Schmidbauer transformers. Get the power. Turn it on.

3 PHASE AUTOTRANSFORMER
Coolant bores | natural convection DAL
Horizontal mounting version 2kVA … 5kVA

TYPICAL APPLICATIONS

3 phase autotransformer according to IEC/ 3 phase autotransformer


EN61558-2-13 for general applications without
the need of a galvanic isolation, e.g. for trans-
according to EN61558-2-13
forming typical mains voltage to other voltages Voltage range
needed by tools, machinery or other devices.
for input / output:
Autotransformers do not provide any elec- 100 … 550 V
trical protection due to the lack of galvanic
Power range:
isolation between input and output windings.
2 kVA ... 5 kVA

EN61558-2-13

SPECIFICATIONS TECHNICAL DATA


3 phase transformer, protection class I ready.
3 phase autotransformer according to IEC/EN61558-
Autotransformers are provided for a voltage Description
2-13
range from 100V up to 550V (special voltage
versions on request). Voltage range for
100 … 550 V
input / output
Standard switching matrix: Yan0 (typical
star load approx. 10%). If typical star load Frequency 50/ 60 Hz
should reach rated current, switching matrix
Power range 2 kVA ... 5 kVA
Zan0 is used.
Important transformer Transformer completely vacuum impregnated
Please add switching matrix requested
when ordering the transformer. features No galvanic isolation
For further information, don´t hesitate to Standard switching matrix: Yan0
contact us. (typical star load approx. 10%)
Output design
Switching matrix - on request: Zan0
Final operation position must allow natu- (typical star load 100%)
ral convection through coolant bores. Protection class Protection class I ready
Due to innovative vacuum impregnation in Insulation class B
polyester varnish, the noise level is extra-
ordinary low. Fire protection class UL94 HB (V0 possible)

Screw terminals are contact proof according Max. ambient temperature 40°C
to VBG4. Degree of protection IP00 - open transformer
Transformer provides 2 loops for safe trans-
Connections Screw terminals contact proof according to VBG4
portation or craning (core sizes > 3UI150 / 65
– 4.5kVA). Ready for horizontal mounting -
including angle brackets
Other data
Final operation position must allow natural
convection through coolant bores.

©Schmidbauer GmbH • Spanberg 16 • D-84332 Hebertsfelden • Generated 05/ 2003 • Data may differ or change without notice
Phone +49 (0) 87 21-96 62-0 • Faximile +49 (0) 87 21-96 62-50 • eMail: trafo@schmidbauer.net • www.schmidbauer.net
Schmidbauer transformers. Get the power. Turn it on.

DAL STANDARD TYPES

2kVA … 5 kVA

Dimensions
Power A B*) C D E F Copper weight Total weight Type and
Size
kVA approx. mm KG KG ordering no.
2.0 290 120 200 258 160 9.0 x 13.0 6.30 19.30 3UI 120 / 51 DAL0200
2.5 290 110 220 258 176 9.0 x 13.0 7.50 20.50 3UI 132 / 46 DAL0250
3.2 290 125 220 258 176 9.0 x 13.0 8.20 25.50 3UI 132 / 60 DAL0320
4.0 330 125 250 298 200 9.0 x 13.0 12.20 31.80 3UI 150 / 52 DAL0400
4.5 330 150 250 298 200 9.0 x 13.0 11.40 36.50 3UI 150 / 65 DAL0450
5.0 360 142 280 322 224 9.0 x 13.0 17.00 44.00 3UI 168 / 58 DAL0500

*)Note:
Dimension „B“ indicates a reference value Coolant bore between primary and secundary
only. Phase current and therefore size of screw winding.
terminals used depends on transformer ratio Winding on polyamide coil former.
(identical size).

©Schmidbauer GmbH • Spanberg 16 • D-84332 Hebertsfelden • Generated 05/ 2003 • Data may differ or change without notice
Phone +49 (0) 87 21-96 62-0 • Faximile +49 (0) 87 21-96 62-50 • eMail: trafo@schmidbauer.net • www.schmidbauer.net
Schmidbauer transformers. Get the power. Turn it on.

USE OF 1 PHASE AND 3 PHASE


AUTOTRANSFORMERS
INFO
Mains supplied power
without transformer
Autotransformers do not provide „serial winding“
galvanic isolation. Electroconductive
connection between input and output
winding. Transformed
Input power
If difference between input voltage and „parallel winding“
Output
output voltage is small...:

Load
...mains power may be higher
...transformed power is lower
...size can be reduced (core, copper winding)

Please note:
Equation to calculate the requested size:
Equation: Regarding input/ output „upper“
or „lower voltage“ is independant, voltage Example: 1 phase autotransformer
related only Input voltage 440V | Output voltage 400V
For 3 phase autotransformers value „Rated power“ needed for application: 5kVA
of phase voltage is important.
lower voltage
Example shows 90% power saving Size load
upper voltage
compared isolating transformers.
Identical equation works with 3 phase
transformers. Size

Standard circuit design of 3 phase


Size
autotransformers is Yan0.
Max. load at neutral wire is approx. max.
10% of nominal current (phase current). Description
Circuit Schematic Circuit diagram Star point
If 100% neutral wire load is requested, circuit Code
design Zan0 is manufactured (Note: Yan0 design
design can be used in certain circumstances,
if neutral wire at input provides full load
and transformer star point is permanently
connected to load. Approx. 10% load

Please don´t hesitate to contact us for


further informations.

100% load

©Schmidbauer GmbH • Spanberg 16 • D-84332 Hebertsfelden • Generated 05/ 2003 • Data may differ or change without notice
Phone +49 (0) 87 21-96 62-0 • Faximile +49 (0) 87 21-96 62-50 • eMail: trafo@schmidbauer.net • www.schmidbauer.net