEE ProcGener. Trunsm. Distrib.. Vol. 149, No. 2. March 2002 179
Table 3: Network voltage stability assessment results (3:OO p.m.1 with/without voltage control sit bus 50

Bus 50 PV Bus 50 PQ
Bus number and name Voltage Si cv BPV s’,” SI

10 ANGRA-1MQ* 1.020 6.06 19.7 107 18.0 117 -0.09


44 GRAJAU-ZCS” 0.979 0.55 10.1 172 1.8 -179 -0.82
48 IBIUNA-3CSY 1.021 0.86 13.4 -127 36.1 -82 -1.69
50 T.PRET0-1CS** 1.050 2.92 26.2 108 26.2 108 0.00
60 F.IGUACU-765 0.964 6.36 69.4 34 66.2 31 -0.05
61 FOZ-500-60 HZ 1.021 0.00 84.1 32 80.9 29 -0.04
65 IVAIPORA-765 0.987 0.00 57.3 55 52.7 53 -0.08
66 IVAIPORA-525 1.014 0.00 57.2 64 53.7 62 -0.06
67 IVAIPORA-69 1.012 0.00 27.1 78 23.9 75 -0.12
72 ITABERA-765 0.980 6.47 52.3 73 46.9 73 -0.10
76 T.PRET0-765 0.939 3.10 56.6 107 48.8 110 -0.14
77 T.PRET0-500 1.080 0.00 51.8 115 45.6 120 -0.12
78T.PRETO-345 1.029 8.23 71.1 125 57.0 129 -0.20
79 T.PRET0-69 0.930 0.00 24.6 102 23.1 106 -0.06
86 IBIUNA-345 1.042 78.92 104.9 105 99.2 110 -0.05
87 IBIUNA-500 1.089 0.00 50.5 106 46.3 111 -0.08
104 C.PAULIS-500 1.062 0.00 54.1 137 49.2 143 -0.09
105 ANGRA-500 1.061 0.00 46.9 129 44.0 135 -0.06
106 ADRIANO-500 1.055 0.00 46.0 146 42.9 150 -0.07
107 GRAJAU-500 1.043 0.00 44.3 145 41.6 150 -0.06
108 S.JOSE-500 1.054 0.00 41.9 144 39.3 148 -0.06
140 ADRIANO-345 1.025 3.33 34.2 140 32.3 145 -0.05
173 ADRIANO-138 1.046 0.00 21.9 130 20.8 134 -0.05
178 GRAJAU-138 1.007 0.00 54.1 149 51.0 153 -0.06
183 C.PAULIS-138 1.044 0.00 25.3 116 24.0 121 -0.05
185 ANGRA-138 1.025 0.45 7.1 100 6.9 101 -0.03
1106 ITAIPU60-500 1.023 0.00 87.8 32 84.6 29 -0.04
1107 ITAIPUGO-8MQ” 1.030 56.16 65.5 -40 68.5 -56 -0.05

* voltage controlled bus** from PV to PO bus

operational purposes including real-time operation. Active including contingency analysis for real systems such as the
and reactive power flows that can be transmitted from 1758 bus SjSE one.
generators to loads are evaluated. The proposed two nodal Advanced online applications will significantly improve
indices S,,, and p have physical meaning: they indicate the the security and efficiency of the operation of the electric
MVA margin to the maximum and the region of operation. power grid for the benefit of all users.
The size of the margin is correctly interpreted. There is no
problem of scaling, i.e. the relative importance among buses 6 Acknowledgments
is well established. A measure of difficulty in power
transmission is given. Indices are calculated for all buses, This work was carried out under contract 16/98 between
including the generator and compensator buses. Although CEPEL and PUC/Rio. The first and second authors
several popular indices ignore them, results have shown that acknowledge support from the Brazilian Government
Q- I/ relationships must be assessed in PV buses even with Research Agency (CNPq).
reactive power generation reserve. They play a major rule in
meshed network loadability and long term voltage collapse. 7 References
The location of stressed network areas is immediately 1 HIRSCH, P., and LEE, S.: ‘Security applications and architecture for
shown out because the indices are nodal. There is no an open market’, IEEE Comput. Appl. Power, 1999, 12, (3), pp. 26-31
difficulty in classifying buses according to their degree of 2 TAYLOR, C.W.: ‘Power system voltage stability’ (McGraw Hill,
1994)
loading. The effect of reinforcement actions is easily 3 GAO, B., MORISON, G.K., and KUNDUR, P.: ‘Voltage stability
evaluated i.e. it is straightforward to compare the network evaluation using modal analysis’, IEEE Trans.. Power Syst., 1992, 7,
loadability of two different operating points. The adequacy (4), pp. 1529-1542
4 LOF, P.-A,, SMED, T., ANDERSSON, G., and HILL, D.J.: ‘Fast
and applicability of the proposed indices are corroborated calculation of a voltage stability index’, IEEE Trans. Power Syst.,
by the numerical results presented for the Itaipu bulk 1992, 7, (l), pp. 5 + 6 &
transmission network in the S/SE of Brazil immediately 5 CORSI, S., POZZI, M.,, BAZZI, U., MOCENIGO, M., and
MARANNINO. P.: ‘A s m d e and real-tune and on-line voltage
before a voltage stability blackout in April 1997. Computa- stability index under test inLit.dian secondary voltage regulatiol;’.
tional efficiency is no burden for real-time operation CIGRE Biannual Session, Pans, France, 2000, pp. 3&115

180 IEE Proc-Gener. Tramin. Distrib.. Vol. 149, No. 2, March 2002
6 PRADA, R.B., CORY, B.J., and NAVARRO-PEREZ, R.: ‘Assess- 8 ALSAC, 0.. STO‘IT, B., and, TINNEY, W.F.: ‘Sparsity-oriented
ment of steady state voltage collapse critical conditions’. Proceedinys compensahon methods for modified network solutions’, IEEE Tram.
of the 10th power systems computation Conference, Graz, Austria, Power Appar. Syst., 1983, 102, (2), pp. 105&1060
1990, pp. 1189-1 195 9 PRADA, R.B., and DOS SANTOS, J.O.R.: ‘Fast nodal assessment of
7 PRADA, R.B., VIEIRA FILHO, X., GOMES, P., and DOS static stability including contingency analysis’, Electr. Power Syst.
SANTOS, M.G.: ‘Voltage stability system critical area identification Res., 1999, 51, (l), pp. 55-59
based on the existence of maximum power flow transmission’.
Proceedings of the 11th Power systems computation Conference,
Avignon, France, 1993, pp. 315-321

ZEE l’roc.-Gener. Tra”. Divtrib, YuL 149,No. 2,Murch 2002

Anda mungkin juga menyukai