Anda di halaman 1dari 36

ENERGY WORLD CORPORATION LIMITED

Sengkang LNG Plant - 88 800 m³ LNG Storage Tank for EWC

Safety

Hydraulic calculation for deluge system

01 First issue 15/04/2013


SOFG
DATE
REVISION LABEL ECR NBR DESCRIPTION BY CHECKED APPROVED
DD/MM/YYYY

TECHNICAL DIVISION
EWC - Sengkang LNG Plant - 88 800 m³ LNG Storage Tank for EWC
TO BE APPLIED TO TANK NUMBERS : SEE DOC T025B TD LIST GST SYSTEM

HYDRAULIC CALCULATION FOR DELUGE SYSTEM

1, route de Versailles
78470 St-Rémy-lès-Chevreuse - FRANCE T025B SAF CN 000020
6408-S-Z-CH-SGZ-100001
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of
PAGE: 1 NBR OF PAGES: 36 undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the
exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by
SCALE: None SHEET SIZE: A4 any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal
liability - © GTT, 2010-2011

document_projet-rev09
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 2 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

REVISION SHEET

Page Nbr
REV.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45

01 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x

-
-
Sheets affected by the current revision

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 3 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

CONTENTS

EXECUTIVE SUMMARY .................................................................................................................................................. 4


1. INTRODUCTION ....................................................................................................................................................... 5
1.1. GENERAL ........................................................................................................................................................... 5
1.2. SCOPE ............................................................................................................................................................... 5
1.3. LIMITATION ........................................................................................................................................................ 5
1.4. REFERENCE DOCUMENTS ............................................................................................................................. 5
1.5. LIST OF ABBREVIATIONS ................................................................................................................................ 5
1.6. APPLICATION CODES & STANDARDS ........................................................................................................... 5
2. METHODOLOGY ...................................................................................................................................................... 6
3. STUDY INPUTS ......................................................................................................................................................... 6
3.1. FLUID PROPERTIES ......................................................................................................................................... 6
3.2. PIPING MATERIAL ............................................................................................................................................. 6
3.3. WATER SPRAY NOZZLES ................................................................................................................................ 6
4. RESULTS .................................................................................................................................................................. 7
5. ANALYSIS OF RESULTS ......................................................................................................................................... 7
APPENDIX 1. DELUGE SYSTEM ARRANGEMENT DIAGRAM MODELIZED ON FATHOM SOFTWARE ......... 8
APPENDIX 2. RESULTS FOR WATER SPRAY NOZZLES (10.6 BARG AT DELUGE VALVE OUTLET) ......... 18
APPENDIX 3. RESULTS FOR PIPES (10.6 BARG AT DELUGE VALVE OUTLET) ............................................... 21

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 4 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

EXECUTIVE SUMMARY
With a pressure of 10.6 barg at the deluge valve outlet the requirements of minimum 3 barg at the hydraulically most
remote water spray nozzle and a maximum velocity in pipes of 5 m/s are satisfied.
A Restrictive Orifice downstream each deluge valve is not required for the deluge skids L201A and L201B.

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 5 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

1. INTRODUCTION
3
This document deals with one 88 800 m LNG storage tank equipped with the GST membrane system. This tank is
part of a liquefaction unit to be constructed in the Sengkang Province, Indonesia.

1.1. GENERAL
The purpose of this document is to provide steady state hydraulic verification of the deluge system used for the
protection of the LNG Storage tank platforms.
The hydraulic verification has been performed for the deluge system piping downstream of the deluge valves located
within skid tag numbers L201A and L201B.
The analysis has been performed for the normal mode operation, i.e. the system is supplied from only one deluge
valve skid.
The hydraulic verification has been performed based on firewater isometrics extracting from 3D model. The main
design requirements to be checked through the actual exercise with the proposed recommendations are provided in
section 5 of the present report.

1.2. SCOPE
The main objectives of the steady state hydraulic verification of the deluge system are as follows:
- To ensure that the design specification for the deluge system network in terms of flow and pressure are
achieved at all spray nozzles, including the hydraulically most remote nozzle.
- To determine the flow characteristics downstream of the deluge valves i.e. pressure, flow and velocity.
- To ensure that the velocity does not exceed 5m/s in the system.
- To define if a Restrictive Orifice is necessary or not at the deluge valve outlet.

1.3. LIMITATION
This document presents the hydraulic calculations for the deluge system of the LNG storage Tank and should be
integrated in the overall firewater system hydraulic analysis of the plant.

1.4. REFERENCE DOCUMENTS


[1]: List of applicable codes & standards n° T025B GL COD 000001
[2]: Safety Design Philosophy n° T025B SAF HYP 000010
[3]: Firewater Demand Calculation Note n° T025B SAF CN 000010
[4]: UID Deluge System n° T025B SAF DIAG 000020
[5]: Piping isometrics n° T025B PIP ISO 000010

1.5. LIST OF ABBREVIATIONS


RO Restrictive Orifice

1.6. APPLICATION CODES & STANDARDS


Full consideration will be given to the latest issues of the codes and standards listed in document referenced [1].
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 6 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

2. METHODOLOGY
The steady state hydraulic verification of the LNG Storage tank deluge system was carried out using the software
FATHOM version 6.0.
The various steps involved in the analysis are:
- Prepare detailed inputs for simulation model by determining various fittings, lengths, diameter, elevation and
equipment specifications present in all pipe sections
- Define the K factor of each water spray nozzle
- Define the fluid properties involved in the system
- Determine a pressure at the outlet of the deluge valve
- Carry out simulation checking if the pressure at the hydraulically most remote water spray nozzle does not fall
under 3barg and if the velocity in the pipes is lower than 5m/s
- Make iterative cases in order to define the pressure necessary at the outlet of the deluge valve complying with
the criteria here above mentioned

3. STUDY INPUTS
The diagram showing details of the arrangement of the deluge system is enclosed in Appendix 1 of this report.

3.1. FLUID PROPERTIES


- Fluid: Seawater
3
- Density: 1025 kg/m
- Dynamic viscosity: 0.0007 Pa.s
- Vapour pressure: 0.048 bar

3.2. PIPING MATERIAL


Deluge distribution piping material is made of steel.

3.3. WATER SPRAY NOZZLES


The following properties are considered for the nozzles designed for the deluge system of the LNG storage Tank:

K factor
Quantity of Nozzles
( (l/min) / √barg )

38 97

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 7 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

4. RESULTS
The results of the simulation of the deluge system are enclosed in Appendix 2.
A brief summary of the results of the simulation are presented in table below. The flow and the pressure reported are
outlet of the deluge valve skid. The maximum velocity in pipe and the pressure at the hydraulically most remote water
spray nozzle inlet are also indicated:

Flow at outlet of the Pressure at outlet of the Minimum pressure at


Maximum velocity in pipe
deluge valve skid deluge valve skid water spray nozzle inlet
3 (m/s)
(m /h) (barg) (barg)

410 10,6 4,8 3,06

5. ANALYSIS OF RESULTS
At this stage of the project, the firewater network operating pressure in the LNG storage area is not known.
In order to respect NFPA 15 Standard, which allows a minimum pressure of 1.4 barg at water spray nozzle, it is
3
recommended that the pressure at deluge valve is included within the 9-10,6 barg range at 410 m /h.
Optimum conditions are reached with 10,6 barg at deluge valve (full development of the water spray pattern of each
nozzle and better coverage under windy conditions).
It is not anticipated a firewater network working pressure above 10,6 barg. As a consequence, a restriction orifice
downstream deluge valves is not required.

