1. P740 – ERROR CODES


Please find hereafter the error codes for the

Communication Board: ref 2070273 001

Coprocessor Board: ref 2070273 002

Main Board: ref GN0068001 (P741) - GN004001 (P742) - GN006001 (P743)


Error Codes P740/EN

MiCOM P740 Page 1/12

Code Problem Verify or modify

0x81 10 xxxx Software initialisation error Contact your P740 Competency Centre
0x81 11 xxxx Software initialisation error Contact your P740 Competency Centre
0x81 12 xxxx Software initialisation error Contact your P740 Competency Centre
0x81 13 xxxx Software initialisation error Contact your P740 Competency Centre
0x81 14 xxxx Software initialisation error Contact your P740 Competency Centre
0x81 15 xxxx Software initialisation error Contact your P740 Competency Centre
0x81 16 xxxx Software initialisation error Contact your P740 Competency Centre
0x81 17 xxxx Incorrect model number Cortec code
0x81 18 xxxx Software initialisation error Contact your P740 Competency Centre
0x81 19 xxxx Software initialisation error Contact your P740 Competency Centre
0x81 1A xxxx Software initialisation error Contact your P740 Competency Centre
0x81 1B xxxx Software initialisation error Contact your P740 Competency Centre
0x81 1C xxxx Software initialisation error Contact your P740 Competency Centre
0x81 1D xxxx Software initialisation error Contact your P740 Competency Centre
0x81 1E xxxx Software initialisation error Contact your P740 Competency Centre
0x81 1F xxxx Software initialisation error Contact your P740 Competency Centre

0x82 20 xxxx TASK PRO software error Contact your P740 Competency Centre
0x82 21 xxxx TASK PRO software error Contact your P740 Competency Centre
0x82 22 xxxx TASK PRO software error Contact your P740 Competency Centre
0x82 23 xxxx TASK PRO software error Contact your P740 Competency Centre
0x82 24 xxxx TASK PRO software error Contact your P740 Competency Centre

0x83 50 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 51 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 52 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 53 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 54 xxxx Incorrect relay type Cortec code or the Coprocessor board address
0x83 55 xxxx 2 reboots within 5 minutes have lead to
stop
0x83 56 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 57 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 58 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 59 xxxx Main to Coprocessor board double access Contact your P740 Competency Centre
memory communication problem
0x83 60 xxxx Main to Coprocessor board double access Contact your P740 Competency Centre
memory read error
0x83 61 xxxx Main to Coprocessor communication Coprocessor board address
problem
0x83 70 xxxx Boot - Main to Coprocessor board comm Cortec or Coprocessor board or number of comms
problem board
0x83 71 xxxx Boot - Main to Coprocessor board comm Cortec or Coprocessor board or number of comms
problem board
0x83 72 0000 Boot - Main to Coprocessor board comm Cortec or Coprocessor board or number of comms
problem board
0x83 72 0001 Boot - Main to Coprocessor board comm Cortec or Coprocessor board or number of comms
problem board
0x83 72 0002 Boot - Main to Coprocessor board comm Cortec or Coprocessor board or number of comms
problem board
0x83 72 0003 Boot - Main to Coprocessor board comm Cortec or Coprocessor board or number of comms
problem board
0x83 72 0004 Boot - Main to Coprocessor board comm. Cortec or Coprocessor board or number of comms
problem board
0x83 72 0005 Boot - Main to Coprocessor board comm Cortec or Coprocessor board or number of comms
problem board
0x83 72 0006 Boot - Main to Coprocessor board comm Cortec or Coprocessor board or number of comms
problem board
0x83 72 0007 Relay ON - Main to Coprocessor comm Cortec or Coprocessor board or number of comms
problem board
0x83 73 xxxx See list of CU_OPER_MAJOR to
PU_OPER_MAJOR
0x83 74 xxxx See list of CU_OPER_PERIPH to
Error Codes P740/EN

