RX3I PLC WITH VERSAMAX I/O’S ON 2 SETS OF THE GBC HBR


CONFIGURATION

This application note covers the procedure for configuration of the


hardware and redundancy software for RX3i PLC with two sets of the
GBC with Versamax I/O module level diagnostics in Proficy Cimplicity
HMI. This configuration is suitable for systems having two RX3i CPU
system in redundant configuration with two sets dual redundant Genius
I/O LAN and I/O’s on remote Genius Versamax Network Interface Unit.

Ravi Kumar. Ronanki


Bangalore, India

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 1
TABLE OF CONTENTS
TABLE OF CONTENTS................................................................................................... 2
REVISION HISTORY....................................................................................................... 2
1) Typical System Architecture.................................................................................3
2) System Requirements.......................................................................................... 3
3) Inclusions:............................................................................................................ 4
4) Steps for PLC Hardware & Logic Configuration.....................................................5
5) Cimplicity Diagnostics:.......................................................................................26

REVISION HISTORY

Versio Date Page- Remarks Author


n paragra
ph
0.01 05-Oct-2010 First Version Ravi / Shanmugavel

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 2
1) Typical System Architecture

2) System Requirements

Hardware:
A Typical system would have the following components

 CPU System:
1) Rx3i Base plate (IC69SCHS0xx) - Qty (2
Nos.)
2) Rx3i Power supply (IC695PSx040/140) - Qty (2
Nos.)
3) Rx3i CPU (IC695CPU310) - Qty (2
Nos.)
4) Rx3i Genius Bus Controller (IC694BEM331) - Qty (8
Nos.)
5) Rx3i Ethernet Interface Module (IC695ETM001) - Qty (4
Nos.)

 I/O System:
1) Versamax Genius NIU (IC200GBI001) - Qty (As
required)
2) Versamax Power Supply (IC200PWRxxx) - Qty (As
required)

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 3
3) Versamax Input/ Output modules - Qty (As
required)
(IC200MDLxxx/ IC200ALGxxx)
Software:
 For configuration and programming of a Rx3i & Versamax based
Hot standby redundant system, the following software’s are
required
1) Proficy Machine Edition 5.6 or Latest
2) Proficy Cimplicity 8.0 With Sim 11 or Latest

3) Inclusions:

The following files are included in the Rx3i_HBR.ZIP file that


accompanies this document

 Rx3i_HBR_4GBC_FNL Proficy ME project which contains the PLCA,


PLCB & HBR targets.
 Rx3i_HBR.xls is the system configuration file for GBC SBA’s
configuration & Data block parameters
 Cimplicity Classes FAULT_TABLE.soc, PLC.soc and SBA.soc for
cimplicity HMI diagnostics.

Rx3i_hbr.zip

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 4
4) Steps for PLC Hardware & Logic Configuration
Step-1
Extract the Rx3i_HBR.zip.
Update the Rx3i_HBR.xls Module quantity, channels per modules as per
the system configuration.
Step-2
Open Proficy machine edition and restore the Rx3i_HBR_4GBC_FNL,
open the Rx3i_HBR_4GBC_FNL project in PLCA, PLCB targets Hardware
configuration shuffle the Power supply, CPU, GBC1, GBC2, GBC3, GBC4,
ETM1, ETM2 Slot ID’s as per system configuration (don’t delete the
CPU, GBC, ETM modules only shift the slot ID’s as per the system
configuration)
Step-3
In PLCA Target Hardware configuration in GBC1, GBC2, GBC3, GBC4
add the SBA (Generic IO) and edit the starting reference address and
length as per the Rx3i_HBR.xls.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 5
Step-4

Copy the PLCA GBC1

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 6
Step-5

Past in PLCB target in GBC1 slot ID & make sure that all SBA’s %I, %Q,
%AI and %AQ reference address and length as per the configuration
file Rx3i_HBR.xls.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 7
Step-6

Change the IC694BEM331 SBA Address 31 to 30

In Global data output1 address change to %R32001.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 8
Step-7

Change the SBA 30 (Generic IO) SBA 30 to 31

Change the Input-1 Reference Address %R32002

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 9
Step-8

Copy the PLCA GBC2

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 10
Step-9

Past in PLCB target in GBC2 slot ID & make sure that all SBA’s %I, %Q,
%AI and %AQ reference address and length as per the configuration
file Rx3i_HBR.xls.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 11
Step-10

Change the IC694BEM331 SBA Address 31 to 30

In Global data output1 address change to %R32001.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 12
Step-11

Change the SBA 30 (Generic IO) SBA 30 to 31

Change the Input-1 Reference Address %R32003

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 13
Step-12

Copy the PLCA GBC3

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 14
Step-13

Past in PLCB target in GBC3 slot ID & make sure that all SBA’s %I, %Q,
%AI and %AQ reference address and length as per the configuration
file Rx3i_HBR.xls.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 15
Step-14

Change the IC694BEM331 SBA Address 31 to 30

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 16
Step-15

Copy the PLCA GBC4

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 17
Step-16

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 18
Past in PLCB target in GBC4 slot ID & make sure that all SBA’s %I, %Q,
%AI and %AQ reference address and length as per the configuration
file Rx3i_HBR.xls.