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 8 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

APPENDIX 1. DELUGE SYSTEM ARRANGEMENT DIAGRAM MODELIZED ON FATHOM SOFTWARE

Zoom 1
Zoom 3 Zoom 4

Zoom 2

Zoom 5 Zoom 8

Zoom 9

Zoom 7
Zoom 6

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 9 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Zoom 1

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 10 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Zoom 2

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 11 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Zoom 3

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 12 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Zoom 4

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 13 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Zoom 5

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 14 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Zoom 6

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 15 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Zoom 7

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 16 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Zoom 8

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 17 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Zoom 9

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property
of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 18 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

APPENDIX 2. RESULTS FOR WATER SPRAY NOZZLES (10.6 BARG


AT DELUGE VALVE OUTLET)

Pressure Static In Volumetric Flow


Spray Discharge N°
(barg) Rate (l/min)
37 3,483 70,62
43 3,417 69,94
46 3,418 69,95
52 3,433 70,11
55 3,434 70,12
62 3,42 69,98
66 3,417 69,94
78 3,51 70,89
85 3,454 70,32
88 3,456 70,34
95 3,46 70,38
98 3,461 70,4
105 3,471 70,5
108 3,473 70,52
116 3,446 70,24
119 3,447 70,26
125 3,435 70,13
128 3,437 70,15
137 3,369 69,45
142 3,332 69,07
148 3,335 69,1
157 3,223 67,93
162 3,189 67,57
165 3,189 67,57
170 3,203 67,72
173 3,203 67,72
181 3,056 66,15
185 3,207 67,76
198 3,215 67,85
205 3,162 67,29
208 3,164 67,3
215 3,168 67,35
218 3,169 67,36
226 3,155 67,21
229 3,156 67,22
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 19 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Pressure Static In Volumetric Flow


Spray Discharge N°
(barg) Rate (l/min)
238 3,175 67,43
241 3,176 67,44
248 3,176 67,44
251 3,178 67,45
262 3,192 67,61
267 3,14 67,05
270 3,141 67,06
275 3,161 67,27
278 3,161 67,28
283 3,126 66,9
291 3,182 67,5
295 3,06 66,2
308 3,546 71,26
311 3,529 71,08
314 3,522 71,02
322 3,513 70,93
325 3,416 69,94
330 3,299 68,73
334 3,347 69,23
352 3,584 71,64
357 3,585 71,64
361 3,604 71,83
368 3,638 72,18
371 3,662 72,41
379 3,653 72,32
382 3,649 72,28
389 3,749 73,26
392 3,743 73,21
396 3,709 72,88
404 3,803 73,79
407 3,799 73,76
414 3,803 73,79
417 3,826 74,02
427 3,739 73,17
432 3,738 73,16
456 3,455 70,34
461 3,458 70,37
466 3,466 70,44
470 3,53 71,1
479 3,561 71,41
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 20 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Pressure Static In Volumetric Flow


Spray Discharge N°
(barg) Rate (l/min)
482 3,561 71,41
487 3,527 71,07
490 3,48 70,59
498 3,693 72,71
503 3,657 72,37
506 3,61 71,89
514 3,721 72,99
517 3,714 72,93
525 3,746 73,24
528 3,739 73,17
536 3,835 74,1
539 3,828 74,03
548 3,917 74,89
551 3,91 74,82
561 3,898 74,7
564 3,932 75,03
574 3,821 73,96
578 3,817 73,93
590 3,419 69,97
595 3,415 69,92
605 3,126 66,91
609 3,126 66,9

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 21 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

APPENDIX 3. RESULTS FOR PIPES (10.6 BARG AT DELUGE


VALVE OUTLET)

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

1 FW506 409,547 3,5248 0 3,41 10,6 10,145


2 FW501 0 0 0 3,41 10,522 10,18
3 FW506 409,547 3,5248 3,41 3,41 10,118 10,116
4 FW501 409,547 3,5248 3,41 3,41 10,116 10,108
5 FW501 409,547 3,5248 3,41 4,11 10,081 10,006
6 FW501 409,547 3,5248 4,11 4,11 9,992 9,983
7 FW501 409,547 3,5248 4,11 48,988 9,956 5,235
8 FW501 409,547 3,5248 48,988 48,988 5,208 5,188
9 FW501 409,547 3,5248 48,988 48,988 5,161 5,125
10 FW501 409,547 3,5248 48,988 51,598 5,098 4,824
11 FW501 409,547 3,5248 51,598 51,598 4,797 4,712
12 FW501 409,547 3,5248 51,598 51,598 4,685 4,678
13 FW501 409,547 3,5248 51,598 55,167 4,651 4,275
14 FW502 209,806 3,1268 55,167 57,611 4,289 4,031
15 FW504 199,74 2,9768 55,167 55,167 4,294 4,286
16 FW502 209,806 3,1268 57,611 57,611 4,008 3,999
17 FW502 209,806 3,1268 57,611 57,611 3,976 3,974
18 FW502 180,366 2,688 57,611 57,611 3,987 3,969
19 FW502 125,524 4,2454 57,611 57,584 3,913 3,852
20 FW502 125,524 4,2454 57,584 57,584 3,805 3,777
21 FW502 125,524 4,2454 57,584 57,584 3,73 3,718
22 FW502 113,067 3,8241 57,584 57,584 3,735 3,671
23 FW502 84,722 2,8654 57,584 57,584 3,704 3,665
24 FW502 32,212 1,0895 57,584 57,584 3,701 3,696
25 FW502 0 0 57,584 57,584 3,702 3,702
26 FW530 29,441 3,7776 57,611 57,611 3,951 3,946
27 FW530 29,441 3,7776 57,611 57,611 3,924 3,913
28 FW530 29,441 3,7776 57,611 57,611 3,891 3,884
29 FW530 21,045 2,7003 57,611 57,611 3,92 3,907
30 FW530 12,631 1,6207 57,611 57,611 3,931 3,914
31 FW530 4,237 0,5437 57,611 57,611 3,926 3,923
32 FW530 0 0 57,611 57,611 3,925 3,925
33 FW536 4,237 0,8962 57,611 57,854 3,921 3,896

This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 22 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