MiCOM P740 Page 2/12

PU_OPER_PERIPH
0x83 75 xxxx See list of CU_OPER_MAJOR to
PU_OPER_MAJOR
0x83 76 xxxx See list of CU_OPER_PERIPH to
PU_OPER_PERIPH
0x83 77 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 78 xxxx See list of CU_INIT_MAJOR to
PU_INIT_MAJOR
0x83 79 xxxx See list of CU_INIT_PERIPH to
PU_INIT_PERIPH
0x83 7A xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 7B xxxx See list of CU_INIT_MAJOR to
PU_INIT_MAJOR
0x83 7C xxxx See list of CU_INIT_PERIPH to
PU_INIT_PERIPH
0x83 7D xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 7E xxxx See list of CU_OPER_MAJOR to
PU_OPER_MAJOR
0x83 7F xxxx See list of CU_OPER_PERIPH to
PU_OPER_PERIPH
0x83 80 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 81 0001 Boot - wrong number of comm board Cortec or Coprocessor board or number of comms
board
0x83 81 0002 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0004 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0008 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0010 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0020 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0040 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0080 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0100 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0200 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0400 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 0800 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 1000 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 2000 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 4000 Boot - firmware downloading error Contact your P740 Competency Centre
0x83 81 8000 Boot - wrong number of comm board or Cortec or number of comms board or opto address 0
opto board
0x83 81 8001 Boot - opto board address 0 faulty Cortec or opto address 0
0x83 81 8002 Boot - wrong number of comm board Cortec or number of comms board
0x83 84 xxxx See list of CU_OPER_MAJOR to
PU_OPER_MAJOR
0x83 85 xxxx See list of CU_OPER_PERIPH to
PU_OPER_PERIPH
0x83 86 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 87 xxxx See list of CU_OPER_MAJOR to
PU_OPER_MAJOR
0x83 88 xxxx See list of CU_OPER_PERIPH to
PU_OPER_PERIPH
0x83 89 xxxx TASK DIAL software error Contact your P740 Competency Centre
0x83 8A xxxx See list of CU_OPER_MAJOR to
PU_OPER_MAJOR
0x83 8B xxxx See list of CU_OPER_PERIPH to
PU_OPER_PERIPH
0x83 8C xxxx TASK DIAL software error Contact your P740 Competency Centre

0x84 A0 xxxx TASK PSLOG software error Contact your P740 Competency Centre

0x85 30 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 31 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 32 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 33 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 34 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 35 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 36 xxxx TASK SUP software error Contact your P740 Competency Centre
Error Codes P740/EN

MiCOM P740 Page 3/12

0x85 37 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 38 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 39 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 3A xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 3B xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 3C xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 3D xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 3E xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 3F xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 40 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 41 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 42 xxxx TASK SUP software error Contact your P740 Competency Centre
0x85 70 xxxx Coprocessor board error Coprocessor

0x86 B0 xxxx TASK CBF software error Contact your P740 Competency Centre
0x86 B1 xxxx TASK CBF software error Contact your P740 Competency Centre
0x86 B2 xxxx TASK CBF software error Contact your P740 Competency Centre
P741 - INIT MODE

CU_INIT_MAJOR
2000 System error Coprocessor firmware
4008 External autotest RAM Coprocessor
4010 Autotest interruptions Coprocessor
4018 Comm board autotest Coprocessor
8001 Main to Coprocessor communication Coprocessor or Main board
8002 Main to Coprocessor communication Coprocessor or Main board
8003 Main to Coprocessor communication Coprocessor or Main board
8004 Main to Coprocessor communication Coprocessor or Main board
8005 Main to Coprocessor communication Coprocessor or Main board
8006 Main to Coprocessor communication Coprocessor or Main board
8007 Main to Coprocessor communication - no Coprocessor address or Coprocessor or Main board
IT

Logical See lines included in the logical OR See lines included


OR

CU_INIT_PERIPH
0081 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0082 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0083 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0084 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0085 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0086 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0087 Coprocessor to Comm board 6 Coprocessor or Comm board 6 or Comm board 6
communication - no IT address
0101 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0102 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0103 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0104 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0105 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0106 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0107 Coprocessor to Comm board 5 Coprocessor or Comm board 5 or Comm board 5
communication - no IT address
0201 Coprocessor to Comm board 4 Coprocessor or Comm board 4
Error Codes P740/EN

