Anda di halaman 1dari 8

Winding Temperature Monitoring on Transformer With OLTC

Jacques Aubin Sylvain Lapointe Claude Rajotte Pierre Pepin


GE Energy Hydro-Québec – TransÉnergie

Summary
Transmission network transformers are typically provided with on-load tap changers to regulate
the voltage delivered to customers and to adjust power flow in the system. By virtue of OLTC
operation, per unit (p.u.) currents are bound to be different on the HV winding and LV winding.
Usually the rated current is established for both windings at the mid-tap position, and this leads
to a transformer with a reduced rated power on some taps. When such transformers are requested
to operate under overload conditions during system contingency, the on-load tap changer
typically moves from the normal operating position to the end of the tapping range to
compensate for the voltage drop taking place on the system. Depending on transformer design,
the winding hottest spot may well move from the high-voltage winding to the low-voltage
winding or vice versa. Most transformers are provided with a single winding temperature
indicator, which does not allow for a direct control of temperature on each winding.

In order to take full advantage of transformer loading capabilities during emergency conditions
without jeopardizing reliability of the unit, accurate evaluation of temperature on both windings
is needed. Limitations of the classical thermo-mechanical Winding Temperature Indicator (WTI)
are discussed along with difficulties related to the installation of an additional system for the
monitoring of the second winding. As an alternative, a simple digital device, capable of
monitoring temperature on three windings, is proposed. Field experience is reported
demonstrating the accuracy of the thermal model and the capabilities to provide control functions
for the cooling system and protection functions to trip the transformer if a winding reaches
excessive temperature.

Limitations of Traditional Winding Temperature Indicator


For many decades it has been a standard practice to install on new power transformers a winding
temperature indicator. This device typically comprises a temperature-sensing bulb inserted in a
well in the top layer of the insulating oil. Surrounding the bulb is a heater element to which a
sample of the load current is applied as shown in Figure 1. This current causes the temperature
bulb to read the oil temperature plus a temperature rise from the heater which is intended to be
the same as the winding hottest temperature rise above top-oil temperature. The fluid in the bulb
expands through a capillary tube connected to a dial gage equipped with switches that can be
adjusted to any temperature within the operating range. These mechanical devices provide
accuracy of 3 to 5 °C, assuming that the transformer designer has properly evaluated the winding
hottest-spot temperature. These devices can be used for cooling control temperature alarm and
they are sufficiently rugged to be used for protection purpose if the recommended maintenance is
carried out at regular intervals. WTI’s are offered by several manufacturers and provide
dependable winding temperature indication at a cost effective price.

A single WTI is fine for a transformer without tap changer because the calibration circuit allows
for the simulation of the hottest winding even if the current is measured on a different winding.
For instance if the CT feeding the heating elements is on the LV winding and it is known from

1
heat run test and design reviews that the HV winding is the hottest, then the HV gradient can be
used to calibrate the winding temperature simulator.
LV
Calibration system
Heater element

Capillary tube

Dial gage & Switches

Figure 1 – Thermo-mechanical Winding Temperature Indicator

The situation is different on a transformer with a tap changer as the ratio between primary and
secondary currents varies continuously with changes in tap position. In this case the WTI cannot
be used to monitor the temperature on the primary side if the CT is on the secondary winding.
Common practice requires the winding hot-spot temperature indicator to be fed by a CT on the
LV winding. This provides a good control over the temperature of low-voltage winding
regardless of the transformer load. For the HV winding the situation is not so clear.

Let’s consider a 47-MVA transformer, 120 / 26.4 kV, wye/delta connection, with a tap changer
of ± 8 steps in the neutral of the HV winding. Each step changes the rated voltage on the primary
by 2.25 kV or 1.875 % of the rated voltage in the neutral position. On these transformers the tap
changer is intended to regulate the voltage on the secondary side (26.4 kV). Therefore the
voltage and current variations can be depicted as shown in Figure 2.

