Simulation is the best way to identify cheapest but technically suitable solution allowing in this ma
the choice.
Generators circit breaker is a device that require a detailled study cause phenomena that happen m
applications:
-Missing current zero phenomena
-Out of phase switching
-High TRV and RRRV
If the user is confident that phenomena involved, (i.e. asymmetry of the current, Missing current ze
phase switching, TRV) during operation of CB in his own plant are "below" the limits of the tests rep
standard, no simulation is required (i.e. If user is sure that fault conditions are covered from test ma
standard IEC/IEEE 62271-37-013 a new VD4G can be provided without further check).
If no information about fault condition are present, a simulation is required in order to evaluate ana
the product and evaluate
In order to facilitate the data collection we elaborate 7 sheet in each one in yellow are marked the f
of the plant, no other data except those reported in this sheet will be considered.
If a dual logo braker (IEC/IEEE 62271-37-013) is required here below the limits under that analisys o
In all the other case a detailled studyn and simulation is necessary.
n allowing in this manner an optimization of
Generator Data
Resistance Values:
- Stator Resistance Ra
Mechanical Data:
- Speed ..................................
- Moment of Inertia of Turbine/Generator/Exciter ..................................
-4- AGV-3/04/26/2019
ABB High Voltage Technologies Ltd.
Generator-CB Connection
Cable
-Length
-Cable cross section
-Number of parallel cable per phase
-Nominal voltage of cable
Bus bar
Type
-5- AGV-3/04/26/2019
ABB High Voltage Technologies Ltd.
.................................. MVA
.................................. Hz
.................................. kV
.................................. kV
.................................. kV
.................................. --
.................................. --
.................................. pu
.................................. pu
.................................. pu
.................................. pu
.................................. pu
.................................. pu
.................................. pu
............................ %
.................................. pu
.................................. s
.................................. s
.................................. s
.................................. s
.................................. s
.................................. rpm
.................................. kgm2
.................................. Ohm
.................................. kV
-6- AGV-3/04/26/2019
ABB High Voltage Technologies Ltd.
.................................. kV
………………………… m
…………………………. mm^2
…………………………. Qty.
…………………………… kV
………………………… m
……………………….. mm^2
………………………… Qty
………………………… kV
……………………….
-7- AGV-3/04/26/2019
For each motor we should know:
* = Mandatory Data, in alternative, i
Nominal Power Kw * too much high please send us data
Nominal voltage Kv *
Power factor *
Efficiency % *
Nominal rotation speed RPM *
Starting current/Nominal current ratio p.u. *
Motor-CB Connection
Cable *
-Length *
-Cable cross section *
-Number of parallel cable per phase *
-Nominal voltage of cable *
atory Data, in alternative, if the number of MV motor are
h high please send us data sheet of all motor
ABB High Voltage Technologies Ltd.
Two-Winding Transformer
Losses:
- Short-Circuit Losses (Referred to the Reference Power) .................................. kW
Impedance Values:
- Short-Circuit Impedance:
-Nominal Tap .................................. pu
- Tolerance on Short-Circuit Impedance ............................ %
- 10 - AGV-3/04/26/2019
ABB High Voltage Technologies Ltd.
HV-System Data
Rated Frequency
Rated Voltage of HV-System
Minimum Service Voltage of HV-System
Maximum Service Voltage of HV-System
Possible Island conditions? (Island= Plant run without contribution from the network but only f
- 11 - AGV-3/04/26/2019
ABB High Voltage Technologies Ltd.
.................................. Hz
.................................. kV
.................................. kV
.................................. kV
.................................. Ohm
.................................. Ohm
.................................. MVA
.................................. --
Yes No
n from the network but only from own generators)
- 12 - AGV-3/04/26/2019
ABB High Voltage Technologies Ltd.
Three-Winding Transformer
Losses:
- Short-Circuit Losses HV-LV1 ............................ kW
- Corresponding Reference Power ............................ MVA
- Short-Circuit Losses HV-LV2 ............................ kW
- Corresponding Reference Power ............................ MVA
- Short-Circuit Losses LV1-LV2 ............................ kW
- Corresponding Reference Power ............................ MVA
Impedance Values:
- Short-Circuit Impedance between HV- and LV1-Side:
- Nominal Tap ............................ pu
- Corresponding Reference Power ............................ MVA
- Tolerance on Short-Circuit Impedance ............................ %
- Short-Circuit Impedance between HV- and LV2-Side:
- Nominal Tap ............................ pu
- Corresponding Reference Power ............................ MVA
- Tolerance on Short-Circuit Impedance ............................ %
- Short-Circuit Impedance between LV1- and LV2-Side:
- Nominal Tap ............................ pu
- Corresponding Reference Power ............................ MVA
- Tolerance on Short-Circuit Impedance ............................ %
- 13 - AGV-3/04/26/2019
ABB High Voltage Technologies Ltd.
Two-Winding Transformer
Losses:
- Short-Circuit Losses (Referred to the Reference Power) .................................. kW
Impedance Values:
- Short-Circuit Impedance:
- Nominal Tap .................................. pu
- Tolerance on Short-Circuit Impedance ............................ %
- 14 - AGV-3/04/26/2019
ABB High Voltage Technologies Ltd.
Three-Winding Transformer
Losses:
- Short-Circuit Losses HV-LV1 ............................ kW
- Corresponding Reference Power ............................ MVA
- Short-Circuit Losses HV-LV2 ............................ kW
- Corresponding Reference Power ............................ MVA
- Short-Circuit Losses LV1-LV2 ............................ kW
- Corresponding Reference Power ............................ MVA
Impedance Values:
- Short-Circuit Impedance between HV- and LV1-Side:
- Nominal Tap ............................ pu
- Corresponding Reference Power ............................ MVA
- Tolerance on Short-Circuit Impedance ............................ %
- Short-Circuit Impedance between HV- and LV2-Side:
- Nominal Tap ............................ pu
- Corresponding Reference Power ............................ MVA
- Tolerance on Short-Circuit Impedance ............................ %
- Short-Circuit Impedance between LV1- and LV2-Side:
- Nominal Tap ............................ pu
- Corresponding Reference Power ............................ MVA
- Tolerance on Short-Circuit Impedance ............................ %
- 15 - AGV-3/04/26/2019
ABB High Voltage Technologies Ltd.
- X/R-Ratio ............................ --
- 16 - AGV-3/04/26/2019