MiCOM P740 Page 4/12

communication
0202 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
0203 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
0204 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
0205 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
0206 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
0207 Coprocessor to Comm board 4 Coprocessor or Comm board 4 or Comm board 4
communication - no IT address
0401 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0402 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0403 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0404 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0405 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0406 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0407 Coprocessor to Comm board 3 Coprocessor or Comm board 3 or Comm board 3
communication - no IT address
0801 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0802 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0803 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0804 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0805 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0806 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0807 Coprocessor to Comm board 2 Coprocessor or Comm board 2 or Comm board 2
communication - no IT address
1001 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1002 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1003 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1004 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1005 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1006 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1007 Coprocessor to Comm board 1 Coprocessor or Comm board 1 or Comm board 1
communication - no IT address
2001 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2002 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2003 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2004 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2005 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2006 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2007 Coprocessor to Comm board 0 Coprocessor or Comm board 0 or Comm board 0
communication - no IT address
Error Codes P740/EN

MiCOM P740 Page 5/12

3FC0 no IT Comm board to Coprocessor board Coprocessor or Com or ribbon cable


4008 Relay 1 board missing Relay 1 board or Relay 1 board address
4010 Relay 1 board writing error Relay 1 board
8008 Opto 1 board missing Opto 1 board or Opto 1 board address
8010 Opto 1 board read error Opto 1 board

Logical See lines included in the logical OR See lines included


OR
Ex: 3006 = 2006 OR 1006
P741 -OPERATING MODE

CU_OPER_MAJOR
04xx Topology autotest Coprocessor firmware
08xx Fixed Scheme Logic Autotest Coprocessor firmware
1100 Measurement or Topology autotest Coprocessor firmware
1200 Measurement or Topology autotest Coprocessor firmware
2000 System error Coprocessor firmware
4008 Data RAM autotest Coprocessor
4010 RAM program autotest Coprocessor
4018 Double access memory autotest Coprocessor
8001 Main to Coprocessor communication Coprocessor or Main board
8002 Main to Coprocessor communication Coprocessor or Main board
8003 Main to Coprocessor communication Coprocessor or Main board
8004 Main to Coprocessor communication Coprocessor or Main board
8005 Main to Coprocessor communication Coprocessor or Main board
8006 Main to Coprocessor communication Coprocessor or Main board
8007 Main to Coprocessor communication - no Coprocessor address or Coprocessor or Main board
IT

Logical See lines included in the logical OR See lines included


OR

CU_OPER_PERIPH
0081 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0082 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0083 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0084 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0085 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0086 Coprocessor to Comm board 6 Coprocessor or Comm board 6
communication
0087 Coprocessor to Comm board 6 Coprocessor or Comm board 6 or Comm board 6
communication - no IT address
0101 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0102 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0103 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0104 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0105 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0106 Coprocessor to Comm board 5 Coprocessor or Comm board 5
communication
0107 Coprocessor to Comm board 5 Coprocessor or Comm board 5 or Comm board 5
communication - no IT address
0201 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
0202 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
0203 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
Error Codes P740/EN

MiCOM P740 Page 6/12

0204 Coprocessor to Comm board 4 Coprocessor or Comm board 4


communication
0205 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
0206 Coprocessor to Comm board 4 Coprocessor or Comm board 4
communication
0207 Coprocessor to Comm board 4 Coprocessor or Comm board 4 or Comm board 4
communication - no IT address
0401 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0402 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0403 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0404 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0405 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0406 Coprocessor to Comm board 3 Coprocessor or Comm board 3
communication
0407 Coprocessor to Comm board 3 Coprocessor or Comm board 3 or Comm board 3
communication - no IT address
0801 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0802 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0803 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0804 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0805 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0806 Coprocessor to Comm board 2 Coprocessor or Comm board 2
communication
0807 Coprocessor to Comm board 2 Coprocessor or Comm board 2 or Comm board 2
communication - no IT address
1001 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1002 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1003 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1004 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1005 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1006 Coprocessor to Comm board 1 Coprocessor or Comm board 1
communication
1007 Coprocessor to Comm board 1 Coprocessor or Comm board 1 or Comm board 1
communication - no IT address
2001 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2002 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2003 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2004 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2005 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2006 Coprocessor to Comm board 0 Coprocessor or Comm board 0
communication
2007 Coprocessor to Comm board 0 Coprocessor or Comm board 0 or Comm board 0
communication - no IT address
3FC0 no IT Comm board to Coprocessor board Coprocessor or Com or ribbon cable
4008 Relay 1 board missing Relay 1 board or Relay 1 board address
4010 Relay 1 board writing error Relay 1 board
8008 Opto 1 board missing Opto 1 board or Opto 1 board address
8010 Opto 1 board read error Opto 1 board
Error Codes P740/EN