On tap positions between 1 and 9, the current in the HV winding is less than the rated value for
the neutral position; therefore this winding will be cooler than the rated value. If the tap position
is between 9 and 17, the HV winding will be carrying more current and will be at a higher
temperature than the rated value at neutral position, although this situation will not be revealed
by the WTI. When the transformer in designed to deliver full MVA on any tap, the HV winding
has to be enlarged by a value close to the tapping range to be capable of carrying the extra
current on tap 17.

2
HV current
HV voltage

P.U. Current
1.15 1.15
P.U. Voltage

1.00 1.00
0.95 LV voltage LV current
0.90
0.85 0.85
1 9 17
1 9 17
Tap position Tap position

Figure 2 – Voltage and Current Characteristics for a Transformer


With Full Capacity on Any Tap

In most cases, the maximum load losses are to be found on tap position 17; therefore this is the
tap position that will be used to carry out the temperature rise test. Since the winding temperature
rise is known in position 17 and the winding temperature indicator is fed by a CT on the
secondary winding, the winding temperature simulation, on any tap position, will be realistic for
the LV winding and conservative for the HV winding.

In practice transformers with on-load tap changers are commonly designed with a reduced
capacity for some parts of the tap range. This is a practice well recognized in Standards (1). A
transformer similar to the one described above but with reduced capacity on some taps can be
represented as shown in Figure 3. The full capacity is available from tap 1 to tap 9 but from tap 9
to tap 17 there is a progressive reduction of capacity because the current is limited by the
capacity of the primary winding.

1.15
HV voltage
P.U. Voltage

P.U. Current

1.15

1.00
HV current
1.00
LV voltage
0.85 LV current
0.85
1 9 17 1 9 17
Tap position Tap position

Figure 3 – Voltage and Current Characteristics for a Transformer


With Reduced Capacity on Some Taps

For transformers with full capacity on any tap, the position showing maximum load losses is
tap 17. For transformers with reduced capacity on some taps, the highest losses are found on
tap 1 and this is the connection that will be used for the temperature rise test. This situation
makes it more difficult to monitor with confidence the HV winding hot-spot temperature from a
measurement of the secondary winding current. Although test results normally show a lower
temperature rise for HV winding it is clear that between tap positions 9 and 17, the primary
winding will reach its temperature limit long before the secondary winding. The difference
between the temperature patterns for the two types of transformer is illustrated in Figure 4. It is

3
assumed that both transformers show a winding hot spot temperature rise at the limit of 80 °C
comprising 55 °C for the top oil rise and 25 °C for the winding rise above top oil.

HV winding
80 80
Temperature Rise°C

LV winding

Temperature Rise°C
70 70
LV winding

HV winding
60 60
Top oil
50 50
Top oil

40 40
1 9 17 1 9 17
Tap position Tap position

a) Full capacity on any taps b) Reduced capacity on some taps

Figure 4 – Winding Temperature Pattern for the Two Different Types of Transformers

It can be seen that for a full capacity transformer tested on tap 17, the LV winding is always the
limiting factor. But for transformers with reduced capacity and tested on tap 1, the highest
temperature may shift from one winding to another depending on the tap position.

This limitation of the traditional practice of monitoring only the low-voltage winding
temperature can be deemed acceptable for loads up to nameplate rating but this situation
becomes unacceptable when overloading is considered. It can be shown that for a few hours at
150 % overload the temperature difference can exceed 20 °C.

Thermal protection of transformers is normally provided by the winding temperature indicator.


The HV transformer overcurrent protection could provide a partial thermal backup depending on
the relay setting. If the overcurrent protection setting is raised to allow for overload conditions,
the winding temperature indicator must be considered as the main thermal protection for the
transformer. Hence it is not acceptable anymore to rely on the traditional devices, which monitor
only one winding of the power transformer.

One option would be to add a winding temperature indicator on the second winding so that both
windings would be protected independently whatever the tap changer position. If not already
available this would require the installation of an additional CT on one of the HV bushings to
monitor the HV current. It is generally not practical to add a CT on existing bushings. Therefore
this option is applicable only on new units where the additional CT can be provided at a
competitive price.

4
Digital Transformer Temperature Controller
The preferred method implies the use of a fully electronic device that can calculate separately the
temperature on primary, secondary and eventually tertiary windings using as inputs the measured
top oil temperature and the current in each winding as shown in Figure 5.

