MATAK JETTY REPAIR

Contract No.: BF10562


IDC Number: SE-MATAK-MEDCO-T-00096
Interdiscipline Check Form
Accountable Person: Era Islami
Status
Document Number Rev Status Title
Received

ID-F-MA-CC0-PRT-JY-00-0001 0B IFA Soil Investigation Report

Responsible Person to advice by marking the action code column "R,A,C,I"


ACTION
NAME TITLE DATE IN DUE DATE INITIAL
CODE
PROJECT TEAM
Agus Ibrahim (Project Manager) 26/01/18 30/01/18 I
Awan Umbaran (Lead Engineering & Project Control ) 26/01/18 30/01/18 R
Era Islami (Team Lead Civil Structure Engineer) 26/01/18 30/01/18 A
Bela Arrosyid ( Civil Engineer ) 26/01/18 30/01/18 C
Jones Saragih ( Construction Supt ) 26/01/18 30/01/18 C
Dody Lesmana ( Tm Lead Operability Assurance ) 26/01/18 30/01/18 C
Irvansyah ( Project QA/QC Inspector ) 26/01/18 30/01/18 C

ACTION CODES:
( R ): Responsible – to approve (A ):Accountable – to consolidate ( C ):Consulted – to review ( I ) : Information

NOTES:
Review/Approval from Company does not constitute acceptance of design details, calculations, test methods or materials
developed or selected by Supplier/Contractor nor does relieve Supplier/Contractor from full compliance with contractual or
other obligations
DOCUMENT REVIEW STATUS SIGNATURE (RESPONSIBLE
1 Not Approved. Revise and Re-Issue Incorporating Comments PERSON):

1 Returned without Comments 1 Approved with Comments


1 Returned with Comments 1 Approved without Comments
Next Issue as follows:

X for Approval for Construction for Purchase for Use


1 for Bid for Design Others
1 Approved:
1 for Use for Construction for Purchase
1 for Bid for Design Others

COMMENTS:

PLEASE RETURN THE DOCUMENT TO RESPONSIBLE PERSON BY : 30-Jan-18


ENGINEERING, PROCUREMENT, CONSTRUCTION (EPC)
MATAK JETTY REPAIR PROJECT

DOCUMENT TRANSMITTAL

To : Medco E&P Natuna Ltd. Date : January 24, 2018


Ratu Prabu 2 Building, 1st, 6th-9th Floor Transmittal No. : SE-MATAK-MEDCO-T-00096
Jl. TB Simatupang Kav. 1B Job / Inquiry No. : BF10562
Jakarta 12560 - Indonesia

Attn : Mr. Awan Umbaran


Mrs. Dewi R. Prabandani
Mr. Yogas Ismanto

From : Mrs. Rurita Sari Copy to : Document Control


Document Control

The following Prints X Originals (Orig.) Reproducible copies (R)


are transmitted herewith for your
Review X Information Record

X Approval Reference Construction


as per your request of
The documents are :
Preliminary Final X Revision

No. of
No. Doc./Drawings No. Rev. Status Document Title
Copies

1 1 set ID-F-MA-CC0-PRT-JY-00-0001 0B IFA Soil Investigation Report


Detail Connection Calculation Clamp of Bored Pile to
2 1 set ID-F-MA-CC0-CAL-JY-00-0004 0B IFA
Frame

Receipt acknowledge PT. Shaftindo Energi

Rurita Sari
By Rurita Sari
Signature Date 24-Jan-2018 Document Controller

Remarks :
Please acknowledge the receipt and return the original

Page 1 of 1
Project Report ID-F-MA-CC0-PRT-JY-00-0001_R0B
Soil Investigation
Medco E&P Natuna Ltd. Page 2 of 26

Revision Sheet

REVISION DATE DESCRIPTION OF CHANGE

0A 08 Nov 17 Issued for Comment

0B 22 Jan 18 Issued for Approval

Additional Approvers (If Applicable)

Name Designation Signature Date


Project Report ID-F-MA-CC0-PRT-JY-00-0001_R0B
Soil Investigation
Medco E&P Natuna Ltd. Page 3 of 26

Contents
Contents ....................................................................................................................................................... 3
List of Figures ............................................................................................................................................. 3
List of Tables ............................................................................................................................................... 3
1 INTRODUCTION ...................................................................................................................... 4
1.1 Project Overview ....................................................................................................................... 4
1.2 Terminology .............................................................................................................................. 4
1.3 Objective of Soil Investigation................................................................................................... 4
1.4 Scope of Soil Investigation Work .............................................................................................. 4
1.5 Project Location ........................................................................................................................ 5
1.6 Terms and Abbreviation ............................................................................................................ 5
1.7 Codes, Standards, and References.......................................................................................... 6
1.8 Units .......................................................................................................................................... 6
2 Investigation Methodology .................................................................................................... 6
2.1 Geotechnical Drilling ................................................................................................................. 6
2.2 Standard Penetration Test (SPT) ............................................................................................. 6
2.3 Laboratory Testing .................................................................................................................... 8
3 SOIL INVESTIGATION RESULTS........................................................................................... 8
3.1 Subsurface condition based on soil investigation results ......................................................... 8
3.2 Laboratory Test Result ............................................................................................................. 9
4 DESIGN SOIL PARAMETER ................................................................................................. 10
4.1 Soil Parameter ........................................................................................................................ 10
5 PILE CAPACITY OF BORED PILE ....................................................................................... 17
5.1 Axial Capacity ......................................................................................................................... 17
5.2 Lateral Capacity ...................................................................................................................... 18
6 CLOSURE AND LIMITATION ................................................................................................ 20

List of Figures
Figure 1 Location of Matak Jetty ................................................................................................................... 5
Figure 2 Borehole Location Relative to Jetty Refurbishment Plan ............................................................... 7
Figure 3 Drilling Activity and Core Box depth 0.0 – 5.0 m of BH-01 ............................................................. 8
Figure 4 Drilling Activity and Core Box depth 25.0 – 30.0 m of BH-03 ......................................................... 9
Figure 5 Distribution of Unit Weight ............................................................................................................ 12
Figure 6 Distribution of Effective Stress Parameters (Geotechnical Drilling) ............................................. 13
Figure 7 Distribution of Total Stress Parameters (Geotechnical Drilling) ................................................... 14
Figure 8 Distribution of Soil Modulus .......................................................................................................... 15
Figure 9 Soil Profile at Matak Jetty ............................................................................................................. 16
Figure 10 Load-Transfer Mechanism: a) Axial Compressive Loads; b) Axial Tension Loads; c) Lateral
Loads ................................................................................................................................................... 17
Figure 11 Axial Pile Capacity of Bored Pile (OD 1000m) ........................................................................... 19
Figure 12 Lateral Pile Capacity of Bored Pile (Free Head) ......................................................................... 20
Figure 13 Lateral Pile Capacity of Bored Pile (Fixed Head) ....................................................................... 20

List of Tables
Table 1 Summary Laboratory Test Result .................................................................................................... 9
Table 2 Design Soil Parameter for BH-01 and BH-03 ................................................................................ 11
Table 3 Summary of Bored Pile Axial Capacity .......................................................................................... 18
Table 4 Structural Properties of Existing Bored Pile ................................................................................... 18
Table 5 Summary of Lateral Pile Capacity of Bored Pile ............................................................................ 18

Appendix
Appendix A Boreholo Location
Appendix B Soil Profile
Appendix C Borelog
Appendix D Soil Laboratory Test Result
Appendix E Field Work Documentation
Project Report ID-F-MA-CC0-PRT-JY-00-0001_R0B
Soil Investigation
Medco E&P Natuna Ltd. Page 4 of 26

1 INTRODUCTION
1.1 Project Overview
Medco Energy (COMPANY) operates a jetty at Matak Island in the South China Sea, which
are used by general cargo vessels berthing at the Natuna Logistics Base. The Main Jetty
was constructed in 1993 and consists of a tied back sheet pile wall with a steel plate coping,
also a piled fender system connected to and braced back to the face of sheet pile wall. The
jetty loads behind the coping are carried by a concrete deck supported on bored concrete
piles, the deck and piles are independent from the sheet pile jetty wall.

Currently, the dock is still operating and Medco energy (COMPANY) is planning to add dock
capacity that can accommodate 3,500 DWT vessel (max). Therefore Medco energy
(COMPANY) asked Zekon Indonesia (SUBCONTRACTOR) for review whether the element
elements can endure of design load or not.

The soil investigation is carried out to determine soil strength parameter for design review.
Two (2) boreholes have been successfully completed and a borehole was terminated due to
a operational reason for approval from COMPANY. Each completed borehole is located as
follow:

Coordinate (UTM ZONE : 48 N)


BOREHOLE ID
Easting Northing
BH-01 640060 mE 370195 mN
BH-03 640057 mE 370293 mN

1.2 Terminology
In this document, the following words and terms shall have the meanings hereby assigned to
them, unless noted otherwise.
COMPANY : Medco Energy (MEDCO) or CLIENT, as the ultimate user and owner or
the authorized representative of COMPANY.
CONTRACTOR : PT. Shaftindo Energi
SUB CONTRACTOR : PT. Zekon Indonesia

1.3 Objective of Soil Investigation


The objective of Soil Investigation Work includes:
(a) Characterization of the soil conditions encountered
(b) Characterization soil/rock parameters for each soil/rock stratum;

(c) Geotechnical assessment and recommendations regarding but not limited to foundation
and settlement analysis.

1.4 Scope of Soil Investigation Work


Summary of soil investigation works are listed below:
1. Field Work
a. Geotechnical drilling of three (3) boreholes to depth of 30 meters and perform
SPT tests at 1.50 meter intervals in natural soils.
b. If possible, collect nine (9) undisturbed (UDS) sample at appropriate intervals for
laboratory tests.
2. Laboratory Work
a. Index Properties
Project Report ID-F-MA-CC0-PRT-JY-00-0001_R0B
Soil Investigation
Medco E&P Natuna Ltd. Page 5 of 26

b. Strength Properties
3. Perform Geotechnical Assessment and Recommendation
4. Provide Soil Investigation Report

1.5 Project Location


The jetty is located at Matak Island, part of Anambas Island, Riau, Indonesia. The location is
shown in Figure 1 below.

Figure 1 Location of Matak Jetty

1.6 Terms and Abbreviation


The following abbreviations have been used where applicable throughout this document. All
other abbreviations will in the first occurrence include a full description.

ASTM D American Society for Testing and Material Designation


BH Borehole Identification
C Cohesion of Soil
e Void Ratio of Soil
Eundrained Undrained Modulus Elasticity of Soil
Edrained Drained Modulus Elasticity of Soil
 Internal Friction Angle of Soil
Gs Specific Gravity of Soil
m Moist Unit Weight of Soil
dry Dry Unit Weight of Soil
Saturated Saturated Unit Weight of Soil
' Effective Unit Weight of Soil
n Porosity of Soil
N-SPT Number of Standard Penetration Test
N1(60) Corrected Number of Standard Penetration Test
Project Report ID-F-MA-CC0-PRT-JY-00-0001_R0B
Soil Investigation
Medco E&P Natuna Ltd. Page 6 of 26

PI Plasticity Index
SPT Standard Penetration Test
Sr Degree of Saturation of Soil
UDS Undisturbed Sample
Wn Natural Water (Moisture) Content of Soil
WL Liquid Limit of Soil
WP Plastic Limit of Soil

1.7 Codes, Standards, and References


International Codes and Standards

[1.] American Society of Testing Material


[2.] British Standards. (1999). Code of Practice for Site Investigations. BSI 2007.
[3.] Federal Highway Administration. (1997). Subsurface Investigations. US Department
of Transportation.

Handbooks

[1.] Bowles, J.E. (1996). Foundation Analysis and Design, 5th Edition, McGraw Hill.
[2.] Coduto, D.P. (2001). Foundation Design-Principles and Practices, 2nd Edition,
Prentice Hall.
[3.] Das, B.M. (2011). Principles of Foundation Engineering, 7th Edition, Cengage
Learning.
[4.] Look, Burt G. (2007). Handbook of Geotechnical Investigation and Design Tables,
published by Taylor & Francis Group.

1.8 Units
All units are in SI (Système international d'unités), unless noted otherwise.

2 Investigation Methodology
2.1 Geotechnical Drilling
The drilling is performed with Modified TOHO-1 rotary drilling machine with tag equipment
SDK-03. Deep boring was done according to American Standard Testing Method (ASTM)
D1452, ASTM D 420, ASTM 2488. Full coring method was conducted.

