PVS 800 INVERTER FALUT TRACING

1. NO COMMUNICATION FAULT
1. Check the inverter SMPS voltage (G10), (If it is less than 25.5V please increase)
2. Check the buffer (G12.1, G12.2, G12.3) (properly charging, and discharging or not, during the
contactor pickup)
3. Go to 16.3 parameter in ID2 and put pass code 2303 then do the following
4. If above said is okay, then check the 211.3, 211.6, 211.7 parameters
1. 211.3 - should be 7.5s, if it is not, please increase that
2. 211.6 and 211.7 – should be 2.5s if it is not, please increase that.

2. DI1 FAULT
1. Check the K16 relay, enable or not (if it is not enable, check the relay supply ( ac 230 V)
2. If supply is not getting there, Check the X51 MCB 3 to 9 point, that should be in continuity
3. Check the F13, F14 MCB on condition or not.

3. MAIN CNT FAULT (MAIN CONTACTOR FAULT)


1. Start the inverter by using back charge
2. Check the light is present or not in the A411 DI 1 and DI 2 point, if it is not please do following
point
3. During the AC contactor pickup check the 24 v dc supply in following point
1. A41 ( X22.3, X22.9) first AC contactor
2. A411 (X11.1, X11.2) second AC contactor
3. A411 (X12.1, X12.2) third AC contactor
4. If supply is not there check the ADDER BLOCK on K1.1, K1.2, K.13 which present in the ISU1,
ISU2, ISU3.

4. DC BRK POS ( DC BREAK POSITION FAULT)


1. Check the contactor feedback green LED light in A412 DI 1, DI 2&A411 DI 3 point
2. If the light is not present during inverter working condition, check the wiring and contactor add
on block.
3. Check Contactors coil healthiness by External looping on Particular Relay Output on Cards

5. DI4 FAUlT
1. Check the DC INCOMMING voltage at bus bar side in ISOLATOR OFF and ON condition.

6. Gnd ClS Err Fault (Ground close error)


1. If PV field is okay need to check the PGNT(Grounding) card connection.

7. GND HIGH VOLT Fault (GROUND HIGH VOLTAGE)


1. Need to check the AC side, If AC supply grounded somewhere, it may occur.

8. NET LOST
1. Switch off all MCB, AC AND DC. after 5 minutes Turn ON again.

9. CH2 Communication lost (ID1) & COMMON MODULE FAULT (ID2)


1. Check the A231 (NAMU) Board and A413 CH2 FO cables
2. Check the display ID 1 & ID 2 both are present or not.
3. If it is not, check the drive individually.
10. INT CONFIG fault
1. Start the inverter by Back charging
2. Check the green color LED light in AINT card which is present in the ISU1, 2, 3 cubical
3. If light is not present, check the particular Charging fuses and charging resistor which is present
in the ICU (second cubical)

11. CURRENT UNBALANCE FAULT (ID2) /EARTH FAULT (ID1)


1. 90% of this fault indicates the cubical name like current unbal 1, 2, 3(1, 2, 3 indicates the ISU1,
ISU2, ISU3)
2. For this check the AC 1000 A fuses and DC 800 A fuses
3. If fuses are okay, check the tightness of the bus bars joint and screws.

12. SHORT CIRCUIT Fault (SC INV3 U)


1. It will also indicate the cubical name, which phase like u, v, w)
2. If it is happened, should be Check IGBT cards on that particular cubical.
3. Reset the fault and switch on the inverter.
4. After inverter going to sleep mode. Open particular IGBT cubicle, remove and place the IGBT to
AINT cable. Apply blower will give the solution.

13. TEMP DIFF Fault or AIR TEMP


1. Mostly it will indicate like following
a. Temp diff 1u 1v 1w like that
b. Check the Particular cubical IGBT module fan is running or not
c. If it is not run check the connection, and interchange the fan
d. Is above said condition okay need to change AFIN cad and AFPS card

14. RUN DISABLE Fault


1. When Grid voltage is low this problem will arise.
2. Grid parameter is not match with inverter parameter, it may occur, it will solve automatically.

15. CHARGING FAULT


1. Initially check the ACB on or not. If it is ON,Check the Charging Ckt
1. Charging Fuses
2. Charging Resistor
3. Charging Contactor

16. AC UNDER FREQ FAULT (ID2) - ISU FAULT (ID1)


1. Need to Check AC supply(ACB-Q1)

17.Ext DI 3-FAULT
1.Check the Surge arrester in DC side & Control circuit(F52)

18.Ext DI 4-FAULT
1.Check DC field +ve to -ve floating voltage.
2. Check all the 315Amps fuses at DC bus bar section and its continuity
REDUCED RUN PROCEDURE (Cubical bypass)

If you want to run the Inverter in group 1 and group 2 individually

1. In ID2 Go to Parameter-16.3 put pass code 2303


2. Goto 16.5 put group 1 or group 2
3. Go to 16.10 put 1 if it is group 1, or put 2 if it is group 2, put 3 if it is group 1&2
4. Go to 151.37 the put ON to OFF
5. Remove the FO-cables from particular IGBT

GROUNDING Bypass
1. 25 PARAMETER in ID 1, make it OFF from Auto or ON
2. Or latch the relay K21