34 FW536 4,237 0,8962 57,854 57,854 3,893 3,887


35 FW536 4,237 0,8962 57,854 61,164 3,884 3,544
36 FW536 4,237 0,8962 61,164 61,153 3,541 3,541
37 FW536 4,237 3,4212 61,153 60,967 3,484 3,483
38 FW537 8,394 1,7752 57,611 57,728 3,911 3,898
39 FW537 8,394 1,7752 57,728 61,361 3,893 3,496
40 FW537 8,394 1,7752 61,361 61,361 3,486 3,482
41 FW537 4,197 0,8875 61,361 61,361 3,494 3,492
42 FW537 4,197 3,3883 61,361 61,203 3,435 3,44
43 FW537 4,197 3,3883 61,203 61,017 3,417 3,417
44 FW537 4,197 0,8877 61,361 61,361 3,494 3,494
45 FW537 4,197 3,3888 61,361 61,203 3,436 3,441
46 FW537 4,197 3,3888 61,203 61,017 3,418 3,418
47 FW538 8,414 1,7795 57,611 57,728 3,929 3,916
48 FW538 8,414 1,7795 57,728 61,361 3,91 3,513
49 FW538 8,414 1,7795 61,361 61,361 3,503 3,499
50 FW538 4,207 0,8897 61,361 61,361 3,511 3,51
51 FW538 4,207 3,3966 61,361 61,203 3,452 3,457
52 FW538 4,207 3,3966 61,203 61,017 3,434 3,433
53 FW538 4,207 0,8898 61,361 61,361 3,511 3,511
54 FW538 4,207 3,3971 61,361 61,203 3,453 3,458
55 FW538 4,207 3,3971 61,203 61,017 3,435 3,434
56 FW540 8,396 1,7756 57,611 57,814 3,941 3,919
57 FW540 8,396 1,7756 57,814 57,814 3,909 3,887
58 FW540 8,396 1,7756 57,814 61,361 3,877 3,49
59 FW540 4,199 0,888 61,361 61,361 3,502 3,501
60 FW540 4,199 0,888 61,361 61,361 3,498 3,496
62 FW540 4,199 3,3901 61,361 61,203 3,439 3,444
63 FW540 4,199 3,3901 61,203 61,017 3,421 3,42
64 FW539 4,197 0,8876 61,361 61,361 3,502 3,497
65 FW539 4,197 0,8876 61,361 61,361 3,494 3,493
66 FW539 4,197 3,3884 61,203 61,017 3,417 3,417
67 FW539 4,197 3,3884 61,361 61,203 3,435 3,44
68 FW531 54,842 3,194 57,611 57,611 3,953 3,95
69 FW531 37,995 2,2129 57,611 57,611 3,977 3,97
70 FW531 29,534 1,7201 57,611 57,611 3,98 3,967
71 FW531 21,087 1,2281 57,611 57,611 3,975 3,969
72 FW531 12,647 0,7366 57,611 57,611 3,974 3,972
73 FW531 0 0 57,611 57,611 3,975 3,975
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 23 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

74 FW541 4,254 0,8996 57,611 58,859 3,971 3,842


75 FW541 4,254 0,8996 58,859 59,115 3,841 3,814
76 FW541 4,254 0,8996 59,115 61,247 3,813 3,593
77 FW541 4,254 0,8996 61,247 61,247 3,591 3,589
78 FW541 4,254 3,4343 61,247 61,089 3,53 3,534
79 FW541 4,254 3,4343 61,089 60,973 3,51 3,51
80 FW542 8,44 1,785 57,611 58,877 3,96 3,822
81 FW542 8,44 1,785 58,877 59,115 3,816 3,789
82 FW542 8,44 1,785 59,115 61,411 3,784 3,533
83 FW542 8,44 1,785 61,411 61,411 3,523 3,521
84 FW542 4,219 0,8924 61,411 61,411 3,533 3,531
85 FW542 4,219 3,4068 61,411 61,253 3,473 3,478
86 FW542 4,219 3,4068 61,253 61,067 3,454 3,454
87 FW542 4,221 0,8926 61,411 61,411 3,533 3,533
88 FW542 4,221 3,4076 61,411 61,253 3,475 3,479
89 FW542 4,221 3,4076 61,253 61,067 3,456 3,456
90 FW543 8,447 1,7864 57,611 58,877 3,966 3,828
91 FW543 8,447 1,7864 58,877 59,115 3,822 3,795
92 FW543 8,447 1,7864 59,115 61,411 3,79 3,539
93 FW543 8,447 1,7864 61,411 61,411 3,528 3,527
94 FW543 4,223 0,8931 61,411 61,411 3,539 3,537
95 FW543 4,223 3,4096 61,411 61,253 3,479 3,483
96 FW543 4,223 3,4096 61,253 61,067 3,46 3,46
97 FW543 4,224 0,8933 61,411 61,411 3,539 3,539
98 FW543 4,224 3,4104 61,411 61,253 3,481 3,485
99 FW543 4,224 3,4104 61,253 61,067 3,462 3,461
100 FW544 8,461 1,7894 57,611 58,877 3,978 3,84
101 FW544 8,461 1,7894 58,877 59,115 3,834 3,807
102 FW544 8,461 1,7894 59,115 61,411 3,802 3,55
103 FW544 8,461 1,7894 61,411 61,411 3,54 3,539
104 FW544 4,23 0,8946 61,411 61,411 3,551 3,549
105 FW544 4,23 3,4152 61,411 61,253 3,491 3,495
106 FW544 4,23 3,4152 61,253 61,067 3,472 3,471
107 FW544 4,231 0,8948 61,411 61,411 3,551 3,551
108 FW544 4,231 3,4161 61,411 61,253 3,492 3,497
109 FW544 4,231 3,4161 61,253 61,067 3,473 3,473
110 FW546 16,847 2,1616 57,611 57,87 3,979 3,95
111 FW546 16,847 2,1616 57,87 57,87 3,937 3,911
112 FW546 8,43 1,0817 57,87 57,87 3,929 3,929
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 24 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

113 FW546 8,43 1,7829 57,87 61,411 3,915 3,528


114 FW546 8,43 1,7829 61,411 61,411 3,518 3,513
115 FW546 4,215 0,8913 61,411 61,411 3,525 3,523
116 FW546 4,215 3,4028 61,411 61,253 3,465 3,47
117 FW546 4,215 3,4028 61,253 61,067 3,446 3,446
118 FW546 4,215 0,8915 61,411 61,411 3,525 3,524
119 FW546 4,215 3,4035 61,411 61,253 3,467 3,471
120 FW546 4,215 3,4035 61,253 61,067 3,448 3,447
121 FW545 8,417 1,78 57,87 61,411 3,919 3,532
122 FW545 8,417 1,78 61,411 61,411 3,522 3,517
123 FW545 8,417 1,78 61,411 61,411 3,507 3,502
124 FW545 4,208 0,8899 61,411 61,411 3,514 3,512
125 FW545 4,208 3,3974 61,411 61,253 3,454 3,458
126 FW545 4,208 3,3974 61,253 61,067 3,435 3,435
127 FW545 4,209 0,8901 61,411 61,411 3,514 3,513
128 FW545 4,209 3,3982 61,411 61,253 3,456 3,46
129 FW545 4,209 3,3982 61,253 61,067 3,437 3,437
130 FW532 12,457 1,5984 57,584 57,584 3,797 3,796
131 FW532 8,311 1,0664 57,584 57,584 3,803 3,795
132 FW532 4,167 0,5347 57,584 57,584 3,799 3,798
133 FW532 0 0 57,584 57,584 3,799 3,799
134 FW547 4,167 0,8813 57,584 57,952 3,795 3,758
135 FW547 4,167 0,8813 57,952 57,952 3,755 3,751
136 FW547 4,167 0,8813 57,952 60,764 3,749 3,46
137 FW547 4,167 3,3644 60,764 60,753 3,403 3,391
138 FW547 4,167 3,3644 60,753 60,567 3,369 3,369
139 FW548 4,144 0,8764 57,584 58,052 3,797 3,749
140 FW548 4,144 0,8764 58,052 58,052 3,746 3,744
141 FW548 4,144 0,8764 58,052 61,164 3,742 3,422
142 FW548 4,144 3,3459 61,164 61,153 3,366 3,354
143 FW548 4,144 3,3459 61,153 60,967 3,331 3,332
144 FW549 4,146 0,8769 57,584 58,052 3,805 3,757
145 FW549 4,146 0,8769 58,052 58,052 3,755 3,753
146 FW549 4,146 0,8769 58,052 58,052 3,75 3,748
147 FW549 4,146 0,8769 58,052 61,164 3,745 3,425
148 FW549 4,146 3,3477 61,164 61,153 3,369 3,357
149 FW549 4,146 3,3477 61,153 60,967 3,335 3,335
150 FW533 28,345 3,6369 57,584 57,584 3,678 3,673
151 FW533 20,31 2,606 57,584 57,584 3,706 3,665
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 25 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