2.2 Standard Penetration Test (SPT)


The standard penetration tests (SPT) were performed to determine the relative density or
consistency of subsoil and to obtain soil samples for a visual description. SPT were carried
out using automatic drop system hammers. The sampler tube used for SPT test is a Split
Spoon Sampler with an external diameter of 2” (5.08 cm), the internal diameter of 1 3/8” (3.49
cm), and length of 24” (60.96 cm). This sampler is driven by a hammer weighing 140 lbs.
(63.5 kg). To pull the hammer, a manila rope or equivalent is used to raise the hammer before
it falls freely onto the anvil and drive the sampler. The sampler is driven 18” (45.72 cm) and
the number of blows (to drive the last 12” (30.48 cm)) is called N-SPT value with a unit of
blow/feet. The SPT tube is then lifted, the split spoon is opened and the sample is put into a
plastic bag and labelled.
SPT is usually performed following the collection of the undisturbed sample. The procedure
for SPT was in general conformance with standard test method ASTM D1586 Penetration
Test and Split-Barrel Sampling of Soils. SPT samples were also collected and secured with a
plastic bag and placed in the wooden boxes together with the core samples.
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 7 of 26

Figure 2 Borehole Location Relative to Jetty Refurbishment Plan


New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 8 of 26

2.3 Laboratory Testing


Laboratory tests were performed using standard equipment and methods to determine the
index properties, engineering properties, and chemical properties. The following are soil tests
are expected to be performed in Soil Mechanics Laboratory :
1. Natural Water (Natural Water Content); this test was intended to determine the water
content of soil samples. Implementation of this test was based on to the standard
procedure ASTM D 2216
2. Specific Gravity; this test aimed to determine the soil density. The standard procedure
used was ASTM D 854
3. Density Test; the purpose of this test was to determine the density of soil samples in
the original condition (bulk) and dry conditions (dry). This test was done based on the
standard procedure ASTM D 4254
4. Grain Size Analysis; this test was conducted to determine the gradation/particle size
distribution. The standard procedure used was ASTM D 421 & 422
5. Atterberg Limits; this test was intended to study the response of soil to water content.
Atterberg Limits covers the liquid limit, plastic limit and plasticity index of soil. This test
based on the standard procedure ASTM D 4318
6. Direct Shear Test; this test is performed to determine the soil strength parameter
especially for granular material. This test standard procedure used was ASTM D3080.

3 SOIL INVESTIGATION RESULTS


3.1 Subsurface condition based on soil investigation results
 BH-1
Below the ground surface, the Fill Material consists of GRAVEL with sand with medium
brown colour is appeared with 3.0 m thickness and has compactness of medium dense.
Below the first layer, the Fill material mixture of CORAL and medium-grained sand mixture
with Granite has appeared. The thickness of the second layer is about 8.0 m. CORAL and
followed by fine-grained SAND with medium dense compactness is appeared on the third
and fourth layer. The colour of third and fourth layer is white to grey. These layers
appeared until 15 m depth of drilling. The fifth and sixth layers are Sandy SILT with light
grey to medium brown colour. The compactness of the layers is Loose and appeared until
28.5 m depth of drilling. Very Dense SAND with a trace of Coral is encountered on the final
depth of borehole from 28.5 m to 30.0 m depth of drilling.

Figure 3 Drilling Activity and Core Box depth 0.0 – 5.0 m of BH-01
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 9 of 26

 BH-3
Below the concrete deck, the Fill Material (Silty SAND with GRAVEL has a brown colour)
was encountered. The Fill material has very loose to loose density with SPT value around
10. The thickness of Fill material is 5.0 m. Below the Fill Material is CORAL with Clayey
SAND and trace of ROCK (Granite) was encountered. The CORAL a has grey colour. The
density of the CORAL is mostly Very Loose with some lenses of Very Dense CORAL. The
thickness of CORAL is about 10 m. Beneath the CORAL layer, Sandy SILT with very soft
consistency appeared with 10 m thickness. At the end of drilling, the Sandy GRAVEL with
Very Dense densities has appeared.

Figure 4 Drilling Activity and Core Box depth 25.0 – 30.0 m of BH-03

3.2 Laboratory Test Result


In addition, controlling soil parameters that have been correlated with field exploration data,
all UDS samples and SPT samples are also tested in geotechnical laboratory to supply
additional soil parameters. The testing in laboratory consists of index properties and strength
properties.

The table below is the summary result of the laboratory test for BH-03. The laboratory test on
BH-01 is still in progress:
Table 1 Summary Laboratory Test Result
Sample Index Properties
Hole
No Depth m d Void Ratio Porosity Sr
ID Wn (%) Gs
(m) (gr/cm3) (gr/cm3) (e) (n) (%)
1 BH-03 3.00 – 3.45 21.33 1.59 1.31 1.1 0.52 53.51 2.754
2 BH-03 4.50 – 4.95 18.93 1.63 1.37 0.97 0.49 52.89 2.704
3 BH-03 7.50 – 7.95 17.36 1.7 1.44 0.91 0.48 52.61 2.76
4 BH-03 9.00 – 9.45 21.73 1.62 1.33 1.08 0.52 55.63 2.769
5 BH-03 22.50 – 22.95 20.67 1.73 1.43 0.87 0.47 63.52 2.687
6 BH-03 25.50 – 25.95 32.51 1.75 1.32 1.03 0.51 84.81 2.677
7 BH-03 27.00 – 27.45 12.76 1.88 1.67 0.62 0.38 55.48 2.715
8 BH-03 28.50 – 28.95 28.1 1.63 1.28 1.11 0.53 68.21 2.69
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 10 of 26

Atterberg Limit Particle Size Distribution


Hole Sample USCS Finest
No WL WP PI GRAVEL SAND SILT CLAY
ID Depth (m) Class. Content
(%) (%) (%) (%) (%) (%) (%)
(%)
1 BH-03 3.00 – 3.45 SM - - - 26.42 41.55 17.47 14.06 32.03
2 BH-03 4.50 – 4.95 SM - - - 2.54 62.38 14.05 20.53 35.08
3 BH-03 7.50 – 7.95 SC - - - 10.27 53.83 12.98 22.41 35.9
4 BH-03 9.00 – 9.45 SC - - - 19.28 57.26 10.99 11.96 23.46
5 BH-03 22.50 – 22.95 CL - - - 0.41 43.84 35.72 19.53 55.75
6 BH-03 25.50 – 25.95 CL 41.25 22.68 18.6 0 36.46 30.66 32.39 63.54
7 BH-03 27.00 – 27.45 SC - - - 9.07 59.43 14.89 16.1 31.49
8 BH-03 28.50 – 28.95 SC - - - 3.19 65.5 10.47 20.34 31.31

Sample Depth Direct Shear


No Hole ID
(m) c (kg/cm )
2
 ()
1 BH-03 3.00 – 3.45 0.029 34.99
2 BH-03 4.50 – 4.95 0.057 31.99
3 BH-03 7.50 – 7.95 0.063 32.73
4 BH-03 9.00 – 9.45 0.034 34.24
5 BH-03 22.50 – 22.95 0.052 28.20
6 BH-03 25.50 – 25.95 0.076 23.80
7 BH-03 27.00 – 27.45 0.045 33.71
8 BH-03 28.50 – 28.95 0.045 33.71

4 DESIGN SOIL PARAMETER


4.1 Soil Parameter
This chapter presents values of engineering properties for types of soil encountered in field.
The scope of this chapter is limited to correlations with soil classification tests, index
properties, and Standard Penetration N-values. Interested readers are encouraged to refer to
works by Kulhawy and Mayne (1990), Carter and Bentley (1991) which present a a
comprehensive compilation of correlations. Other references of comprehensive compilation of
correlations could be seen in FHWA-HI-97-021 (Training Course in Geotechnical and
Foundation Engineering Subsurface Investigations - Participants Manual).

It must be emphasized that calculations based on correlation can never be substituted for
proper testing. In general, all correlations must be considered approximate since various
factors such as sensitivity, stress history, and ageing can significantly influence soil
properties. Soil parameters will consist of total stress parameters, effective stress
parameters, modulus of elasticity and unit weight.

The summary of correlated soil parameters with field exploration data will be presented in
tables and charts. The table shows the typical value of soil parameter whilst charts present
the soil parameter value distribution according to soil type and depth of exploration.
Tables and charts of soil parameters from each point of field exploration are viewed as follow.
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 11 of 26

Table 2 Design Soil Parameter for BH-01 and BH-03


BH-01
Depth (m) Unit Weight Total Stress Effective Stress Modulus of Elasticity
Soil Layer Seabed (N1)60  ' Eundrained Edrained
sat (kN/m3)  ' (kN/m3)  c (kN/m2) c' (kN/m2)
From To ( °)  ( °)  (kN/m2) (kN/m2)

GRAVEL with SAND 0.00 3.00 9.8 18.6 8.6 - - - 30.9 11700 11700
CORAL with SAND 3.00 7.95 31.1 19.6 9.6 - - - 39.5 37350 37350
CORAL with SAND 7.95 9.45 25.5 19.6 9.6 - - - 37.7 30600 30600
SAND 9.45 15.00 21.1 19.6 9.6 - - - 36.0 25269 25269
Sandy SILT 15.00 28.50 4.3 18.1 8.1 - - - 26.9 5152 5152
SAND trace of CORAL 28.50 30.00 23.1 19.6 9.6 - - - 36.8 27672 27672

BH-03
Depth (m) Unit Weight Total Stress Effective Stress Modulus of Elasticity
Soil Layer Seabed (N1)60 sat  ' Eundrained Edrained
' (kN/m3)  c (kN/m2) c' (kN/m2)
From To (kN/m3)  ( °) ( °)  (kN/m2) (kN/m2)
Silty SAND with
0.00 5.00
GRAVEL 6.8 18.3 8.3 - - - 29.1 8100 8100
CORAL with Clayey
5.00 7.50
SAND 6.0 18.2 8.2 - - - 28.6 7200 7200
CORAL with Clayey
7.50 11.00
SAND 29.3 19.6 9.6 - - - 38.7 35100 35100
CORAL with Clayey
11.00 15.00
SAND 2.0 17.7 7.7 - - - 25.0 2454 2454
Sandy SILT with
15.00 19.00
CORAL 6.0 18.2 8.2 36.0 - 17.3 14.7 7200 6480
Sandy SILT with
19.00 25.00
CORAL 1.5 17.6 7.6 9.0 - 4.0 9.0 1800 1620
Sandy CLAY trace of
25.00 27.00
CORAL 12.0 18.9 8.9 72.0 - 36.0 23.0 14400 12960
Clayey SAND 27.00 30.00 23.3 19.6 9.6 - - - 36.9 27918 27918
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 12 of 26

Figure 5 Distribution of Unit Weight


New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 13 of 26

Figure 6 Distribution of Effective Stress Parameters (Geotechnical Drilling)


New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 14 of 26

Figure 7 Distribution of Total Stress Parameters (Geotechnical Drilling)


New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 15 of 26

Figure 8 Distribution of Soil Modulus


New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 16 of 26

Figure 9 Soil Profile at Matak Jetty


New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 17 of 21

5 PILE CAPACITY OF BORED PILE


In general, the ultimate axial capacity of deep foundation(e.g. bored pile or driven pile) can be
obtained as the summation of tip resistance plus skin friction resistance. In practice, the
calculation of deep foundation capacity will be referring to Meyerhof (1976) when dealing with
the driven pile and O’Neill & Reese (1999) while dealing with the bored pile. The load-transfer
mechanisms depend on the type of load being imposed, so it is convenient to divide
structural loads into 2 (two) categories:
1. Axial loads
Applied tensile or compressive loads that act parallel to the axis of the foundation. These
loads induce either tension or compression in the foundation, but no flexure. If the foundation
is vertical, then the axial load is equal to the vertically applied load.’

2. Lateral loads
Those that act perpendicular to the axis of the foundation. This category includes shear and
moment loads.

Figure 10 Load-Transfer Mechanism: a) Axial Compressive Loads; b) Axial Tension Loads;


c) Lateral Loads
Allowable axial capacity has been calculated referring to Engineering Manual (EM 1110-1-
1904) with a minimum factor of safety of about 3.0 while the allowable pullout capacity has
been calculated with a minimum factor of safety of about 3.0.
Existing bored pile has Diameter 1.0 m and 30 m. The capacities of existing bored pile have
been calculated with the current soil investigation.

5.1 Axial Capacity


In general, the ultimate axial capacity of pile foundation can be obtained by a simple equation
as the sum of the end bearing capacity plus the skin friction resistance, or:
Qu = Qb + Qf = qb Ab + fs As
where,
Qu = Ultimate axial capacity /ultimate load applied on the top of pile
qb = Ultimate bearing capacity of the pile at the base
Ab = Bearing area of the base of the pile
As = Total surface area of pile embedded below ground surface
fs = Unit skin friction (ultimate)
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 18 of 21

In this analysis, 1000 mm of diameter is used for calculating bored pile bearing capacity. The
allowable bearing capacities of the bored pile for each borehole references are given in the
following table, and also presented graphically in Figure 11.