HV
LV

Top-oil Temperature
HV Current
LV Current

Control Intellix
Cabinet PR 100

Figure 5 – Variables Used for the Calculation of Windings’ Hottest-Spot Temperature

The winding temperature is calculated as recommended in the IEEE® Loading Guide (2). For the
HV winding hottest spot, the ultimate value of temperature rise above top oil is given by:
2m
 I HV 
∆Θ = ∆Θ  
HVu HVR  I 
 HVR 

The response of the winding to a sudden load increase is not instantaneous. Considering the
winding time constant τw the actual winding hot-spot temperature rise above top oil at time t is
given by:
∆Θ
HVt
(
= ∆Θ
HVu

− ∆Θ
HVi 
)
− ∆t / τ 
1 − e w  + ∆Θ
 HVi
 
where:
∆ΘHVu is the ultimate HV winding hot-spot temperature rise above top oil
∆ΘHVR is the rated HV winding hot-spot temperature rise above top oil
∆ΘHVt is the HV winding hot-spot temperature rise above top oil at time t
∆ΘHVi is the HV winding hot-spot temperature rise above top oil at time t-∆t
IHV is the load current in the HV winding
IHVR is the rated value of load current in the HV winding
∆t is the time increment used in the calculation
τw is the winding time constant

5
A similar set of equations allow for calculation of winding temperature rise above top oil for LV
windings and tertiary windings. This winding rise is then added to the measured top oil
temperature. This calculation method has shown to be sufficiently accurate for reliable
monitoring of the winding temperature and the insulation aging. Test results on a converter
transformer (3) equipped with fiber optic sensors inserted in the winding insulation have shown a
good correlation even when the unit was subjected to rapid load changes as shown in Figure 6.

Hot-spot temperature model


Load Hot-spot measured with fiber optic
70 700

60 600
Temperature °C

50 500

Load A
40 400

30 300
Top-oil
20 200

10 100
0 12 24 36 48 60 72 84 96
Time (hours)

Figure 6 – Comparison of Winding Hot-Spot Temperature Model


With Fiber Optic Measurement

Temperature Controller Characteristics


The temperature controller Intellix* PR100 developed by GE Energy used this winding hot-spot
model to provide continuous assessment of temperature of each winding. It comprises analog
inputs to measure the top oil temperature and the current in each winding. The computation
makes use of these measured values and the configured parameters specific to the transformer,
such as the rated current, the rated hot-spot temperature rise for each winding and the thermal
time constant for the windings. Simultaneous monitoring of the three windings allows for
continuous identification of the insulation hottest-spot temperature even if this hottest spot
moves from one winding to another. The calculated hot-spot temperature is used to generate two
alarm levels and a third level for tripping the transformer.

The Intellix* PR100 is also intended for cooling system control. The controller comprises digital
outputs to control the cooling as well as digital inputs to monitor the cooling status and to detect
discrepancies between control and status. Starting and stopping the various cooling stages take
into consideration the oil temperature, the hottest-spot temperature in the windings and the
highest load on the windings.

Because of its sturdiness, this controller qualifies as a protection instrument and can be utilized
to trip the transformer in accordance with protection requirements. Efficient packaging allows
for installation of the unit in the transformer control cabinet or in a separate NEMA 4X
enclosure. The input / output characteristics are summarized in Figure 7.

Maintenance is significantly simplified. WTI manufacturers recommend calibration verification


at regular intervals. It is known that with time, the accuracy tends to degrade due to component

6
oxidation and increased friction. If maintenance is not done in time, it may result in inaccurate
measurements, which in turn can lead to the cooling system not being turned on at the correct
time. In the Intellix* PR100, sensors are checked continuously and the system carries a self-test
twice a month to ensure proper functioning of all components.
Ambient temperature

Breaker trip RS -232 local port

Cooling control 1 Expansion (CANBUS)


Cooling control 2

Cooling alarm Current H


DC voltage alarm
Current X
System OK alarm
Current Y
Winding hot -spot
Alarm Hi and Hi -Hi
DC V supervision
Top oil alarm
Hi and Hi -Hi Top -oil RTD

Fan 1&2 status


Power input
Max reset and
Next screen

Figure 7 – Input / Output Layout on the Intellix* PR100

Protection vs. Monitoring


One important characteristic of this application is the need to provide protection functions in
addition to the usual monitoring functions. It is required that the thermal protection be qualified
to trip the transformer whenever the critical temperature setting is reached on any winding. This
is of special interest for the case of unattended substations where the alarm signal would not have
been followed by appropriate actions to reduce the load.