152 FW533 12,184 1,5633 57,584 57,584 3,687 3,673


153 FW533 4,076 0,523 57,584 57,584 3,684 3,682
154 FW533 0 0 57,584 57,584 3,684 3,684
155 FW550 4,076 0,862 57,584 61,164 3,68 3,312
156 FW550 4,076 0,862 61,164 61,164 3,31 3,309
157 FW550 4,076 3,2908 61,164 61,153 3,255 3,244
158 FW550 4,076 3,2908 61,153 60,967 3,222 3,223
159 FW551 8,108 1,7148 57,584 61,361 3,67 3,259
160 FW551 8,108 1,7148 61,361 61,361 3,25 3,248
161 FW551 4,054 0,8574 61,361 61,361 3,259 3,257
162 FW551 4,054 3,2733 61,361 61,203 3,204 3,209
163 FW551 4,054 3,2733 61,203 61,017 3,188 3,189
164 FW551 4,054 0,8574 61,361 61,361 3,259 3,257
165 FW551 4,054 3,2733 61,361 61,203 3,204 3,209
166 FW551 4,054 3,2733 61,203 61,017 3,188 3,189
167 FW552 8,126 1,7186 57,584 61,361 3,685 3,274
168 FW552 8,126 1,7186 61,361 61,361 3,264 3,262
169 FW552 4,063 0,8593 61,361 61,361 3,274 3,272
170 FW552 4,063 3,2805 61,361 61,203 3,218 3,223
171 FW552 4,063 3,2805 61,203 61,017 3,202 3,203
172 FW552 4,063 0,8593 61,361 61,361 3,274 3,272
173 FW552 4,063 3,2805 61,361 61,203 3,218 3,223
174 FW552 4,063 3,2805 61,203 61,017 3,202 3,203
175 FW554 8,035 1,6993 57,584 58,102 3,726 3,67
176 FW554 8,035 1,6993 58,102 58,102 3,66 3,651
177 FW554 8,035 1,6993 58,102 58,102 3,641 3,632
178 FW554 8,035 1,6993 58,102 61,361 3,623 3,269
179 FW553 3,969 0,8394 61,361 62,537 3,28 3,16
180 FW553 3,969 0,8394 62,537 62,537 3,157 3,153
181 FW553 3,969 3,2045 62,537 62,526 3,102 3,093
182 FW553 3,969 3,2045 62,526 62,333 3,054 3,056
183 FW554 4,066 0,8599 61,361 61,361 3,28 3,28
184 FW554 4,066 0,8599 61,361 61,361 3,277 3,276
185 FW554 4,066 3,2827 61,361 61,203 3,223 3,228
186 FW554 4,066 3,2827 61,203 61,017 3,206 3,207
187 FW534 52,509 3,0582 57,584 57,584 3,66 3,657
188 FW534 44,416 2,5868 57,584 57,584 3,671 3,669
189 FW534 36,324 2,1155 57,584 57,584 3,68 3,661
190 FW534 28,258 1,6458 57,584 57,584 3,67 3,661
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 26 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

191 FW534 20,175 1,175 57,584 57,584 3,667 3,662


192 FW533 12,099 0,7047 57,584 57,584 3,667 3,665
193 FW534 0 0 57,584 57,584 3,668 3,668
194 FW555 4,071 0,861 57,584 58,636 3,664 3,556
195 FW555 4,071 0,861 58,636 59,065 3,554 3,51
196 FW555 4,071 0,861 59,065 61,197 3,509 3,29
197 FW555 4,071 0,861 61,197 61,197 3,287 3,285
198 FW555 4,071 3,2869 61,197 61,039 3,231 3,236
199 FW555 4,071 3,2869 61,039 60,923 3,215 3,215
200 FW556 8,076 1,7079 57,584 58,667 3,654 3,536
201 FW556 8,076 1,7079 58,667 59,065 3,531 3,487
202 FW556 8,076 1,7079 59,065 61,361 3,482 3,232
203 FW556 8,076 1,7079 61,361 61,361 3,223 3,221
204 FW556 4,037 0,8539 61,361 61,361 3,232 3,23
205 FW556 4,037 3,2597 61,361 61,203 3,177 3,182
206 FW556 4,037 3,2597 61,203 61,017 3,161 3,162
207 FW556 4,038 0,854 61,361 61,361 3,232 3,231
208 FW556 4,038 3,2604 61,361 61,203 3,178 3,184
209 FW556 4,038 3,2604 61,203 61,017 3,162 3,164
210 FW557 8,083 1,7094 57,584 58,567 3,66 3,553
211 FW557 8,083 1,7094 58,567 59,065 3,548 3,492
212 FW557 8,083 1,7094 59,065 61,361 3,487 3,237
213 FW557 8,083 1,7094 61,361 61,361 3,228 3,226
214 FW557 4,041 0,8546 61,361 61,361 3,238 3,236
215 FW557 4,041 3,2626 61,361 61,203 3,183 3,188
216 FW557 4,041 3,2626 61,203 61,017 3,167 3,168
217 FW557 4,042 0,8548 61,361 61,361 3,238 3,237
218 FW557 4,042 3,2633 61,361 61,203 3,184 3,189
219 FW557 4,042 3,2633 61,203 61,017 3,168 3,169
220 FW558 8,066 1,7059 57,584 58,667 3,669 3,551
221 FW558 8,066 1,7059 58,667 59,065 3,542 3,497
222 FW558 8,066 1,7059 59,065 61,361 3,488 3,238
223 FW558 8,066 1,7059 61,361 61,361 3,215 3,213
224 FW558 8,066 1,7059 61,361 61,361 3,229 3,225
225 FW558 4,033 0,8529 61,361 61,361 3,224 3,222
226 FW558 4,033 3,2559 61,361 61,203 3,169 3,175
227 FW558 4,033 3,2559 61,203 61,017 3,154 3,155
228 FW558 4,033 0,853 61,361 61,361 3,224 3,224
229 FW558 4,033 3,2566 61,361 61,203 3,171 3,176
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 27 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