Table 3 Summary of Bored Pile Axial Capacity


Allowable
Allowable
Bore Pile Length Axial Safety
Axial Pull
Hole ID (m) Compression Factor, SF
Out (kN)
(kN)
BH-01 30 1424 1259 3
BH-03 30 1204 1109 3

5.2 Lateral Capacity


The lateral capacity analyses are performed using the p-y method and the computer program
LPILE 5.0 with employs a finite difference formulation to solve the differential equations with
non-linear p-y curves to model the soil. LPILE 5.0 allows computation of the pile response
with user-specified non-linear pile flexural stiffness, EpIp.

The program contains default p-y curves that can be used for different types of soils. As an
alternative, the program also allows the user to input p-y curves developed using other
formulations. In the analyses, the piles were discretized into 100 elements.

Limitation of lateral deflection of a deep foundation shall be divided into two (2) categories in
order to determine its lateral capacity. We suggest limiting the deflection of 0.25 in for static
condition and 0.5 in for seismic condition.

Pile properties used in the analysis are presented below:


Table 4 Structural Properties of Existing Bored Pile
Pile Properties Ø-1000
Diameter (m) 1.0
4
Inertia (m ) 0.04909
2
Area (m ) 0.784
6
Modulus Elasiticity (kPa) 3.0 x 10
Pile Length (m) 30.0

A series of p-y analyses were carried out using the default p-y curves embedded in the
LPILE program for different types of soils. The default p-y curves recommended by Reese
and Matlock were selected the model of these soils.

The lateral capacities of the concrete bored pile on the free head and fixed are given in the
following table and also presented graphically in the next Figure 12 and Figure 13.
Table 5 Summary of Lateral Pile Capacity of Bored Pile

Pile Lateral Pile Max.


Bore Hole Pile Head Capacity (kN)
Length Moment
ID Condition
(m) (kN.m)
Static Dynamic
BH-01 30 140 220 469
Fixed Head
BH-03 30 87 165 365
BH-01 30 94 135 227
Free Head
BH-03 30 53 104 163
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 19 of 21

Figure 11 Axial Pile Capacity of Bored Pile (OD 1000m)


New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 20 of 21

Figure 12 Lateral Pile Capacity of Bored Pile (Free Head)

Figure 13 Lateral Pile Capacity of Bored Pile (Fixed Head)

6 CLOSURE AND LIMITATION


The recommendations presented in this report are based on our current understanding of the
site conditions. The nature of subsurface conditions may vary between tested locations and
from the assumptions discussed. Variations between the tested locations may not become
evident until construction. The owner’s geotechnical engineer on site should observe the
exposed subsurface during construction. If the subsurface conditions encountered during
construction differ from those encountered by the site investigation, Zekon Indonesia should
be notified so that we might review our recommendations in light of such changes and
provide a written modification or verification of changes.
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy Page 21 of 21

Unanticipated soil conditions are commonly encountered that cannot fully be determined by a
limited number of explorations or soil samples. Such unexpected conditions frequently result
in additional project cost in order to build the project as designed. Therefore, a contingency
for unanticipated conditions should be included in the construction budget and schedule.
Our professional services have been performed, our findings derived, and our
recommendations prepared in accordance with generally accepted geotechnical engineering
principles and standards. Zekon Indonesia is not responsible for the conclusions, opinions,
or recommendations of others based on this data.
Our investigation did not include any assessment or evaluation of environmental conditions or
contamination in the soil.
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy

APPENDIX A
Borehole location Layout
BORE HOLES COORDINATES
UTM : ZONE 48 N
Easting Northing
BH-01 640060 370195
BH-03 640057 370293

BH-03

BH-01

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41

CLIENT CONSULTANT REV. DESCRIPTION INTS. DATE PROJECT


MATAK JETTY REPAIR PROJECT
A - -
DRAWN DATE DRAWING CHECKED DATE STATUS DRAWING TITLE

MEDCO ENERGI B - - -
DESIGNED
- -
DATE APPROVAL
-
DATE
FOR
BORE HOLES LOCATION
C - - REVIEW PLAN
Oil & Gas ZEKON D - -
-
SHEET
- -
TOTAL SHEET
-
SCALE PRINT REVISION DRAWING NO.
DESIGN & BUILD E - - 01 00 1 : 1 (A3) 00 -
NO PART OF THIS DOCUMENT MAY BE REPRODUCED, TRANSMITTED OR RECORDED
FOR THE PURPOSE OF OTHER THAN THIS PROJECT IN ANY FORM OR OTHERWISE
WITHOUT PRIOR WRITTEN PERMISSION OF PT. ZEKON INDONESIA
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy

APPENDIX B
Soil Profile
LEGEND

Fill Material (Silty SAND


with Gravel)

CORAL with Clayey


Sand and Granite

Sandy SILT with Coral

Clayey SAND

BH-01 BH-03
0.00 +0.000
Deck with Thickness Slab : 0.4 m 0.00 +0.000

10.00 10.00

20.00 20.00

30.00 30.00

0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00 45.00 50.00 55.00 60.00 65.00 70.00 75.00 80.00 85.00 90.00 95.00 100.00

SECTION A
SCALE 1 : 300 -

CLIENT CONSULTANT REV. DESCRIPTION INTS. DATE PROJECT


MATAK JETTY REPAIR PROJECT
A - -
DRAWN DATE DRAWING CHECKED DATE STATUS DRAWING TITLE

MEDCO ENERGI B - - -
DESIGNED
- -
DATE APPROVAL
-
DATE
FOR SOIL PROFILE
C - - REVIEW
Oil & Gas ZEKON D - -
-
SHEET
- -
TOTAL SHEET
-
SCALE PRINT REVISION DRAWING NO.
DESIGN & BUILD E - - 01 00 1 : 1 (A3) 00 -
NO PART OF THIS DOCUMENT MAY BE REPRODUCED, TRANSMITTED OR RECORDED
FOR THE PURPOSE OF OTHER THAN THIS PROJECT IN ANY FORM OR OTHERWISE
WITHOUT PRIOR WRITTEN PERMISSION OF PT. ZEKON INDONESIA
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy

APPENDIX C
Borelogs
GEOTECHNICAL LOG HOLE ID

ZEKON
GEOTECHNICAL INVESTIGATION SERVICES BH-01
DESIGN & BUILD MATAK JETTY REPAIR PROJECT
Client : PT. MEDCO ENERGI System Zone : WGS 84; Zone 48N Drilled by : WM
Project : Soil Investigation Matak Jetty Integrity Surface RL : Logged by : DT
Location : Matak, Riau Islands Inclination : 90° Rig / Hammer Type : TOHO-01
Easting : 640060 m Scale : at scale Date Commence : December 19th, 2017
Northing : 370195 m Total Depth : 30.00 m (0.00-20.00 m) Date Complete : December 26th, 2017
DRILLING SAMPLING FIELD MATERIAL DESCRIPTION

CONSISTENCY /
USCS Symbol
RECOVERED

INDEX PROPERTIES STRENGTH PROPERTIES


(metres)

REL. DENSITY
MOISTURE
METHOD

GRAPHIC
(metres)

RQD (%)
SAMPLE

SAMPLE TYPE / TUU TCU DST CONS.

CONTENT, %

( gdry , kN/m3 )
N-SPT Value
GWL

SOIL / ROCK MATERIAL DESCRIPTION

PLASTICITY
DEPTH

DEPTH

gsat , kN/m3
(MSL)

p c , kg/cm²
FIELD TESTED

INDEX, %

( f' , deg )
( f , deg )

( f , deg )

( f , deg )
LOG

FINEST

c , kPa

c', kPa
c , kPa
RL

RL

(C r )
0 10 20 30 40 50 60 70 80

Cc
Fill Material (GRAVEL with SAND), medium brown. W MD
Will Updated after Laboratory Test has been Completed

Will Updated after Laboratory Test has been Completed

SPT 1.50-1.95m
5,3,10 N=13
2 Rec. 0.45m

3.00
3 SPT 3.00-3.45m CORAL with medium grained SAND, brown. Mixture W Ds
9,26,14 N=40
Rec. 0.45m with Granite

SPT 7.50-7.95m
7.95 14,17,26 N=43
8 Rec. 0.45m
CORAL with fine grained SAND, white. W MD

9
FULL CORING

SPT 9.00-9.45m
9.45 12,15,19 N=34
Rec. 0.45m
Fine grained SAND, whitish gray W MD
10

SPT 10.50-10.95m
14,17,20 N=37
11 Rec. 0.45m

12 SPT 12.00-12.45m
12,12,17 N=29
Rec. 0.45m

13

SPT 13.50-13.95m
9,11,14 N=25
14 Rec. 0.45m

15.00
15 SPT 15.00-15.45m
8,8,7 N=15 Sandy SILT, light gray. W Ls
Rec. 0.45m

16

SPT 16.50-16.95m
5,6,5 N=11
17 Rec. 0.45m

18 SPT 18.00-18.45m
11,5,3 N=8
Rec. 0.45m

19

SPT 19.50-19.95m
4,3,3 N=6
20 Rec. 0.45m
Note : - VSt = Very Soft - MS = Med. Stiff - VSf = Very Stiff - VH = Very Hard - Ls = Loose - Ds = Dense -W = Wet -D = Dry - TUU = Triaxial UU - UCT = Unconfined Compression Test
- St = Soft - Sf = Stiff - Hd = Hard - VL = Very Loose - MD = Med. Dense - VD = Very Dense -M = Moist - TCU = Triaxial CU - DST = Direct Shear Test
GEOTECHNICAL LOG HOLE ID

ZEKON
GEOTECHNICAL INVESTIGATION SERVICES BH-01
DESIGN & BUILD MATAK JETTY REPAIR PROJECT
Client : PT. MEDCO ENERGI System Zone : WGS 84; Zone 48N Drilled by : WM
Project : Soil Investigation Matak Jetty Integrity Surface RL : Logged by : DT
Location : Matak, Riau Islands Inclination : 90° Rig / Hammer Type : TOHO-01
Easting : 640060 m Scale : at scale Date Commence : December 19th, 2017
Northing : 370195 m Total Depth : 30.00 m (20.00-30.00 m) Date Complete : December 26th, 2017
DRILLING SAMPLING FIELD MATERIAL DESCRIPTION

CONSISTENCY /
USCS Symbol
RECOVERED

INDEX PROPERTIES STRENGTH PROPERTIES

REL. DENSITY
MOISTURE
METHOD

GRAPHIC
(metres)

(metres)

RQD (%)
SAMPLE

SAMPLE TYPE / TUU TCU DST CONS.

CONTENT, %

( gdry , kN/m3 )
SOIL / ROCK MATERIAL DESCRIPTION N-SPT Value

PLASTICITY
DEPTH

DEPTH

gsat , kN/m3
(MSL)

p c , kg/cm²
FIELD TESTED

INDEX, %

( f' , deg )
( f , deg )

( f , deg )

( f , deg )
GWL

LOG

FINEST

c , kPa

c', kPa
c , kPa
RL

RL

(C r )
0 10 20 30 40 50 60 70 80

Cc
Ditto.

21 SPT 21.00-21.45m
3,3,1 N=4
Rec. 0.45m

22

SPT 22.50-22.95m
6,6,6 N=12
23 Rec. 0.45m

24.00
24 SPT 24.00-24.45m
3,3,4 N=7 Sandy SILT, dark brown. W Ls
Rec. 0.45m

25

SPT 25.50-25.95m
3,3,2 N=5
26 Rec. 0.45m

27 SPT 27.00-27.45m
2,1,1 N=2
Rec. 0.45m

28

28.50
SPT 28.50-28.95m
50
5 ,-,- N=50
SAND trace of CORAL, dark brown. W VD
29 Rec. 0.45m
FULL CORING

30 30.03
SPT 30.00-30.03m
50
3 ,-,- N=50 End of Drilling at Depth of 30.03 meters.
Rec. 0.45m

31

32

33

34

35

36

37

38

39

40
Note : - VSt = Very Soft - MS = Med. Stiff - VSf = Very Stiff - VH = Very Hard - Ls = Loose - Ds = Dense -W = Wet -D = Dry - TUU = Triaxial UU - UCT = Unconfined Compression Test
- St = Soft - Sf = Stiff - Hd = Hard - VL = Very Loose - MD = Med. Dense - VD = Very Dense -M = Moist - TCU = Triaxial CU - DST = Direct Shear Test
GEOTECHNICAL LOG HOLE ID

ZEKON
GEOTECHNICAL INVESTIGATION SERVICES BH-03
DESIGN & BUILD MATAK JETTY REPAIR PROJECT
Client : PT. MEDCO ENERGI System Zone : WGS 84; Zone 48N Drilled by : WM
Project : Soil Investigation Matak Jetty Integrity Surface RL : Logged by : DT
Location : Matak, Riau Islands Inclination : 90° Rig / Hammer Type : TOHO-01
Easting : 640057 m Scale : at scale Date Commence : October 18th, 2017
Northing : 370293 m Total Depth : 30.00 m (0.00-20.00 m) Date Complete : October 28th, 2017
DRILLING SAMPLING FIELD MATERIAL DESCRIPTION

CONSISTENCY /
USCS Symbol
RECOVERED

INDEX PROPERTIES STRENGTH PROPERTIES


(metres)

REL. DENSITY
MOISTURE
METHOD

GRAPHIC
(metres)

RQD (%)
SAMPLE

SAMPLE TYPE / TUU TCU DST CONS.

