Anda di halaman 1dari 12

LAMPIRAN PERCOBAAN 3

PRAKTIKUM
ANALISA SISTEM TENAGA LISTRIK

KELOMPOK 4 KELAS A
I Made Agus Satradiangga (1605541017)
Ravinda Ariestya Pamungkas (1605541019)

PROGRAM STUDI TEKNIK ELEKTRO


FAKULTAS TEKNIK
UNIVERSITAS UDAYANA
2019
1. Line Diagram
Berikut adalah Line Diagram dengan beban yang berbeda
a. Beban 880 MW
G1 A G2
SATU LIMA EMPAT TIGA
A

93%
520 MW
MVA
MVA
491 MW
A

400 Mvar
MVA
k
266 Mvar
slac

TRAFO 1 TRAFO 2
15,000 kV 325,729 kV A A
340,986 kV 80 MW
0,000 Deg -5,729 Deg MVA MVA
-4,323 Deg 40 Mvar
15,388 kV
-1,988 Deg

260,014 kV DUA
-28,660 Deg

880 MW
280 Mvar

P = 51,18 MW
LOSSES :
Q = 346,00 Mvar

Gambar 1. Line Diagram Beban 880 MW

b. Beban 860 MW
G1 A G2
SATU LIMA EMPAT TIGA
A

82%
520 MW
MVA
MVA
463 MW
A

393 Mvar
MVA

ck
164 Mvar sl a

TRAFO 1 TRAFO 2
15,000 kV 332,717 kV A A
349,824 kV 80 MW
0,000 Deg -5,366 Deg MVA MVA
-3,957 Deg 40 Mvar
15,750 kV
-1,731 Deg

276,952 kV DUA
-25,772 Deg

860 MW
280 Mvar

P = 43,28 MW
LOSSES :
Q = 237,61 Mvar

Gambar 2. Line Diagram Beban 860 MW


c. Beban 840 MW
G1 G2
SATU LIMA EMPAT TIGA
A A

520 MW
MVA MVA

440 MW
A

MVA

373 Mvar

k
146 Mvar

slac
TRAFO 1 TRAFO 2
15,000 kV 333,972 kV A A
350,500 kV 80 MW
0,000 Deg -5,088 Deg MVA MVA
-3,574 Deg 40 Mvar
15,750 kV
-1,344 Deg

280,901 kV DUA
-24,581 Deg

840 MW
280 Mvar

P = 40,17 MW
LOSSES :
Q = 198,58 Mvar

Gambar 3. Line Diagram Beban 840 MW

d. Beban 820 MW
G1 G2
SATU LIMA EMPAT TIGA
A A

MVA MVA

417 MW
A
520 MW
MVA

slac 354 Mvar


129 Mvar k

TRAFO 1 TRAFO 2
15,000 kV 335,101 kV 351,107 kV 80 MW
A A

0,000 Deg -4,815 Deg MVA MVA


-3,200 Deg 40 Mvar
15,750 kV
-0,967 Deg

284,439 kV DUA
-23,464 Deg

820 MW
280 Mvar

P = 37,37 MW
LOSSES :
Q = 163,55 Mvar

Gambar 4. Line Diagram Beban 820 MW


e. Beban 800 MW
G1 G2
SATU LIMA EMPAT TIGA
A A

MVA MVA

395 MW
A 520 MW
MVA

k 337 Mvar
114 Mvar ac
sl

TRAFO 1 TRAFO 2
15,000 kV 336,130 kV 351,659 kV 80 MW
A A

0,000 Deg -4,548 Deg MVA MVA


-2,834 Deg 40 Mvar
15,750 kV
-0,597 Deg

287,650 kV DUA
-22,406 Deg

800 MW
280 Mvar

P = 34,84 MW
LOSSES :
Q = 131,76 Mvar

Gambar 5. Line Diagram Beban 800 MW

f. Beban 700 MW
G1 G2
SATU LIMA EMPAT TIGA
A A

MVA MVA

285 MW
A
520 MW
271 Mvar
MVA
ck

56 Mvar
sl a

TRAFO 1 TRAFO 2
15,000 kV 340,210 kV A A
353,855 kV 80 MW
0,000 Deg -3,264 Deg MVA MVA
-1,083 Deg 40 Mvar
15,750 kV
1,166 Deg

300,377 kV DUA
-17,705 Deg

700 MW
280 Mvar

P = 24,90 MW
LOSSES :
Q = 6,87 Mvar

Gambar 6. Line Diagram Beban 700 MW


g. Beban 600 MW
G1 G2
SATU LIMA EMPAT TIGA
A A

MVA MVA

178 MW
A
520 MW
223 Mvar
MVA

slac
17 Mvar k

TRAFO 1 TRAFO 2
15,000 kV 343,121 kV A A
355,432 kV 80 MW
0,000 Deg -2,037 Deg MVA MVA
0,580 Deg 40 Mvar
15,750 kV
2,838 Deg

309,585 kV DUA
-13,599 Deg

600 MW
280 Mvar

P = 18,00 MW
LOSSES :
Q = -80,07 Mvar

Gambar 7. Line Diagram Beban 600 MW

h. Beban 500 MW
G1 G2
SATU LIMA EMPAT TIGA
A A

520 MW
MVA MVA

73 MW
A

MVA

ck 187 Mvar
-9 Mvar sl a

TRAFO 1 TRAFO 2
15,000 kV 345,256 kV A A
356,607 kV 80 MW
0,000 Deg -0,845 Deg MVA MVA
2,189 Deg 40 Mvar
15,750 kV
4,455 Deg

316,595 kV DUA
-9,836 Deg

500 MW
280 Mvar

P = 13,15 MW
LOSSES :
Q = -141,45 Mvar

Gambar 8. Line Diagram Beban 500 MW


2. Parameter Beban (Load)
Berikut adalah Parameter untuk tiap beban
a. Beban 880 MW

Gambar 9. Parameter Beban 880 MW

b. Beban 860 MW

Gambar 10. Parameter Beban 860 MW


c. Beban 840 MW

Gambar 11. Parameter Beban 840 MW

d. Beban 820 MW

Gambar 12. Parameter Beban 820 MW


e. Beban 800 MW

Gambar 13. Parameter Beban 800 MW

f. Beban 700 MW

Gambar 14. Parameter Beban 700 MW


g. Beban 600 MW

Gambar 15. Parameter Beban 600 MW

h. Beban 500 MW

Gambar 16. Parameter Beban 500 MW


NOTE
a. Pada Beban 880 MW, Trafo mengalami persentase panas yang tinggi (93%) akibat
penyuplaian beban.
b. Pada Beban 860 MW, Trafo mengalami persentase panas yang tinggi (82%) akibat
penyuplaian beban.
c. Pada Beban 500 MW, Generator 1 menjadi motor karena menyerap daya reaktif dari
Generator 2 sebesar -9 MVAR, penyerapan Daya Reaktif tersebut dimaksudkan
untuk menyeimbangkan power factor dan penyeimbangan kurva kapabilitas suatu
generator, dikarenakan beban daya aktif yang disuplay terlalu kecil maka generator
1 harus menyerap daya reaktif agar power factor tetap terjaga. Bisa dilihat pada
gambar 17.

Gambar 17. Kurva Kapabilitas Generator


LAMPIRAN