230 FW558 4,033 3,2566 61,203 61,017 3,155 3,156


231 FW559 8,092 1,7114 57,584 57,827 3,688 3,662
232 FW559 8,092 1,7114 57,827 57,827 3,652 3,65
233 FW559 8,092 1,7114 57,827 58,898 3,64 3,524
234 FW559 8,092 1,7114 59,065 61,361 3,495 3,246
235 FW559 8,092 1,7114 58,898 59,065 3,519 3,5
236 FW559 8,092 1,7114 61,361 61,361 3,236 3,234
237 FW559 4,046 0,8556 61,361 61,361 3,245 3,243
238 FW559 4,046 3,2664 61,361 61,203 3,19 3,195
239 FW559 4,046 3,2664 61,203 61,017 3,174 3,175
240 FW559 4,046 0,8558 61,361 61,361 3,245 3,245
241 FW559 4,046 3,267 61,361 61,203 3,191 3,197
242 FW559 4,046 3,267 61,203 61,017 3,175 3,176
243 FW560 8,094 1,7117 57,584 58,102 3,69 3,634
244 FW560 8,094 1,7117 58,102 58,102 3,625 3,614
245 FW560 8,094 1,7117 58,102 61,361 3,605 3,25
246 FW560 8,094 1,7117 61,361 61,361 3,241 3,235
247 FW560 4,046 0,8558 61,361 61,361 3,246 3,245
248 FW560 4,046 3,267 61,361 61,203 3,191 3,197
249 FW560 4,046 3,267 61,203 61,017 3,175 3,176
250 FW560 4,047 0,8559 61,361 61,361 3,246 3,246
251 FW560 4,047 3,2677 61,361 61,203 3,193 3,198
252 FW560 4,047 3,2677 61,203 61,017 3,177 3,178
253 FW535 32,212 4,1332 57,584 57,584 3,615 3,61
254 FW535 24,191 3,1039 57,584 57,584 3,648 3,644
255 FW535 20,176 2,5888 57,584 57,584 3,659 3,618
256 FW535 12,103 1,553 57,584 57,584 3,64 3,624
257 FW535 4,057 0,5205 57,584 57,584 3,635 3,633
258 FW535 0 0 57,584 57,584 3,635 3,635
259 FW561 4,057 0,8579 57,584 57,839 3,631 3,605
260 FW561 4,057 0,8579 57,839 57,839 3,602 3,596
261 FW561 4,057 0,8579 57,839 61,164 3,594 3,253
262 FW561 4,057 0,8579 61,164 61,164 3,25 3,243
263 FW561 4,057 3,2752 61,164 60,967 3,19 3,192
264 FW562 8,047 1,7018 57,584 61,361 3,622 3,211
265 FW562 8,047 1,7018 61,361 61,361 3,202 3,197
266 FW562 4,023 0,8509 61,361 61,361 3,208 3,207
267 FW562 4,023 3,2483 61,361 61,203 3,155 3,16
268 FW562 4,023 3,2483 61,203 61,017 3,139 3,14
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 28 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

269 FW562 4,024 0,8509 61,361 61,361 3,208 3,208


270 FW562 4,024 3,2486 61,361 61,203 3,155 3,161
271 FW562 4,024 3,2486 61,203 61,017 3,139 3,141
272 FW563 8,073 1,7074 57,584 61,311 3,638 3,233
273 FW563 8,073 1,7074 61,311 61,311 3,223 3,218
274 FW563 4,036 0,8537 61,311 61,311 3,23 3,229
275 FW563 4,036 3,259 61,311 61,153 3,176 3,181
276 FW563 4,036 3,259 61,153 60,967 3,16 3,161
277 FW563 4,037 0,8537 61,311 61,311 3,23 3,229
278 FW563 4,037 3,2593 61,311 61,153 3,176 3,181
279 FW563 4,037 3,2593 61,153 60,967 3,16 3,161
280 FW564 4,014 0,849 57,584 57,584 3,69 3,685
281 FW564 4,014 0,849 57,584 57,584 3,682 3,682
282 FW564 4,014 0,849 57,584 62,459 3,679 3,179
283 FW564 4,014 0,849 62,459 62,459 3,176 3,175
284 FW561 4,014 3,2411 62,459 62,262 3,124 3,126
285 FW565 8,022 1,6965 57,584 57,584 3,682 3,674
286 FW565 8,022 1,6965 57,584 57,849 3,665 3,636
287 FW565 8,022 1,6965 57,849 57,849 3,627 3,606
288 FW565 8,022 1,6965 57,849 58,653 3,596 3,509
289 FW565 4,05 0,8565 58,653 61,114 3,52 3,267
290 FW565 4,05 0,8565 61,114 61,114 3,265 3,263
291 FW565 4,05 3,2699 61,114 61,103 3,211 3,202
292 FW565 4,05 3,2699 61,103 60,917 3,181 3,182
293 FW565 3,972 0,84 58,653 58,653 3,52 3,518
294 FW565 3,972 0,84 58,653 62,566 3,515 3,114
295 FW565 3,972 0,84 62,566 62,555 3,111 3,109
296 FW565 3,972 3,2068 62,555 62,369 3,059 3,06
297 FW504 99,451 3,3636 55,167 55,167 4,273 4,222
298 FW504 29,531 3,7891 55,167 55,113 4,207 4,026
299 FW504 29,531 3,7891 55,113 57,313 3,985 3,702
300 FW504 29,531 3,7891 57,313 57,313 3,66 3,642
301 FW504 29,531 3,7891 57,313 57,313 3,6 3,563
302 FW507 12,801 2,7073 57,313 57,313 3,599 3,594
303 FW507 8,526 1,8031 57,313 57,313 3,615 3,596
304 FW507 4,261 0,9012 57,313 57,313 3,609 3,602
305 FW507 0 0 57,313 57,313 3,607 3,607
306 FW507 4,275 0,9042 57,313 57,313 3,627 3,626
307 FW507 4,275 3,452 57,313 57,155 3,567 3,571
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 29 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

308 FW507 4,275 3,452 57,155 56,969 3,547 3,546


309 FW507 4,265 0,902 57,313 57,313 3,609 3,608
310 FW507 4,265 3,4434 57,313 57,155 3,549 3,553
311 FW507 4,265 3,4434 57,155 56,969 3,529 3,529
312 FW507 4,261 0,9012 57,313 57,313 3,602 3,602
313 FW507 4,261 3,4403 57,313 57,155 3,543 3,547
314 FW507 4,261 3,4403 57,155 56,969 3,523 3,522
315 FW570 16,73 3,5382 57,313 57,307 3,572 3,429
316 FW570 12,576 2,6597 57,307 57,307 3,457 3,435
317 FW570 12,576 2,6597 57,307 57,476 3,413 3,392
318 FW570 8,452 1,7875 57,476 57,476 3,412 3,386
319 FW570 4,256 0,9 57,476 57,476 3,398 3,393
320 FW570 0 0 57,476 57,476 3,397 3,397
321 FW566 4,256 0,9 57,476 55,655 3,393 3,572
322 FW566 4,256 3,436 55,655 55,469 3,514 3,513
323 FW567 4,196 0,8875 57,476 57,476 3,398 3,395
324 FW567 4,196 0,8875 57,476 56,655 3,392 3,473
325 FW567 4,196 3,3882 56,655 56,469 3,417 3,416
326 FW568 4,124 0,8722 57,476 57,476 3,425 3,424
327 FW568 4,124 0,8722 57,476 57,476 3,422 3,421
328 FW568 4,124 0,8722 57,476 57,792 3,419 3,386
329 FW568 4,124 3,3296 57,792 57,781 3,331 3,321
330 FW568 4,124 3,3296 57,781 57,595 3,299 3,299
331 FW569 4,154 0,8785 57,307 57,307 3,489 3,488
332 FW569 4,154 0,8785 57,307 57,792 3,486 3,436
333 FW569 4,154 3,3538 57,792 57,781 3,38 3,37
334 FW569 4,154 3,3538 57,781 57,595 3,347 3,347
335 FW503 69,92 4,0722 55,167 57,019 4,195 3,972
336 FW503 69,92 4,0722 57,019 57,019 3,927 3,919
337 FW503 61,141 3,5609 57,019 57,019 3,939 3,896
338 FW503 52,272 3,0444 57,019 57,019 3,913 3,897
339 FW503 43,419 2,5288 57,019 57,019 3,912 3,879
340 FW503 30,258 1,7623 57,019 57,005 3,896 3,896
341 FW503 30,258 3,8824 57,005 57,005 3,835 3,746
342 FW503 21,582 2,7692 57,005 57,005 3,784 3,752
343 FW503 12,907 1,6561 57,005 57,005 3,777 3,761
344 FW503 8,597 1,1031 57,005 57,005 3,769 3,764
345 FW503 8,597 1,1031 57,005 57,005 3,761 3,753
346 FW503 4,298 0,5515 57,005 57,005 3,758 3,756
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 30 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