Step-17

Change the IC694BEM331 SBA Address 31 to 30


GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 19
Step-18

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 20
In PLCA & PLCB Ethernet Global data change the Cons_Synch_LanA_1,
Cons_Synch_LanA_2 consumed exchanges “Adapter Name” to ETH1
Slot ID and Cons_Synch_LanB_1, Cons_Synch_LanB_2 consumed
exchanges “Adapter Name” to ETH2 Slot ID.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 21
Step-19.

In PLCA & PLCB Ethernet


Global data change the
Prod_Synch_LanA_1,
Prod_Synch_LanA_2
produced exchanges
“Adapter Name” to ETH1
Slot ID and
Prod_Synch_LanB_1,
Prod_Synch_LanB_2
produced exchanges
“Adapter Name” to ETH2
Slot ID.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 22
GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 23
Step-20

In HBR target open the


Data block edit the
following parameters
1. No. of DI
Registers
for GBC-
A/B
-
%W5204
(Enter
the data
from

RX3i_HBR.xls configuration file)


2. No. Of AI Registers GBC-A/B -%W5205
(Enter the data from RX3i_HBR.xls configuration file)
3. GBC-1 Rack & Slot ID -%W5206
(Enter the GBC-A Slot ID as per the Hardware
configuration)
4. GBC-2 Rack & Slot ID -%W5207
(Enter the GBC-A Slot ID as per the Hardware
configuration)
5. GBC-3 Rack & Slot ID -%W5208
(Enter the GBC-A Slot ID as per the Hardware
configuration
6. GBC-4 Rack & Slot ID -%W5209
(Enter the GBC-A Slot ID as per the Hardware
configuration
GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 24
7. No. of DI Registers for GBC-C/D -%W5210
(Enter the data from RX3i_HBR.xls configuration file)
8. No. Of AI Registers GBC-C/D -%W5211
(Enter the data from RX3i_HBR.xls configuration file)
9. No. of synchronized %R -%W5200
(Enter the no of %R required for Synchronization)
10. No. of Synchronized %M -%W5201
(Enter the no of %M required for Synchronization)
11. No. of Synchronized %Q -%W5202
(Enter the no of %Q required for Synchronization)
12. No. of Synchronized %AQ -%W5203
(Enter the no of %AQ required for Synchronization)
13. Each SBA DI and AI Starting address and length for
GBC-A/B Staring from %W04860.
(Enter the data from RX3i_HBR.xls configuration file).
14. Each SBA DI and AI Starting address and length for
GBC-C/B
Staring from %W05000.
(Enter the data from RX3i_HBR.xls configuration file)

After completion above all steps download the PLCA hardware


configuration in PLC-A, Download the PLCB hardware configuration in
PLC-B and download the HBR logic in both PLC’s

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 25
5) Cimplicity Diagnostics:

Steps for Creating Cimplicity project for Diagnostics


STEP 1. Create a Cimplicity Project with “S90 TRIPLEX” Protocol
selected.

STEP 2. Create a S90 Triplex Port with Mode address as %M32004

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 26
STEP 3. Create a GE Fanuc Series RX3I duplex device mapped to S90
Triplex port created in step 2.

STEP 4. Configure the Primary & Secondary PLCs IP in TCP/IP tab of


the Device window.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 27
STEP 5. Create New Alarm Class with Class ID “DIAG”

STEP 6. Create New Alarm String with Index “2” with Alarm High as
“LOSS OF MODULE” and Normal as “ADDN OF MODULE”

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 28
GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 29
STEP 7. Import the Class “FAULT_TABLE.soc” from the attached zip
folder into the Project class folder

STEP 8. Create a New Object for the Class “FAULT_TABLE”. Configure


Device Id, Resources ID and Alarm Class in the Object
Window.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 30
STEP 9. Import the Classes “PLC.soc” & “SBA.soc” from the attached
zip folder into the Project class folder

STEP 10.Create a two New Object in Class “PLC” for the redundant
PLCs. Configure Resources ID. In the Fault Table Field enter
the Object Name created for the Class “Fault Table” and in
the PLC ID field enter either “PLCA” or “PLCB” to identify
the controllers.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 31
STEP 11.Create a New Object in Class “SBA” with name GP{1 or
2}_SBAx (x – SBA_NO) for the IO Nodes. Configure
Resources ID and in the Fault Table Field enter the Object
Name created for the Class “Fault Table”. Enter the GBC
Group No as either 1 or 2 in t

STEP 12.Repeat Step 11 until all the required nodes are created.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 32
STEP 13.Create New Screen or Open Existing screen where the
System Diagnostics is required.
STEP 14.Select Drawing  Class object from the menu and Click on
the Screen to invoke the object browser. Select the Main PLC
object created and Click OK.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 33
STEP 15.Double Click on the Inserted Object and Configure the Slots
as per the Configuration. Select the Check Box if it is a 2
Slot Module.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 34
STEP 16.Repeat STEP 14 & 15 for Inserting and configuring
Redundant PLC Object.

STEP 17.Follow STEP 14 for inserting the Object Created for Fault
Table

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 35
STEP 18.Follow STEP 14 for inserting the Object Created for SBA.
Double Click on the inserted Object and Configure the
Module Legend as per the configuration.

STEP 19.Repeat Step 18 for inserting all the nodes as per the
configuration.

STEP 20.Update the configuration and start the project to check the
diagnostics of the PLC.

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 36
REFERENCE MATERIALS USED

 Infolink RX3I Manuals


 Infolink Versamax Manuals
 Cimplicity Help

GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and
assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
No warranties of merchantability or fitness for purpose shall apply
Page 37

Anda mungkin juga menyukai