3.

Determine the design flexural strength


To determine <feMn* (me design flexural strength), refer to the Load Factor Design Selec-
tion Table for Beams in the AISC LRFD Manual. Since the W14 x 159 is not tabulated
therein, the basic equations are used instead.
M1 / M1 \2
Q = 1.75 + 1.05 —l + 0.3 —M < 2.3
M2 \M2I
Again, M1IM2 = -1.0.

Cb = 1.75 + 1.05(-1.0) + 0.3(-1.0)2 = 1.0

If C6 = 1.0, Mn = Mp ZxFy for bending about the jc axis if Lb < L77; Z^ = &QQry/Fy) for W
shapes bent about the x axis [Eq. (F 1-4)}. For a W14 x 159, ry = 4.0 in (10.2 cm) and
(300 x 4.0 in)/(12 in/ft)
£,= ^ 16.7ft(5.1 m)

Because (Lb = 15.0 ft) < (Lp = 16.7 ft),

287in3
M.-ZS,- ,^lkiPS/in2 -8611dp.ft(1167kNm)

and <M4r = 0.90 x 861 kip-ft = 775 kip-ft (1050 kNm)


Substituting the interaction formula, we obtain
8 210 kip-ft
0.65 + — x £—
9 775 kip-ft
= 0.63 + 0.24 = 0.87 < 1.0 o.k.

By a similar solution of interaction formula (Hl-Id)9 it can be shown that a W14 x 145 is
also adequate.

Related Calculations. This procedure is the work of Abraham J. Rokach, MSCE,


Associate Director of Education, American Institute of Steel Construction. SI values were
prepared by the handbook editor.

SELECTION OF CONCRETE-FILLED
STEEL COLUMN

Select a 6-in (15.2-cm) concrete-filled steel-pipe column for a required axial compressive
strength of 200 kips (889.6 kN), where KL = 10.0 ft (3.05 m), Fy = 36 ksi (248 MPa),
fcf = 3.5 ksi (24.1 MPa), using normal-weight concrete = 145 Ib/cu ft (2320 kg/cu m)

Calculation Procedure:

1. Try a standard-weight concrete-filled pipe


2. Analyze the selected column
Check minimum wall thickness of pipe, Fig. 45:

t > D -*- = 6.625 in / 8 x 36 ksi f . = 0.083 in v(0.21 cm)


V 8£ V 29,000 ksi '
t = 0.280 in > 0.083 in o.k.

Check minimum cross-sectional area of steel pipe:

A8= <n(&-RD^(I?-Of)

= -^[(6.625 in)2 - (6.065 in)2] = 5.6 in2 (36.1 cm2)

A0 = TTfl2 = -^A
4
2=
T- x 6 065 in 2 = 28 9 in2
4 ( - ) - O86-5 cm2)

-V-
^ + ^c
^ . 5;6i"20. in2 2= o.i6>4% O.k.
5.6 in2 + 28.9

3. Analyze the selected column


In the absence of reinforcing bars:

Fmy = Fy +C2K^f-
A
S

A0
Em = E + c,Ec-j-
A
s
1 5
where E0 = w - V^, C2 = 0.85, C3 = 0.4.
The modulus of elasticity of the concrete

£ C =145 L5 VI? = 3267 ksi

The modified yield stress for composite design is


28 9
Fmy = 36 ksi + 0.85 x 3.5 ksi x ' ."f

inside diameter Dr

outside diameter D

FIGURE 45