CONTENT, %

( gdry , kN/m3 )
N-SPT Value
GWL

SOIL / ROCK MATERIAL DESCRIPTION

PLASTICITY
DEPTH

DEPTH

gsat , kN/m3
(MSL)

p c , kg/cm²
FIELD TESTED

INDEX, %

( f' , deg )

( f' , deg )
( f , deg )

( f , deg )
LOG

FINEST

c , kPa

c', kPa

c', kPa
c , kPa
RL

RL

(C r )
0 10 20 30 40 50 60 70 80

Cc
0.40 Concrete.
SM Fill Material (Silty SAND with Gravel), brown. W VL
1

3 SPT 3.00-3.45m 2.90 -


13,6,4 N=10 32.03 18.01 - - - -
(34.99)
Rec. 0.45m (13.10)

SPT 4.50-4.95m 5.70


4,3,5 N=8 35.08 18.30 - - - - -
5.00 (31.99)
5 Rec. 0.45m (13.70)
SC CORAL with Clayey SAND, gray. W VL

6 SPT 6.00-6.45m
12,5,3 N=8
Rec. 0.45m

7.50
SPT 7.50-7.95m 6.30
5,12,25 SC CORAL with Clayey SAND, gray. 35.90 18.85 - - - - -
1 N=50 W Ds (32.73)
8 Rec. 0.45m (14.40)

9
FULL CORING

SPT 9.00-9.45m 3.40


9,8,20 N=28 23.46 18.15 - - - - -
(34.24)
Rec. 0.45m (13.30)

10

11.00
11
SC CORAL with Clayey SAND, gray. W VL

12

13

SPT 13.50-13.95m
3,2,1 N=3
14 Rec. 0.45m

15.00
15 SPT 15.00-15.95m
3,2,4 N=6 ML Sandy SILT with CORAL, gray. W MS
Rec. 0.45m

16

SPT 16.50-16.95m
14,4,7 N=11
17 Rec. 0.45m

18 SPT 18.00-18.45m
4,3,4 N=7
Rec. 0.45m

19.00
19
ML Sandy SILT with CORAL, gray. W St
SPT 19.50-19.95m
3,1,1 N=2
20 Rec. 0.45m
Note : - VSt = Very Soft - MS = Med. Stiff - VSf = Very Stiff - VH = Very Hard - Ls = Loose - Ds = Dense -W = Wet -D = Dry - TUU = Triaxial UU - UCT = Unconfined Compression Test
- St = Soft - Sf = Stiff - Hd = Hard - VL = Very Loose - MD = Med. Dense - VD = Very Dense -M = Moist - TCU = Triaxial CU - DST = Direct Shear Test
GEOTECHNICAL LOG HOLE ID

ZEKON
GEOTECHNICAL INVESTIGATION SERVICES BH-03
DESIGN & BUILD MATAK JETTY REPAIR PROJECT
Client : PT. MEDCO ENERGI System Zone : WGS 84; Zone 48N Drilled by : WM
Project : Soil Investigation Matak Jetty Integrity Surface RL : Logged by : DT
Location : Matak, Riau Islands Inclination : 90° Rig / Hammer Type : TOHO-01
Easting : 640057 m Scale : at scale Date Commence : October 18th, 2017
Northing : 370293 m Total Depth : 30.00 m (20.00-30.00 m) Date Complete : October 28th, 2017
DRILLING SAMPLING FIELD MATERIAL DESCRIPTION

CONSISTENCY /
USCS Symbol
RECOVERED

INDEX PROPERTIES STRENGTH PROPERTIES

REL. DENSITY
MOISTURE
METHOD

GRAPHIC
(metres)

(metres)

RQD (%)
SAMPLE

SAMPLE TYPE / TUU TCU DST CONS.

CONTENT, %

( gdry , kN/m3 )
SOIL / ROCK MATERIAL DESCRIPTION N-SPT Value

PLASTICITY
DEPTH

DEPTH

gsat , kN/m3
(MSL)

p c , kg/cm²
FIELD TESTED

INDEX, %

( f' , deg )

( f' , deg )
( f , deg )

( f , deg )
GWL

LOG

FINEST

c , kPa

c', kPa

c', kPa
c , kPa
RL

RL

(C r )
0 10 20 30 40 50 60 70 80

Cc
Ditto.

21.00
21 SPT 21.00-21.45m
4,1,2 N=3 ML Sandy SILT trace of CORAL, gray. W St
Rec. 0.45m

22

SPT 22.50-22.95m 5.20


3,1,1 N=2 55.75 18.64 - - - - -
(28.20)
23 Rec. 0.45m (14.30)

24 SPT 24.00-24.45m
1
45 ,-,- N=1
Rec. 0.45m

25.00
25
CL Sandy CLAY trace of CORAL, gray. W Sf
SPT 25.50-25.95m 7.60
13,11,5 N=16 63.54 17.93 18.56 - - - -
(23.80)
26 Rec. 0.45m (13.20)

27.00
27 SPT 27.00-27.45m 4.50
34
26,16,12 N=50 SC Clayey SAND, brown. W VD 31.49 20.16 - - - - (33.71)
-
Rec. 0.45m (16.70)

28

SPT 28.50-28.95m 4.50


50
10,10 ,- N=50 31.31 17.68 - - - - -
(33.71)
29 Rec. 0.45m (12.80)
FULL CORING

30 30.07 SPT 30.00-30.07m


50
7 ,-,- N=50 End of Drilling at Depth of 30.07 meters.
Rec. 0.45m

31

32

33

34

35

36

37

38

39

40
Note : - VSt = Very Soft - MS = Med. Stiff - VSf = Very Stiff - VH = Very Hard - Ls = Loose - Ds = Dense -W = Wet -D = Dry - TUU = Triaxial UU - UCT = Unconfined Compression Test
- St = Soft - Sf = Stiff - Hd = Hard - VL = Very Loose - MD = Med. Dense - VD = Very Dense -M = Moist - TCU = Triaxial CU - DST = Direct Shear Test
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy

APPENDIX D
Soil Laboratory Test Result
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 1
Document No : - Sample Depth : 3.00 – 3.45 meters

DETERMINATION OF PARTICLE SIZE ANALYSIS (ASTM D 422 – 63)


Total Dry Mass = 62.45 gr
Sieve No. Diameter (mm) Mass Retained (gr) Percent Retained (%) Cumulative Percent Retained (%) Percent Passing (%)
4" 100.000 0.00 0.00 0.00 100.00
3" 75.000 0.00 0.00 0.00 100.00
2" 50.000 0.00 0.00 0.00 100.00
1¼" 31.250 0.00 0.00 0.00 100.00
¾" 19.000 0.00 0.00 0.00 100.00
½" 12.500 5.50 8.81 8.81 91.19
⅜" 9.500 3.84 6.15 14.96 85.04
4 4.750 7.16 11.47 26.42 73.58
10 2.000 8.22 13.16 39.58 60.42
18 1.000 5.72 9.16 48.74 51.26
40 0.425 4.51 7.22 55.96 44.04
60 0.250 2.80 4.48 60.45 39.55
100 0.150 1.12 1.79 62.24 37.76
200 0.075 3.58 5.73 67.97 32.03
Pan 20.00 32.03 100.00 0.00

DETERMINATION OF HYDROMETER TEST (ASTM D 422 – 63 ; ASTM E 100 – 05)


Total Dry Mass = 20.00 gr Temperature = 27.00 °C
Recall Specific Gravity = 2.754 Composite Correction = 1.00
Recall Percent Finer Than No. 200 = 32.03 % a (Correction Faction) = 0.97918
Hydrometer Type = 152H K (Const. Depending Temp. & Gs) = 0.01220
Time (min.) Actual Reading Corr. Reading Eff. Depth, L (cm) Diameter (mm) Percent Remaining (%) Percent Passing (%)
0.5 20 19.00 13.0 0.06219 93.02 29.79
1 19 18.00 13.2 0.04431 88.13 28.22
2 17.5 16.50 13.5 0.03169 80.78 25.87
5 15.5 14.50 13.8 0.02026 70.99 22.74
15 13.5 12.50 14.2 0.01187 61.20 19.60
30 12 11.00 14.3 0.00842 53.85 17.25
60 10 9.00 14.7 0.00604 44.06 14.11
240 6 5.00 15.3 0.00308 24.48 7.84
1440 2 1.00 16.0 0.00129 4.90 1.57

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 1
Document No : - Sample Depth : 3.00 – 3.45 meters

GRAPH OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST

100

90

80

70
Percent Passing (%)

60

50

40

30

20

10

0
0.001 0.010 0.100 1.000 10.000 100.000
Diameter (mm)

COBBLE
SAND GRAVEL
CLAY SILT
Fine Medium Coarse Fine Coarse
0.001 0.005 0.075 0.425 2 4.75 19 76

RESUME OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST


COBBLE (%) 0.00 D10 mm 0.004098 Material will be classified as (ASTM D 2487 - 06) :
GRAVEL (%) 26.42 D30 mm 0.063387 - Coarse Grained Soils (more than 50% retained on sieve No. 200)
SAND (%) 41.55 D60 mm 1.954545 - Silty SAND with GRAVEL
SILT (%) 17.47 Cu Unitless 476.95
CLAY (%) 14.06 Cc Unitless 0.50
COLLOID (%) 0.50

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 2
Document No : - Sample Depth : 4.50 – 4.95 meters

DETERMINATION OF PARTICLE SIZE ANALYSIS (ASTM D 422 – 63)


Total Dry Mass = 68.42 gr
Sieve No. Diameter (mm) Mass Retained (gr) Percent Retained (%) Cumulative Percent Retained (%) Percent Passing (%)
4" 100.000 0.00 0.00 0.00 100.00
3" 75.000 0.00 0.00 0.00 100.00
2" 50.000 0.00 0.00 0.00 100.00
1¼" 31.250 0.00 0.00 0.00 100.00
¾" 19.000 0.00 0.00 0.00 100.00
½" 12.500 0.00 0.00 0.00 100.00
⅜" 9.500 0.00 0.00 0.00 100.00
4 4.750 1.74 2.54 2.54 97.46
8 2.380 9.04 13.21 15.76 84.24
20 0.840 7.14 10.44 26.19 73.81
40 0.420 8.84 12.92 39.11 60.89
80 0.177 4.10 5.99 45.10 54.90
100 0.150 3.95 5.77 50.88 49.12
200 0.075 9.61 14.05 64.92 35.08
Pan 24.00 35.08 100.00 0.00

DETERMINATION OF HYDROMETER TEST (ASTM D 422 – 63 ; ASTM E 100 – 05)


Total Dry Mass = 24.00 gr Temperature = 27.00 °C
Recall Specific Gravity = 2.704 Composite Correction = 2.00
Recall Percent Finer Than No. 200 = 35.08 % a (Correction Faction) = 0.98929
Hydrometer Type = 152H K (Const. Depending Temp. & Gs) = 0.01238
Time (min.) Actual Reading Corr. Reading Eff. Depth, L (cm) Diameter (mm) Percent Remaining (%) Percent Passing (%)
0.5 24 22.00 12.4 0.06164 90.68 31.81
1 23 21.00 12.5 0.04376 86.56 30.36
2 22 20.00 12.7 0.03119 82.44 28.92
5 21 19.00 12.9 0.01988 78.32 27.47
15 19 17.00 13.2 0.01161 70.07 24.58
30 17 15.00 13.5 0.00830 61.83 21.69
60 15 13.00 13.8 0.00594 53.59 18.80
240 11 9.00 14.5 0.00304 37.10 13.01
1440 6 4.00 15.3 0.00128 16.49 5.78

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 2
Document No : - Sample Depth : 4.50 – 4.95 meters

GRAPH OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST

100

90

80

70
Percent Passing (%)

60

50

40

30

20

10

0
0.001 0.010 0.100 1.000 10.000 100.000
Diameter (mm)

COBBLE
SAND GRAVEL
CLAY SILT
Fine Medium Coarse Fine Coarse
0.001 0.005 0.075 0.425 2 4.75 19 76

RESUME OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST


COBBLE (%) 0.00 D10 mm 0.002306 Material will be classified as (ASTM D 2487 - 06) :
GRAVEL (%) 2.54 D30 mm 0.040596 - Coarse Grained Soils (more than 50% retained on sieve No. 200)
SAND (%) 62.38 D60 mm 0.383965 - Clayey SAND
SILT (%) 14.05 Cu Unitless 166.50
CLAY (%) 20.53 Cc Unitless 1.86
COLLOID (%) 0.50

