Anda di halaman 1dari 4

How to evaluate

petrographic reports
Separating facts from conclusions

BY BRUCE A. SUPRENANT AND WARD R. MALISCH

petrographic report is often used in construc- vious experience, which may or may not relate to the

A tion disputes or litigation as evidence of poor


workmanship by contractors. In many of the re-
ports contractors have sent us over the past 10
years, the petrographer concludes that the con-
crete was overfinished or that the air content, water-ce-
ment ratio, or both were outside specified values. Con-
tractors may accept these conclusions because they
concrete on your project.

Facts vs. conclusions


When reading a petrographic report, you must first
separate factual information from conclusions. You may
agree that a petrographer can determine the air content
of hardened concrete, within appropriate precision and
don’t understand the limitations of petrographers’ tech- bias limits, but you may not agree with the conclusions
niques. But because of these limitations, we think some regarding how the measured air content affects the
of the conclusions should be challenged. durability of the structure. Thus it’s important to note
what the petrographer observed, evaluate the accuracy
Check the sampling plan of that observation, and then decide if the observation
Petrographic examination of hardened concrete can and the accuracy support the conclusion.
cost up to $1,000 per sample. Because of this, the num- Based on the factual observations we’ve seen in some pet-
ber of samples the petrographer sees is sometimes lim- rographic reports, conclusions regarding overfinishing, air
ited. In some cases, the petrographer’s conclusions may content, and water-cement ratio were of dubious validity.
not be valid because the sample size is too small or the
sampling plan is inadequate. Use ASTM C 823-95 (Ref. Overfinishing
1) as a guide for sample plans and sizes. Some petrographers conclude that surface defects are
If testing of hardened concrete is to be used to deter- caused by overfinishing, citing a thick layer of mortar
mine compliance with codes or contract documents, and reduced air content in this paste layer as evidence
ASTM C 823 states that not less than five samples that the concrete was overfinished. They also note as ev-
should be taken from each category of concrete for each idence oval-shaped voids near the surface, as compared
test. Thus conclusions based on a sample size of less with spherical voids in the main body of the concrete.
than five don’t meet that criterion. Mortar-layer thickness. How thick must the mortar
Also, don’t automatically accept the conclusions of a layer at the surface be to indicate overfinishing? And will
petrographic examination if only a sample of “bad” con- the thickness vary with the mortar content of the mix? ACI
crete was analyzed. Ideally, the petrographer gets to see 309R-96 (Ref. 2) states that “mortar thicknesses over coarse
samples of concrete known or suspected to be defective, aggregate in excess of 1⁄8 inch (3 mm) indicate overvibration
plus samples of concrete believed to be of good quality. or overfinishing, which can result in reduced abrasion resis-
This is especially important for concrete with surface de- tance.” ACI also indicates that this could mean the mix
fects such as scaling. In such instances, what is “good” used had an excessive mortar content.
and “bad” can only be a relative comparison. Otherwise, It’s difficult to establish a single mortar-layer thick-
what is “bad” is considered from the petrographer’s pre- ness that indicates overfinishing. It’s best to evaluate the
mortar-layer thickness based on a “good” and “bad” sam- the manipulation removes a large portion of the larger
ple from the same concrete. Even then, a thicker mortar voids. This action may decrease the air-void content of
layer may not be the cause of surface defects. the topmost 1⁄16 inch to one-third or less of the air content
ACI Committee 302 studied the effect of finishing of the concrete as a whole. Nevertheless, if the concrete
techniques on delaminations (Ref. 3). In this field was originally adequately air-entrained, the spacing fac-