347 FW503 0 0 57,005 57,005 3,757 3,757


348 FW517 4,298 0,9091 57,005 57,005 3,753 3,753
349 FW517 4,298 0,9091 57,005 57,805 3,75 3,668
350 FW517 4,298 0,9091 57,805 57,805 3,665 3,664
351 FW517 4,298 3,4705 57,805 57,647 3,606 3,61
352 FW517 4,298 3,4705 57,647 57,461 3,585 3,584
353 FW516 4,298 0,9091 57,005 57,005 3,755 3,754
354 FW516 4,298 0,9091 57,005 57,805 3,752 3,669
355 FW516 4,298 0,9091 57,805 57,805 3,667 3,665
356 FW516 4,298 3,4706 57,805 57,647 3,606 3,61
357 FW516 4,298 3,4706 57,647 57,461 3,586 3,585
358 FW515 4,31 0,9115 57,005 57,605 3,771 3,709
359 FW515 4,31 0,9115 57,605 57,605 3,706 3,704
360 FW515 4,31 3,4798 57,605 57,647 3,645 3,629
361 FW515 4,31 3,4798 57,647 57,461 3,605 3,604
362 FW513 8,675 1,8348 57,005 57,605 3,774 3,708
363 FW513 4,345 0,9189 57,605 57,833 3,721 3,697
364 FW513 4,345 0,9189 57,833 57,833 3,696 3,688
365 FW513 0 0 57,833 57,833 3,693 3,693
366 FW513 4,331 0,9159 57,605 57,605 3,721 3,72
367 FW513 4,331 3,4965 57,605 57,447 3,66 3,664
368 FW513 4,331 3,4965 57,447 57,261 3,64 3,638
369 FW514 4,345 0,9189 57,833 57,833 3,688 3,688
370 FW514 4,345 0,9189 57,833 57,447 3,686 3,724
371 FW514 4,345 3,508 57,447 57,261 3,664 3,662
372 FW508 8,676 1,8349 57,005 57,605 3,806 3,74
373 FW508 8,676 1,8349 57,605 57,605 3,729 3,727
374 FW508 4,337 0,9172 57,605 57,605 3,74 3,733
375 FW508 0 0 57,605 57,605 3,738 3,738
376 FW508 4,339 0,9177 57,605 57,605 3,74 3,74
377 FW508 4,339 0,9177 57,605 57,605 3,737 3,736
378 FW508 4,339 3,5035 57,605 57,447 3,675 3,679
379 FW508 4,339 3,5035 57,447 57,261 3,654 3,653
380 FW508 4,337 0,9172 57,605 57,605 3,733 3,733
381 FW508 4,337 3,5017 57,605 57,447 3,671 3,675
382 FW508 4,337 3,5017 57,447 57,261 3,651 3,649
383 FW509 13,161 2,7834 57,019 57,605 3,872 3,801
384 FW509 8,765 1,8537 57,605 57,833 3,823 3,798
385 FW509 8,765 1,8537 57,833 57,833 3,787 3,758
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 31 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

386 FW509 0 0 57,833 57,833 3,776 3,776


387 FW509 4,396 0,9297 57,605 57,605 3,836 3,835
388 FW509 4,396 3,5492 57,605 57,447 3,773 3,776
389 FW509 4,396 3,5492 57,447 57,261 3,751 3,749
390 FW509 8,765 1,8537 57,833 57,833 3,758 3,756
391 FW509 4,392 0,929 57,833 57,447 3,769 3,806
392 FW509 4,392 3,5464 57,447 57,261 3,745 3,743
393 FW509 4,373 0,9247 57,833 58,071 3,769 3,744
394 FW509 4,373 0,9247 58,071 58,071 3,742 3,74
395 FW509 4,373 0,9247 58,071 57,719 3,737 3,772
396 FW509 4,373 3,5304 57,719 57,532 3,711 3,709
397 FW510 8,853 1,8723 57,019 57,833 3,927 3,837
398 FW510 8,853 1,8723 57,833 57,833 3,826 3,824
399 FW510 4,425 0,9359 57,833 57,833 3,837 3,83
400 FW508 0 0 57,833 57,833 3,834 3,834
401 FW510 4,428 0,9364 57,833 57,833 3,837 3,836
402 FW510 4,425 0,9359 57,833 57,833 3,83 3,829
403 FW510 4,428 0,9364 57,833 57,833 3,833 3,833
404 FW510 4,428 0,9364 57,833 57,447 3,83 3,868
405 FW510 4,428 3,5748 57,447 57,261 3,805 3,803
406 FW510 4,425 0,9359 57,833 57,447 3,826 3,864
407 FW510 4,425 3,573 57,447 57,261 3,802 3,799
408 FW511 8,869 1,8756 57,019 57,605 3,943 3,878
409 FW511 4,441 0,9393 57,605 57,833 3,892 3,868
410 FW511 4,441 0,9393 57,833 57,833 3,865 3,857
411 FW511 0 0 57,833 57,833 3,862 3,862
412 FW511 4,427 0,9363 57,605 57,605 3,892 3,891
413 FW511 4,441 0,9393 57,833 57,833 3,857 3,857
414 FW511 4,427 3,5746 57,605 57,447 3,827 3,831
415 FW511 4,427 3,5746 57,447 57,261 3,805 3,803
416 FW511 4,441 0,9393 57,833 57,447 3,854 3,892
417 FW511 4,441 3,5858 57,447 57,261 3,829 3,826
418 FW512 8,78 1,8568 57,019 57,964 3,987 3,883
419 FW512 8,78 1,8568 57,964 58,105 3,877 3,854
420 FW512 4,39 0,9285 58,105 58,105 3,867 3,866
421 FW512 0 0 58,105 58,105 3,87 3,87
422 FW512 4,389 0,9283 58,105 58,105 3,867 3,866
423 FW512 0 0 58,105 58,105 3,87 3,87
424 FW512 4,39 0,9285 58,105 58,105 3,866 3,863
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 32 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