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 4
Document No : - Sample Depth : 7.50 – 7.95 meters

DETERMINATION OF PARTICLE SIZE ANALYSIS (ASTM D 422 – 63)


Total Dry Mass = 68.42 gr
Sieve No. Diameter (mm) Mass Retained (gr) Percent Retained (%) Cumulative Percent Retained (%) Percent Passing (%)
4" 100.000 0.00 0.00 0.00 100.00
3" 75.000 0.00 0.00 0.00 100.00
2" 50.000 0.00 0.00 0.00 100.00
1¼" 31.250 0.00 0.00 0.00 100.00
¾" 19.000 0.00 0.00 0.00 100.00
½" 12.500 0.00 0.00 0.00 100.00
⅜" 9.500 0.00 0.00 0.00 100.00
4 4.750 7.03 10.27 10.27 89.73
8 2.380 8.46 12.36 22.64 77.36
20 0.840 7.89 11.53 34.17 65.83
40 0.420 6.48 9.47 43.64 56.36
80 0.177 6.31 9.22 52.86 47.14
100 0.150 1.91 2.79 55.66 44.34
200 0.075 5.78 8.45 64.10 35.90
Pan 24.56 35.90 100.00 0.00

DETERMINATION OF HYDROMETER TEST (ASTM D 422 – 63 ; ASTM E 100 – 05)


Total Dry Mass = 24.56 gr Temperature = 27.00 °C
Recall Specific Gravity = 2.760 Composite Correction = -2.00
Recall Percent Finer Than No. 200 = 35.90 % a (Correction Faction) = 0.97809
Hydrometer Type = 152H K (Const. Depending Temp. & Gs) = 0.01218
Time (min.) Actual Reading Corr. Reading Eff. Depth, L (cm) Diameter (mm) Percent Remaining (%) Percent Passing (%)
0.5 21 23.00 12.9 0.06185 91.60 32.88
1 20 22.00 13.0 0.04391 87.61 31.45
2 18 20.00 13.3 0.03140 79.65 28.59
5 16 18.00 13.7 0.02016 71.68 25.73
15 14 16.00 14.0 0.01176 63.72 22.87
30 13 15.00 14.2 0.00838 59.74 21.44
60 12 14.00 14.3 0.00594 55.75 20.01
240 9 11.00 14.8 0.00302 43.81 15.72
1440 6 6.50 15.3 0.00126 25.89 9.29

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 4
Document No : - Sample Depth : 7.50 – 7.95 meters

GRAPH OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST

100

90

80

70
Percent Passing (%)

60

50

40

30

20

10

0
0.001 0.010 0.100 1.000 10.000 100.000
Diameter (mm)

COBBLE
SAND GRAVEL
CLAY SILT
Fine Medium Coarse Fine Coarse
0.001 0.005 0.075 0.425 2 4.75 19 76

RESUME OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST


COBBLE (%) 0.00 D10 mm 0.001450 Material will be classified as (ASTM D 2487 - 06) :
GRAVEL (%) 10.27 D30 mm 0.037566 - Coarse Grained Soils (more than 50% retained on sieve No. 200)
SAND (%) 53.83 D60 mm 0.581519 - Clayey SAND
SILT (%) 12.98 Cu Unitless 401.07
CLAY (%) 22.41 Cc Unitless 1.67
COLLOID (%) 0.50

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 5
Document No : - Sample Depth : 9.00 – 9.45 meters

DETERMINATION OF PARTICLE SIZE ANALYSIS (ASTM D 422 – 63)


Total Dry Mass = 63.95 gr
Sieve No. Diameter (mm) Mass Retained (gr) Percent Retained (%) Cumulative Percent Retained (%) Percent Passing (%)
4" 100.000 0.00 0.00 0.00 100.00
3" 75.000 0.00 0.00 0.00 100.00
2" 50.000 0.00 0.00 0.00 100.00
1¼" 31.250 0.00 0.00 0.00 100.00
¾" 19.000 0.00 0.00 0.00 100.00
½" 12.500 0.00 0.00 0.00 100.00
⅜" 9.500 0.00 0.00 0.00 100.00
4 4.750 12.33 19.28 19.28 80.72
8 2.380 10.44 16.33 35.61 64.39
20 0.840 11.09 17.34 52.95 47.05
40 0.420 6.52 10.20 63.14 36.86
80 0.177 3.22 5.04 68.18 31.82
100 0.150 1.15 1.80 69.98 30.02
200 0.075 4.20 6.57 76.54 23.46
Pan 15.00 23.46 100.00 0.00

DETERMINATION OF HYDROMETER TEST (ASTM D 422 – 63 ; ASTM E 100 – 05)


Total Dry Mass = 15.00 gr Temperature = 27.00 °C
Recall Specific Gravity = 2.769 Composite Correction = 1.00
Recall Percent Finer Than No. 200 = 23.46 % a (Correction Faction) = 0.97615
Hydrometer Type = 152H K (Const. Depending Temp. & Gs) = 0.01214
Time (min.) Actual Reading Corr. Reading Eff. Depth, L (cm) Diameter (mm) Percent Remaining (%) Percent Passing (%)
0.5 15 14.00 13.8 0.06380 91.11 21.37
1 14 13.00 14.0 0.04544 84.60 19.84
2 13 12.00 14.2 0.03236 78.09 18.32
5 12 11.00 14.3 0.02054 71.58 16.79
15 11 10.00 14.5 0.01194 65.08 15.26
30 10 9.00 14.7 0.00850 58.57 13.74
60 9 8.00 14.8 0.00603 52.06 12.21
240 7 6.00 15.2 0.00306 39.05 9.16
1440 5 4.00 15.5 0.00126 26.03 6.11

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 5
Document No : - Sample Depth : 9.00 – 9.45 meters

GRAPH OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST

100

90

80

70
Percent Passing (%)

60

50

40

30

20

10

0
0.001 0.010 0.100 1.000 10.000 100.000
Diameter (mm)

COBBLE
SAND GRAVEL
CLAY SILT
Fine Medium Coarse Fine Coarse
0.001 0.005 0.075 0.425 2 4.75 19 76

RESUME OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST


COBBLE (%) 0.00 D10 mm 0.003876 Material will be classified as (ASTM D 2487 - 06) :
GRAVEL (%) 19.28 D30 mm 0.149732 - Coarse Grained Soils (more than 50% retained on sieve No. 200)
SAND (%) 57.26 D60 mm 1.989793 - Clayey SAND with GRAVEL
SILT (%) 10.99 Cu Unitless 513.31
CLAY (%) 11.96 Cc Unitless 2.91
COLLOID (%) 0.50

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 12
Document No : - Sample Depth : 22.50 – 22.95 meters

DETERMINATION OF PARTICLE SIZE ANALYSIS (ASTM D 422 – 63)


Total Dry Mass = 60.99 gr
Sieve No. Diameter (mm) Mass Retained (gr) Percent Retained (%) Cumulative Percent Retained (%) Percent Passing (%)
4" 100.000 0.00 0.00 0.00 100.00
3" 75.000 0.00 0.00 0.00 100.00
2" 50.000 0.00 0.00 0.00 100.00
1¼" 31.250 0.00 0.00 0.00 100.00
¾" 19.000 0.00 0.00 0.00 100.00
½" 12.500 0.00 0.00 0.00 100.00
⅜" 9.500 0.00 0.00 0.00 100.00
4 4.750 0.25 0.41 0.41 99.59
8 2.380 1.24 2.03 2.44 97.56
20 0.840 3.88 6.36 8.80 91.20
40 0.420 8.96 14.69 23.50 76.50
80 0.177 6.71 11.00 34.50 65.50
100 0.150 1.50 2.46 36.96 63.04
200 0.075 4.45 7.30 44.25 55.75
Pan 34.00 55.75 100.00 0.00

DETERMINATION OF HYDROMETER TEST (ASTM D 422 – 63 ; ASTM E 100 – 05)


Total Dry Mass = 34.00 gr Temperature = 27.00 °C
Recall Specific Gravity = 2.687 Composite Correction = 2.00
Recall Percent Finer Than No. 200 = 55.75 % a (Correction Faction) = 0.99263
Hydrometer Type = 152H K (Const. Depending Temp. & Gs) = 0.01244
Time (min.) Actual Reading Corr. Reading Eff. Depth, L (cm) Diameter (mm) Percent Remaining (%) Percent Passing (%)
0.5 34 32.00 10.7 0.05755 93.42 52.08
1 32 30.00 11.1 0.04145 87.59 48.83
2 30 28.00 11.4 0.02970 81.75 45.57
5 26 24.00 12.0 0.01927 70.07 39.06
15 21 19.00 12.9 0.01154 55.47 30.92
30 18 16.00 13.3 0.00828 46.71 26.04
60 14 12.00 14.0 0.00601 35.03 19.53
240 8 6.00 15.0 0.00311 17.52 9.77
1440 2 0.00 16.0 0.00131 0.00 0.00

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 12
Document No : - Sample Depth : 22.50 – 22.95 meters

GRAPH OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST

100

90

80

70
Percent Passing (%)

60

50

40

30

20

10

0
0.001 0.010 0.100 1.000 10.000 100.000
Diameter (mm)

COBBLE
SAND GRAVEL
CLAY SILT
Fine Medium Coarse Fine Coarse
0.001 0.005 0.075 0.425 2 4.75 19 76

RESUME OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST


COBBLE (%) 0.00 D10 mm N/A Material will be classified as (ASTM D 2487 - 06) :
GRAVEL (%) 0.41 D30 mm N/A - Fine Grained Soils (more than 50% passes sieve No. 200)
SAND (%) 43.84 D60 mm N/A - SILT and CLAY
SILT (%) 35.72 Cu Unitless N/A - Atterberg Limit shall be performed to provide USCS symbol
CLAY (%) 19.53 Cc Unitless N/A
COLLOID (%) 0.50

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 14
Document No : - Sample Depth : 25.50 – 25.95 meters

DETERMINATION OF PARTICLE SIZE ANALYSIS (ASTM D 422 – 63)


Total Dry Mass = 50.36 gr
Sieve No. Diameter (mm) Mass Retained (gr) Percent Retained (%) Cumulative Percent Retained (%) Percent Passing (%)
4" 100.000 0.00 0.00 0.00 100.00
3" 75.000 0.00 0.00 0.00 100.00
2" 50.000 0.00 0.00 0.00 100.00
1¼" 31.250 0.00 0.00 0.00 100.00
¾" 19.000 0.00 0.00 0.00 100.00
½" 12.500 0.00 0.00 0.00 100.00
⅜" 9.500 0.00 0.00 0.00 100.00
4 4.750 0.00 0.00 0.00 100.00
8 2.380 0.81 1.61 1.61 98.39
20 0.840 3.26 6.47 8.08 91.92
40 0.420 7.91 15.71 23.79 76.21
80 0.177 3.50 6.95 30.74 69.26
100 0.150 0.74 1.47 32.21 67.79
200 0.075 2.14 4.25 36.46 63.54
Pan 32.00 63.54 100.00 0.00

DETERMINATION OF HYDROMETER TEST (ASTM D 422 – 63 ; ASTM E 100 – 05)


Total Dry Mass = 32.00 gr Temperature = 27.00 °C
Recall Specific Gravity = 2.677 Composite Correction = 2.00
Recall Percent Finer Than No. 200 = 63.54 % a (Correction Faction) = 0.99466
Hydrometer Type = 152H K (Const. Depending Temp. & Gs) = 0.01248
Time (min.) Actual Reading Corr. Reading Eff. Depth, L (cm) Diameter (mm) Percent Remaining (%) Percent Passing (%)
0.5 32 30.00 11.1 0.05880 93.25 59.25
1 31 29.00 11.2 0.04176 90.14 57.28
2 30 28.00 11.4 0.02979 87.03 55.30
5 27.5 25.50 11.9 0.01925 79.26 50.37
15 23.5 21.50 12.5 0.01139 66.83 42.46
30 20 18.00 13.0 0.00821 55.95 35.55
60 17 15.00 13.5 0.00592 46.62 29.63
240 11 9.00 14.5 0.00307 27.97 17.78
1440 4 2.00 15.6 0.00130 6.22 3.95

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 14
Document No : - Sample Depth : 25.50 – 25.95 meters

GRAPH OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST

100

90

80

70
Percent Passing (%)

60

50

40

30

20

10

0
0.001 0.010 0.100 1.000 10.000 100.000
Diameter (mm)

COBBLE
SAND GRAVEL
CLAY SILT
Fine Medium Coarse Fine Coarse
0.001 0.005 0.075 0.425 2 4.75 19 76