study, four panels were finished with float pans and tor is not significantly modified.”
float blades. One panel contained air-entrained con- Newlon (Ref. 5) verified Mielenz’s finding based on ex-
crete and the others didn’t. In addition, finishers began perimental work. He found that the average near-surface
floating one non-air-entrained panel while the bleed- air-void content was reduced by about 70% compared
water sheen was still visible. The petrographic report with the void contents within the concrete mass.
indicates that the mortar layer was 1 to 2 mm thick for Newlon concludes: “Thus, the changes in the air-void
all panels except the one finished early. For this panel, system indicate that the volume of air is reduced, but
the half finished initially by float pans had a 3- to 4- that the air lost is in the form of the larger bubbles,
mm-thick mortar layer while the half finished by float which offer little protection. The more important void
blades had a 1- to 2-mm-thick mortar layer at the sur- properties, specific surface, and spacing factor are im-
face. proved. This finding is consistent with Mielenz.”
Was the panel with the thicker 3- to 4-mm mortar Backstrom et al. (Ref. 6) previously indicated that the
layer overfinished? That might be a reasonable conclu- air-bubble shape becomes distorted during concrete plac-
sion since finishing started while bleedwater was on the ing and finishing due to the compactive effort. The dis-
surface and the panel did receive more finishing than the torted bubble, however, does not diminish its ability to
other three panels. But the thicker mortar layer in this ensure freeze-thaw resistance of the concrete.
case didn’t cause delaminations to form. The air-en- A loss in air content and distorted bubble shapes are typi-
trained concrete panel, however, with a surface mortar cal consequences of the normal procedures for placing and
layer 1 to 2 mm thick, did delaminate. finishing concrete. As Mielenz states, the paste layer can
Loss of air content. As evidence of overfinishing, have an air content of one-third or less of that in the main
many petrographers point to the air content in the top body and still provide adequate freeze-thaw resistance.
surface. If it’s less than that of the main body of concrete These published data and reports provide little support
and the air bubbles are distorted (oval) rather than spher- for the belief that overfinishing invariably produces infe-
ical, they attribute surface defects, such as freeze-thaw rior concrete.
deterioration, to overfinishing.
However, in 1964, Mielenz (Ref. 4) stated: “Air content Air content of hardened concrete
in the uppermost part of a concrete slab, particularly Petrographers normally measure the air content of
within 1⁄2 inch of the finished surface, is characteristically hardened concrete microscopically, using a polished sec-
less than that in the concrete at greater depth because tion of concrete taken from a core. ASTM C 457-98 (Ref.
7) is the test method used.
Don’t expect the air content of hardened concrete to
match that of fresh concrete. The graph on page 29 rep-
resents over 400 separate comparisons of fresh and hard-
ened air contents taken from a variety of laboratory and
field studies. For this data, the mean fresh and hardened
air content is 6.0%. The mean absolute difference be-
tween fresh and hardened concretes is 1.3%. Typically,
the difference in the air contents of the same fresh and
hardened concrete will be within ±2% (Ref. 8).
ASTM C 457 indicates the variability to expect in mea-
suring hardened-concrete air content. A study sponsored
by ASTM showed that in 95% of all cases the expected
difference between two independent measurements of air
content on a single specimen would be less than or equal
to 0.82% if the two tests were performed in the same lab-
oratory. The expected difference would be less than or
equal to 1.16% if tested in two different laboratories. In-
dependent tests by Sommers (Ref. 7) showed that the ex-
pected difference between two measurements of air con-
Ref. 8