MiCOM P740 Page 7/12

Logical See lines included in the logical OR See lines included


OR
Ex: 3006 = 2006 OR 1006
P742 / P743 - INIT MODE

PU_INIT_MAJOR
2000 System error Coprocessor firmware
4008 External autotest RAM Coprocessor
4010 Autotest interruptions Coprocessor
4018 Comm board autotest Coprocessor
8001 Main to Coprocessor communication Coprocessor or Main board
8002 Main to Coprocessor communication Coprocessor or Main board
8003 Main to Coprocessor communication Coprocessor or Main board
8004 Main to Coprocessor communication Coprocessor or Main board
8005 Main to Coprocessor communication Coprocessor or Main board
8006 Main to Coprocessor communication Coprocessor or Main board
8007 Main to Coprocessor communication - no Coprocessor address or Coprocessor or Main board
IT

Logical See lines included in the logical OR See lines included


OR

PU_INIT_PERIPH
0200 Analogue module acquisition problem Analogue module
0408 Relay 3 board missing Relay 3 board or Relay 3 board address
0410 Relay 3 board writing error Relay 3 board
0808 Opto 3 board missing Opto 3 board or Opto 3 board address
0810 Opto 3 board read error Opto 3 board
1008 Relay 2 board missing Relay 2 board or Relay 2 board address
1010 Relay 2 board writing error Relay 2 board
2008 Opto 2 board missing Opto 2 board or Opto 2 board address
2010 Opto 2 board read error Opto 2 board
4008 Relay 1 board missing Relay 1 board or Relay 1 board address
4010 Relay 1 board writing error Relay 1 board
8008 Opto 1 board missing Opto 1 board or Opto 1 board address
8010 Opto 1 board read error Opto 1 board

Logical See lines included in the logical OR See lines included


OR
Ex: 5010 = 4010 OR 1010
P742 / P743 - OPERATING MODE

PU_OPER_MAJOR
04xx Topology autotest Coprocessor firmware
08xx Fixed Scheme Logic Autotest Coprocessor firmware
1100 Measurement or Topology autotest Coprocessor firmware
1200 Measurement or Topology autotest Coprocessor firmware
2000 System error Coprocessor firmware
4008 External autotest RAM Coprocessor
4010 Interruptions autotest Coprocessor
4018 Comm board autotest Coprocessor
8001 Main to Coprocessor communication Coprocessor or Main board
8002 Main to Coprocessor communication Coprocessor or Main board
8003 Main to Coprocessor communication Coprocessor or Main board
8004 Main to Coprocessor communication Coprocessor or Main board
8005 Main to Coprocessor communication Coprocessor or Main board
8006 Main to Coprocessor communication Coprocessor or Main board
8007 Main to Coprocessor communication - no Coprocessor address or Coprocessor or Main board
IT

Logical See lines included in the logical OR See lines included


OR

PU_OPER_PERIPH
Error Codes P740/EN

MiCOM P740 Page 8/12

0200 analogue module acquisition problem Analogue module


0408 Relay 3 board missing Relay 3 board or Relay 3 board address
0410 Relay 3 board writing error Relay 3 board
0808 Opto 3 board missing Opto 3 board or Opto 3 board address
0810 Opto 3 board read error Opto 3 board
1008 Relay 2 board missing Relay 2 board or Relay 2 board address
1010 Relay 2 board writing error Relay 2 board
2008 Opto 2 board missing Opto 2 board or Opto 2 board address
2010 Opto 2 board read error Opto 2 board
4008 Relay 1 board missing Relay 1 board or Relay 1 board address
4010 Relay 1 board writing error Relay 1 board
8008 Opto 1 board missing Opto 1 board or Opto 1 board address
8010 Opto 1 board read error Opto 1 board

Logical See lines included in the logical OR See lines included


OR
Ex: a010 = 2010 OR 8010