FAULT
• Short circuit produced by failure of insulation.
PROTECTION IS INSTALLED TO :
• Detect fault occurrence and isolate the faulted equipment.
SO THAT :
• Damage to the faulted equipment is limited;
• Disruption of supplies to adjacent equipment is minimized.
• Danger to staff or the public is avoided
Faults Are Mainly Caused By Insulation
Failure
Underground Cables
Diggers
Overloading
Oil Leakage
Ageing
Faults Are Mainly Caused By Insulation
Failure
Overhead Lines
Lightning
Kites
Trees
Moisture
Salt
Birds
Failure of discs
Broken Conductors
Faults Are Mainly Caused By Insulation
Failure
Machines
Mechanical Damage
Unbalanced Load
Types of Fault
a
b
Ø/E
c
a
b
Ø/Ø/E
c
e
a
Ø/Ø b
c
a a
3Ø b b
c 3Ø/E c
e
BREAKER
EQPT / FEEDER
INSTRUMENT
RELAY
TRANSFOR
MERS
BATTERY
Types Of Protection - Principles
51
DC SHUNT
BATTERY TRIP COIL
E/F OC OC OC E/F OC OC
51 A C 51
I2 LOAD
51 B D 51
Relays ‘C’ and ‘D’ see the same fault current (I2). As ‘C’ and
‘D’ have similar settings both feeders will be tripped.
Parallel Feeders
Solution:- Directional Control at ‘C’ and ‘D’
I1 + I2
I1
C
51 A I2 67 LOAD
51 B D 67
VC VB
A
B
C
VRES
Protected object
Relay
Differential Protection Principle (1)
P1 P2 P2
Protected P1
Circuit
S1 S2 S2 S1
P1 P2 Protected P2 P1
Circuit
S2 S1
S1 S2
64
64
64
Restricted Earthfault Protection
P1 S1
P2 S2
External earth fault - Current circulates between the phase & neutral
CTs; no current thro’ the relay
So, No Operation
Restricted Earthfault Protection
For an internal earth fault the unbalanced current flows thro’ the relay
F1
Relaying Relaying
Point Point
R R
Trip A Trip B
Relay at End ‘B’ measures current and transmits the value to Relay
at end ‘A’ thru optical fibre cable. Relay ‘A’ compares measured
value and the value recived from ‘B’.
If both values are same, relay keeps restraint state.
If there is difference in values. Relays operates.
Pilot wire protection
Used for
– EHT cables
– short distance EHT transmission lines
4.Distance
• . Distance
For : Transmission and Sub-Transmission Circuits
Also used as Back-up Protection for Transformers
and Generators
Impedance Relay
jIX
IF zF
IZ
V1
V2
VF V3
IR
Spring
Relay
ZS PT.
IR ZL
Normal
VS VR ZLOAD
Load
VR
Impedance measured ZR = = Z L + Z LOAD
ΙR
The relay is set based on the line impedance.
The measured ZR is more than the relay setting Z ,
hence relay restrains
Basic Principle of Distance Protection
ZL
ZS IR ZF
VS VR ZLOAD Fault
jX
D Z3A
C Z2A
B
Z1A
A
R
Zones of Protection
Time
Z3A Z3C
T3
Z2A Z2C
T2
Z1A Z1C
A Z1B B C D
T2
Z2B
AUTORECLOSING
MAINTAINS STABILITY AND SUPPLY BY FAST
RECLOSING OF THE TRIPPED FEEDER.
CARRIER INTERTRIPS are provided for fast
clearance of faults for entire line.
Distance Relay Applications
• Transmission lines
• Sub transmission line
• Backup protection for generators
Other type of relays used in
substation
1.Under / Over Voltage Relays
Causes
Low frequency
High voltage
Geomagnetic disturbances
Overfluxing Relay
Effects
NO
TRIP
BACK-UP
BREAKERS
10.Low SF6 alarm/lockout
Stage-1 : Alarm
•Alarm stage indicates the inadequate gas
pressure inside CB.
Stage-2 :Lockout.
•Lock out stage blocks the operation of CB. No
tripping or closing will happen then.
11.Control Relays
• Auto-Reclose Relay
Used to auto reclosing of EHT feeders
Temperature
indicator
Sensing device
S1=alarm S2=trip
S4=cooler control 2
S3=cooler control 1
12.2 Pressure Relief Device (PRD)
• When pressure inside transformer exceeds
the PRV will operate to release excessive
pressure inside the transformer.
• It issues a trip command and visual indication
by operation of a liver (from horizontal
position to vertical position)
Spring Operated Pressure relief device
12.3 Buchholtz relay
• Mechanical relay which has two mercury
switches.
• When gas enters the chamber the position of
switches deflects and it will make alarm in
stage-1 and trip in stage-2 in Main tank
Buchholz relay.
• Only trip signal is provided in OLTC buchholz
relay.
Buchholz Relay Installation
3 x internal pipe
Conservator
diameter (minimum)
5 x internal pipe
diameter (minimum)
Oil conservator
3 minimum
Transformer
Buchholtz Relay arrangement.
12.4 MAGNETIC OIL LEVEL
GAUGE (MOLG)
• Mounting 15 0 Inclination.
• The movement of the float is transmitted to
the pointer by using a magnetic coupling.
• The follower magnet follows the driving
magnet.
• The driving magnet remains inside the
conservator and the other magnet out side
the conservator.
1/2
1/4 3/
4
FU
BEARING
PTY
LL
EM
FLOATING MEMBER
MOLG
PERMANENT MAGNET