tent on the same specimen would be 1.61% within the


Relationship between the air contents of fresh and hardened same laboratories, and 2.01% if performed in different
concrete (Ref. 8).
laboratories. void-system spacing factor is 0.01 in- water-cement ratio of hardened con-
As Hover (Ref. 9) points out, none stead of the recommended 0.008, crete.
of these studies has replicated the but the concrete surface is in good A recent textbook, Concrete Petrog-
typical conditions on a concrete pro- condition, does this mean poor fu- raphy (Ref. 13), states: “In practice, ac-
ject, with random sampling on ture performance? In concrete tech- curate estimation of the water-ce-
nonuniform concrete combined nology there are few absolutes. Con- ment ratio in a concrete is rarely
with variable surface preparation crete with the 0.01 spacing factor necessary. Often the petrographer
and local variations in procedures, may perform adequately under some will only be required to establish
operators, and equipment. ASTM C conditions (Ref. 10) and inade- whether or not a particular concrete
457 therefore advises: “The variabil- quately under others. Perhaps the had a water-cement ratio which sig-
ity of the test method would be pertrographer should recommend nificantly exceeded a given value. Al-
higher in actual practice for speci- scaling-resistance tests on samples of though there is relationship between
mens sampled and prepared from in- the in-place concrete. the proportion of residual unhy-
place concrete since additional varia- drated cement particles and water-ce-
tion due to sample selection and Estimating water-cement ment ratio, the degree of hydration is
surface preparation in different labo- ratio also strongly dependent upon curing
ratories would increase the coeffi- Petrographers often estimate the conditions and the properties of the
cient of variation.” water-cement ratio of hardened con- particular cement involved.”
So if the specifications call for 5% crete. Their reports may indicate that According to French (Ref. 14), “the
to 7% air and the air content of a they have performed the examina- amount of unhydrated portland ce-
hardened concrete is reported as 8%, tion in accordance with ASTM C ment (residual clinker) is related to
it doesn’t necessarily mean that the 856-95 (Ref. 11). This standard, how- the original water-cement ratio of
contractor or producer has somehow ever, doesn’t contain a methodology the mixture and the conditions and
increased the air content to beyond for determining water-cement ratio. duration of curing. In concretes
the specified value. It can simply It simply states in section 4.2.5 that made at normal ambient tempera-
mean that normal variability ac- an “unusually high water-cement tures of around 20° C (68° F) and
counts for the difference. ratio” of the paste can be described. where curing is limited to a few days,
The precision of the fresh-con- In 1981, Campbell (Ref. 12) said the amount of unhydrated portland
crete air test is better than that of that “an interpretation of concrete cement is directly dependent on the
the hardened-concrete air test. Thus water-cement ratio can be made uti- original water-cement ratio. In prac-
to obtain a level of confidence for air lizing an estimate of the unhydrated tice, it is found that if the water-ce-
content of hardened concrete that portland cement abundance and the ment ratio is approximately 0.61 or
equals that of fresh concrete, more types and distributions of hydration 0.62, the cement powder is virtually
samples are required. Yet petrogra- products, combined with other pet- completely hydrated. At water-ce-
phers rarely measure air content of rographic data such as paste hard- ment ratios of about 0.5, between 3%
hardened concrete on as many sam- ness, color, and luster and the depth and 4% of the total cement paste
ples as are used for fresh concrete. of carbonation.” He also indicated typically consists of unhydrated ma-
ASTM C 457 does, however, state that the interpretation must be re- terial, and if the water-cement ratio
a minimum sample requirement: fined by knowledge of the curing is as low as 0.4, 7% or 8% of the ma-
“For referee purposes or to deter- conditions of the concrete and the terial may be unhydrated.”
mine the compliance of hardened environment to which it has subse- French also acknowledges that the
concrete with requirements of speci- quently been subjected. amount of unhydrated portland ce-
fications for the air-void system, ob- Petrographers typically have pre- ment in concrete may increase or
tain samples for analysis by this test pared samples of concrete with vary- decrease depending on the ambient
method from at least three ran- ing water-cement ratios for use as temperature at which the concrete is
domly selected locations over the comparison samples. Thin slices, placed. For concretes placed in cold
area or throughout the body of con- called thin sections, are removed weather, he says, “the unhydrated
crete to be tested.” This would apply from these concretes and examined portland cement of the concrete
only when the project specification at magnifications up to 400X. The may appear to have a water-cement
requests measurement of the hard- petrographer can then estimate the ratio of about 0.4 when in fact it was
ened-concrete air-void system. water-cement ratio of the field-con- made with a ratio of 0.6 or above.”
If properties of the air-void system crete samples by comparing their Because curing temperatures can in-
in hardened concrete are not within characteristics with those of the fluence the amount of unhydrated
commonly accepted ranges, does samples with known water-cement portland cement, a few petrogra-
this mean that the concrete will al- ratios. Unfortunately, ASTM C 856 phers supplement the estimate of