RESUME OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST


COBBLE (%) 0.00 D10 mm N/A Material will be classified as (ASTM D 2487 - 06) :
GRAVEL (%) 0.00 D30 mm N/A - Fine Grained Soils (more than 50% passes sieve No. 200)
SAND (%) 36.46 D60 mm N/A - SILT and CLAY
SILT (%) 30.66 Cu Unitless N/A - Atterberg Limit shall be performed to provide USCS symbol
CLAY (%) 32.39 Cc Unitless N/A
COLLOID (%) 0.50

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 15
Document No : - Sample Depth : 27.00 – 27.45 meters

DETERMINATION OF PARTICLE SIZE ANALYSIS (ASTM D 422 – 63)


Total Dry Mass = 66.68 gr
Sieve No. Diameter (mm) Mass Retained (gr) Percent Retained (%) Cumulative Percent Retained (%) Percent Passing (%)
4" 100.000 0.00 0.00 0.00 100.00
3" 75.000 0.00 0.00 0.00 100.00
2" 50.000 0.00 0.00 0.00 100.00
1¼" 31.250 0.00 0.00 0.00 100.00
¾" 19.000 0.00 0.00 0.00 100.00
½" 12.500 0.00 0.00 0.00 100.00
⅜" 9.500 0.00 0.00 0.00 100.00
4 4.750 6.05 9.07 9.07 90.93
8 2.380 5.44 8.16 17.23 82.77
20 0.840 12.91 19.36 36.59 63.41
40 0.420 12.52 18.78 55.37 44.63
80 0.177 4.36 6.54 61.91 38.09
100 0.150 1.09 1.63 63.54 36.46
200 0.075 3.31 4.96 68.51 31.49
Pan 21.00 31.49 100.00 0.00

DETERMINATION OF HYDROMETER TEST (ASTM D 422 – 63 ; ASTM E 100 – 05)


Total Dry Mass = 21.00 gr Temperature = 27.00 °C
Recall Specific Gravity = 2.715 Composite Correction = 1.00
Recall Percent Finer Than No. 200 = 31.49 % a (Correction Faction) = 0.98709
Hydrometer Type = 152H K (Const. Depending Temp. & Gs) = 0.01234
Time (min.) Actual Reading Corr. Reading Eff. Depth, L (cm) Diameter (mm) Percent Remaining (%) Percent Passing (%)
0.5 21 20.00 12.9 0.06267 94.01 29.61
1 20 19.00 13.0 0.04448 89.31 28.13
2 19 18.00 13.2 0.03170 84.61 26.65
5 18 17.00 13.3 0.02012 79.91 25.17
15 16 15.00 13.7 0.01179 70.51 22.21
30 14 13.00 14.0 0.00843 61.11 19.24
60 12 11.00 14.3 0.00602 51.70 16.28
240 8.5 7.50 15.0 0.00308 35.25 11.10
1440 5 4.00 15.5 0.00128 18.80 5.92

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 15
Document No : - Sample Depth : 27.00 – 27.45 meters

GRAPH OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST

100

90

80

70
Percent Passing (%)

60

50

40

30

20

10

0
0.001 0.010 0.100 1.000 10.000 100.000
Diameter (mm)

COBBLE
SAND GRAVEL
CLAY SILT
Fine Medium Coarse Fine Coarse
0.001 0.005 0.075 0.425 2 4.75 19 76

RESUME OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST


COBBLE (%) 0.00 D10 mm 0.002700 Material will be classified as (ASTM D 2487 - 06) :
GRAVEL (%) 9.07 D30 mm 0.065237 - Coarse Grained Soils (more than 50% retained on sieve No. 200)
SAND (%) 59.43 D60 mm 0.763783 - Clayey SAND
SILT (%) 14.89 Cu Unitless 282.84
CLAY (%) 16.10 Cc Unitless 2.06
COLLOID (%) 0.50

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 16
Document No : - Sample Depth : 28.50 – 28.95 meters

DETERMINATION OF PARTICLE SIZE ANALYSIS (ASTM D 422 – 63)


Total Dry Mass = 47.91 gr
Sieve No. Diameter (mm) Mass Retained (gr) Percent Retained (%) Cumulative Percent Retained (%) Percent Passing (%)
4" 100.000 0.00 0.00 0.00 100.00
3" 75.000 0.00 0.00 0.00 100.00
2" 50.000 0.00 0.00 0.00 100.00
1¼" 31.250 0.00 0.00 0.00 100.00
¾" 19.000 0.00 0.00 0.00 100.00
½" 12.500 0.00 0.00 0.00 100.00
⅜" 9.500 0.00 0.00 0.00 100.00
4 4.750 1.53 3.19 3.19 96.81
8 2.380 1.73 3.61 6.80 93.20
20 0.840 8.09 16.89 23.69 76.31
40 0.420 11.39 23.77 47.46 52.54
80 0.177 3.58 7.47 54.94 45.06
100 0.150 2.45 5.11 60.05 39.95
200 0.075 4.14 8.64 68.69 31.31
Pan 15.00 31.31 100.00 0.00

DETERMINATION OF HYDROMETER TEST (ASTM D 422 – 63 ; ASTM E 100 – 05)


Total Dry Mass = 15.00 gr Temperature = 27.00 °C
Recall Specific Gravity = 2.690 Composite Correction = 0.00
Recall Percent Finer Than No. 200 = 31.31 % a (Correction Faction) = 0.99192
Hydrometer Type = 152H K (Const. Depending Temp. & Gs) = 0.01243
Time (min.) Actual Reading Corr. Reading Eff. Depth, L (cm) Diameter (mm) Percent Remaining (%) Percent Passing (%)
0.5 15 14.50 13.8 0.06528 95.89 30.02
1 14 14.00 14.0 0.04650 92.58 28.99
2 13 13.00 14.2 0.03311 85.97 26.92
5 12 12.00 14.3 0.02102 79.35 24.84
15 11 11.00 14.5 0.01222 72.74 22.77
30 10 10.00 14.7 0.00870 66.13 20.70
60 9 9.00 14.8 0.00617 59.52 18.63
240 7 7.00 15.2 0.00313 46.29 14.49
1440 4 4.00 15.6 0.00129 26.45 8.28

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
PARTICLE SIZE ANALYSIS AND HYDROMETER TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 16
Document No : - Sample Depth : 28.50 – 28.95 meters

GRAPH OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST

100

90

80

70
Percent Passing (%)

60

50

40

30

20

10

0
0.001 0.010 0.100 1.000 10.000 100.000
Diameter (mm)

COBBLE
SAND GRAVEL
CLAY SILT
Fine Medium Coarse Fine Coarse
0.001 0.005 0.075 0.425 2 4.75 19 76

RESUME OF PARTICLE SIZE ANALYSIS AND HYDROMETER TEST


COBBLE (%) 0.00 D10 mm 0.001801 Material will be classified as (ASTM D 2487 - 06) :
GRAVEL (%) 3.19 D30 mm 0.064910 - Coarse Grained Soils (more than 50% retained on sieve No. 200)
SAND (%) 65.50 D60 mm 0.551863 - Clayey SAND
SILT (%) 10.47 Cu Unitless 306.46
CLAY (%) 20.34 Cc Unitless 4.24
COLLOID (%) 0.50

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
ATTERBERG LIMIT WITH LINEAR SHRINKAGE
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Borehole ID : BH – 05
Project No : - Sample ID : SPT – 14
Document No : - Sample Depth : 25.50 – 25.95 meters

DETERMINATION OF ATTERBERG LIMIT (ASTM D 4318 – 05)


Type of Test Liquid Limit Plastic Limit
Test Number I II III IV I II
Container ID. A B C D E F
Number of Blows n 16 21 26 36
Weight of container + wet soil w1 gr 17.55 20.44 19.25 18.25 15.45 17.25
Weight of container + dry soil w2 gr 13.93 16.13 15.49 14.97 13.69 15.10
Weight of water w3 = w 1 - w 2 gr 3.62 4.31 3.76 3.28 1.76 2.15
Weight of container w4 gr 6.14 6.17 6.16 6.20 6.20 5.27
Weight of dry soil w5 = w 2 - w 4 gr 7.79 9.96 9.33 8.77 7.49 9.83
Water content ( w3 / w5 ) x 100 % % 46.47 43.27 40.30 37.40 23.50 21.87

60
1.00 2.00 3.00 4.00
50 16.00 21.00 26.00 36.00 99.00 4.00
41.25 46.47 43.27 40.30 37.40 167.44 41.86
40 2.77 3.04 3.26 3.58 12.66 3.16
Water Content (%)

128.84 131.75 131.30 134.02 525.91


30
7.69 9.27 10.62 12.84 40.41 -11.33
20 46.47 43.27 40.30 37.40 167.44 77.71
41.25 41.25 0.00
10
10.00 25.00 25.00

0
10 100
Number of Blows (n)

DETERMINATION OF SHRINKAGE LIMIT (ASTM D 4943 – 02)


Ring ID - N/A
Weight of Ring + Wet Soil w1 gr N/A
Weight of Ring + Dry Soil w2 gr N/A
Weight of Water w3 = w 1 - w 2 gr N/A
Weight of Ring w4 gr N/A
Weight of Dry Soil w 5 = w2 - w4 gr N/A
Water content wc = ( w3 / w5 ) x 100 % % N/A
v1 3
Volume of Ring cm N/A
Volume of Dry Soil v2 cm3 N/A
v3 = v 1 - v 2 3
Volume of Ring - Volume Dry Soil cm N/A
Shrinkage Limit LS = wc - {(v3 x gw)/w5} x 100 % N/A

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
ATTERBERG LIMIT WITH LINEAR SHRINKAGE
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Borehole ID : BH – 05
Project No : - Sample ID : SPT – 14
Document No : - Sample Depth : 25.50 – 25.95 meters

DETERMINATION OF USCS SOIL CLASSIFICATION (ASTM D 2487 – 11)

100

90

80

70
Platicity Index (%)

60

50 CH

40

30

20
CL MH or OH

10
CL or ML ML or OL

0
0 10 20 30 40 50 60 70 80 90 100 110 120

Liquid Limit (%)

RESUME OF ATTERBERG LIMIT WITH LINEAR SHRINKAGE


Water Content Liquid Limit Plastic Limit Plastic Index Shrinkage Limit USCS
Borehole ID Sample ID
(%) (%) (%) (%) (%) Classification
BH – 05 SPT – 14 41.86 41.25 22.68 18.56 N/A CL

Tested By Checked By Approved By

Tatang Suhanda Dyas Tedja S., S.T. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
INDEX PROPERTIES
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 1
Document No : - Sample Depth : 3.00 – 3.45 meters

DETERMINATION OF NATURAL WATER CONTENT (ASTM D 2216 – 10)


Container No. 195 180
Weight of container + wet soil w1 gr 47.16 77.25
Weight of container + dry soil w2 gr 40.25 64.72
Weight of water w3 = w 1 - w2 gr 6.91 12.53
Weight of container w4 gr 7.23 7.09
Weight of dry soil w5 = w 2 - w 4 gr 33.02 57.63
Water content ( w3 / w5 ) x 100 % % 20.93 21.74
Average Water Content % 21.33

DETERMINATION OF UNIT WEIGHT OF SOIL (ASTM D 7263 – 09)


Ring No. 9A
Weight of Ring + Wet Soil w1 gr 70.00
Weight of ring w2 gr 30.07
Weight of Wet Soil w3 = w 1 - w2 gr 39.93
3
Volume of Ring v cm 25.07
g = w3/v 3
Unit Weight gr/ cm 1.59
3
Average Unit Weight gr/ cm 1.59

DETERMINATION OF SPECIFIC GRAVITY OF SOLIDS (ASTM D 854 – 92)


Picnometer No. - 58
°
Temperature - C 27.00
Weight of picno + sample w1 gr 47.12
Weight of picnometer w2 gr 32.00
Weight of sample w3 = w 1 - w2 gr 15.12
Weight of picnometer + water w4 gr 88.26
Weight of pic + sample + water w5 gr 97.89
v = [w4-(w5-w3)] / gw 3
Volume of Sample cm 5.49
Specific Gravity Gs = w3 / v Unitless 2.754

RESUME OF INDEX PROPERTIES


Water Content (%) 21.33 Material - Silty SAND
3
Wet Density (t/m ) 1.59 Colour - Brown
Dry Density (t/m3) 1.31 Volume of Soil Volume of Air (%) 24.33
Specific Gravity Unitless 2.75 Volume of Water Volume of Water (%) 28.01
Void Ratio (e) Unitless 1.10 Volume of Air Volume of Soil (%) 47.66
Porosity (n) Unitless 0.52
Saturated Degree (%) 53.51

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
INDEX PROPERTIES
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 2
Document No : - Sample Depth : 4.50 – 4.95 meters

DETERMINATION OF NATURAL WATER CONTENT (ASTM D 2216 – 10)