Tripping of a transformer is an event of severe consequences for the customers and should in no
case be triggered by false information, electric disturbance in the substation environment, or
unusual climatic conditions. In order to carry the tripping duty with confidence, the temperature
controller must satisfy stringent requirements usually intended for protection relays. These
requirements are well described in the IEC® 61000 series covering electromagnetic
compatibility. At Hydro-Quebec, requirements and testing procedures for electronic devices and
protection material are collated in technical specifications SN-62-1008 and SN-62-210. This new
field of application for monitoring material involves new challenges that had to be met. Below
are given examples of some of these requirements specific to protection material.

Processor Immunity to Electrostatic Discharges


For monitoring functions it is usually acceptable to initiated automatic rebooting when a severe
electrostatic discharge occurs. For protection functions however, the device should be capable of
sustaining electrostatic discharges up to 6 kV on any input or output terminals without disturbing
the operation of the protection device.

7
Immunity to Vibration and Shock
For monitoring duty, Hydro-Quebec requires a vibration test with an acceleration of 1 G in the
frequency range of 10 Hz to 150 Hz. For the first frequency sweep the device is energized and
operating to check the electrical behavior. The test is repeated 20 times without being energized
to check the mechanical behavior.

A protective device needs to withstand these mechanical stresses but it must also be able to
sustain severe mechanical shocks. In order to avoid false tripping, especially under earthquake
conditions, the trip relay must be very stable. The electrical behavior is demonstrated with
acceleration of 10 G applied three times in every axis while the mechanical sturdiness is
demonstrated with 15-G impulsions. The resistance to transport stresses is demonstrated with an
additional test of 1000 impulsions of 10 G in every axis.

Relay Capacity for Closing Current


For monitoring purposes, the digital output relays usually have light duty such as alarms where a
rated current of 1 A is sufficient. In a protective device, the output relay dedicated to circuit
breaker tripping will typically have a rated current and breaking capacity of 5 A under a 129-Vdc
source. In the Hydro-Quebec application, the maximum closing current withstand was set at
30 A for 200 ms.

Conclusions
Transformers with on-load tap changers deserve a special thermal protection scheme especially if
the unit is expected to operate properly under overload conditions. Information provided by
traditional Winding Temperature Indicator can be misleading if the unit is designed with reduced
capacity on some taps. In this case the winding not being monitored could be the hottest one and
the underestimation of winding hottest-spot temperature could be very significant during
overload occurrence.

Proper thermal protection implies that winding hottest-spot temperature is calculated on both
windings. Since it is not practical to install a classical Winding Temperature Indicator on each
winding that deserves monitoring, it is found that a good solution is to use a fully digital system
such as the Intellix* PR100. This device calculates the winding hottest-spot temperature using the
measured top-oil temperature, the load current on each winding and the winding time constant.
The calculation method follows IEEE recommended practices that has been used in the industry
for many years.
.
References
1. IEEE C57.12.00-1993 “IEEE Standard General Requirements for Liquid-Immersed
Distribution, Power, and Regulating Transformers”
2. IEEE Std C57.91-1995 “IEEE Guide for Loading Mineral-Oil-Immersed Transformers”
3. J. Aubin, P. Gervais, A. Glodjo, “Field Experience With the Application of Dynamic Models
for On-Line Transformer Monitoring”

* Trademark(s) of General Electric Company.


IEEE is a registered trademark of Institute of Electrical Electronics Engineers, Inc.
IEC is a registered trademark of Commission Electrotechnique Internationale.

Anda mungkin juga menyukai