ways perform poorly? For instance, doesn’t provide a precision and bias the water-cement ratio by examin-
if the petrographer finds the air- statement for the estimation of ing the size, amount, and distribu-
tion of calcium hydroxide crystals in or contractor met the maximum 1998.
the cement paste. The estimated water-cement ratio required by the 8. David A. Whiting and Mohamad A.
amount of unhydrated portland ce- specifications or the approved mix Nagi, Manual on Control of Air Content
ment may also be influenced by the design. in Concrete, Portland Cement Associa-
tion, Skokie, Ill., and National Ready
presence of some supplementary ce- The legal community and some Mixed Concrete Association, Silver
mentitious materials that react with consultants and petrographers are Spring, Md., 1998.
available mixing water and reduce using water-cement ratios estimated 9. Kenneth C. Hover, “Air Content and
the amount of calcium hydroxide in from a very limited sample size to Unit Weight of Hardened Concrete,”
the cement paste. make statements about whether all chap. 28 in Significance of Tests and
In the reports we reviewed, it ap- the concrete on a project is in com- Properties of Concrete and Concrete-
pears that most petrographers esti- pliance with the specifications. Since Making Materials, ASTM 169C, Paul
Klieger and Joseph F. Lamond editors,
mated the water-cement ratio based 1956, the past three editions of ASTM, 1994.
primarily on the amount of unhy- ASTM 169 (Refs. 15, 16, and 17) in- 10. Kenneth C. Hover, “Specifying Air-
drated portland cement. Above a dicate that the ability to evaluate Entrained Concrete,” Concrete Con-
water-cement ratio of about 0.60, water-cement ratio is in the range of struction, May 1993, pp. 361-367.
there is very little (less than 1%) un- ±0.05. It would appear that many 11. ASTM C 856-95, “Standard Prac-
hydrated portland cement that can petrographers are estimating water- tice for Petrographic Examination of
be observed in thin section. This is cement ratios with a greater accu- Hardened Concrete,” ASTM, 1995.
why ASTM C 856 states that a petro- racy than can be justified. 12. Donald H. Campbell, “Application of
grapher can determine when a con- Contractors shouldn’t conclude the Microscope in the Concrete Indus-
try,” Proceedings of the Third Interna-
crete has an usually high water-ce- that all petrographic reports are tional Conference on Cement Mi-
ment ratio. flawed. But we’ve seen enough bad croscopy, Houston, 1981.
However, determining a water-ce- reports to conclude that they should 13. Donald A. St. John, Alan W. Poole,
ment ratio below 0.60 becomes be carefully read and the conclu- and Ian Sims, Concrete Petrography,
more difficult, as evidenced by the sions evaluated. When unwarranted John Wiley & Sons, New York, 1998.
varied conclusions in the petro- conclusions have been drawn from 14. W.J. French, “Concrete Petrogra-
graphic reports we reviewed. One the facts presented, those conclu- phy: a Review,” Quarterly Journal of En-
petrographer stated in his report sions should be challenged. m gineering Geology, Vol. 24, No. 1, The
Geological Society, 1991.
that there was 3% to 5% unhydrated
15. Bernard Erlin, “Petrographic Exami-
portland cement in the concrete, References
nation,” chap. 22 in Significance of
and estimated the water-cement 1. ASTM C 823-95,”Standard Practice Tests and Properties of Concrete and
ratio as 0.50 to 0.55. Another petro- for Examination and Sampling of Hard- Concrete-Making Materials, ASTM
grapher indicated that 3% to 5% un- ened Concrete in Constructions,” 169C, Paul Klieger and Joseph F. Lam-
hydrated portland cement shows ASTM, West Conshohocken, Pa., ond editors, ASTM, 1994.
1995. 16. Katharine Mather, “Petrographic Ex-
concrete with a water-cement ratio
2. ACI 309R-96, “Guide for Consolida- amination,” Significance of Tests and
of 0.45 to 0.55. Another indicated
tion of Concrete,” American Concrete Properties of Concrete and Concrete
that 5% to 10% unhydrated port- Institute, Farmington Hills, Mich., 1996. Aggregates, ASTM 169, 1956.
land cement shows concrete with a 3. Carl Bimel, “Is Delamination Really a 17. Katharine Mather, “Petrographic Ex-
water-cement ratio of 0.45 to 0.50. Mystery?” Concrete International, amination,” chap. 11 in Significance of
And a fourth indicated that 9% to American Concrete Institute, January Tests and Properties of Concrete and
12% unhydrated portland cement 1998. Concrete-Making Materials, ASTM
indicates a water-cement ratio of 4. R.C. Mielenz, “Diagnosing Concrete 169B, 1978.
0.42 to 0.50. Failures,” Stanton Walker Lecture, Uni-
versity of Maryland, 1964.
Most surprising was the conclu-
sion of one petrographer who exam- 5. Howard H. Newlon Jr., “Comparison
of Properties of Fresh and Hardened Publication #C99K027
ined a polished concrete section at Concrete in Bridge Decks,” Virginia Copyright© 1999, The Aberdeen Group,
magnifications up to only 60X and Highway Research Council, Char- a division of Hanley-Wood, Inc.
estimated the water-cement ratio at lottesville, Va., June 1971. All rights reserved
0.55 to 0.60. This estimate wasn’t 6. James E. Backstrom, Richard W.
based on the amount of unhydrated Burrows, Richard C. Mielenz, and
portland cement since that can’t be Vladimir E. Wolkodoff, “Origin, Evolu-
tion, and Effects of the Air Void System
seen in polished sections at 60X.
in Concrete, Part 3: Influence of Water-
The petrographer stated that a thin- Cement Ratio and Compaction,” Jour-
section analysis was beyond the nal of the American Concrete Institute,
scope of the investigation. Unfortu- September 1958.
nately, the petrographer’s estimate 7. ASTM C 457-98, “Standard Test
of water-cement ratio is being used Method for Microscopical Determina-
to determine whether the producer tion of Parameters of the Air-Void Sys-
tem in Hardened Concrete,” ASTM,

Anda mungkin juga menyukai