STEP 3 - AUTONOMOUS MAINTENANCE


TENTATIVE STANDARDS FOR AUTONOMOUS MAINTENANCE
Machine :Hot water Boiler (Diesel Fired ) Make:Thermax Area: Left side
In OFF Condition
SN Action Item Standard Method Resp Freq Time Action if Abnormal

11 Clean Electrical control To be free from dirt,dust Opr Weekly 2min Clean
panel and stain

12 Retighten Terminals in Should not be loose Opr Monthly 1min Retighten the terminals
electrical control
panel

13 Retighten Earth flat Should not be loose Opr Monthly 30sec Retighten the terminals

14 Retighten Terminals of water Should not be loose Opr Monthly 1min Retighten the terminals
circulation pump
Vivanta by Taj Fisherman's Cove - Chennai
STEP 3 - AUTONOMOUS MAINTENANCE
TENTATIVE STANDARDS FOR AUTONOMOUS MAINTENANCE
Machine :Hot water Boiler (Diesel Fired ) Make:Therm
In ON Condition
SN Action Item Standard Method

20 Inspect Fuel pressure Pressure Should be 8 to


10 kg/cm2

21 Inspect Main door- No escape of flue gas


leakage

22 Inspect Blower and should have no


Fuel Pump abnormal noise

23 Inspect Fuel pipeline- Should be free from leak


supply to the
pump

24 Inspect Boilet Inlet Pressure Should be 2 to


pressure 4 kg/cm2
Gauge

25 Inspect Boilet Outlet Pressure Should be 2 to


pressure 3 kg/cm2
Gauge

Vivanta by Taj Fisherman's Cove - Chennai


STEP 3 - AUTONOMOUS MAINTENANCE
TENTATIVE STANDARDS FOR AUTONOMOUS MAINTENANCE
Machine :Hot water Boiler (Diesel Fired ) Make:Therm
In ON Condition
SN Action Item Standard Method
26 Inspect Boiler Inlet should be between 70-
water 75 deg celsius
Temperature
controller
27 Inspect Boiler outlet should be between 90-
waterTemperat 95 deg celsius
ure controller

28 Inspect water Should be free from


circulation abnormal noise
pump

29 Inspect water Should be free from leak


circulation
pump

30 Inspect safety Valve Should be free from leak

Vivanta by Taj Fisherman's Cove - Chennai


STEP 3 - AUTONOMOUS MAINTENANCE
TENTATIVE STANDARDS FOR AUTONOMOUS MAINTENANCE
Machine :Hot water Boiler (Diesel Fired ) Make:Therm
In ON Condition
SN Action Item Standard Method

31 Inspect Flue gas Should be between 90


temperature to 130oc

32 Inspect Exhaust flange Should be free from leak

Vivanta by Taj Fisherman's Cove - Chennai


STEP 3 - AUTONOMOUS MAINTENANCE
TENTATIVE STANDARDS FOR AUTONOMOUS MAINTENANCE
Machine :Hot water Boiler (Diesel Fired ) Make:Therm
In ON Condition
SN Action Item Standard Method

33 Inspect Fuel filter Should be free from leak


NCE
Area : Front Side

Resp Freq Time Action if Abnormal

Opr Daily 3sec Check the fuel pump

Opr Daily 3min Replace the rope

Opr Daily 30sec Replace the bearing

Opr Daily 30sec If leaks are observed,find


out the point of leakage
and arrest immediately

Opr Daily 3sec Check the water circulation


pump

Opr Daily 3sec Check the water circulation


pump

NCE
Area: Left side

Resp Freq Time Action if Abnormal


Opr Daily 5 sec Set the temperature
Opr Daily 5 sec Set the temperature

Opr Daily 10sec If noisy, retight the base


bolts and nuts and replace
the bearings

Opr Daily 60sec If leaks are


observed,replace the seal

Opr Daily 60sec If leaks are


observed,replace the
safety Valve

NCE
Area: Rear side

Resp Freq Time Action if Abnormal

Opr Daily 5 sec Adjust damper setting


accordingly

Opr Daily 10sec If leaks are observed,find


out the point of leakage
and arrest

NCE
Area: Right side
Resp Freq Time Action if Abnormal

Opr Daily 10sec replace the gaskets