425 FW512 4,39 0,9285 58,105 58,305 3,86 3,839


426 FW512 4,39 3,5447 58,305 58,294 3,778 3,766
427 FW512 4,39 3,5447 58,294 58,108 3,741 3,739
428 FW512 4,389 0,9283 58,105 58,105 3,866 3,862
429 FW512 4,389 0,9283 58,105 58,305 3,86 3,839
430 FW512 4,389 0,9283 58,305 58,305 3,836 3,836
431 FW512 4,389 3,5439 58,305 58,294 3,774 3,765
432 FW512 4,389 3,5439 58,294 58,108 3,74 3,738
433 FW505 100,289 3,3919 55,167 56,819 4,272 4,09
434 FW505 100,289 3,3919 56,819 56,819 4,06 4,056
435 FW505 91,415 3,0918 56,819 56,819 4,066 4,042
436 FW505 82,431 2,7879 56,819 56,819 4,052 4,044
437 FW505 82,431 4,8009 56,819 56,806 3,965 3,959
438 FW505 73,449 4,2777 56,806 56,806 3,983 3,892
439 FW505 64,561 3,7601 56,806 56,806 3,913 3,855
440 FW505 55,776 3,2485 56,806 56,806 3,874 3,848
441 FW505 47,021 2,7386 56,806 56,806 3,864 3,843
442 FW505 34,003 1,9804 56,806 56,806 3,861 3,854
443 FW505 34,003 4,3629 56,806 56,806 3,776 3,66
444 FW505 16,935 2,1729 56,806 56,806 3,733 3,697
445 FW505 12,669 1,6255 56,806 56,806 3,707 3,705
446 FW505 12,669 1,6255 56,806 56,806 3,697 3,691
447 FW505 8,442 1,0832 56,806 56,806 3,698 3,691
448 FW505 4,22 0,5415 56,806 56,806 3,695 3,694
449 FW505 4,22 0,5415 56,806 57,244 3,693 3,649
450 FW505 4,22 0,5415 57,244 57,244 3,648 3,647
451 FW505 0 0 57,244 57,244 3,648 3,648
452 FW521 4,22 0,8925 57,244 58,252 3,644 3,541
453 FW521 4,22 0,8925 58,252 58,252 3,538 3,535
454 FW521 4,22 0,8925 58,252 58,252 3,533 3,532
455 FW521 4,22 3,4073 58,252 58,094 3,474 3,479
456 FW521 4,22 3,4073 58,094 57,908 3,456 3,455
457 FW520 4,222 0,8929 56,806 58,252 3,693 3,544
458 FW520 4,222 0,8929 58,252 58,252 3,541 3,539
459 FW520 4,222 0,8929 58,252 58,252 3,536 3,536
460 FW520 4,222 3,4089 58,252 58,094 3,478 3,482
461 FW520 4,222 3,4089 58,094 57,908 3,459 3,458
462 FW519 4,227 0,8939 56,806 58,252 3,7 3,551
463 FW519 4,227 0,8939 58,252 58,252 3,549 3,546
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 33 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

464 FW519 4,227 0,8939 58,252 58,252 3,544 3,543


465 FW519 4,227 3,4125 58,252 58,094 3,485 3,489
466 FW519 4,227 3,4125 58,094 57,908 3,466 3,466
467 FW518 4,266 0,9022 56,806 56,792 3,717 3,716
468 FW518 4,266 0,9022 56,792 57,605 3,714 3,63
469 FW518 4,266 3,4441 57,605 57,594 3,571 3,56
470 FW518 4,266 3,4441 57,594 57,461 3,536 3,53
471 FW522 17,068 3,6098 56,806 57,605 3,69 3,582
472 FW522 8,569 1,8123 57,605 57,605 3,632 3,624
473 FW522 0 0 57,605 57,605 3,641 3,641
474 FW522 8,499 1,7975 57,605 57,605 3,632 3,6
475 FW522 0 0 57,605 57,605 3,616 3,616
476 FW522 8,569 1,8123 57,605 57,605 3,624 3,616
477 FW522 4,285 0,9061 57,605 57,442 3,629 3,642
478 FW522 4,285 3,4593 57,442 57,284 3,582 3,586
479 FW522 4,285 3,4593 57,284 57,098 3,562 3,561
480 FW522 4,285 0,9061 57,605 57,442 3,629 3,642
481 FW522 4,285 3,4593 57,442 57,284 3,582 3,586
482 FW522 4,285 3,4593 57,284 57,098 3,562 3,561
483 FW522 8,499 1,7975 57,605 57,605 3,6 3,598
484 FW522 4,264 0,9018 57,605 57,605 3,61 3,61
485 FW522 4,264 0,9018 57,605 57,605 3,607 3,607
486 FW522 4,264 3,4427 57,605 57,447 3,548 3,552
487 FW522 4,264 3,4427 57,447 57,261 3,528 3,527
488 FW522 4,235 0,8957 57,605 58,291 3,61 3,54
489 FW522 4,235 0,8957 58,291 58,291 3,537 3,536
490 FW522 4,235 3,4195 58,291 58,094 3,479 3,48
491 FW523 13,018 2,7532 56,806 57,605 3,843 3,746
492 FW523 4,363 0,9227 57,605 57,605 3,78 3,778
493 FW523 0 0 57,605 57,605 3,782 3,782
494 FW523 8,656 1,8306 57,605 57,605 3,767 3,734
495 FW523 0 0 57,605 57,605 3,751 3,751
496 FW523 4,363 0,9227 57,605 57,605 3,778 3,777
497 FW523 4,363 3,5225 57,605 57,447 3,716 3,719
498 FW523 4,363 3,5225 57,447 57,261 3,694 3,693
499 FW523 8,656 1,8306 57,605 57,605 3,734 3,732
500 FW523 4,342 0,9183 57,605 57,605 3,745 3,744
501 FW523 4,342 0,9183 57,605 57,605 3,742 3,741
502 FW523 4,342 3,5057 57,605 57,447 3,68 3,684
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 34 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

503 FW523 4,342 3,5057 57,447 57,261 3,659 3,657


504 FW523 4,314 0,9123 57,605 58,291 3,745 3,674
505 FW523 4,314 0,9123 58,291 58,291 3,672 3,669
506 FW523 4,314 3,4828 58,291 58,094 3,61 3,61
507 FW524 8,755 1,8516 56,806 57,605 3,885 3,797
508 FW524 4,38 0,9262 57,605 57,605 3,81 3,808
509 FW524 0 0 57,605 57,605 3,812 3,812
510 FW524 4,376 0,9254 57,605 57,605 3,81 3,801
511 FW524 0 0 57,605 57,605 3,805 3,805
512 FW524 4,38 0,9262 57,605 57,605 3,808 3,807
513 FW524 4,38 3,536 57,605 57,447 3,744 3,748
514 FW524 4,38 3,536 57,447 57,261 3,723 3,721
515 FW524 4,376 0,9254 57,605 57,605 3,801 3,8
516 FW524 4,376 3,5328 57,605 57,447 3,738 3,741
517 FW524 4,376 3,5328 57,447 57,261 3,716 3,714
518 FW525 8,784 1,8578 56,806 57,605 3,91 3,822
519 FW525 4,394 0,9293 57,605 57,605 3,835 3,833
520 FW525 0 0 57,605 57,605 3,838 3,838
521 FW525 4,39 0,9285 57,605 57,605 3,835 3,826
522 FW525 0 0 57,605 57,605 3,831 3,831
523 FW525 4,394 0,9293 57,605 57,605 3,833 3,832
524 FW525 4,394 3,5478 57,605 57,447 3,77 3,773
525 FW525 4,394 3,5478 57,447 57,261 3,748 3,746
526 FW525 4,39 0,9285 57,605 57,605 3,826 3,826
527 FW525 4,39 3,5447 57,605 57,447 3,763 3,766
528 FW525 4,39 3,5447 57,447 57,261 3,741 3,739
529 FW526 8,888 1,8797 56,806 57,605 3,968 3,878
530 FW526 4,446 0,9403 57,605 57,858 3,891 3,863
531 FW526 0 0 57,858 57,858 3,868 3,868
532 FW525 4,442 0,9394 57,605 57,858 3,891 3,857
533 FW525 0 0 57,858 57,858 3,861 3,861
534 FW526 4,446 0,9403 57,858 57,858 3,863 3,863
535 FW526 4,446 0,9403 57,858 57,447 3,86 3,9
536 FW526 4,446 3,5896 57,447 57,261 3,837 3,835
537 FW526 4,442 0,9394 57,858 57,858 3,857 3,856
538 FW526 4,442 0,9394 57,858 57,447 3,853 3,893
539 FW526 4,442 3,5864 57,447 57,261 3,83 3,828
540 FW527 8,982 1,8997 56,806 57,752 4,059 3,954
541 FW527 8,982 1,8997 57,752 57,858 3,948 3,936
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 35 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