Container No. 206 183
Weight of container + wet soil w1 gr 48.03 66.13
Weight of container + dry soil w2 gr 41.72 56.43
Weight of water w3 = w 1 - w2 gr 6.31 9.70
Weight of container w4 gr 7.06 7.07
Weight of dry soil w5 = w 2 - w 4 gr 34.66 49.36
Water content ( w3 / w5 ) x 100 % % 18.21 19.65
Average Water Content % 18.93

DETERMINATION OF UNIT WEIGHT OF SOIL (ASTM D 7263 – 09)


Ring No. 9A
Weight of Ring + Wet Soil w1 gr 71.04
Weight of ring w2 gr 30.07
Weight of Wet Soil w3 = w 1 - w2 gr 40.97
3
Volume of Ring v cm 25.07
g = w3/v 3
Unit Weight gr/ cm 1.63
3
Average Unit Weight gr/ cm 1.63

DETERMINATION OF SPECIFIC GRAVITY OF SOLIDS (ASTM D 854 – 92)


Picnometer No. - 63
°
Temperature - C 27.00
Weight of picno + sample w1 gr 47.14
Weight of picnometer w2 gr 32.00
Weight of sample w3 = w 1 - w2 gr 15.14
Weight of picnometer + water w4 gr 69.67
Weight of pic + sample + water w5 gr 79.21
v = [w4-(w5-w3)] / gw 3
Volume of Sample cm 5.60
Specific Gravity Gs = w3 / v Unitless 2.704

RESUME OF INDEX PROPERTIES


Water Content (%) 18.93 Material - Clayey SAND
3
Wet Density (t/m ) 1.63 Colour - Gray
Dry Density (t/m3) 1.37 Volume of Soil Volume of Air (%) 23.16
Specific Gravity Unitless 2.70 Volume of Water Volume of Water (%) 26.01
Void Ratio (e) Unitless 0.97 Volume of Air Volume of Soil (%) 50.83
Porosity (n) Unitless 0.49
Saturated Degree (%) 52.89

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
INDEX PROPERTIES
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 4
Document No : - Sample Depth : 7.50 – 7.95 meters

DETERMINATION OF NATURAL WATER CONTENT (ASTM D 2216 – 10)


Container No. 205 197
Weight of container + wet soil w1 gr 49.57 78.48
Weight of container + dry soil w2 gr 43.75 67.17
Weight of water w3 = w 1 - w2 gr 5.82 11.31
Weight of container w4 gr 7.07 7.16
Weight of dry soil w5 = w 2 - w 4 gr 36.68 60.01
Water content ( w3 / w5 ) x 100 % % 15.87 18.85
Average Water Content % 17.36

DETERMINATION OF UNIT WEIGHT OF SOIL (ASTM D 7263 – 09)


Ring No. 1
Weight of Ring + Wet Soil w1 gr 72.57
Weight of ring w2 gr 30.07
Weight of Wet Soil w3 = w 1 - w2 gr 42.50
3
Volume of Ring v cm 25.07
g = w3/v 3
Unit Weight gr/ cm 1.70
3
Average Unit Weight gr/ cm 1.70

DETERMINATION OF SPECIFIC GRAVITY OF SOLIDS (ASTM D 854 – 92)


Picnometer No. - 64
°
Temperature - C 27.00
Weight of picno + sample w1 gr 47.15
Weight of picnometer w2 gr 32.00
Weight of sample w3 = w 1 - w2 gr 15.15
Weight of picnometer + water w4 gr 69.53
Weight of pic + sample + water w5 gr 79.19
v = [w4-(w5-w3)] / gw 3
Volume of Sample cm 5.49
Specific Gravity Gs = w3 / v Unitless 2.760

RESUME OF INDEX PROPERTIES


Water Content (%) 17.36 Material - Clayey SAND
3
Wet Density (t/m ) 1.70 Colour - Gray
Dry Density (t/m3) 1.44 Volume of Soil Volume of Air (%) 22.58
Specific Gravity Unitless 2.76 Volume of Water Volume of Water (%) 25.07
Void Ratio (e) Unitless 0.91 Volume of Air Volume of Soil (%) 52.35
Porosity (n) Unitless 0.48
Saturated Degree (%) 52.61

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
INDEX PROPERTIES
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 5
Document No : - Sample Depth : 9.00 – 9.45 meters

DETERMINATION OF NATURAL WATER CONTENT (ASTM D 2216 – 10)


Container No. 171 169
Weight of container + wet soil w1 gr 47.50 76.65
Weight of container + dry soil w2 gr 40.47 63.86
Weight of water w3 = w 1 - w2 gr 7.03 12.79
Weight of container w4 gr 6.90 7.04
Weight of dry soil w5 = w 2 - w 4 gr 33.57 56.82
Water content ( w3 / w5 ) x 100 % % 20.94 22.51
Average Water Content % 21.73

DETERMINATION OF UNIT WEIGHT OF SOIL (ASTM D 7263 – 09)


Ring No. 1
Weight of Ring + Wet Soil w1 gr 70.67
Weight of ring w2 gr 30.07
Weight of Wet Soil w3 = w 1 - w2 gr 40.60
3
Volume of Ring v cm 25.07
g = w3/v 3
Unit Weight gr/ cm 1.62
3
Average Unit Weight gr/ cm 1.62

DETERMINATION OF SPECIFIC GRAVITY OF SOLIDS (ASTM D 854 – 92)


Picnometer No. - 66
°
Temperature - C 27.00
Weight of picno + sample w1 gr 47.12
Weight of picnometer w2 gr 32.00
Weight of sample w3 = w 1 - w2 gr 15.12
Weight of picnometer + water w4 gr 69.81
Weight of pic + sample + water w5 gr 79.47
v = [w4-(w5-w3)] / gw 3
Volume of Sample cm 5.46
Specific Gravity Gs = w3 / v Unitless 2.769

RESUME OF INDEX PROPERTIES


Water Content (%) 21.73 Material - Clayey SAND
3
Wet Density (t/m ) 1.62 Colour - Gray
Dry Density (t/m3) 1.33 Volume of Soil Volume of Air (%) 23.05
Specific Gravity Unitless 2.77 Volume of Water Volume of Water (%) 28.90
Void Ratio (e) Unitless 1.08 Volume of Air Volume of Soil (%) 48.04
Porosity (n) Unitless 0.52
Saturated Degree (%) 55.63

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
INDEX PROPERTIES
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 12
Document No : - Sample Depth : 22.50 – 22.95 meters

DETERMINATION OF NATURAL WATER CONTENT (ASTM D 2216 – 10)


Container No. 200 178
Weight of container + wet soil w1 gr 50.29 72.57
Weight of container + dry soil w2 gr 43.16 60.94
Weight of water w3 = w 1 - w2 gr 7.13 11.63
Weight of container w4 gr 6.92 7.24
Weight of dry soil w5 = w 2 - w 4 gr 36.24 53.70
Water content ( w3 / w5 ) x 100 % % 19.67 21.66
Average Water Content % 20.67

DETERMINATION OF UNIT WEIGHT OF SOIL (ASTM D 7263 – 09)


Ring No. 1
Weight of Ring + Wet Soil w1 gr 73.44
Weight of ring w2 gr 30.07
Weight of Wet Soil w3 = w 1 - w2 gr 43.37
3
Volume of Ring v cm 25.07
g = w3/v 3
Unit Weight gr/ cm 1.73
3
Average Unit Weight gr/ cm 1.73

DETERMINATION OF SPECIFIC GRAVITY OF SOLIDS (ASTM D 854 – 92)


Picnometer No. - 68
°
Temperature - C 27.00
Weight of picno + sample w1 gr 47.10
Weight of picnometer w2 gr 32.00
Weight of sample w3 = w 1 - w2 gr 15.10
Weight of picnometer + water w4 gr 69.93
Weight of pic + sample + water w5 gr 79.41
v = [w4-(w5-w3)] / gw 3
Volume of Sample cm 5.62
Specific Gravity Gs = w3 / v Unitless 2.687

RESUME OF INDEX PROPERTIES


Water Content (%) 20.67 Material - Sandy CLAY
3
Wet Density (t/m ) 1.73 Colour - Gray
Dry Density (t/m3) 1.43 Volume of Soil Volume of Air (%) 17.01
Specific Gravity Unitless 2.69 Volume of Water Volume of Water (%) 29.63
Void Ratio (e) Unitless 0.87 Volume of Air Volume of Soil (%) 53.36
Porosity (n) Unitless 0.47
Saturated Degree (%) 63.52

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
INDEX PROPERTIES
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 14
Document No : - Sample Depth : 25.50 – 25.96 meters

DETERMINATION OF NATURAL WATER CONTENT (ASTM D 2216 – 10)


Container No. 194 190
Weight of container + wet soil w1 gr 50.89 72.51
Weight of container + dry soil w2 gr 40.26 56.31
Weight of water w3 = w 1 - w2 gr 10.63 16.20
Weight of container w4 gr 7.00 7.30
Weight of dry soil w5 = w 2 - w 4 gr 33.26 49.01
Water content ( w3 / w5 ) x 100 % % 31.96 33.05
Average Water Content % 32.51

DETERMINATION OF UNIT WEIGHT OF SOIL (ASTM D 7263 – 09)


Ring No. 1
Weight of Ring + Wet Soil w1 gr 73.96
Weight of ring w2 gr 30.07
Weight of Wet Soil w3 = w 1 - w2 gr 43.89
3
Volume of Ring v cm 25.07
g = w3/v 3
Unit Weight gr/ cm 1.75
3
Average Unit Weight gr/ cm 1.75

DETERMINATION OF SPECIFIC GRAVITY OF SOLIDS (ASTM D 854 – 92)


Picnometer No. - 71
°
Temperature - C 27.00
Weight of picno + sample w1 gr 47.15
Weight of picnometer w2 gr 32.00
Weight of sample w3 = w 1 - w2 gr 15.15
Weight of picnometer + water w4 gr 69.93
Weight of pic + sample + water w5 gr 79.42
v = [w4-(w5-w3)] / gw 3
Volume of Sample cm 5.66
Specific Gravity Gs = w3 / v Unitless 2.677

RESUME OF INDEX PROPERTIES


Water Content (%) 32.51 Material - Sandy CLAY
3
Wet Density (t/m ) 1.75 Colour - Gray
Dry Density (t/m3) 1.32 Volume of Soil Volume of Air (%) 7.69
Specific Gravity Unitless 2.68 Volume of Water Volume of Water (%) 42.95
Void Ratio (e) Unitless 1.03 Volume of Air Volume of Soil (%) 49.36
Porosity (n) Unitless 0.51
Saturated Degree (%) 84.81

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
INDEX PROPERTIES
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 15
Document No : - Sample Depth : 27.00 – 27.45 meters

DETERMINATION OF NATURAL WATER CONTENT (ASTM D 2216 – 10)


Container No. 444 172
Weight of container + wet soil w1 gr 54.60 76.08
Weight of container + dry soil w2 gr 49.65 67.71
Weight of water w3 = w 1 - w2 gr 4.95 8.37
Weight of container w4 gr 7.36 7.14
Weight of dry soil w5 = w 2 - w 4 gr 42.29 60.57
Water content ( w3 / w5 ) x 100 % % 11.70 13.82
Average Water Content % 12.76

DETERMINATION OF UNIT WEIGHT OF SOIL (ASTM D 7263 – 09)


Ring No. 1
Weight of Ring + Wet Soil w1 gr 77.31
Weight of ring w2 gr 30.07
Weight of Wet Soil w3 = w 1 - w2 gr 47.24
3
Volume of Ring v cm 25.07
g = w3/v 3
Unit Weight gr/ cm 1.88
3
Average Unit Weight gr/ cm 1.88

DETERMINATION OF SPECIFIC GRAVITY OF SOLIDS (ASTM D 854 – 92)


Picnometer No. -
°
Temperature - C 27.00
Weight of picno + sample w1 gr 47.12
Weight of picnometer w2 gr 32.00
Weight of sample w3 = w 1 - w2 gr 15.12
Weight of picnometer + water w4 gr 93.77
Weight of pic + sample + water w5 gr 103.32
Volume of Sample v = [w4-(w5-w3)] / gw cm3 5.57
Specific Gravity Gs = w3 / v Unitless 2.715

RESUME OF INDEX PROPERTIES


Water Content (%) 12.76 Material - Sandy CLAY
3
Wet Density (t/m ) 1.88 Colour - Gray
Dry Density (t/m3) 1.67 Volume of Soil Volume of Air (%) 17.11
Specific Gravity Unitless 2.71 Volume of Water Volume of Water (%) 21.33
Void Ratio (e) Unitless 0.62 Volume of Air Volume of Soil (%) 61.56
Porosity (n) Unitless 0.38
Saturated Degree (%) 55.48

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
INDEX PROPERTIES
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 16
Document No : - Sample Depth : 28.50 – 28.95 meters