542 FW527 4,493 0,9503 57,858 57,858 3,949 3,947


543 FW527 0 0 57,858 57,858 3,952 3,952
544 FW527 4,489 0,9494 57,858 57,858 3,949 3,94
545 FW527 0 0 57,858 57,858 3,945 3,945
546 FW527 4,493 0,9503 57,858 57,858 3,947 3,947
547 FW527 4,493 0,9503 57,858 57,447 3,944 3,984
548 FW527 4,493 3,6278 57,447 57,261 3,92 3,917
549 FW527 4,489 0,9494 57,858 57,858 3,94 3,939
550 FW527 4,489 0,9494 57,858 57,447 3,937 3,977
551 FW527 4,489 3,6245 57,447 57,261 3,913 3,91
552 FW528 8,984 1,9 56,819 57,292 4,073 4,02
553 FW528 4,502 0,9521 57,292 58,008 4,034 3,96
554 FW528 4,502 0,9521 58,008 58,008 3,957 3,948
555 FW528 0 0 58,008 58,008 3,953 3,953
556 FW528 4,482 0,9479 57,292 57,292 4,034 4,033
557 FW528 4,482 0,9479 57,292 57,292 4,03 4,028
558 FW528 4,482 0,9479 57,292 57,605 4,025 3,993
559 FW528 4,482 0,9479 57,605 57,605 3,99 3,989
560 FW528 4,482 3,6189 57,605 57,447 3,924 3,927
561 FW528 4,482 3,6189 57,447 57,261 3,9 3,898
562 FW528 4,502 0,9521 58,008 58,008 3,948 3,947
563 FW528 4,502 0,9521 58,008 57,447 3,944 3,999
564 FW528 4,502 3,6347 57,447 57,261 3,935 3,932
565 FW529 8,874 1,8767 56,819 57,964 4,097 3,97
566 FW529 8,874 1,8767 57,964 58,105 3,965 3,94
567 FW529 4,438 0,9385 58,105 58,105 3,953 3,951
568 FW529 0 0 58,105 58,105 3,956 3,956
569 FW529 4,436 0,9381 58,105 58,105 3,953 3,947
570 FW529 0 0 58,105 58,105 3,952 3,952
571 FW529 4,438 0,9385 58,105 58,105 3,951 3,948
572 FW529 4,438 0,9385 58,105 58,305 3,945 3,924
573 FW529 4,438 3,583 58,305 58,294 3,86 3,849
574 FW529 4,438 3,583 58,294 58,108 3,823 3,821
575 FW529 4,436 0,9381 58,105 58,105 3,947 3,944
576 FW529 4,436 0,9381 58,105 58,305 3,941 3,921
577 FW529 4,436 3,5814 58,305 58,294 3,857 3,845
578 FW529 4,436 3,5814 58,294 58,108 3,82 3,817
580 FW571 8,393 1,7751 57,611 57,611 3,959 3,951
581 FW571 8,393 1,7751 57,611 57,837 3,946 3,92
This document contains information resulting from testing, experience and know-how of GTT, which are protected under the legal regime of undisclosed information and trade secret (notably TRIPS
Art. 39) and under Copyright law. This document is strictly confidential and the exclusive property of GTT. It cannot be copied, used, modified, adapted, disseminated, published or communicated, in
whole or in part, by any means, for any purpose, without express prior written authorization of GTT. Any violation of this clause may give rise to civil or criminal liability - © GTT, 2010-2011
3
88 800 m LNG Storage Tank for EWC T025B SAF CN 000020
ENERGY WORLD CORPORATION LIMITED
Revision : 01

HYDRAULIC CALCULATION FOR DELUGE SYSTEM 15/04/2013


Page : 36 / 36

SAFETY 6408-S-Z-CH-SGZ-100001

Volumetric Elevation Elevation Pressure Pressure


Velocity
Pipe Name Flow Rate Inlet Outlet Static In Static Out
3 (m/s)
(m /hr) (m) (m) (barg) (barg)

582 FW571 8,393 1,7751 57,837 57,837 3,915 3,88


583 FW571 8,393 1,7751 57,837 57,837 3,87 3,864
584 FW571 8,393 1,7751 57,837 61,197 3,854 3,487
585 FW571 4,198 0,8879 61,197 61,197 3,499 3,498
586 FW571 4,195 0,8873 61,197 61,197 3,499 3,498
587 FW571 4,198 0,8879 61,197 61,197 3,496 3,495
588 FW571 4,198 3,3896 61,197 61,039 3,438 3,442
589 FW571 4,198 3,3896 61,039 60,853 3,42 3,419
590 FW571 4,195 0,8873 61,197 61,197 3,496 3,495
591 FW571 4,195 0,8873 61,197 61,197 3,492 3,49
592 FW571 4,195 3,3872 61,197 61,039 3,433 3,438
593 FW571 4,195 3,3872 61,039 60,853 3,415 3,415
594 FW531 4,254 0,2477 57,611 57,611 3,975 3,975
595 FW533 4,071 0,2371 57,584 57,584 3,667 3,667
596 FW572 8,028 1,6979 57,584 57,584 3,653 3,645
597 FW572 8,028 1,6979 57,584 57,584 3,64 3,638
598 FW572 8,028 1,6979 57,584 57,584 3,633 3,599
599 FW572 8,028 1,6979 57,584 57,827 3,59 3,561
600 FW572 8,028 1,6979 57,827 61,197 3,552 3,185
601 FW572 4,014 0,849 61,197 61,197 3,196 3,196
602 FW572 4,014 0,8489 61,197 61,197 3,196 3,196
603 FW572 4,014 0,849 61,197 61,197 3,194 3,193
604 FW572 4,014 3,2412 61,197 61,039 3,141 3,146
605 FW572 4,014 3,2412 61,039 60,853 3,125 3,126
606 FW572 4,014 0,8489 61,197 61,197 3,194 3,193
607 FW572 4,014 3,241 61,197 61,039 3,14 3,146
608 FW572 4,014 3,241 61,039 60,853 3,125 3,126