DETERMINATION OF NATURAL WATER CONTENT (ASTM D 2216 – 10)


Container No. 208 184
Weight of container + wet soil w1 gr 48.21 82.26
Weight of container + dry soil w2 gr 39.57 65.15
Weight of water w3 = w 1 - w2 gr 8.64 17.11
Weight of container w4 gr 7.23 7.13
Weight of dry soil w5 = w 2 - w 4 gr 32.34 58.02
Water content ( w3 / w5 ) x 100 % % 26.72 29.49
Average Water Content % 28.10

DETERMINATION OF UNIT WEIGHT OF SOIL (ASTM D 7263 – 09)


Ring No. 1
Weight of Ring + Wet Soil w1 gr 71.05
Weight of ring w2 gr 30.07
Weight of Wet Soil w3 = w 1 - w2 gr 40.98
3
Volume of Ring v cm 25.07
g = w3/v 3
Unit Weight gr/ cm 1.63
3
Average Unit Weight gr/ cm 1.63

DETERMINATION OF SPECIFIC GRAVITY OF SOLIDS (ASTM D 854 – 92)


Picnometer No. - 74
°
Temperature - C 27.00
Weight of picno + sample w1 gr 47.12
Weight of picnometer w2 gr 32.00
Weight of sample w3 = w 1 - w2 gr 15.12
Weight of picnometer + water w4 gr 100.83
Weight of pic + sample + water w5 gr 110.33
v = [w4-(w5-w3)] / gw 3
Volume of Sample cm 5.62
Specific Gravity Gs = w3 / v Unitless 2.690

RESUME OF INDEX PROPERTIES


Water Content (%) 28.10 Material - Clayey SAND
3
Wet Density (t/m ) 1.63 Colour - Brown
Dry Density (t/m3) 1.28 Volume of Air Volume of Air (%) 16.71
Specific Gravity Unitless 2.69 Volume of Water Volume of Water (%) 35.86
Void Ratio (e) Unitless 1.11 Volume of Soil Volume of Soil (%) 47.43
Porosity (n) Unitless 0.53
Saturated Degree (%) 68.21

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
DIRECT SHEAR TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 1
Document No : - Sample Depth : 3.00 – 3.45 meters

DETERMINATION OF DIRECT SHEAR TEST (ASTM D 3080 - 98)


Specimen Diameter = 60.00 mm
Specimen Height = 20.00 mm
Specimen A B C
3
Wet Density t/m 1.596 1.702 1.706
Initial Water Content % 21.330 21.330 21.330
3
Dry Density t/m 1.315 1.317 1.328
3
Wet Density t/m
At Test Water Content %
Dry Density t/m3
Strain Rate mm/min
Strain %
Failure Condition sf kg/cm2 0.50 1.00 2.00
2
g fmax kg/cm 0.369 0.744 1.424
2
g fmin kg/cm
Specific Gravity = 2.754098
Initial Void Ratio = 1.078
Degree of Saturation = 53.902 %
TEST RESULTS
2
Shear Stress (kg/cm2)

1.5

0.5

0
0.00 0.50 1.00 1.50 2.00 2.50
Normal Stress (kg/cm2)

TEST SUMMARY

Cohesion, c = 0.029 kg/cm2

Friction Angle, f = 34.99 °

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
DIRECT SHEAR TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 2
Document No : - Sample Depth : 4.50 – 4.95 meters

DETERMINATION OF DIRECT SHEAR TEST (ASTM D 3080 - 98)


Specimen Diameter = 60.00 mm
Specimen Height = 20.00 mm
Specimen A B C
3
Wet Density t/m 1.637 1.641 1.646
Initial Water Content % 18.930 18.930 18.930
3
Dry Density t/m 1.377 1.380 1.384
3
Wet Density t/m
At Test Water Content %
Dry Density t/m3
Strain Rate mm/min
Strain %
Failure Condition sf kg/cm2 0.50 1.00 2.00
2
g fmax kg/cm 0.363 0.690 1.303
2
g fmin kg/cm
Specific Gravity = 2.7036
Initial Void Ratio = 0.948
Degree of Saturation = 53.420 %
TEST RESULTS
2.000
Shear Stress (kg/cm2)

1.500

1.000

0.500

0.000
0.00 0.50 1.00 1.50 2.00 2.50
Normal Stress (kg/cm2)

TEST SUMMARY

Cohesion, c = 0.057 kg/cm2

Friction Angle, f = 31.99 °

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
DIRECT SHEAR TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 4
Document No : - Sample Depth : 7.50 – 7.95 meters

DETERMINATION OF DIRECT SHEAR TEST (ASTM D 3080 - 98)


Specimen Diameter = 60.00 mm
Specimen Height = 20.00 mm
Specimen A B C
3
Wet Density t/m 1.698 1.702 1.706
Initial Water Content % 17.360 17.360 17.360
3
Dry Density t/m 1.447 1.450 1.453
3
Wet Density t/m
At Test Water Content %
Dry Density t/m3
Strain Rate mm/min
Strain %
Failure Condition sf kg/cm2 0.50 1.00 2.00
2
g fmax kg/cm 0.382 0.708 1.347
2
g fmin kg/cm
Specific Gravity = 2.7596
Initial Void Ratio = 0.898
Degree of Saturation = 52.939 %
TEST RESULTS
2.000
Shear Stress (kg/cm2)

1.500

1.000

0.500

0.000
0.00 0.50 1.00 1.50 2.00 2.50
Normal Stress (kg/cm2)

TEST SUMMARY

Cohesion, c = 0.063 kg/cm2

Friction Angle, f = 32.73 °

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
DIRECT SHEAR TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 5
Document No : - Sample Depth : 9.00 – 9.45 meters

DETERMINATION OF DIRECT SHEAR TEST (ASTM D 3080 - 98)


Specimen Diameter = 60.00 mm
Specimen Height = 20.00 mm
Specimen A B C
3
Wet Density t/m 1.625 1.630 1.635
Initial Water Content % 21.730 21.730 21.730
3
Dry Density t/m 1.335 1.339 1.343
3
Wet Density t/m
At Test Water Content %
Dry Density t/m3
Strain Rate mm/min
Strain %
Failure Condition sf kg/cm2 0.50 1.00 2.00
2
g fmax kg/cm 0.374 0.715 1.395
2
g fmin kg/cm
Specific Gravity = 2.7692
Initial Void Ratio = 1.062
Degree of Saturation = 56.149 %
TEST RESULTS
2.000
Shear Stress (kg/cm2)

1.500

1.000

0.500

0.000
0.00 0.50 1.00 1.50 2.00 2.50
Normal Stress (kg/cm2)

TEST SUMMARY

Cohesion, c = 0.034 kg/cm2

Friction Angle, f = 34.24 °

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
DIRECT SHEAR TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 12
Document No : - Sample Depth : 22.50 – 22.95 meters

DETERMINATION OF DIRECT SHEAR TEST (ASTM D 3080 - 98)


Specimen Diameter = 60.00 mm
Specimen Height = 20.00 mm
Specimen A B C
3
Wet Density t/m 1.735 1.739 1.746
Initial Water Content % 20.670 20.670 20.670
3
Dry Density t/m 1.438 1.441 1.447
3
Wet Density t/m
At Test Water Content %
Dry Density t/m3
Strain Rate mm/min
Strain %
Failure Condition sf kg/cm2 0.50 1.00 2.00
2
g fmax kg/cm 0.330 0.572 1.129
2
g fmin kg/cm
Specific Gravity = 2.6868
Initial Void Ratio = 0.858
Degree of Saturation = 64.129 %
TEST RESULTS
2.000
Shear Stress (kg/cm2)

1.500

1.000

0.500

0.000
0.00 0.50 1.00 1.50 2.00 2.50
Normal Stress (kg/cm2)

TEST SUMMARY

Cohesion, c = 0.052 kg/cm2

Friction Angle, f = 28.20 °

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
DIRECT SHEAR TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 14
Document No : - Sample Depth : 25.50 – 25.95 meters

DETERMINATION OF DIRECT SHEAR TEST (ASTM D 3080 - 98)


Specimen Diameter = 60.00 mm
Specimen Height = 20.00 mm
Specimen A B C
3
Wet Density t/m 1.757 1.761 1.766
Initial Water Content % 32.510 32.510 32.510
3
Dry Density t/m 1.326 1.329 1.333
3
Wet Density t/m
At Test Water Content %
Dry Density t/m3
Strain Rate mm/min
Strain %
Failure Condition sf kg/cm2 0.50 1.00 2.00
2
g fmax kg/cm 0.301 0.494 0.945
2
g fmin kg/cm
Specific Gravity = 2.6767
Initial Void Ratio = 0.998
Degree of Saturation = 86.091 %
TEST RESULTS
2.000
Shear Stress (kg/cm2)

1.500

1.000

0.500

0.000
0.00 0.50 1.00 1.50 2.00 2.50
Normal Stress (kg/cm2)

TEST SUMMARY

Cohesion, c = 0.076 kg/cm2

Friction Angle, f = 23.38 °

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
DIRECT SHEAR TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 15
Document No : - Sample Depth : 27.00 – 27.45 meters

DETERMINATION OF DIRECT SHEAR TEST (ASTM D 3080 - 98)


Specimen Diameter = 60.00 mm
Specimen Height = 20.00 mm
Specimen A B C
3
Wet Density t/m 1.892 1.897 1.900
Initial Water Content % 12.760 12.760 12.760
3
Dry Density t/m 1.678 1.682 1.685
3
Wet Density t/m
At Test Water Content %
Dry Density t/m3
Strain Rate mm/min
Strain %
Failure Condition sf kg/cm2 0.50 1.00 2.00
2
g fmax kg/cm 0.380 0.710 1.380
2
g fmin kg/cm
Specific Gravity = 2.7145
Initial Void Ratio = 0.621
Degree of Saturation = 55.654 %
TEST RESULTS
2.000
Shear Stress (kg/cm2)

1.500

1.000

0.500

0.000
0.00 0.50 1.00 1.50 2.00 2.50
Normal Stress (kg/cm2)

TEST SUMMARY

Cohesion, c = 0.045 kg/cm2

Friction Angle, f = 33.71 °

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
LABORATORY OF SOIL MECHANICS
DIRECT SHEAR TEST
Project : Matak Jetty Integrity Date of Entry : November, 5th 2017
Location : Matak, Riau Islands Date of Completion : November, 15th 2017
Client : PT. Medco Energi Internasional Borehole ID : BH – 03
Project No : - Sample ID : SPT – 16
Document No : - Sample Depth : 28.50 – 28.95 meters

DETERMINATION OF DIRECT SHEAR TEST (ASTM D 3080 - 98)


Specimen Diameter = 60.00 mm
Specimen Height = 20.00 mm
Specimen A B C
3
Wet Density t/m 1.640 1.647 1.652
Initial Water Content % 27.200 27.200 27.200
3
Dry Density t/m 1.289 1.295 1.299
3
Wet Density t/m
At Test Water Content %
Dry Density t/m3
Strain Rate mm/min
Strain %
Failure Condition sf kg/cm2 0.50 1.00 2.00
2
g fmax kg/cm 0.342 0.666 1.273
2
g fmin kg/cm
Specific Gravity = 2.6904
Initial Void Ratio = 1.070
Degree of Saturation = 67.584 %
TEST RESULTS
2.000
Shear Stress (kg/cm2)

1.500

1.000

0.500

0.000
0.00 0.50 1.00 1.50 2.00 2.50
Normal Stress (kg/cm2)

TEST SUMMARY

Cohesion, c = 0.045 kg/cm2

Friction Angle, f = 33.71 °

Tested By Checked By Approved By

Tatang Suhanda Fadli Ahmad Naufal, S.Si. Nanto Satrio, S.T., M.T.
New fender selection load calculation
DED of Matak Jetty Integrity ID-F-MA-CC0-CAL-JY-00-0001
Medco Energy

APPENDIX E
Field Work Documentation
Core Recovery at BH-01 (0.00 m – 5.00 m)

Core Recovery at BH-01 (5.00 m – 10.00 m)


Core Recovery at BH-01 (10.00 m – 15.00 m)

Core Recovery at BH-01 (15.00 m – 20.00 m)


Core Recovery at BH-01 (20.00 m – 25.00 m)

Core Recovery at BH-01 (25.00 m – 30.00 m)


Drilling Activity at BH-01
Core Recovery at BH-03 (0.00 m – 5.00 m)

Core Recovery at BH-03 (5.00 m – 10.00 m)


Core Recovery at BH-03 (10.00 m – 15.00 m)

Core Recovery at BH-03 (15.00 m – 20.00 m)


Core Recovery at BH-03 (20.00 m – 25.00 m)

Core Recovery at BH-03 (25.00 m – 30.00 m)


Drilling Activity at BH-03

Anda mungkin juga menyukai